IR 05000338/1981018

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-338/81-18 & 50-339/81-15 on 810706-10. Noncompliance Noted:Several Fire Doors Found Nonfunctional
ML20010J108
Person / Time
Site: North Anna  
Issue date: 07/30/1981
From: Conlon T, Miller W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20010J069 List:
References
50-338-81-18, 50-339-81-15, NUDOCS 8109290598
Download: ML20010J108 (12)


Text

c

.

..

UNITED STATES

! "'

7, NUCLEAR REGULATORY COMMISSION

$

, E REGION 11 o

101 MARIETTA ST., N.W., SUITE 3100 ATLANTA, GEORGIA 30303

-

s

Report Nos. 50-338/81-18 and 50-339/81-15 Licensee:

Virginia Electric and Power Company Richmond, VA 23261 Facility Name:

North Anna Docket Nos. 50-338 and 50-339 License Nos. NPF-4 and NPF-7 Inspection at Nort Anna site near Mineral, VA Inspector:, [-

4-( 4

N/

x W. H. Miller, Jr. -

i Oate Signed

~

Approved b 8mV

~7 - Je - 71 T. E. Conlon, Section Chief

,

Date Signed Engineering Inspection Branch Engineering and Technical Inspection Division SUMMARY Inspection on Jul.v 6-10, 1981 Areas Inspected l

This routine, unannounced inspection involved 17 inspector-hours onsite in the l

areas of fire protection / prevention.

The inspector spent 20 additional hours l

on-site investigating the transformer fire covered in IE inspection reports l

338/81-19 and 339/81-16.

l

'

Results Of the areas inspected, one violation was found (Nonfunctional fire doors for l

emergency switchgear rooms and diesel generator rooms).

l l

No deviations were found.

l l

<

0109290598 810920 ~

PDR ADOCK 05000338 O

PDR

,

.

..

.

.

.

REPORT DETAILS 1.

Persons Contacted Licensee Employees

'

  • W. R. Cartwright, Station Manager
  • E. W. Harrell, Assistant Station Manager
  • J. W. Orge;;, Supervisor, Administrative Services
  • J. A. Hanson, Superintendent Technical Services
  • M. A. Harrison, Resident QC Engineer
  • M. E. Fellows, Staf f Assistant
  • L. E. Retzer, Acting Fire Marshall Other Organizations
  • P. H. Griffin, Lead Advisory Engineer, Stone and Webster NRC Resident-Inspector
  • D. J. Burke, Acting Senior Resident Inspector
  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on July 10, 1981 with'

those persons indicated in pa.ragraph 1 above.

3.

Licensee Action on Previous Inspection Findings

,

a.

(Closed) Inspector Followup Item (338/78-11-07)

. Verify fire protec-tion program modifications completed prior to startup after second

'

refueling outage per license condition: All fire protection modifi-cations have been completed.

b.

(0 pen) Unresolved Item (339/79-03-01 and 338/80-42-04) - Fire Rating of

,

'

dampers between battery rooms and control rooms. The licensee (Dower Station Engineering and Construction Group) is presently eva'stting

!

these dampers to determine their fire resistant rating. The inspector reviewed the current installation and found that the dampers are now held in the open position by means of a fusible link device. This item will remain open pending completion of the evaluation.

c.

(Closed) Infraction Item (338/79-49-03) - 1-PT-1.03 not performed at required frequency. The licensee could not locate the documentation

,

for this surveillance inspection but the operations department verified i

,

_

~

.

.

.

~

.

l

that the inspection and tests were actually accomplished. A " procedure unaccounted for" form has been filed in the station records file. This item is closed.

d.

(Closed) Unresolved Item (339/79 08-01) - Licer.see to promulgate guidance concerning Technical Specification 3.7.15 as to applicable spaces and functional definition. The licensee sent a memorandum to the operations and QA departments on February 26, 1981, which listed the functional requirements for fire doors. This same infer.i.ation was included in the fire door inspaction procedure, PT-105.1.1, Fire Door Inspection - Turbine Building, Control Room and Office Area. This item is closed.

e.

(r'osed) Inspector Followup - Item (338/80-03-01 and 139/80-03-01) -

"

inkler system deficiencies. Hest collectors have been provided for sprinkler heads in the open areas. QA/QC documentation for these systems is currently being reviewed by the plant staff. This item is closed.

f.

(Closed) Inspector Followup Item (338/80-03-07) - Revisions to fire fighting procedures. These procedures have been revised. This item is-closed.

g.

(Closed) Infraction Item (338/80-03-08) - Inadequate nus.oer of fire

!

brigade drills for 1979, The fire brigade did not participate in a sufficient number of drills for 1980 and 1981 to meet the provisions of the North Anna Fire Protection Program. This infraction is closed but a repeat violation is issued for this item.

h.

(Closed) Deviation Item (338/80-03-10) - Substandard supervision of fire protection control valves. Procedure PT-100.3 has been revised to require all of the fire protection control valves to be inspected

weekly and for all valves' to be either secured in the open position by locks, seals or to be electrically supervised. This item is closed.

(Closed) Infraction Item (339/80-33-04) - Diesel generator room 2H fire

.

door does not operate. Refer to above' paragraph 3.d for the licensee's l

action on this item. This item is closed; however, on this inspection the fire doors between the turbine building and diesel generator rooms

,

for units 2J and 2H were found with inoperative door latches and the doors were not fully closed. This will be. listed as a new violation.

i

'

j.

(0 pen) Unresolved Item (338/,0-42-01 and 339/80-39-01) - Fire hose not

'

provided at each standpipe '.ose connection within the reactor contain-ment. This item is being e aluated by the licensee and remains open.

.

k.

(0 pen) Unresolved Item (338/00-42-04 and 339/80-39-04) - Substandard

'

fire / smoke detector installation.

The licensee stated that modifi-cations to the existing system are currently under design. This item remains open until these modificatisns are completed.

_.

._.

._

.

.

.

.

.

.

1.

(Closed) Violation Item (338/80-42-02 and 339/80-39-02) - Inadequate QA/QC surveillance of fire dampers. The licensee inspected the fire damper between the Units I and 2 cable tunnels on March 16, 1981 and found that this damper was in need of repair. Maintenance was per-formed and the damper was verified operational. The licensee is to require all future design changes and modifications to fire protection related systems to be 100% inspected by the QA organization. This item is closed.

m.

(Closed) Violation Item (339/80-39-03) - Failure to implement fire protection modification requirements of operating license.

The inspector verified the corrective action taken by the licensee as outlined in VEPCO's letter (serial No.163) dated March 24,1981, which

<

indicated that the fusible links were removed from the sprinkler heads and that a portable fire extinguisher was provided for the Auxiliary service water pump house. This item is closed.

'

(0 pen) Unresolved Item ('338/81-42-06 and 339/81-39-06) - Fire barrier n.

surveillance inspection procedure.

Corrective action has not been taken on this item. This item remains open.

4.

Unresolved Items Unresolved items were not identified during this inspection.

5.

Transformer Fire On July 3,1981, a fault in Unit 2B main transformer caused a fire which damaged this transformer, a portion of the exterior wall of the turbine building and the incoming offsite power supply from reserve station service transformer C.

Details on.th's fire are provided in Region II Report Nos.

338/81-19 and 339/81-16. A portion of the inspector's time (20 hours2.314815e-4 days <br />0.00556 hours <br />3.306878e-5 weeks <br />7.61e-6 months <br />) was devoted to obtaining data for that report.

6.

Fire Protection Program (Module 647038)

a.

Administrative Procedures The licensee's fire protection / prevention procedures are in a manual entitled "Nortn Anna Power Station

- Fire Protection Plan", dated September 10, 1980. This procedure was reviewed by the inspector and found to meet-the provisions of the NRC guidelines in the document entitled " Nuclear Plant Fire Protection Functional Responsibilities, Administrative Contris and Quality Assurance", dated June 14, 1977.

!

.

_.

_ _

._

.- _

_ -

.

- -

- -


.

.

.

.

.

.

b.

Fire Brigade Organization and Training (1) Organization The licensee stated that the plant fire brigade is composed of various plant employees with a minimum of five members maintained onsite at all times. Normally, the fire brigade leader and one member comes from the operations group and three members are from security.

(2) Training and Drills The inspector reviewed the recent plant training records and noted that routine brigade training was conducted for the first quarter of 1981, but training had not been conducted for the second

,

quarter.

However, the licensee had scheduled training for all fire brigade members for July and stated that this training would be compelted prior 'to July 21, 1981, which would meet the 21 day grace period permitted by the licensee's Fire Protection Plan.

The licensee stated that future training would be scheduled to meet the quarterly requirement.

Records of fire brigade drills conducted for 1980 and 1981 were not all stored with the training records. The licensee was able to locate a number of drill data sheets but drills were not conducted every 92 days for each brigade as required by Section 7.2.3 of the licensee's Fire Protection Plan.

For 1980, three (shifts A, B, and D) of the four cecurity shifts did not parti-cipate in two quarterly drills and one (shift C) did not parti-cipate.in one quarterly drill.

For the first two quarters of 1981, one of the shifts (shift B) did not participate in a quarterly drill.

For 1980, two of the four operations shifts (shifts B and C) did not participate in two quarterly drills and two (shifts A and D) did not participate in one quarterly drill.

For 1981, one shift (shift D) did not participate in a quarterly drill. This data was obtained by the inspector from the licensee by phone on July 16, 1981. The failure to meet fire brigade drill training requirement is identified as a violation item in Report Nos. 338/81-19 and 33981-16. A similar violation was identified in Report 338/80-03.

(3) Equipment Most of the fire brigade members have been issued protective turnout gear (coat, pants, boots and helmet). Also, five addi-tional sets of turnout gear is available and stored adjacent to the control room.

.

.

-

.

.

.

.

The fire brigade has assigned 12 self contained breathing apparatus and 24 spare cylinders which are stored in the turbine building adjacent te the control room. Additional units are also available from the nealth physics group, if needed. The brigade cylinders are refilled by means of a cascade system.

This j

arrangement meets the commitments to the NRC.

I

'

c.

Facility Tour (1) A tour was made of the plant to verify that the fire protection

,

modifications made as a result of the Fire Protection Safety Evaluaticn Report were completed.

Refer to paragraph 7 for details on i 2ms inspected. During the tour, the following fire protection systems were also inspected and verified to be opera-tional:

(a) Fire Alarm System (b) Low pressure carbon dixoide system for cable tunnels and vaults, charcoal filters and diesel generators (c) High pressure carbon dioxide system for fuel oil pump rooms

(d) Halon system for control room

!

(e) Interior fire bose station for auxiliary building, fuel,

building and turbine building (f) Fire hydrant equipment houses A and C (2) The inspector found the fire doors between the turbine building ge' erator rooms 2J and 2H (Doors T-16 and T-18),

and diesel n

,

between turbine building and emergency switchgear room for Unit 2 5 9oor S-53-11) and the doors between emergency switchgear rooms v' stairway (doors S-54-6 and S-54-7) not latched due to dsfective hardware.

The licensees's procedure PT-105.1.1, Fire Door Inspection - Turbine Building, Control Room and Health Physics, states that for fire doors to be functional they must close and latch.

This item is identified as Violation Item (338/B1-18-01 and 339/81-15-01), Nonfunctional fire doors for

!

emergency switchgear and diesel generator rooms.

7.

Fire Protection / Prevention Commitments This inspection evaluated the licensee's progress and action on the fire protection commitments made to the NRC.

The NRC Fire Protection Safety Evaluation Report (FPSER) for North Anna dated February 1979 and the licensee's Fire Protection System Review (FPSR) dated April 1,1977 with

.

.

.

.

Supplements 1, 2, and 3 were used in this evaluation. These documents describe the fire protection requirements, commitments and dates of imple-mentation.

Items applicable to both units are so noted. The commitments and findings are as follows:

a.

Commitments Item No.

Location / Description Status Reactor Containment - Fire Area 1, Units 1 & 2 (1) Fire Detector

(a) Recirculation Air System (b) Containment Cable Penetration A' as

-

(c) Residual Heat Removal Pumps (d) Reactor Coolant Pumps (2) Standpipe System /with Fire Hose Open (3)

Instrumentation Closed (a) Loop Temperatures (b) Pressurizer Pressure (c) Pressurizer Level (4) 011 Collection System for Reactor Coolant Pumps

(5) Fire Stops for Vertical Cable Tray Risers

Control Room - Fire Area 2 (6) Fire Detection (a) General Area Closed (b) Return Air Duct Closed (7) Replace lh Hour Fire Damper with 3 Hour Damper

^* Closed in Duct a Turbine Building

-

(8) Additional Electrical Separation Between Main

Control Board Circuits and Auxiliary Shutdown Panel Via 43X Contacts (9) Emergency Lighting Units - 8 Hour Battery Type Closed Cable Vault and Tunnel - Fire Area 3, Units 1 & 2 (11) Portable Extinguishers Closed (a) Type W in Cable Vault Closed (b) Type D in Motor Control Center Closed

.

..

.

.

.

(12) Fire Dampers Replace 1 Hour Dampers With 3 Hour Dampers Closed (13) Emergency Lighting - 2 Hour Battery Closed (14) Sprinkler Systems / Manual Type Closed (a) High Ceiling Area - Open Heads (b)

Low Ceiling Area - Closed Heads Cable Spreading Room - Fire Area 4, Units 1 & 2 (15)

Interior Fire Hose Station with 100' of Hose Closed Emergency Switchgear and Instrument Room - Fire Area 6, Units 1 & 2 (16) Fire Detection (Smoke)

Open (17) Fire Hose Station with 100' of Hose Closed (18) Type W Extinguisher's - 3 Units Closed (19) Barrier (3 Hr) Duct Through Chiller Room Closed (20) Emergency Lighting - 8 Hour Battery Type (a) Auxiliary Shutdown Panel Closed (b) Egress Closed Diesel Generator Rooms - Units 1 & 2 (21) Emergency Lighting - 2 Hour Battery Type Closed Battery Rooms - Fire Areas 7A, 78, & 7C, Units 1 & 2 (22) Loss of Ventilation Alarm Closed (23) Fire Dampers (1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)

Open Turbine Building - Fire Area 3, Units 1 & 2 (24) Fire Detection - Chiller and Air Conditioning Closed Rooms (25) Fire hose racks /100' Hose at Entrance to Control Closed Room and Diesel Generator Room (26) Fire Door (3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />) between HVAC Room anf Chiller Closed Room Fuel Oil Pump House - Fire Area 11 (27) Fire Detection - Motor Control Center Closed Auxiliary Building - Fire Area 11

..

.

,

'I-

.

.-

.

.

.

,

E

]

(28)

Fire Detection-Refer to

(a) Charging Pump Above Item i

(b) Component Cooling Pump Area

(c) Resin & Filter Storage Area Exhaust Duct

'

(d) Exhaust Duct of Small Cubicle (e) General Floor Areas (29) ' Sprinkler System

_ 244 & 259)

Closed-(a) Component Cooling Pumo (EL (30)

Fire Hose Systems - Increase Hose to 100'

Closed Unit 2 Cable Tunnel EL 259' All Racks en l

EL 274'

(31) Cross-Connection of Units 1 and 2 Charging Closed Pumps (32) Dike Around Ladder to Charging Pumps Closed

(33) Emergency Lighting - 2 Hour Bat'ery Type Closed I

Service Water Pump House - Fire Area 12

(34) Fire Detection - General Area

(35)

Fire Hose Cabinet Closed (36) Type C Extinguisher in Hose Cabinet Closed Auxiliary Service Water Pump House - Fire Area 13, U' nits 1 & 2 (37)

Fire Detection - General Area

(38) Type C Extinguisher - Near Door Closed Auxiliary Feedwater Pump House - Fire Areas 14A & 148, Units 1 & 2 (39) Fire Detection Refer to

j (a) Turbir.e Pump Room Above Item i

(b) fiotor_ Pump Room Closed

!

'

Quench Spray Pump House - Fire Area 15, Units 1_& 2 (40) Fire Detection Refer to Item 16 (a) General Area of Lower Elevation

,

[

(b) Ventilation Exhaust Ducts l

(41) Type D Fire Extinguisher Near Door Closed i

(42) Emergency Lighting - 2 Hour Battery Type Closed b

i

. _. _

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

.

..

.

.

.

Safeguards Area - Fire Area 16 (43) Fire Detection - Ventilation Exhaust Ducts Refer to Above Item

(44) Type D Fire Extinguisher Closed (45) Emergency Lighting - 2 Hour Battery Type Closed

'

Main 3 team Valve House - Fire Area 17, Units 1 & 2 (46) Fire Detection - General Area

    • Closed (47) Two Type "D" Fire Extinguishers Closed (48) Emergency Lighting - 2 Hour Battery Type Closed Fuel Building - Fire Area 18 (49) Fire Detection - General Area Refer to-Above Item

(50) Hose Rack with 100' of Hose - EL 288'

Closed (51) Auxiliary Instrument Panel and Power Supply Closed (52) Emergency Lighting - 8 Hour Battery Type (a) Auxiliary Panel Closed (b) Egress Closed Waste Disposal Building - Fire Area 19A (53) Fire Detection - Gei,eral Area

Boron Recovery Building - Fire Area 198 (54) Fire Detection - General Area Refer to Above Item l

I Decontamination Building - Fire Area 20 (55) Fire Detection - G. eral Area Refer to Above Item

Fire Pump House - Fire Area 26 (56) Fire Detection - General Area

Intake Structure Contrci House - Fire Area 32 (57) Fire Detection - General Area

,.

--

.

..

..

.

..

- _ _ _ _ _ _ _ _ _ _ _ _

.

.

.

.

.

.

Post Accident Recombiner Vault - Fire Area 38 (58)

Fire Detection - General Area

Auxiliary Power Supply Building - Lire Area 39 (59) Fire Detection - General Area

Casing Cooling Pump - Fire Area 41, Units 1 and 2 (60) Fire Detection - General Area Closed Notes:

  • This item was not inspected
    • Refer to Paragraph 5.b for additional information

"Open" Item Contains Discrepancies.

Refer to Paragraph 5.b for Details

" Closed" Visual Inspection and Random Review of Documenta-l tion Records Indicates That This Item Appears Satis-f l

factorily Completed j

b.

Findings Additional information on the "Open" items and items marked "*" in Paragraph 5.a is listed below. The below listed numbers correspond to the numbered items in paragraph 5.a (2) Fire hose has not been provided at each standpipe hose outlet in the containments as stated in Table 1 of the FPSER.

The hose and equipment are located in cabinets adjacent to each personnel hatch.

The licensed advised that a ' commitment was not made to install fire hoses at each standpipe outlet but that hose was to be provided in cabinets adjacent to the personnel entrance outside each containment.

Enclosure 1 to VEPCO's letter Serial No. 4581080178 to NRR dated September 29, 1978, states that dry hose connection standpipes will be located within the reactor containment with " lengths of hose (to be located) immediately outside of personnel hatch in auxiliary building el 291 ft".

The licensee is to resolve this discrepancy with NRR.

This item was previously identified as an unresolved item in Report Nos. 338/80-42 and 339/80-39.

(7) VEPCO's letter Serial No. 148/0306679 to NRR dated June 11, 1979 stated that replacement of this damper was not necessa y since the ventiiation duct was schedule 40 pipe provided with two normally closed seismically qualified butterfly valves in series directly inside the control room wall which would provide the equivalent, or better than a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> damper. This evaluation was apparently acceptable to NP.R.

--

.

.

-.

.

.

.

j

.

.,

.

.

.

.

(16) In general, the installatian of the smoke detection systems do not -

fully meet the criterion of NFPA-72E, Automatic Fire Detectors, in many areas. The licensee stated that a commitment wat neve, made to the NRC for the installation of the detection systems to meet the provisions of NPFA-72E. However, the licensee has reviewed the existing design and installation and is to provide some additional detectors.

This is presently identified as an unresolved item. Refer to above paragraph 3.K.

(23) The fire dampers are not stt:ndard type dampers and documentation as to the fire resistant rating of these fire dampers is not available at the site. The license > is to provide NRC, Region II, documentation which will indicate the,1re resitant rating of these dampers. This item is presently -identified as an -unresolved item.

Refer to above pragraph 3.b.

(46) The fire detectors installed within the main steam valve houses are located approximately 10 feet beneath the ceiling which do not conform to the pn/isions of NFPA-72E.

The amount of combustibles within this area is exceptionally small; therefore, no additional changes to the detection system appears warranted.

Except as noted above, within the areas examined, no additional violations or deviations were identified.

.

i

!

!

i

,

J w