Text

-__ _ ___ - ____

,

UNITE 3 STATES -

  • [ $mpfou

,

'o NUCLEAR HEGULATORY COMMISSION

-

~

y REGloN li p

g'

j 101 MARIETTA STREET, N.W.

's ATL ANTA, GEORGI A 30323

\\...+ /

Report Nos.: 50-338/86-12 and 50-339/86-12

-

Licensee: Virginia Electric and Power Company Richmond, VA 23261 Docket Nos.: 50-338 and 50-339 License Nos.: NPF-4 and NPF-7 Facility Name: North Anna 1 and 2 Inspection Conduct d:

pril 22-23, 1986 Inspector:

MC Mt'M

6I

~~

N. Econor50s'

AatySignid

^

' Approved Ihfu 6. -& [M v

J. J. Blake,'Section Chief I

Date Signed Engineering Branch Division of Reactor Safety l

SUMMARY Scope:

Routine, unannounced inspection in the areas of licensee action on previcus open items, review and evaluation of inservice inspection results, review of the progress in the development of a program to generate and issue controlled drawings for future ISI activity at both units.

Results: No violations or deviations were identified.

.

8606300437 860617 PDR ADOCK 05000338 G

PDR l --

,.

_

,

..

-

.

REPORT DETAILS 1.

Persons Contacted

.

Licensee Employees E. W. Harrell, Station Manager

  • E. R. Smith, Jr., Assistant Station Manager
  • J. A. Stall, Superintendent Technical Services
  • D. J. Forten, ISI Supervisor Corporate
  • L. N. Hartz, ISI Supervisor North Anna Power Station (NAPS)

R. E. Tegethoff, Staff Engineer, ISI Group

  • J. H. Liberstien, Licensing Coordinator NAPS V. L. Lawshe, Lead QC Inspector, NAPS Other licensee employees contacted included technicians, and office personnel.

NRC Resident Inspector L. King, Resident Inspector

  • Attended exit interview 2.

Exit Interview

~

The inspection scope and findings were summarized on April 23, 1986, with those persons indicated in paragraph I above. The inspector followup item (IFI) listed below was discussed in detail.

(0 pen) IFI 338, 339/86-12-01, Reactor Coolant Pump (RCP) Fly Wheel Assembly Procedure, paragraph 6.

The licensee did not identify as proprietary any of the materials provided to or reviewed by the inspector during this inspection.

3.

Licensee Action on Previous Enforcement Matters This subject was not addressed.

4.

Unresolved Items Unresolved items were not identified during this inspection.

5.

Inspector Followup Items (Closed) IFI 338/84-34-03, Corrective Action on Recirculation Heat Exchanger.

This item should have been included in the documentation of the closing action discussed in previous Report No. 50-338, 339/85-17.

_

---

____

____

I

.

.

(0 pen) IFI 338, 339/85-37-01, Review of Computer Aided Drafting Program:

This item was generated when the inspector noted that the isometric drawings used in the Inservice Inspection (ISI) plan for North Anna did not necessarily reflect existing as-built conditions. In response to this observation, the licensee indicated that the ISI program including this matter was under review by NUTECH and would be in a better position to discuss the matter in more detail during the next inspection.

During this inspection, the inspector held a meeting with cognizant person-nel involved in this matter and aoain expressed concern over the lack of controlled ISI isometric drawings and administrative controls, plans, and procedures for issuing and updating these drawings. The licensee's represen-tative described North Anna's plan for preparing controlled isometric drawings in time for the upcoming 10 year outages and the appropriate administrative procedures to control the issuance and revisions as required.

The licensee agreed to provide the inspector by May 5,1986, a tentative schedule for accomplishing these tasks. This matter will remain open as an IFI until the proposed drawings have been issued and administrative controls as appropriate have been implemented.

6.

Inservice Inspection - Data Review and Evaluation (737558) (Unit 2)

Records of completed nondestructive examinations were selected and reviewed to ascertain whether the methods, technique and extent of the examination complied with the ISI plans and applicable NDE procedures; findings were properly recorded and evaluated by qualified personnel; programmatic deviations were recorded as required; personnel and instruments, calibrations blocks and NDE materials (penetrants, couplets) were designated and qualification:/ certifications were on file.

The applicable code for this activity was ASME,Section XI,1974 Edition through the 1975 Summer Addenda.

Records selected for this review were as follows:

-

Examination Comments Component Weld Method Results

'

Fly Wheel"C" Surface / Visual /

Indications identified

--

  1. 02-RC-P-1C Volumetric with liquid penetrant repaired per EWR#

86-028 Pipe to Safe 16DM Surface /

Three indications l

End B4.1 volumetric indentified with liquid penetrant repaired per EWR #86-124.

Reactor Vessel 20 thru 38 Surface /

Clear Studs and Nuts volumetric repaired per EWR#86-124 Bl.8

_ _ _ _ _.

-

.

.

CRDM Housing 39,51,63 Surface /

Welds B1.18 volumetric Steam Generator "A" Girth Weld, Surface (MT-)

Clear 4 areas @ 90*

intervals ~

2 ft/ area RC pipe loop 2 -4(DM) Pipe to Surface 84.1 Safe End volumetric-5(DM) Pipe Safe End to Elbow RPV Head to Weld Segment volumetric Flange 120* - 240 Bl.3 RPV Shell to Partial volumetric Flange 139.66 -195.52 Bl.3 238.97 -270 344.49 -356.9 Within these areas, the inspector noted that the indications observed on the flywheel race surface were identified as drag marks which line up with vertical indications in two different position on the shaft. In that this damage appeared to be a maintenance problem, i.e.,

an error in alignment during reassembly. The inspector asked to review the applicable procedure for this activity entitled, " Trouble Shooting, Repair and Inspection of Reactor Coolant Pump Motor," EMP-C-RC-4 dated 01-16-86. In reference to the subject activity, the above procedure was found lacking in specific instruction for the disassembly and reassembly of the flywheel as it only referenced the vendors manual, i.e., Section 4 of the Westinghouse Technical Manual. The inspector stated that providing instructions only by reference defeats the intent of such procedures which are written for the purpose of providing detail instruction to the craft.

In this case, it was apparent that failure of the procedure to provide the required instruction for reassembly resulted in the damage to the flywheel. The licensee agreed to review the procedure in question, and revise it to contain the information

'

presently in the vendor's manual. The inspector identified this matter as IFI 50-339/86-12-01, RCP Flywheel Assembly Procedure.

Within the area inspected, no deviations or violations were identified.

l l

l l

l

.