Letter Sequence Other |
---|
|
|
MONTHYEARML0215501202002-06-0303 June 2002 Technical Specifications to Amendments 223 and 248 Technical Specification Surveillance Frequency and Action Requirement for Suppression Chamber-to-Drywell Vacuum Breakers Project stage: Other ML0215402992002-06-0303 June 2002 Issuance of Amendment Re TS Surveillance Frequency and Action Requirements for Suppression chamber-to-drywell Vacuum Breakers Project stage: Approval 2002-06-03
[Table View] |
Technical Specifications to Amendments 223 and 248 Technical Specification Surveillance Frequency and Action Requirement for Suppression Chamber-to-Drywell Vacuum BreakersML021550120 |
Person / Time |
---|
Site: |
Brunswick ![Duke Energy icon.png](/w/images/7/75/Duke_Energy_icon.png) |
---|
Issue date: |
06/03/2002 |
---|
From: |
NRC/NRR/DLPM |
---|
To: |
|
---|
References |
---|
TAC MB2110, TAC MB2111 |
Download: ML021550120 (4) |
|
|
---|
Category:Technical Specifications
MONTHYEARML23195A0782023-08-29029 August 2023 Issuance of Amendments Regarding the Adoption of Technical Specifications Task Force Traveler TSTF-554, Revision 1 ML22082A2682022-05-0202 May 2022 Issuance of Amendment Nos. 308 and 336 Regarding the Adoption of Technical Specifications Task Force Traveler TSTF-505, Revision 2 ML21067A2242021-04-30030 April 2021 Issuance of Amendment Nos. 305 and 333 to Revise License Conditions to Adopt 10 CFR 50.69, Risk Informed Categorization and Treatment of Structures, Systems, and Components for Nuclear Power Reactors RA-21-0141, Units 1 & 2 - Supplement to License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative2021-04-26026 April 2021 Units 1 & 2 - Supplement to License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative ML20069J6312020-03-19019 March 2020 Correction to Amendment No. 304 Regarding Request to Relocate Specific Surveillance Frequencies to a Licensee Controlled Program ML19346C7922020-02-0606 February 2020 Issuance of Amendments Nos. 298 and 326 to Modify Technical Specification to Extend Containment Leakage Test Intervals BSEP 17-0111, Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension of Surveillance Requirements2017-11-28028 November 2017 Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension of Surveillance Requirements BSEP 17-0078, Request for License Amendment - DC Sources - Operating Surveillance Requirement (SR) 3.8.4.52017-10-0303 October 2017 Request for License Amendment - DC Sources - Operating Surveillance Requirement (SR) 3.8.4.5 ML17180A5962017-08-29029 August 2017 Issuance of Amendments to Adopt TSTF-423 Technical Specifications End States, NEDC-32988-A ML17130A7802017-07-12012 July 2017 Issuance of Amendments Regarding Request to Adopt Technical Specifications Task Force (TSTF) Traveler TSTF-545 ML17066A3742017-04-26026 April 2017 Issuance of Amendments Re. Application to Revise TSs to Adopt TSTF-427, Rev. 2, Using the Consolidated Line Item Improvement Process (CAC Nos. MF8039 Through MF8049) ML16019A0292016-02-0909 February 2016 Issuance of Amendments Regarding the Adoption of Topical Report ANP-10298P-A, Revision 1 ML15344A1532016-01-0808 January 2016 Issuance of Amendments Regarding Emergency Action Level Scheme Upgrade BSEP 15-0007, Request for License Amendments - Adoption of Topical Report ANP-10298P-A, Revision 12015-02-19019 February 2015 Request for License Amendments - Adoption of Topical Report ANP-10298P-A, Revision 1 ML12339A0672012-12-18018 December 2012 Issuance of License Amendments Regarding Cyber Security BSEP 12-0050, Request for License Amendments - Diesel Generator (DG) Completion Time (CT) Extension for Technical Specification (TS) 3.8.1, AC Sources - Operating2012-06-19019 June 2012 Request for License Amendments - Diesel Generator (DG) Completion Time (CT) Extension for Technical Specification (TS) 3.8.1, AC Sources - Operating BSEP 09-0019, Application to Revise Technical Specifications Regarding Primary Containment Isolation Instrumentation in Accordance with TSTF-306, Revision 22009-10-27027 October 2009 Application to Revise Technical Specifications Regarding Primary Containment Isolation Instrumentation in Accordance with TSTF-306, Revision 2 ML0923702842009-08-18018 August 2009 Units, 1 and 2, Request for License Amendments to Revise Local Power Range Monitor Calibration Frequency BSEP-09-0026, Request for License Amendment - Technical Specification 3.6.1.6, Suppression Chamber-to-Drywell Vacuum Breakers.2009-03-0909 March 2009 Request for License Amendment - Technical Specification 3.6.1.6, Suppression Chamber-to-Drywell Vacuum Breakers. BSEP 08-0156, Request for License Amendment - Adoption of TSTF-478, Revision 2 - BWR Technical Specification Changes That Implement the Revised Rule for Combustible Gas Control2008-11-24024 November 2008 Request for License Amendment - Adoption of TSTF-478, Revision 2 - BWR Technical Specification Changes That Implement the Revised Rule for Combustible Gas Control ML0817503332008-07-25025 July 2008 Technical Specifications, Adopted TSTF-448, Revision 3, Control Room Habitability (Tac Nos. MD6336 and MD6337) ML0819801252008-07-0909 July 2008 Submittal of Updated Technical Specifications Pages Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using Consolidated Line Item Improvement Process BSEP 08-0037, Progress Energy Carolinas' Submittal of Revision to Technical Specification 3.2.3, Linear Heat Generation Rate as Part of License Amendments for the Brunswick Steam Electric Plant Units 1 & 22008-03-0505 March 2008 Progress Energy Carolinas' Submittal of Revision to Technical Specification 3.2.3, Linear Heat Generation Rate as Part of License Amendments for the Brunswick Steam Electric Plant Units 1 & 2 BSEP 07-0139, Response to Request for Additional Information Regarding Application to Revise Technical Specifications Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 32008-02-27027 February 2008 Response to Request for Additional Information Regarding Application to Revise Technical Specifications Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3 ML0801800872008-02-0808 February 2008 Technical Specifications ML0801800952008-02-0808 February 2008 Technical Specifications ML0733203672007-11-27027 November 2007 Technical Specifications, Issuance of Amendment Storage of Areva Np Fuel BSEP 07-0081, Request for License Amendments to Revise Technical Specification 5.5.6, Inservice Testing Program, to Adopt Technical Specification Task Force (TSTF) Standard Technical Specification Change Traveler TSTF-479, Revision 02007-09-26026 September 2007 Request for License Amendments to Revise Technical Specification 5.5.6, Inservice Testing Program, to Adopt Technical Specification Task Force (TSTF) Standard Technical Specification Change Traveler TSTF-479, Revision 0 BSEP 07-0103, Supplement to Request for License Amendment Technical Specification 3.8.3, Diesel Fuel Oil, Provisions for Main Fuel Oil Storage Tank Inspection, Cleaning, or Repair2007-09-20020 September 2007 Supplement to Request for License Amendment Technical Specification 3.8.3, Diesel Fuel Oil, Provisions for Main Fuel Oil Storage Tank Inspection, Cleaning, or Repair BSEP 07-0058, Application to Revise Technical Specifications Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using the Consolidated Line Item Improvement Process2007-07-17017 July 2007 Application to Revise Technical Specifications Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using the Consolidated Line Item Improvement Process ML0704705612007-02-15015 February 2007 Tech Spec Pages for Amendments 241 and 269 to Adopt TSTF-372 BSEP 06-0136, Request for License Amendment, Technical Specification 3.4.1, Recirculation Loops Operating Recirculation Loop Operating Requirements.2006-12-21021 December 2006 Request for License Amendment, Technical Specification 3.4.1, Recirculation Loops Operating Recirculation Loop Operating Requirements. BSEP 06-0067, Request for License Amendment, Technical Specification 3.8.3, Diesel Fuel Oil, Provisions for Main Fuel Oil Storage Tank Inspection, Cleaning, or Repair2006-09-28028 September 2006 Request for License Amendment, Technical Specification 3.8.3, Diesel Fuel Oil, Provisions for Main Fuel Oil Storage Tank Inspection, Cleaning, or Repair ML0521703612005-08-0505 August 2005 Technical Specifications, Correct Omitted Page BSEP 05-0076, Submittal of Updated Technical Specification Pages, Technical Specification 3.4.5, RCS Leakage Detection Instrumentation2005-06-0909 June 2005 Submittal of Updated Technical Specification Pages, Technical Specification 3.4.5, RCS Leakage Detection Instrumentation ML0515403142005-05-31031 May 2005 Technical Specification Pages Technical Specification Improvement to Revise Control Rod Scram Time Testing Frequency ML0515403132005-05-31031 May 2005 Technical Specification Pages Technical Specification Improvement to Revise Control Rod Scram Time Testing Frequency ML0516800952005-05-23023 May 2005 E-mail Brunswick Cooling Tower Information BSEP 05-0060, Request for License Amendment Technical Specification 3.4.5, RCS Leakage Detection Instrumentation.2005-05-17017 May 2005 Request for License Amendment Technical Specification 3.4.5, RCS Leakage Detection Instrumentation. ML0506601502005-03-0404 March 2005 Technical Specification Pages, Amendment on Addition of Tracg Methodology for Determining Core Operating Limits (Tac No. MC4385) ML0503905032005-02-0202 February 2005 Tech Spec Pages for Amendment No. 261 Elimination of Requirements for Hydrogen and Oxygen Monitors Using the Consolidated Line Item Improvement Process ML0504002762005-02-0202 February 2005 Tech Spec Pages for Amendment No. 234 Elimination of Requirements for Hydrogen and Oxygen Monitors Using the Consolidated Line Item Improvement Process ML0501202082005-01-11011 January 2005 Technical Specifications, Increase Flexibility in Mode Restraints ML0501202112005-01-11011 January 2005 Technical Specifications, Increase Flexibility in Mode Restraints BSEP 04-0124, Application for Technical Specification Change Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process2004-09-0303 September 2004 Application for Technical Specification Change Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process ML0408906732004-03-26026 March 2004 Technical Specification Pages 2.0-1 and 5.0-20, Amendment No. 231 Re. Minimum Critical Power Ratio Safety Limit ML0336001152003-12-19019 December 2003 Application for Technical Specification Change Re Mode Change Limitations Using Consolidated Line Item Improvement Process BSEP 03-0148, Request for License Amendment Technical Specification 2.1.1.2, Reactor Core Minimum Critical Power Ration Safety Limits and Revision to References in Technical Specification 5.6.5, Core Operating Limits Report2003-10-31031 October 2003 Request for License Amendment Technical Specification 2.1.1.2, Reactor Core Minimum Critical Power Ration Safety Limits and Revision to References in Technical Specification 5.6.5, Core Operating Limits Report BSEP-03-0003, Radioactive Effluent Release Report for 2002, Index, Section 6 Through Appendix H2003-04-28028 April 2003 Radioactive Effluent Release Report for 2002, Index, Section 6 Through Appendix H ML0308706642003-03-25025 March 2003 Technical Specification Page for Amendment 254 to License DPR-62, Revising Safety Limit Minimum Critical Power Ratio Values from 1.09 to 1.11 2023-08-29
[Table view] |
Text
Suppression Chamber-to-Drywell Vacuum Breakers 3.6.1.6 3.6 CONTAINMENT SYSTEMS 3.6.1.6 Suppression Chamber-to-Drywell Vacuum Breakers LCO 3.6.1.6 Eight suppression chamber-to-drywell vacuum breakers shall be OPERABLE for opening.
AND Ten suppression chamber-to-drywell vacuum breakers shall be closed, except when performing their intended function.
APPLICABILITY: MODES 1, 2, and 3.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required A.1 Restore one vacuum 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> suppression chamber- breaker to OPERABLE to-drywell vacuum status.
breaker inoperable for opening.
B. One suppression B.1 Close the open vacuum 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> chamber-to-drywell breaker.
vacuum breaker not closed.
C. Required Action and C.1 Be in MODE 3. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met. AND C.2 Be in MODE 4. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> Brunswick Unit 1 3.6-18 Amendment No.223
Suppression Chamber-to-Drywell Vacuum Breakers 3.6.1.6 cZIIDJITE i AMCF PFf1IIIPFMFNTS 4.J11111S* I **m.-9 . -_____________________
SURVEILLANCE FREQUENCY SR 3.6.1.6.1 NOTE ----- -------------------.
Not required to be met for vacuum breakers that are open during Surveillances.
Verify each vacuum breaker is closed. 14 days AND Within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> after any discharge of steam to the suppression chamber from any source 3.6.1.6.2 Perform a functional test of each 31 days required vacuum breaker. AND Within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after any discharge of steam to the suppression chamber from any source SR 3.6.1.6.3 Verify the full open setpoint of each 24 months required vacuum breaker is
3.6-19 Amendment No.223 Brunswick Unit 1
Suppression Chamber-to-Drywell Vacuum Breakers 3.6.1.6 3.6 CONTAINMENT SYSTEMS 3.6.1.6 Suppression Chamber-to-Drywell Vacuum Breakers
[CO 3.6.1.6 Eight suppression chamber-to-drywell vacuum breakers shall be OPERABLE for opening.
AND Ten suppression chamber-to-drywell vacuum breakers shall be closed, except when performing their intended function.
APPLICABILITY: MODES 1, 2, and 3.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required A.1 Restore one vacuum 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> suppression chamber- breaker to OPERABLE to-drywell vacuum status.
breaker inoperable for opening.
B. One suppression B.1 Close the open vacuum 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> I chamber-to-drywell breaker.
vacuum breaker not closed.
C. Required Action and C.1 Be in MODE 3. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met. AND C.2 Be in MODE 4. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> Brunswick Unit 2 3.6-18 Amendment No.248
Suppression Chamber-to-Drywell Vacuum Breakers 3.6.1.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY i
SR 3.6.1.6.1 -------------
-- NOTE----------------
Not required to be met for vacuum breakers that are open during Surveillances.
Verify each vacuum breaker is closed. 14 days AND Within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> after any discharge of steam to the suppression chamber from any source
.4-SR 3.6.1.6.2 Perform a functional test of each 31 days required vacuum breaker.
AND Within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after any discharge of steam to the suppression chamber from any source SR 3.6.1.6.3 Verify the full open setpoint of each 24 months required vacuum breaker is
Brunswick Unit 2 3.6-19 Amendment No. 248