Distribution Systems-Shutdown 3.8.8 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
(continued)
A.2.3 Initiate action to suspend Immediately operations with a potential for draining the reactor vessel.
AND A.2.4 Initiate actions to restore Immediately required AC and DC electrical power distribution subsystems to OPERABLE status.
AND A.2.5 Declare associated Immediately required shutdown cooling subsystem(s) inoperable and not in operation.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.8.1 Verify correct breaker alignments and indicated power 7 days availability to required AC and DC electrical power distribution subsystems.
Brunswick Unit 2 3.8-39 Amendment No. 235 l