iRort Palla - Cost Benefit Equation Terms Page 1 From:

Robert Palla To:

jojones@sandia.gov Date:

05/24/2007 7:10:00 AM

Subject:

Cost Benefit Equation Terms Joe - I am not sure whether I had provided you with this table previously. It shows how each of the terms in the cost benefit equation are derived, and their relative significance for Pilgrim. Bob CC:

nbixler@sandia.gov

1. C':\\t6ýip\\GW)00001.ýýTýýý'MPý-'

-P-aiWi 11 I c:\\te1~n p\\GW}OOQOl.TMP Page 1<

Mail Envelope Properties (46557288.5A6 :18 :10412)

Subject:

Creation Date From:

Created By:

Cost Benefit Equation Terms 05/24/2007 7:10:00 AM Robert Palla RLP3 (@l)nrc.gov Recipients sandia.gov AM jojones (ioiones(asandia.gov) nbixler CC (nbixler(asandia.gov)

Action Transferred Date & Time 05/24/2007 7:10:30 Post Office Delivered Route sandia.gov Files Size MESSAGE 505 Cost benefit equation and description of terms.wpd AM Date & Time 05/24/2007 7:10:00 AM 9603 02/21/2007 11:13:12 Options Auto Delete:

Expiration Date:

Notify Recipients:

Priority:

ReplyRequested:

Return Notification:

Concealed

Subject:

Security:

To Be Delivered:

Status Tracking:

No None Yes Standard No None No Standard Immediate Delivered & Opened

.3 4

Net Value = (APE + AOC + AOE + AOSC) - COE, where APE

=

AOC

=

AOE

=

AOSC =

COE-averted public exposure costs averted offsite property damage costs averted occupational exposure costs averted onsite costs averted cleanup and decontamination costs (ACC) + averted replacement power costs (ARPC) cost of enhancement Cost Significance NUREG/BR-Related Parameters Value If All Internally-Initiated Core Factor 0184 Section Damage Events at Pilgrim Are Eliminated APE Offsite exposure 5.7.1 AP-Rem (from MACCS2)

$314K AOC Offsite economic 5.7.5 AOffsite Economic Cost Risk - OECR (from MACCS2)

$566K From 12/12/2006 Entergy letter, Attachment C, Table E. 1-15:

- CAPB-12: $4.85E6/event

- CAPB-14: $4.96E9/event

- CAPB-15: $18.0E9/event

- frequency-weighted sum for all CAPBs = $8.21 E9/event From NUREG/BR-0184, Table 5.6 (1990$ costs, within 50 miles):

- average for all NUREG-1 150 plants = $2.46E8/event -

- highest NUREG-1 150 plant (Peach Bottom) = $2.71 E9/event AOE Onsite exposure 5.7.3 Immediate occupational dose (3,300 P-Rem)

$2K Long term occupational dose (20,000 P-Rem)

ACC Onsite economic 5.7.6.1 Onsite cleanup and decontamination cost ($1.1E9.single event, PW)

$76K ARPC Onsite economic 5.7.6.2 Plant power level.

$51 K