IR 05000220/2019011

From kanterella
(Redirected from IR 05000410/2019011)
Jump to navigation Jump to search
Design Basis Assurance Inspection (Programs) Inspection Report 05000220/2019011 and 05000410/2019011
ML19336B928
Person / Time
Site: Nine Mile Point  
(DPR-063, NPF-069)
Issue date: 11/29/2019
From: Glenn Dentel
Engineering Region 1 Branch 2
To: Bryan Hanson
Exelon Generation Co, Exelon Nuclear
Dentel G
References
IR 2019011
Download: ML19336B928 (9)


Text

November 29, 2019

SUBJECT:

NINE MILE POINT NUCLEAR STATION - DESIGN BASIS ASSURANCE INSPECTION (PROGRAMS) INSPECTION REPORT 05000220/2019011 AND 05000410/2019011

Dear Mr. Hanson:

On November 7, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Nine Mile Point Nuclear Station and discussed the results of this inspection with Mr. Peter Orphanos, Site Vice President and other members of your staff. The results of this inspection are documented in the enclosed report.

The NRC inspectors did not identify any finding or violation of more than minor significance.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/

Glenn T. Dentel, Chief Engineering Branch 2 Division of Reactor Safety

Docket Nos. 05000220 and 05000410 License Nos. DPR-63 and NPF-69

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000220 and 05000410

License Numbers:

DPR-63 and NPF-69

Report Numbers:

05000220/2019011 and 05000410/2019011

Enterprise Identifier: I-2019-011-0019

Licensee:

Exelon Generation Company, LLC

Facility:

Nine Mile Point Nuclear Station

Location:

Oswego, NY

Inspection Dates:

October 21, 2019 to November 7, 2019

Inspectors:

C. Bickett, Senior Reactor Inspector

D. Kern, Senior Reactor Inspector

J. Schoppy, Senior Reactor Inspector

Approved By:

Glenn T. Dentel, Chief

Engineering Branch 2

Division of Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a design basis assurance inspection of the environmental qualification program implementation at Nine Mile Point Nuclear Station in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

===71111.21N - Design Bases Assurance Inspection (Programs)

The inspectors evaluated environmental qualification program implementation through the sampling of the components listed below.

Select Sample Components to Review - Risk Significant/Low Design (Inside/Outside Containment) (IP Section 02.01)===

(1) Unit 1, Reactor Pressure High/High Trip Pressure Transmitter - (PT-36-08C)

[transmitter, seal]

(2) Unit 1, Motor Actuator - Core Spray Discharge Isolation Valve 11 (ACT-40-12)

[actuator, circuit breaker, torque switch, position switch, thermal relay]

(3) Unit 1, Drywell Temperature Element (TE-201-64) [thermocouple, quick disconnect connectors]
(4) Unit 2, Outboard Main Steam Isolation Valve (2MSS*AOV7B) [solenoid valve cluster assembly, limit switches]
(5) Unit 2, Reactor Core Isolation Cooling Steam Supply Valve to Turbine (2ICS*MOV120) [actuator, motor, limit switch, lubricant]
(6) Unit 2, Drywell Area High Range Radiation Monitor (2RMS*RE1B) [radiation monitoring system]

Select Sample Components to Review - Primary Containment (Inside Containment) (IP Section 02.01) (2 Samples)

(1) Unit 1, Pressure Safety Valve - Automatic Depressurization System Electromatic Relief Valve 121 (PSV-01-102C) [solenoid operated valve, position switch, cables]
(2) Unit 2, Containment Monitoring System from Drywell, Inside Automatic Isolation Valve (2CMS*SOV61A) [solenoid, limit switch, seal]

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On November 7, 2019, the inspectors presented the design basis assurance inspection (programs) inspection results to Mr. Peter Orphanos, Site Vice President and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N Calculations

1EQNORMTEMP.0001

Determination of Normal Ambient Temperatures Used

as Input to the Unit 1 Environmental Qualification

Program

Revision 0

1EQPBD

Nine Mile Point Unit 1 Environmental Qualification

Program Basis Document (Volumes 1, 2, and 3)

Revision 4

1NER-EQ-004

Unit 1 Environmental Qualification Master Equipment

List (EQML) Reconstitution

Revision 8

2EQNORMTEMP.0001

Determination of Normal Ambient Temperatures Used

as Input to the Unit 2 Environmental Qualification

Program

Revision 0

2EQNORMTEMP.2014

Temperature Monitoring Data Collected from 2012 to

2014 at Unit 2 for Use by the EQ Program

Revision 0

2EQPBD

Nine Mile Point Unit 2 Environmental Qualification

Program Basis Document (Volumes 1, 2, and 3)

Revision 4

2NER-EQ-005

Unit 2 Environmental Qualification Master List

(EQML) Reconstitution

Revision 3

ECP 17-000670

EQ Program Impact Evaluation

Revision 0

EQ1AGEPCMULTIP.0001 Qualified Life for EGS Quick Disconnects

Revision 0

EQ2AGEPCMSS04

Qualified Life Calculation for MSIV Solenoid Valve

Cluster Assembly (SVCA) with AVCO Solenoid

Valves

Revision 0

Corrective Action

Documents

Resulting from

Inspection

290078*

290145*

290625*

290633*

290635*

292360*

293204*

294393*

295049*

295065*

295227*

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

295712*

Engineering

Evaluations

1EQDP-CABL006

Control and Low Voltage Power Cable Environmental

Qualification Document Package

Revision 1

1EQDP-CABL013

Low Voltage Power, Control, Thermocouple, and

Instrumentation Cable Environmental Qualification

Document Package

Revision 2

1EQDP-MCC001

MCC Electrical Replacement Components

Environmental Qualification Document Package

Revision 2

1EQDP-MCC002DOR

Motor Control Center (MCC) Environmental

Qualification Document Package

Revision 2

1EQDP-MOV001

Components for use in Limitorque Valve Motor

Operator Environmental Qualification Document

Package

Revision 3

1EQDP-MOV002DOR

Valve Motor Operator Environmental Qualification

Document Package

Revision 2

1EQDP-POS003DOR

Position Switch Environmental Qualification

Document Package

Revision 1

1EQDP-SEAL004

SAIC/EGS Quick Disconnect Connector Model

Numbers 880701 and 913601

Revision 3

1EQDP-SOV002DOR

Solenoid Operated Valve (Solenoid Actuator

Assembly) Environmental Qualification Document

Package

Revision 2

1EQDP-TE004

PYCO Corp. Models 102-3171-08-2.0-4, 102-3171-

08-1.8-4.0, 102-9039-08-6 Thermocouple

Temperature Detector

Revision 2

1EQDP-XMTR007

Rosemount 1152N Series Transmitters

Revision 1

2EQDP-MOV003

Motor on Motor Operated Valve Environmental

Qualification Document Package

Revision 1

2EQDP-POS001

Namco Controls EA740 Series Limit Switch

Revision 4

2EQDP-RE002

High Range Radiation Monitor - Kaman

Instrumentation Corporation

Revision 1

2EQDP-SEAL001

Conax Electric Conductor Seal Assembly (SCSA) -

N-11XXX Series

Revision 7

2EQDP-SOV005

Solenoid Valves Cluster Assembly - Ralph A. Hiller

Revision 2

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Company

2EQDP-SOV008

Target Rock Solenoid Valve - 76P Series

Revision 2

Miscellaneous

NMP Environmental Qualification Program FASA

dated

10/18/19

ECN 2009-000280

Revision of SRV Acoustic Monitoring System for RG 1.97 Category 2 to Category 3

Revision 0

ECP 15-000422-CN-018

EQ Exemption Basis for ECP-15-000422 which

Downgraded the H2-O2 System from Safety Related

to Non-Safety Related

Revision 0

N2H19800VALVOP001

Maintenance and Instruction Manual for Main Steam

Isolation Valve Actuator Model SA-A087

Revision 1

N2T02000VALVE06

Project Technical Manual Target Rock Solenoid

Operated Valve

Revision 12

Procedures

CC-AA-203

Environmental Qualification Program

Revision 14

N1-IPM-TRS-001

EQ Area Temperature Data Logger Maintenance

Revision 2

N2-IPM-TRS-001

EQ Area Temperature Data Logger Maintenance

Revision 2

NMP-CM-7.01-2000

Environmental Qualification (EQ) Program

Administration

Revision 0

NMP-CM-7.01-2003

Preparation and Revision of an Environmental

Qualification Document Package

Revision 1