MathCad Worksheet TAC:

S.F. LaVie, NRR/DSSA/SPSB MB7863,MB7864 Catawba MOX for AST--Weir MWt 1.0 106 watt INITIALIZATIONS Ci 3.7 1010 sec 1 rem 100 erg gm Bq 1.0 sec 1 Sv 100 rem ORIGIN 1

uCi 1.0 10 6 Ci mrem 0.001 rem I131 13 kr85 3

j 1

12 i 13 17 k

1 17 Read in nuclide database NUCLIDE.DAT.>>>>>

Re-assign arrays and assign units M

READPRN(

)

nuclide

M 2

sec 1

======================================================================
======================================================================

INPUT DATA Radial peaking factor:k p 1.65 Assembly Inventory from Staff ST report Table 7 Decay Time T decay 468 hr Kr83m Kr85m Kr85 Kr87 Kr88 Xe131m Xe133m Xe133 Xe135m Xe135 Xe137 Xe138 I131 I132 I133 I134 I135 Assign gap fractions:

F gk 0.075 noble gases and iodines F gI131 0.12 F gkr85 0.15 Assign pool DF:

DFj 1.0 DFi 1

200 A MOX 4.2840 104 7.8550 104 4.0430 103 1.4910 105 2.0010 105 7.5110 103 3.2540 104 9.8000 105 2.3070 105 5.3860 105 0.0 7.6430 105 5.1950 105 7.4150 105 9.7630 105 1.0420 106 9.2860 105 Ci A LEU 6.5010 104 1.3870 105 6.4860 103 2.8040 105 3.9230 105 7.3460 103 3.1380 104 9.9350 105 2.1390 105 2.9230 105 0.0 8.6920 105 4.8690 105 7.0520 105 9.9410 105 1.1140 106 9.4100 105 Ci We'll assume 4 of the 7 assemblies affected are MOX A core A MOX 4 A LEU 3 catwbaMOX_weir.mcd 3/30/1904 1

CALCULATION Activity available for release:

A relk A corek k p DFk F gk e

k T decay RG1.183 (RG1.25) stipulates that the activity is released over a two hour period. While it is typical to model an offsite release as a puff release of the total release inventory.

However, for a control room assessment, the release must be expressed in terms of a rate. We'll assume that 99% is released in two hours.

Kr83m Kr85m Kr85 Kr87 Kr88 Xe131m Xe133m Xe133 Xe135m Xe135 Xe137 Xe138 I131 I132 I133 I134 I135 A o 1.0 A f A o e t

=

A rel 0

0 8.788 103 0

0 2.07 103 57.614 6.49 104 0

1.189 10 10 0

0 652.18 0

7.184 10 4 0

0 Ci A f 0.01 solve for t

2 hr

ln A f A o t

=

5.526 103 day catwbaMOX_weir.mcd 3/30/1904 2

RNEditor v1.0 File Name:

C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\CatawbaMOX_WGD.RFT C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\CatawbaMOX_WGD.NIF Description Catawba Weir Gate w/4mox & 3LEU RELEASE FRACTION Duration, hr 1.0000E-04 0.0000E+00 0.0000E+00 0.0000E+00 Noble Gases:

1.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Iodine:

1.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Cesium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Tellurium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Strontium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Barium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Ruthenium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Cerium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Lanthanium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Non-Radioactive Aerosols (kg):

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 ACTIVITY, Ci (Stored in NIF File as Ci/MWt)

Co-58 0.0000E+00 Co-60 0.0000E+00 Kr-83m 0.0000E+00 Kr-85 8.7867E+03 Kr-85m 0.0000E+00 Kr-87 0.0000E+00 Kr-88 0.0000E+00 Rb-86 0.0000E+00 Sr-89 0.0000E+00 Sr-90 0.0000E+00 Sr-91 0.0000E+00 Sr-92 0.0000E+00 Y-90 0.0000E+00 Y-91 0.0000E+00 Y-92 0.0000E+00 Y-93 0.0000E+00 Zr-95 0.0000E+00 Zr-97 0.0000E+00 Nb-95 0.0000E+00 Mo-99 0.0000E+00 Tc-99m 0.0000E+00 Ru-103 0.0000E+00 Ru-105 0.0000E+00 Ru-106 0.0000E+00 Rh-105 0.0000E+00 Sb-127 0.0000E+00 Sb-129 0.0000E+00 Te-127 0.0000E+00 Te-127m 0.0000E+00 Te-129 0.0000E+00 Te-129m 0.0000E+00 Te-131m 0.0000E+00 Te-132 0.0000E+00 I-131 6.5218E+02 I-132 0.0000E+00 I-133 7.1836E-04 I-134 0.0000E+00 I-135 0.0000E+00 Xe-131m 2.0701E+03 Xe-133 6.4911E+04 Xe-133m 5.7612E+01 Xe-135 0.0000E+00 Xe-135m 0.0000E+00 Xe-138 0.0000E+00 Cs-134 0.0000E+00 Cs-136 0.0000E+00 Cs-137 0.0000E+00 Ba-139 0.0000E+00 Ba-140 0.0000E+00 La-140 0.0000E+00 La-141 0.0000E+00 La-142 0.0000E+00 Ce-141 0.0000E+00 Ce-143 0.0000E+00 Ce-144 0.0000E+00 Pr-143 0.0000E+00 Nd-147 0.0000E+00 Np-239 0.0000E+00 Pu-241 0.0000E+00 Cm-242 0.0000E+00

RADTRAD Version 3.03 (Spring 2001) run on 12/27/2003 at 0:16:59 File information Plant file = C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\catawbawgd_mOX.psf Inventory file = C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\CatawbaMOX_WGD.NIF Release file = C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\CatawbaMOX_WGD.RFT Dose Conversion file = c:\\program files\\radtrad3.03\\defaults\\dba_fg11&12.inp WEIR GATE CASE Radtrad 3.03 4/15/2001 Nuclide Inventory File:

C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\CatawbaMOX_WGD.NIF Plant Power Level:

3.4110E+03 Compartments:

3 Compartment 1:

FHB/CNMT 3

1.0000E+00 0

0 0

0 0

Compartment 2:

Environm 2

0.0000E+00 0

0 0

0 0

Compartment 3:

Control Room 1

1.1790E+05 0

0 1

0 0

Pathways:

4 Pathway 1:

FHB/CNMT to Environm 1

2 4

Pathway 2:

Environm to Control Room-unfilt 2

3 2

Pathway 3:

Environm to Control Room Filt 2

3 2

Pathway 4:

Control Room to Environm 3

2 2

End of Plant Model File Scenario Description Name:

Plant Model Filename:

Source Term:

1 1 1.0000E+00 c:\\program files\\radtrad3.03\\defaults\\dba_fg11&12.inp C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\CatawbaMOX_WGD.RFT 0.0000E+00 0

0.0000E+00 5.7000E-01 4.3000E-01 1.0000E+00 Overlying Pool:

0 0.0000E+00 0

0 0

0 Compartments:

3 Compartment 1:

0 1

0 0

0 0

0 0

0 Compartment 2:

0 1

0 0

0 0

0 0

0 Compartment 3:

0 1

0 0

0 0

1 1.5000E+03 3

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 5.0000E-01 9.9000E+01 9.9000E+01 9.5000E+01 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0

0 Pathways:

4 Pathway 1:

0 0

0 0

0 0

0 0

0 0

1 2

0.0000E+00 5.5260E+03 2.0000E+00 0.0000E+00 0

Pathway 2:

0 0

0 0

0 1

3 0.0000E+00 2.1000E+03 0.0000E+00 0.0000E+00 0.0000E+00 5.0000E-01 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0

0 0

0 0

0 Pathway 3:

0 0

0

0 0

1 3

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 5.0000E-01 2.0000E+03 9.9000E+01 9.9000E+01 9.5000E+01 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0

0 0

0 0

0 Pathway 4:

0 0

0 0

0 1

3 0.0000E+00 2.1000E+03 1.0000E+02 1.0000E+02 1.0000E+02 5.0000E-01 2.1000E+03 1.0000E+02 1.0000E+02 1.0000E+02 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0

0 0

0 0

0 Dose Locations:

3 Location 1:

EAB 2

1 2

0.0000E+00 4.7800E-04 2.0000E+00 0.0000E+00 1

4 0.0000E+00 3.4700E-04 8.0000E+00 1.7500E-04 2.4000E+01 2.3200E-04 7.2000E+02 0.0000E+00 0

Location 2:

LPZ 2

1 2

0.0000E+00 6.8500E-05 2.0000E+00 0.0000E+00 1

4 0.0000E+00 3.4700E-04 8.0000E+00 1.7500E-04 2.4000E+01 2.3200E-04 7.2000E+02 0.0000E+00 0

Location 3:

Control Room 3

0 1

2 0.0000E+00 3.4700E-04 7.2000E+02 0.0000E+00 1

4 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 0.0000E+00 Effective Volume Location:

1 2

0.0000E+00 1.0400E-03 2.0000E+00 0.0000E+00 Simulation Parameters:

1 0.0000E+00 0.0000E+00 Output Filename:

C:\\Documents and Settings\\Normal\\My Documents\\A_NRC\\MOX\\catawbawgd_mOX.o0 1

1 1

0 0

End of Scenario File RADTRAD Version 3.03 (Spring 2001) run on 12/27/2003 at 0:16:59 Plant Description Number of Nuclides = 60 Inventory Power = 1.0000E+00 MWth Plant Power Level = 3.4110E+03 MWth Number of compartments = 3 Compartment information Compartment number 1 (Source term fraction = 1.0000E+00

)

Name: FHB/CNMT Compartment volume = 1.0000E+00 (Cubic feet)

Compartment type is Normal Pathways into and out of compartment 1 Exit Pathway Number 1: FHB/CNMT to Environm Compartment number 2 Name: Environm Compartment type is Environment Pathways into and out of compartment 2 Inlet Pathway Number 1: FHB/CNMT to Environm

Inlet Pathway Number 4: Control Room to Environm Exit Pathway Number 2: Environm to Control Room-unfilt Exit Pathway Number 3: Environm to Control Room Filt Compartment number 3 Name: Control Room Compartment volume = 1.1790E+05 (Cubic feet)

Compartment type is Control Room Removal devices within compartment:

Filter(s)

Pathways into and out of compartment 3 Inlet Pathway Number 2: Environm to Control Room-unfilt Inlet Pathway Number 3: Environm to Control Room Filt Exit Pathway Number 4: Control Room to Environm Total number of pathways = 4 RADTRAD Version 3.03 (Spring 2001) run on 12/27/2003 at 0:16:59 Scenario Description Radioactive Decay is enabled Release Fractions and Timings GAP EARLY IN-VESSEL LATE RELEASE RELEASE MASS 0.000100 hr 0.0000 hrs 0.0000 hrs (gm)

NOBLES 1.0000E+00 0.0000E+00 0.0000E+00 2.274E+01 IODINE 1.0000E+00 0.0000E+00 0.0000E+00 5.261E-03 CESIUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 TELLURIUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 STRONTIUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 BARIUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 RUTHENIUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 CERIUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 LANTHANUM 0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 Inventory Power = 3411. MWt Nuclide Group Specific half Whole Body Inhaled Inhaled Name Inventory life DCF Thyroid Effective (Ci/MWt) (s) (Sv-m3/Bq-s) (Sv/Bq) (Sv/Bq)

Kr-85 1 2.576E+00 3.383E+08 1.190E-16 0.000E+00 0.000E+00 I-131 2 1.912E-01 6.947E+05 1.820E-14 2.920E-07 8.890E-09 I-133 2 2.106E-07 7.488E+04 2.940E-14 4.860E-08 1.580E-09 Xe-131m 1 6.069E-01 1.023E+06 7.890E-16 0.000E+00 0.000E+00 Xe-133 1 1.903E+01 4.532E+05 1.560E-15 0.000E+00 0.000E+00 Xe-133m 1 1.689E-02 1.892E+05 2.160E-15 0.000E+00 0.000E+00 Iodine fractions Aerosol = 0.0000E+00 Elemental = 5.7000E-01 Organic = 4.3000E-01 COMPARTMENT DATA Compartment number 1: FHB/CNMT

Compartment number 2: Environm Compartment number 3: Control Room Compartment Filter Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.5000E+03 0.0000E+00 0.0000E+00 0.0000E+00 5.0000E-01 1.5000E+03 9.9000E+01 9.9000E+01 9.5000E+01 7.2000E+02 1.5000E+03 0.0000E+00 0.0000E+00 0.0000E+00 PATHWAY DATA Pathway number 1: FHB/CNMT to Environm Convection Data Time (hr) Flow Rate (% / day) 0.0000E+00 5.5260E+03 2.0000E+00 0.0000E+00 Pathway number 2: Environm to Control Room-unfilt Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 2.1000E+03 0.0000E+00 0.0000E+00 0.0000E+00 5.0000E-01 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Environm to Control Room Filt Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 5.0000E-01 2.0000E+03 9.9000E+01 9.9000E+01 9.5000E+01 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 4: Control Room to Environm Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 2.1000E+03 1.0000E+02 1.0000E+02 1.0000E+02 5.0000E-01 2.1000E+03 1.0000E+02 1.0000E+02 1.0000E+02 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LOCATION DATA Location EAB is in compartment 2 Location X/Q Data Time (hr) X/Q (s

  • m^-3) 0.0000E+00 4.7800E-04 2.0000E+00 0.0000E+00 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1)

0.0000E+00 3.4700E-04 8.0000E+00 1.7500E-04 2.4000E+01 2.3200E-04 7.2000E+02 0.0000E+00 Location LPZ is in compartment 2 Location X/Q Data Time (hr) X/Q (s

  • m^-3) 0.0000E+00 6.8500E-05 2.0000E+00 0.0000E+00 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.4700E-04 8.0000E+00 1.7500E-04 2.4000E+01 2.3200E-04 7.2000E+02 0.0000E+00 Location Control Room is in compartment 3 Location X/Q Data Time (hr) X/Q (s
  • m^-3) 0.0000E+00 1.0400E-03 2.0000E+00 0.0000E+00 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.4700E-04 7.2000E+02 0.0000E+00 Location Occupancy Factor Data Time (hr) Occupancy Factor 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 0.0000E+00 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 0.0000E+00

RADTRAD Version 3.03 (Spring 2001) run on 12/27/2003 at 0:16:59 Dose Output EAB Doses:

Time (h) = 0.0001 Whole Body Thyroid TEDE Delta dose (rem) 2.3604E-05 1.3454E-02 4.3321E-04 Accumulated dose (rem) 2.3604E-05 1.3454E-02 4.3321E-04 LPZ Doses:

Time (h) = 0.0001 Whole Body Thyroid TEDE Delta dose (rem) 3.3825E-06 1.9280E-03 6.2081E-05 Accumulated dose (rem) 3.3825E-06 1.9280E-03 6.2081E-05 Control Room Doses:

Time (h) = 0.0001 Whole Body Thyroid TEDE Delta dose (rem) 1.2113E-10 1.5641E-06 4.7740E-08 Accumulated dose (rem) 1.2113E-10 1.5641E-06 4.7740E-08 EAB Doses:

Time (h) = 0.5000 Whole Body Thyroid TEDE Delta dose (rem) 1.4005E-01 7.9850E+01 2.5711E+00 Accumulated dose (rem) 1.4008E-01 7.9864E+01 2.5715E+00 LPZ Doses:

Time (h) = 0.5000 Whole Body Thyroid TEDE Delta dose (rem) 2.0071E-02 1.1443E+01 3.6845E-01 Accumulated dose (rem) 2.0074E-02 1.1445E+01 3.6852E-01 Control Room Doses:

Time (h) = 0.5000 Whole Body Thyroid TEDE Delta dose (rem) 3.5074E-03 4.5308E+01 1.3829E+00 Accumulated dose (rem) 3.5074E-03 4.5308E+01 1.3829E+00 EAB Doses:

Time (h) = 2.0000 Whole Body Thyroid TEDE

Delta dose (rem) 6.2525E-02 3.5688E+01 1.1490E+00 Accumulated dose (rem) 2.0260E-01 1.1555E+02 3.7206E+00 LPZ Doses:

Time (h) = 2.0000 Whole Body Thyroid TEDE Delta dose (rem) 8.9602E-03 5.1142E+00 1.6466E-01 Accumulated dose (rem) 2.9034E-02 1.6559E+01 5.3318E-01 Control Room Doses:

Time (h) = 2.0000 Whole Body Thyroid TEDE Delta dose (rem) 1.1265E-02 7.3312E+01 2.2433E+00 Accumulated dose (rem) 1.4772E-02 1.1862E+02 3.6262E+00 EAB Doses:

Time (h) = 8.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.0260E-01 1.1555E+02 3.7206E+00 LPZ Doses:

Time (h) = 8.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.9034E-02 1.6559E+01 5.3318E-01 Control Room Doses:

Time (h) = 8.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.5479E-03 5.5258E+00 1.7178E-01 Accumulated dose (rem) 1.8320E-02 1.2415E+02 3.7980E+00 EAB Doses:

Time (h) = 24.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.0260E-01 1.1555E+02 3.7206E+00 LPZ Doses:

Time (h) = 24.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.9034E-02 1.6559E+01 5.3318E-01 Control Room Doses:

Time (h) = 24.0000 Whole Body Thyroid TEDE Delta dose (rem) 5.5884E-06 1.0406E-04 8.7566E-06 Accumulated dose (rem) 1.8326E-02 1.2415E+02 3.7980E+00 EAB Doses:

Time (h) = 96.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.0260E-01 1.1555E+02 3.7206E+00 LPZ Doses:

Time (h) = 96.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00

Accumulated dose (rem) 2.9034E-02 1.6559E+01 5.3318E-01 Control Room Doses:

Time (h) = 96.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.5373E-13 5.8931E-17 2.5373E-13 Accumulated dose (rem) 1.8326E-02 1.2415E+02 3.7980E+00 EAB Doses:

Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.0260E-01 1.1555E+02 3.7206E+00 LPZ Doses:

Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 2.9034E-02 1.6559E+01 5.3318E-01 Control Room Doses:

Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 4.3918E-47 1.6120E-73 4.3918E-47 Accumulated dose (rem) 1.8326E-02 1.2415E+02 3.7980E+00 308 I-131 Summary FHB/CNMT Environm Control Room Time (hr) I-131 (Curies) I-131 (Curies) I-131 (Curies) 0.000 6.5211E+02 7.5077E-02 7.7381E-05 0.401 2.5891E+02 3.9258E+02 3.1839E-01 0.500 2.0590E+02 4.4550E+02 3.3786E-01 0.800 1.0309E+02 5.4814E+02 2.0183E-01 1.100 5.1611E+01 5.9952E+02 1.2001E-01 1.400 2.5840E+01 6.2525E+02 7.1091E-02 1.700 1.2937E+01 6.3813E+02 4.1980E-02 2.000 6.4770E+00 6.4458E+02 2.4725E-02 2.300 6.4700E+00 6.4458E+02 1.4347E-02 2.600 6.4631E+00 6.4458E+02 8.3258E-03 2.900 6.4561E+00 6.4458E+02 4.8315E-03 3.200 6.4491E+00 6.4458E+02 2.8038E-03 3.500 6.4422E+00 6.4458E+02 1.6271E-03 3.800 6.4353E+00 6.4458E+02 9.4430E-04 4.100 6.4283E+00 6.4458E+02 5.4803E-04 4.400 6.4214E+00 6.4458E+02 3.1806E-04 4.700 6.4145E+00 6.4458E+02 1.8459E-04 5.000 6.4076E+00 6.4458E+02 1.0714E-04 5.300 6.4007E+00 6.4458E+02 6.2183E-05 5.600 6.3938E+00 6.4458E+02 3.6092E-05 5.900 6.3869E+00 6.4458E+02 2.0949E-05 6.200 6.3800E+00 6.4458E+02 1.2160E-05 6.500 6.3731E+00 6.4458E+02 7.0580E-06 6.800 6.3663E+00 6.4458E+02 4.0969E-06 7.100 6.3594E+00 6.4458E+02 2.3782E-06 7.400 6.3526E+00 6.4458E+02 1.3805E-06 7.700 6.3457E+00 6.4458E+02 8.0139E-07

8.000 6.3389E+00 6.4458E+02 4.6522E-07 8.300 6.3321E+00 6.4458E+02 2.7007E-07 8.600 6.3253E+00 6.4458E+02 1.5679E-07 8.900 6.3184E+00 6.4458E+02 9.1022E-08 9.200 6.3116E+00 6.4458E+02 5.2844E-08 9.500 6.3048E+00 6.4458E+02 3.0680E-08 9.800 6.2980E+00 6.4458E+02 1.7812E-08 10.100 6.2913E+00 6.4458E+02 1.0342E-08 10.400 6.2845E+00 6.4458E+02 6.0046E-09 24.000 5.9849E+00 6.4458E+02 1.2130E-19 96.000 4.6210E+00 6.4458E+02 4.9770E-76 720.000 4.9127E-01 6.4458E+02 0.0000E+00 Cumulative Dose Summary EAB LPZ Control Room Time Thyroid TEDE Thyroid TEDE Thyroid TEDE (hr) (rem) (rem) (rem) (rem) (rem) (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.401 7.0377E+01 2.2661E+00 1.0085E+01 3.2474E-01 3.2128E+01 9.8064E-01 0.500 7.9864E+01 2.5715E+00 1.1445E+01 3.6852E-01 4.5308E+01 1.3829E+00 0.800 9.8263E+01 3.1640E+00 1.4082E+01 4.5341E-01 7.7425E+01 2.3639E+00 1.100 1.0747E+02 3.4605E+00 1.5402E+01 4.9591E-01 9.6570E+01 2.9495E+00 1.400 1.1209E+02 3.6090E+00 1.6063E+01 5.1719E-01 1.0793E+02 3.2978E+00 1.700 1.1440E+02 3.6834E+00 1.6393E+01 5.2785E-01 1.1466E+02 3.5042E+00 2.000 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.1862E+02 3.6262E+00 2.300 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2094E+02 3.6978E+00 2.600 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2229E+02 3.7395E+00 2.900 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2307E+02 3.7638E+00 3.200 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2352E+02 3.7779E+00 3.500 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2378E+02 3.7862E+00 3.800 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2394E+02 3.7911E+00 4.100 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2402E+02 3.7939E+00 4.400 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2408E+02 3.7956E+00 4.700 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2411E+02 3.7965E+00 5.000 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2412E+02 3.7971E+00 5.300 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2413E+02 3.7975E+00 5.600 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2414E+02 3.7977E+00 5.900 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2414E+02 3.7978E+00 6.200 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2414E+02 3.7979E+00 6.500 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7979E+00 6.800 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 7.100 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 7.400 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 7.700 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 8.000 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 8.300 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 8.600 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 8.900 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 9.200 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 9.500 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 9.800 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 10.100 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 10.400 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 24.000 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 96.000 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00 720.000 1.1555E+02 3.7206E+00 1.6559E+01 5.3318E-01 1.2415E+02 3.7980E+00

Worst Two-Hour Doses EAB Time Whole Body Thyroid TEDE (hr) (rem) (rem) (rem) 0.0 2.0260E-01 1.1555E+02 3.7206E+00 Licensee results: 3.5 at EAB, 0.5 at LPZ, 3.798 in CR