MONTHYEARML22346A2052022-12-14014 December 2022 Acknowledgment of Response to NRC Inspection Report 05000313/2022011 and 05000368/2022011 and Notice of Violation ML21236A3222021-09-19019 September 2021 Request for Information ML21026A2682021-01-26026 January 2021 Request for Information ML19256A0192019-09-11011 September 2019 Notification of Evaluations of Changes, Tests, and Experiments Inspection (Inspection Report 05000313/2019004 and 05000368/2019004) and Request for Information IR 05000313/20184052018-10-22022 October 2018 NRC Cyber Security Inspection Report 05000313/2018405 and 05000368/2018405 ML17093A8622017-03-31031 March 2017 Notification of NRC Retake Operator Licensing Examination 05000313/2017302 IR 05000313/20164032016-07-19019 July 2016 Cover Letter for NRC Security Inspection Report 05000313/2016403 and 05000368/2016403 IR 05000313/20154022016-03-0202 March 2016 Non-Public Security Inspection Plan for Arkansas Nuclear One (NRC Physical Security Inspection Report Numbers 05000313/2015402 and 05000368/2015402) IR 05000313/20105012011-01-10010 January 2011 IR 05000313-10-501 & 05000368-10-501, Arkansas Nuclear One, Units 1 and 2, Emergency Preparedness Annual Inspection Report ML1013105012010-05-11011 May 2010 Notification of an NRC Triennial Fire Protection Baseline Inspection (NRC Inspection Report 05000313-10-006; 05000368-10-006) and Request for Information IR 05000313/20094012010-03-26026 March 2010 NRC Physical Security Annual Inspection Report 05000313-09-401 and 05000368-09-401 ML0822108242008-08-0808 August 2008 IR 05000313-08-006, and IR 05000368-08-006, on 09/08/2008, Arkansas Nuclear One, Units 1 and 2 - Site-Specific Implementation of B.5.B Phase 2 and 3, Mitigating Strategies Temporary Instruction Inspection IR 05000313/20060052007-04-0909 April 2007 Errata for Arkansas Nuclear One NRC Integrated Inspection Report 05000313-06-005 and 05000368-06-005 ML0708903512007-03-30030 March 2007 Errata for Arkansas Nuclear One NRC Integrated Inspection Report 05000313/2006005 and 05000368/2006005 IR 05000313/20050012005-03-0202 March 2005 Annual Assessment Letter - Arkansas Nuclear One (IR 05000313-05-001; 05000368-05-001) ML0335804052003-11-21021 November 2003 Letter to Craig G. Anderson - Response to Backfit Claim Re NRC IR 05000313-01-006, 05000368-01-006 ML0335803982003-11-21021 November 2003 Letter to Craig G. Anderson - Response to Backfit Claim Re NRC Inspection Report ML0335803952003-11-21021 November 2003 Letter to Craig G. Anderson from Merschoff with Enclosures - Response to Backfit Claim Re NRC IR 05000313-01-006, 05000368-01-006 2022-12-14
[Table view] Category:Letter
MONTHYEARML23326A0392024-01-24024 January 2024 Issuance of Amendment No. 281 Revision to Technical Specifications to Adopt TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b ML24017A1582024-01-17017 January 2024 Submittal of Emergency Plan Revision 50 IR 05000313/20234202024-01-10010 January 2024 Security Baseline Inspection Report 05000313/2023420 and 05000368/2023420 IR 05000313/20234022024-01-0202 January 2024 Security Baseline Inspection Report 05000313/2023402 and 05000368/2023402 ML23354A0022023-12-21021 December 2023 Request for Withholding Information from Public Disclosure ML23349A1672023-12-21021 December 2023 Request for Withholding Information from Public Disclosure ML23348A3572023-12-14014 December 2023 Application to Revise Technical Specifications to Use Online Monitoring Methodology Slides and Affidavit for Pre-Submittal Meeting ML23352A0292023-12-13013 December 2023 Entergy - 2024 Nuclear Energy Liability Evidence of Financial Protection ML23340A1592023-12-13013 December 2023 Entergy Operations, Inc. - Entergy Fleet Project Manager Assignment IR 05000313/20234052023-12-12012 December 2023 Security Baseline Inspection Report 05000313/2023405 and 05000368/2023405 ML23341A0832023-12-11011 December 2023 Material Control and Accounting Program Inspection Report 05000313/368/2023404- Cover Letter ML23305A0922023-12-0707 December 2023 Summary of Regulatory Audit Regarding License Amendment Request to Revise Technical Specifications to Adopt TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times RITSTF Initiative 4b ML23333A1362023-11-29029 November 2023 Supplement to Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation ML23275A2072023-11-28028 November 2023 Issuance of Amendment No. 280 Removal of Technical Specification Condition Allowing Two Reactor Coolant Pump Operation ML23325A1412023-11-21021 November 2023 Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation IR 05000313/20230032023-11-21021 November 2023 Revised - ANO Revised Integrated Inspection Report 05000313/2023003 and 05000368/2023003 and Independent Spent Fuel Storage Installation Inspection Report 07200013/ 2023001 ML23243B0452023-11-13013 November 2023 Request for Withholding Information from Public Disclosure ML23313A0962023-11-13013 November 2023 Integrated Inspection Report 05000313/2023003 and 05000368/2023003 and Independent Spent Fuel Storage Installation Inspection Report 07200013/2023001 ML23311A2082023-11-0909 November 2023 Reassignment of U.S. Nuclear Regulatory Commission Branch Chief in the Division of Operating Reactor Licensing for Plant Licensing Branch IV IR 05000313/20230112023-10-10010 October 2023 Commercial Grade Dedication Inspection Report 05000313/2023011 and 05000368/2023011 IR 05000313/20230052023-08-21021 August 2023 Updated Inspection Plan for Arkansas Nuclear One, Units 1 and 2 (Report 05000313/2023005 and 05000368/2023005) - Mid Cycle IR 05000313/20243012023-08-14014 August 2023 Notification of NRC Initial Operator Licensing Examination 05000313/2024301 IR 05000313/20230022023-08-11011 August 2023 Integrated Inspection Report 05000313/2023002 and 05000368/2023002 and Notice of Violation ML23209A6022023-08-0909 August 2023 Regulatory Audit Plan in Support of License Amendment Request to Revise Technical Specifications to Adopt Risk- Informed Completion Times IR 05000416/20230022023-08-0808 August 2023 Integrated Inspection Report 05000416/2023002 and Independent Spent Fuel Storage Installation Inspection Report 07200050/2023001 ML23208A2132023-08-0303 August 2023 Regulatory Audit Summary Concerning Review of License Amendment Request to Remove Technical Specification Condition Allowing Two Reactor Coolant Pump Operation ML23208A2112023-07-27027 July 2023 Entergy Operations Inc., Application to Revise Technical Specifications to Adopt TSTF-205, Revision of Channel Calibration, Channel Functional Test, and Related Definitions ML23188A1732023-07-12012 July 2023 Request for Withholding Information from Public Disclosure ML23142A2022023-06-29029 June 2023 Issuance of Amendment Nos. 279 and 332 Emergency Plan Staffing Requirements IR 05000313/20234032023-06-28028 June 2023 Security Baseline Inspection Report 05000313/2023403 and 05000368/2023403 ML23178A0892023-06-26026 June 2023 August 2023 Emergency Preparedness Program Inspection-Request for Information ML23166B0902023-06-21021 June 2023 Request for Relief ANO1 ISI 036 Regarding Volumetric Examination Requirements ML23180A1082023-06-20020 June 2023 ANO Unit 1 SAR Amendment 31, TRM, TS Bases, 10 CFR 50.59 Report, and Commitment Change Summary Report IR 05000313/20234012023-06-13013 June 2023 Cyber Security Inspection Report 05000313/2023401 and 05000368/2023401 ML23130A2972023-05-17017 May 2023 Notification of Inspection (NRC Inspection Report 05000313/2023003) and Request for Information ML23121A3012023-05-10010 May 2023 Regulatory Audit Plan in Support of License Amendment Request to Revise Technical Specifications to Adopt Risk - Informed Completion Times ML23114A3572023-05-10010 May 2023 Regulatory Audit Summary Concerning Review of Request for Alternative ANO-CISI-002 Regarding Containment Inservice Inspection Frequency ML23130A2732023-05-10010 May 2023 and Waterford 3 Steam Electric Station - Response to Regulatory Issue Summary 2023-01, Preparation and Scheduling of Operator Licensing Examinations IR 05000313/20230012023-05-0909 May 2023 Integrated Inspection Report 05000313/2023001 and 05000368/2023001 ML23118A3202023-05-0808 May 2023 Notification of Biennial Problem Identification and Resolution Inspection and Request for Information (05000313;05000368/2023010) IR 05000368/20233012023-05-0101 May 2023 NRC Examination Report 05000368/2023301 ML23117A2172023-05-0101 May 2023 Safety Evaluation for Quality Assurance Program Manual Reduction in Commitment ML23108A1362023-04-24024 April 2023 Approval of Request for Half-Nozzle Repair of Reactor Vessel Closure Head Penetration No. 46 ML23110A1122023-04-20020 April 2023 Annual Report for Entergy Quality Assurance Program Manual Changes Under 10 CFR 50.54(a)(3), 10 CFR 71.106, and 10 CFR 72.140(d). Notification of Application of Approved Appendix B to 10 CFR 72 Subpart G 2024-01-24
[Table view] |
Text
4t*^ tC1t, UNITED STATES 0 in NUCLEAR REGULATORY COMMISSION 611 RYAN PLAZA DRIVE, SUITE 400 ARLINGTON, TEXAS 760111-B064 Craig G. Anderson, Vice President Operations 0071 Arkansas Nuclear One Entergy Operations, Inc.
1448 S.R. 333 Russeliville, Arkansas 72801-0967
SUBJECT:
RESPONS GARDING NRC INSPECTION REPOR
Dear Mr. Anderson:
a ..
As documented in NRC Inspection Report 50-313;-368/01-06, dated August 20, 2001, the NRC identified an unresolved item in the Unit 1 emergency diesel generator corridor and the Unit 1.
north electrical switchgear room concerning use of manual actions in lieu of providing protection for cables associated with equipment necessary for achieving and maintaining hot shutdown as specified in 10 CFR Part 50, Appendix R.Section III.G.2. This issue was considered unresolved pending further NRC review and the determination of its risk. Subsequently, in an exit meeting held on August 30, 2001, the NRC informed Entergy Operations, Inc., that the existing configurations did not conform to the .requirements of 10 CFR Part 50, Appendix R, Section III.G.2. However, the issue remained unresolved pending the completion of the NRC's risk determination.
Your letter of September 28, 2001, claimed that our position that manual actions cannot be used to comply with 10 CFR Part 50, Appendix R, Section Il1.G.2, was a backfit. At issue is your use of manual actions for achieving and maintaining hot shutdown conditions in the event of a fire in the Unit 1 emergency diesel generator corridor (Fire Zone 98J) and north switchgear room (Fire Zone 99M). In this letter, you asserted that the NRC has accepted such manual actions in the past, and stated that our position with respect to disallowing the use of manual actions for complying with Section III.G.2 of Appendix R should be considered a backlit that is generic to all plants.
On October 26, 2001, and again on January 17, 2002, we convened a backfit panel in accordance with NRC Management Directive 8.4, NRC Program for Management of Plant-Specific Backfitting of Nuclear Power Plants," to review your backfit claim as stated in your letter of September 28, 2001. After careful consideration of your appeal, we have determined that (1) the NRC did not impose a regulatory staff position that is new or different from a
- previously applicable staff position relative to the requirements of 10 CFR Part 50, Appendix R, SectionJll.G.2; (2) the NRC did not approve the use of manhual'actions for complying with 10 CFR Part 50, Appendix R, Section III.G.2, in the Unit 1 diesel generator corridor and north
- ~ electrical switchgear room in lieu of meeting the requirements of 10 CFR Part 50, Appendix R, Section II.G.2.a, Il.G.2.b, or IllI.G.2.c; and (3) youflethodology for using manual actions (in 1he event of a fire in the Unit 1 diesel generator corridor and north switchgear room), in lieu of