October 17, 2019
SUBJECT:
NINE MILE POINT NUCLEAR STATION, UNITS 1 AND 2 - EMERGENCY PREPAREDNESS BIENNIAL EXERCISE INSPECTION REPORT 05000220/2019501 AND 05000410/2019501
Dear Mr. Hanson:
On October 10, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Nine Mile Point Nuclear Station, Units 1 and 2 and discussed the results of this inspection with Mr. Peter Orphanos and other members of your staff. The results of this inspection are documented in the enclosed report.
The NRC inspectors did not identify any finding or violation of more than minor significance.
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely,
/RA/
Fred L. Bower, III, Chief Plant Support Branch Division of Reactor Safety
Docket Nos. 05000220 and 05000410 License Nos. DPR-63 and NPF-69
Enclosure:
As stated
Inspection Report
Docket Numbers:
05000220 and 05000410
License Numbers:
Report Numbers:
05000220/2019501 and 05000410/2019501
Enterprise Identifier: I-2019-501-0023
Licensee:
Exelon Generation Company, LLC
Facility:
Nine Mile Point Nuclear Station, Units 1 and 2
Location:
Scriba, NY
Inspection Dates:
October 7, 2019 to October 10, 2019
Inspectors:
J. DeBoer, Reactor Inspector
B. Haagensen, Senior Resident Inspector
J. Lilliendahl, Sr Emergency Response Coord
J. Schoppy, Senior Reactor Inspector
Approved By:
Fred L. Bower, III, Chief
Plant Support Branch
Division of Reactor Safety
SUMMARY
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an emergency preparedness biennial exercise inspection at Nine Mile Point Nuclear Station, Units 1 and 2 in accordance with the Reactor Oversight Process.
The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.
List of Findings and Violations
No findings or violations of more than minor significance were identified.
Additional Tracking Items
None.
INSPECTION SCOPES
Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.
REACTOR SAFETY
71114.01 - Exercise Evaluation
Inspection Review (IP Section 02.01-02.11) (1 Sample)
- (1) The inspectors evaluated the biennial emergency plan exercise. The exercise scenario simulated a seismic event, a reactor coolant system leak inside primary containment, and an aftershock seismic event which led to a reactor coolant system leak outside primary containment on October 8, 2019.
71114.04 - Emergency Action Level and Emergency Plan Changes
Inspection Review (IP Section 02.01-02.03) (1 Sample)
- (1) The inspectors evaluated the following submitted Emergency Action Level and Emergency Plan changes:
Evaluation 19-24, EP-AA-111, EP-CE-111, Emergency Classification and Protective Action Recommendations, Revisions 22 & 8
Evaluation 19-26, EP-AA-120-1006, EP Reportability-Loss of Emergency Preparedness, Revision 5
This evaluation does not constitute NRC approval.
71114.08 - Exercise Evaluation Scenario Review
Inspection Review (IP Section 02.01 - 02.04) (1 Sample)
- (1) The inspectors reviewed and evaluated the proposed scenario for the biennial emergency plan exercise on September 9,
OTHER ACTIVITIES - BASELINE
===71151 - Performance Indicator Verification
The inspectors verified licensee performance indicators submittals listed below:
EP01: Drill/Exercise Performance (IP Section 02.12)===
- (1) July 1, 2018 - September 30, 2019
EP02: ERO Drill Participation (IP Section 02.13) (1 Sample)
- (1) July 1, 2018 - September 30, 2019
EP03: Alert & Notification System Reliability (IP Section 02.14) (1 Sample)
- (1) July 1, 2018 - September 30,
INSPECTION RESULTS
No findings were identified.
EXIT MEETINGS AND DEBRIEFS
The inspectors verified no proprietary information was retained or documented in this report.
On October 10, 2019, the inspectors presented the emergency preparedness biennial exercise inspection results to Mr. Peter Orphanos and other members of the licensee staff.
DOCUMENTS REVIEWED
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Corrective Action
Documents
286090
286391
286423
286444
286447
286448
286451
286464
286479
286483
286528
Miscellaneous
Nine Mile Point 2019 Emergency Preparedness Biennial
Exercise Scenario Package
71151
Corrective Action
Documents
4158484
4163100
4164892
200222
211532
26475
245155
273651
Corrective Action
Documents
Resulting from
Inspection
286464
286680