IR 05000336/2004007

From kanterella
Jump to navigation Jump to search
IR 05000336-04-007, 05000423-04-007; 07/01/2004 - 09/30/2004; Millstone Power Station, Unit 2 and Unit 3; Permanent Plant Modifications, Post-Maintenance Testing, Event Followup, Other Activities
ML043090220
Person / Time
Site: Millstone  
(DPR-065, NPF-049)
Issue date: 10/29/2004
From: Ronald Bellamy
NRC/RGN-I/DRP/PB6
To: Christian D
Dominion Resources
Bellamy R DNMS, 610-337-5200
References
FOIA/PA-2005-0208 IR-04-007
Download: ML043090220 (59)


Text

October 29, 2004

SUBJECT:

MILLSTONE POWER STATION UNIT 2 AND UNIT 3 - NRC INTEGRATED INSPECTION REPORT 05000336/2004007 AND 05000423/2004007

Dear Mr. Christian:

On September 30, 2004, the U.S. Nuclear Regulatory Commission (NRC) completed inspections at your Millstone Power Station Unit 2 & Unit 3. The enclosed integrated inspection report documents the inspection findings, which were discussed on October 14, 2004, with Mr. J. Alan Price and other members of your staff.

The inspections examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.

The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.

This report documents three NRC-identified findings and one self-revealing finding of very low safety significance (Green). All of these findings were determined to involve violations of NRC requirements. However, because of their very low safety significance and because they have been entered into your corrective action program, the NRC is treating these issues as Non-Cited Violations, in accordance with Section VI.A.1 of the NRCs Enforcement Policy. If you contest these non-cited violations, you should provide a response within 30 days of the date of these inspection reports, with the basis for your denial, to the Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington DC 20555-0001; with copies to the Regional Administrator, Region I; the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC Resident Inspector at the Millstone Power Station.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its enclosures, and your response (if any) will be available electronically for public inspection in the

Mr. D. NRC Public Document Room or from the Publicly Available Records component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Website at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Ronald R. Bellamy, Chief Projects Branch 6 Division of Reactor Projects Docket Nos.: 50-336, 50-423 License Nos.: DPR-65, NPF-49 Enclosure:

Inspection Report 05000336/2004007 and 05000423/2004007 w/Attachment: Supplemental Information cc w/encl:

J. A. Price, Site Vice President - Millstone C. L. Funderburk, Director, Nuclear Licensing and Operations Support D. W. Dodson, Supervisor, Station Licensing L. M. Cuoco, Senior Counsel C. Brinkman, Manager, Washington Nuclear Operations W. Meinert, Massachusetts Municipal Wholesale Electric Company First Selectmen, Town of Waterford V. Juliano, Waterford Library J. Markowicz, Co-Chair, NEAC E. Woollacott, Co-Chair, NEAC E. Wilds, Director, State of Connecticut SLO Designee J. Buckingham, Department of Public Utility Control G. Proios, Suffolk County Planning Dept.

R. Shadis, New England Coalition Staff G. Winslow, Citizens Regulatory Commission (CRC)

S. Comley, We The People D. Katz, Citizens Awareness Network (CAN)

R. Bassilakis, CAN J. M. Block, Attorney, CAN

Mr.

SUMMARY OF FINDINGS

IR 05000336/2004007, 05000423/2004007; 07/01/2004 - 09/30/2004; Millstone Power Station,

Unit 2 and Unit 3; Permanent Plant Modifications, Post-Maintenance Testing, Event Followup,

Other Activities.

The report covered a 3-month period of inspection by resident inspectors and announced inspections by regional inspectors. Four (Green) non-cited violations (NCVs) were identified.

The significance of most findings is indicated by their color (Green, White, Yellow, Red) using Inspection Manual Chapter (IMC) 0609, "Significance Determination Process" (SDP). Findings for which the SDP does not apply may be Green or be assigned a severity level after NRC management review. The NRC's program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, "Reactor Oversight Process," Revision 3, dated July 2000.

NRC-Identified and Self-Revealing Findings

Cornerstone: Initiating Events

Unit 2

!

Green.

The inspectors identified a non-cited violation of 10 CFR 50 Appendix B,

Criterion XVI, for the failure to take effective corrective actions to preclude main steam code safety valves from lifting following design basis turbine trips/reactor trips from 100% power. Following two uncomplicated reactor trips at Unit 2 in March 2004, the inspectors noted that main steam code safety valves lifted and reseated. The inspectors determined that Unit 2 had a history of main steam code safety valves lifting and reseating following uncomplicated trips. The inspectors concluded that cycling main steam code safety valves following trips from full power increases the likelihood that they may not reseat. Dominion had not taken effective corrective actions to correct this longstanding issue.

Dominion has undertaken a study (to complete by the end of 2004) to evaluate this system condition and to specify long term design changes which will be scheduled for completion in refueling outage 2R17 (fall of 2006). Dominion has entered this issue into their corrective action program.

This issue is more than minor because it affects the equipment performance attribute of the Initiating Events Cornerstone and the objective to limit the likelihood of those events that upset plant stability. Cycling of main steam code safety valves results in a greater likelihood that the valves will not reseat properly during an event. The finding was determined to have a very low safety significance since it did not contribute to the likelihood of a primary loss of coolant accident, did not contribute to both the likelihood of a reactor trip and the unavailability of mitigating equipment, and did not increase the likelihood of a fire or internal/external flood. This finding is related to the cross-cutting area of Problem Identification and Resolution. (Section 1R17.2)

iv

!

Green.

The inspectors identified a non-cited violation of Technical Specification (TS) 6.8.1, for the failure to adequately implement post-maintenance testing following replacement of a pressurizer level instrument. On July 28, 2004,

Operations and Maintenance personnel failed to meet a "Unit 2 Shutdown" procedural prerequisite and did not perform a procedure step to place charging pump controls in pull-to-lock during post-maintenance testing of pressurizer level control circuitry. As a result, both standby charging pumps started with one charging pump already operating. Dominion has specified training for both Operations and Maintenance organizations describing the circumstances of this event and management expectations for work evolution briefs, peer checking, and actions to be taken for unexpected conditions. Additionally, Maintenance management reinforced work practice expectations for the use of "N/A" in procedures and work planning process improvements. Dominion has entered this issue into their corrective action program.

This issue is more than minor because it is associated with the human performance attribute of the Initiating Events Cornerstone and the objective to limit the likelihood of those events that upset plant stability. The start of both standby charging pumps with one charging pump already operating was the precursor to the failure of the charging system on March 7, 2003. The finding was determined to have a very low safety significance since it did not contribute to the likelihood of a primary loss of coolant accident, did not contribute to both the likelihood of a reactor trip and the unavailability of mitigating equipment, and did not increase the likelihood of a fire or internal/external flood. This finding is related to the cross-cutting area of Human Performance. (Section 1R19)

Cornerstone: Mitigating Systems

Unit 3

!

Green.

The inspectors identified a non-cited violation of Technical Specification (TS) 3.8.3.2, Onsite Power Distribution - Shutdown, for the failure to enter Technical Specifications following the loss of a vital inverter. The required actions were to immediately stop all reactivity additions. However, operators failed to stop both a plant heatup and reactor coolant system (RCS) dilutions (hydrazine addition), which resulted in positive reactivity additions to the reactor.

Dominion specified operator training to reinforce the management expectation for completing procedures, however, additional corrective actions will be specified in an upcoming revision to the Licensee Event Report based on the issues identified by the inspectors in the finding description. Dominion has entered this issue into their corrective action program.

This issue is more than minor because it is associated with the human performance attribute of the Mitigating System Cornerstone and the objective of ensuring the availability of systems to respond to initiating events to prevent undesirable circumstances. The failure of the vital inverter resulted in an electrical lineup that did not meet the TS requirements for one complete train of electrical buses. Additionally, the failure to recognize the need to enter TS precluded taking corrective actions to prevent adding positive reactivity with this v electrical lineup. Several positive reactivity additions from heatup and RCS dilutions occurred as a result. The finding is of very low safety significance because the reactivity addition from the heatup and the dilutions was small compared to the reactivity needed for criticality. Additionally, the finding did not increase the likelihood of a loss of RCS inventory, degrade Dominions ability to add inventory if needed, or degrade the ability to recover the residual heat removal system if it was lost. This finding is related to the cross-cutting issue of Human Performance. (Section 4OA3)

!

Green.

The inspectors identified a non-cited violation of Technical Specification (TS) 6.8.1a for the failure to adequately implement procedures for venting the reactor coolant system (RCS) and the residual heat removal (RHR) system. On May 28, 2004, Dominion conducted a quarterly vent and valve lineup of the "A" train of the RHR system in which air was vented from several vent valves. The inspectors investigated whether the voids in the "A" train of the RHR system and portions of suction piping leading to both trains of the safety injection (SI) and charging systems would have adversely affected these systems ability to respond to a small break loss of coolant accident (SBLOCA). The inspectors reviewed the engineering technical evaluation and determined that the amount of air in the RHR system did not adversely impact the RHR pumps, SI pumps, or the charging pumps. The inspectors reviewed Dominion's root cause investigation and determined that the cause of the entrapped air was due to securing one of the two RHR pumps on April 28, 2004, during the RCS sweep and vent procedure following completion of the refueling outage. Dominion revised the RCS sweep and vent procedure to add a precaution to avoid securing an RHR pump during this procedure. Dominion has entered this issue into their corrective action program.

This issue is more than minor because it is associated with the equipment performance attribute of the Mitigating Systems cornerstone and the objective to ensure availability of systems that respond to initiating events to prevent undesirable consequences. The entrapped air had the potential to make the "A" RHR pump, SI pumps, and charging pumps inoperable. The finding is of very low safety significance because it did not represent an actual loss of safety function of the RHR, SI, or charging system since the amount of air identified in these systems would not have prevented them from functioning. This finding is related to the cross-cutting issue of Human Performance. (Section 40A5.1).

Licensee-Identified Violations

None.

REPORT DETAILS

Summary of Plant Status

Unit 2 operated at essentially 100% power for the duration of the inspection period with one exception. From July 20, 2004 to July 26, 2004 the unit reduced power to 94% to perform maintenance on the circulating water system. Unit 2 returned to 100% power on July 26, 2004 and operated at essentially 100% for the remainder of the period.

Unit 3 operated at essentially 100% power for the duration of the inspection period with one exception. On August 11, 2004, the plant reduced load to approximately 91% power due to the No. 3 and No. 5 turbine intercept valves closing caused by the failure of a servo valve. The unit returned to 100% power on August 14, 2004, but reduced load to 90% power that same day to back flush the circulating water bays due to condenser fouling. The plant returned to 100%

power on August 15, 2004, and remained at full power for the remainder of the inspection period.

REACTOR SAFETY

Cornerstones: Initiating Events, Mitigating Systems, and Barrier Integrity

==1R01 Adverse Weather Protection (71111.01 - 2 Unit 2 Samples and 1 Unit 3 Sample )

a. Inspection Scope

==

Seasonal Site Inspection (1 Unit 2 and 1 Unit 3 sample)

The inspectors performed a review of severe weather preparations during the onset of the hurricane season to evaluate the sites readiness for seasonal susceptibilities. The inspectors reviewed Dominions preparations/protection for severe weather and its impact on the protection of safety-related systems, structures and components. The inspection was intended to ensure that the indicated equipment, its instrumentation, and its supporting structures were configured in accordance with Dominions procedures and that adequate controls were in place to ensure functionality of the systems. The inspectors reviewed the Unit 2 and 3 Final Safety Analysis Report (FSAR) and Technical Specifications and compared the analysis with procedure requirements to ascertain that procedures were consistent with the FSAR. The inspectors performed partial walkdowns of the Unit 2 and Unit 3 intake structures, service water systems, intake structure traveling screens and emergency diesel generators to ascertain the adequacy of protection of equipment from the effects of hurricanes. The inspectors verified that operator actions defined in the adverse weather procedures maintain readiness of essential systems and that adequate operator staffing is specified. Documents reviewed during the inspection are listed in the Attachment.

System Inspection (1 Unit 2 Sample)

The inspectors reviewed one sample of the readiness of the Unit 2 service water system for extreme weather conditions, specifically, hurricanes, high winds, high tides, and other severe weather events. The inspection was intended to ensure that the indicated equipment, its instrumentation, and its supporting structures were configured in accordance with Dominion procedures and that adequate controls were in place to ensure functionality of the system. The inspectors reviewed licensee procedures and walked down the system. Documents reviewed during the inspection are listed in the

.

b. Findings

No findings of significance were identified.

1R04 Equipment Alignment

a. Inspection Scope

Partial System Walkdowns (71111.04Q - 4 Unit 2 and 3 Unit 3 Samples)

The inspectors performed seven partial system walkdowns during this inspection period.

The inspectors reviewed the documents listed in the Attachment to determine the correct system alignment. The inspectors conducted a walkdown of each system to verify that the critical portions of selected systems were correctly aligned in accordance with these procedures and to identify any discrepancies that may have had an effect on operability. The inspectors verified that equipment alignment problems that could cause initiating events, impact mitigating system availability or function, or affect barrier functions, were identified and resolved. The following systems were reviewed based on their risk significance for the given plant configuration:

Unit 2

  • Partial equipment alignment of the charging system (8/19/2004)
  • Partial equipment alignment of the "B" train of containment spray system during maintenance on the "A" train (9/17/2004)

Unit 3

  • Partial equipment alignment of 4160 VAC system following station blackout diesel maintenance (7/28/2004)

b. Findings

No findings of significance were identified.

Complete System Walkdown. (71111.04S - 1 Unit 2 Sample)

The inspectors completed a detailed review of the alignment and condition of the Unit 2 high pressure safety injection (HPSI) System. The inspectors conducted a walkdown of the system to verify that the critical portions, such as valve positions, switches, and breakers, were correctly aligned in accordance with procedures to identify any discrepancies that may have had an effect on operability.

The inspectors also conducted a review of outstanding maintenance work orders to verify that the deficiencies did not significantly affect the HPSI system function. In addition, the inspectors discussed system health with the system engineer and reviewed the condition report database to verify that equipment alignment problems were being identified and appropriately resolved. Documents reviewed during the inspection are listed in the Attachment.

b. Findings

No findings of significance were identified.

1R05 Fire Protection

Quarterly Sample Review (71111.05Q - 6 Unit 2 and 6 Unit 3 Samples)

a. Inspection Scope

The inspectors performed twelve walkdowns of fire protection areas during the inspection period. The inspectors reviewed Dominion's fire protection program to determine the required fire protection design features, fire area boundaries, and combustible loading requirements for the selected areas. The inspectors walked down those areas to assess Dominion's control of transient combustible material and ignition sources. In addition, the inspectors evaluated the material condition and operational status of fire detection and suppression capabilities, fire barriers, and any related compensatory measures. The inspectors then compared the existing conditions of the inspected fire protection areas to the fire protection program requirements to ensure all program requirements were being met. Documents reviewed during the inspection are listed in the Attachment. The fire protection areas reviewed included:

Unit 2

  • Diesel Generator Room "B" - Auxiliary Building, 14'6" Elevation - (Fire Area A-16)
  • DC Switchgear Area - Turbine Building, 31'6" Elevation - (Fire Area T-1D)
  • Charging Pump Room - Auxiliary Building, -25'6" Elevation - (Fire Area A-6A)

Unit 3

  • Fuel Building, 11'-0" Elevation, 24'-6" Elevation, 34'-0" Elevation, 52'-4" Elevation

- (Fire Area FB-1)

  • Fuel Building, 11'-0" Elevation, 24'-6" Elevation, 42'-6" Elevation - (Fire Area FB-2)
  • Station Blackout Diesel Enclosure, 24' 6" Elevation - (Fire Area SBO-1)
  • East Motor Control Cabinet (MCC)/Rod Control Area, 24'-6" Elevation - (Fire Area AB-5)
  • West MCC/Rod Control Area, 24'-6" Elevation - (Fire Area AB-6)

b. Findings

No findings of significance were identified.

Annual Fire Drill Observation (71111.05A - 1 Unit 3 Sample)

a. Inspection Scope

Unit 3 The inspectors observed personnel performance during a fire brigade drill on July 1, 2004, to evaluate the readiness of station personnel to prevent and fight fires. The drill simulated a fire in the Unit 3 Cable Spreading Room. The inspectors observed the fire brigade members using protective clothing, turnout gear, and self-contained breathing apparatus and entering the fire area in a controlled manner. The inspectors also observed the fire fighting equipment brought to the fire scene to evaluate whether sufficient equipment was available to effectively control and extinguish the simulated fire. The inspectors evaluated whether the permanent plant fire hose lines were capable of reaching the fire area and whether hose usage was adequately simulated. The inspectors observed the fire fighting directions and communications between fire brigade members. The inspectors verified that the pre-planned drill scenario was followed and observed the post drill critique to evaluate if the drill objectives were satisfied and that any drill weaknesses were discussed.

b. Findings

No findings of significance were identified.

1R06 Flood Protection Measures (71111.06 - 2 Unit 2 and 2 Unit 3 Samples)

Internal Flooding Inspection (1 Unit 2 Sample and 1 Unit 3 Sample)

a. Inspection Scope

The inspectors reviewed two samples of flood protection measures for equipment in the two safety related rooms listed below. This review was conducted to evaluate Dominions protection of the enclosed safety-related systems from internal flooding conditions. The inspectors performed a walkdown of the area, reviewed the FSAR, the internal flooding evaluation and related documents. The inspectors compared the as-found equipment and conditions to ensure that they remained consistent with those indicated in the design basis documentation, flooding mitigation documents, and risk analysis assumptions. Documents reviewed during the inspection are listed in the

.

b. Findings

No findings of significance were identified.

External Flooding Inspection (1 Unit 2 Sample and 1 Unit 3 Sample)

a. Inspection Scope

The inspectors evaluated Dominion's preparation and protection from the effects of external flooding conditions for Unit 2 and Unit 3. The inspectors reviewed the FSAR and applicable procedures to determine the readiness of protection for applicable safety-related structures, systems, and components. The inspectors performed walkdowns of the Unit 2 floodgates and fire pump houses and the Unit 3 intake structure to verify the adequacy of the floodgates, flood doors, and temporary equipment and that removable flood planks were able to perform their design function. Additionally, the inspectors reviewed recent Dominion inspection results including floodgate inspections, and verified that previously identified deficiencies had been entered into Dominion's corrective action program for resolution. Documents reviewed during the inspection are listed in the Attachment.

b. Findings

No findings of significance were identified.

==1R07 Heat Sink Performance (71111.07B - 3 Unit 2 Samples) Refer to Section 4OA5.2.

1R11==

Licensed Operator Requalification Program (71111.11Q - 1 Unit 2 and 1 Unit 3 Sample)

a. Inspection Scope

The inspectors observed one sample of Unit 2 licensed operator classroom training on August 20, 2004 and one sample of Unit 3 licensed operator classroom training on September 17, 2004. The inspectors observed licensed operator training on the Independent Spent Fuel Storage Installation during the August 20, 2004 classroom session. The inspectors verified that the training evaluators adequately addressed that the applicable training objectives had been achieved. Documents reviewed during the inspection are listed in the Attachment.

b. Findings

No findings of significance were identified.

1R12 Maintenance Effectiveness

Routine Maintenance Effectiveness Inspection (71111.12Q - 2 Unit 2 and 3 Unit 3 Samples)

a. Inspection Scope

The inspectors reviewed five samples of Dominion's evaluation of degraded conditions, involving safety related structures, systems and/or components (SSC) for maintenance effectiveness during this inspection period. The inspectors reviewed licensee implementation of the Maintenance Rule (MR), 10 CFR 50.65, and verified that the conditions associated with the referenced CRs were appropriately evaluated against applicable MR functional failure criteria as found in licensee scoping documents and procedures. The inspectors also discussed these issues with the system engineers and maintenance rule coordinators to verify that they were appropriately tracked against each system's performance criteria and that the systems were appropriately classified in accordance with MR implementation guidance. Documents reviewed during the inspection are listed in the Attachment. The following conditions were reviewed:

Unit 2

  • Post Incident Recirculation Fan Timer Failure (CR-04-08427)

Unit 3

"B" EDG Output Breaker Would Not Close During Surveillance (CR-04-07193)

  • Control Building Isolation Actuation Due To HVC*RE 16A Going Into Alarm (CR-04-06929)
  • Control Building Air Conditioning Unit Failure (CR-04-06510)

b. Findings

No findings of significance were identified.

Biennial Periodic Evaluation Inspection (71111.12B - 3 Unit 2 and 3 Unit 3 Samples)

a. Inspection Scope

The inspectors conducted a review of Dominions periodic evaluation of the implementation of the Maintenance Rule required by 10 CFR 50.65 (a)(3). The evaluation covered a period from September 2001 to June 2003. The purpose of this review was to ensure that Millstone Unit 2 and Unit 3 effectively assessed its goals for reasonable assurance that structures and systems and components as defined in 10 CFR 50.65

(b) fulfill their intended functions. The inspections verified certain performance criteria, system monitoring, and preventive maintenance activities. The inspectors verified that the assessment was completed within the required time period and that industry operating experience was properly utilized. Additionally, the inspectors verified that Dominion appropriately balanced equipment reliability with unavailability when planning maintenance activities.

The inspectors selected a sample of six risk-significant systems to verify that:

(1) the structures, systems, and components were properly characterized,
(2) goals and performance criteria were appropriate,
(3) corrective action plans were adequate, and
(4) performance was being effectively monitored in accordance with MP-24-MR-FAP730, Rev. 0, "Maintenance Rule Goal Setting and Monitoring," and other Maintenance Rule procedures. The following systems were selected for this detailed review:

Unit 2

  • Station Blackout Diesel Generator
  • Containment Isolation These systems were either currently in increased monitoring status as required by 10 CFR 50.65 a(1) or at some time during the assessment period had been in an increased monitoring status or had experienced degraded performance. The inspectors reviewed corrective action documents for malfunctions and failures of these systems to determine if:
(1) they had been correctly categorized as functional failures;
(2) they were correctly categorized as maintenance preventable; and
(3) their performance was adequately monitored to determine if classifying a system as (a)(1) was appropriate.

b. Findings

No findings of significance were identified.

1R13 Maintenance Risk Assessments and Emergent Work Evaluation (71111.13 - 4 Unit 2 and 4 Unit 3 Samples)

a. Inspection Scope

The inspectors reviewed eight samples of the adequacy of maintenance risk assessments of emergent and planned activities during the inspection period. The inspectors utilized the Equipment Out of Service (EOOS) quantitative risk assessment tool to evaluate the risk of the plant configurations and compared the results to Dominion's stated risk. The inspectors verified that Dominion entered appropriate risk categories and implemented risk management actions as necessary. Documents reviewed during the inspection are listed in the Attachment. The inspectors verified the conduct and adequacy of scheduled maintenance risk assessments for plant conditions affected by the conduct of the following maintenance and testing activities:

Unit 2

  • Work Schedule for the week of 7/12/04 - maintenance and testing on the charging system
  • Work Schedule for the week of 7/26/04 - emergent risk assessment for maintenance/testing
  • Work Schedule for the week of 8/9/04 - risk assessment for maintenance/testing
  • Work Schedule for the week of 9/4/04 - maintenance and testing on the instrument air, reactor plant component cooling water, and auxiliary feedwater systems Unit 3
  • Work Schedule for the week of 7/19/04 - maintenance and testing on the "A" engineered safety features building, air conditioning, and "A" safety injection pump
  • Work Schedule for the week of 7/26/04 - maintenance and testing on the station blackout diesel, safety injection slave relay, and solar disturbance
  • Work Schedule for the week of 8/30/04 - maintenance and testing on the "B" safety injection (SI) pump, "1B" engineered safety feature building air conditioning, service water to "B" SI pump cooler

b. Findings

No findings of significance were identified.

1R14 Personnel Performance During Non-Routine Plant Evolutions and Events (71111.14 -

2 Unit 2 and 2 Unit 3 Samples)

a. Inspection Scope

The inspectors reviewed four samples of events that demonstrated personnel performance in coping with non-routine evolutions and transients. The inspectors observed operations in the control room and reviewed applicable operating and alarm response procedures, technical specifications, plant process computer indications, and control room shift logs to evaluate the adequacy of Dominion's response to these events. The inspectors also verified the events were entered into the corrective action program to resolve identified adverse conditions. Documents reviewed during the inspection are listed in the Attachment.

Unit 2

  • On July, 28, 2004, Operations personnel responded to the unexpected start of two standby charging pumps while one charging pump was running. An Instrumentation and Control (I&C) loop calibration of letdown controls was in progress as a post maintenance test activity for the replacement of a pressurizer level instrument. During this test, I&C personnel initiated signals into the Reactor Regulating System, which caused both standby charging pumps to start. Neither Operations nor I&C personnel had recognized that this activity would cause these pumps to start. Operators secured the two standby charging pumps, reviewed the I&C procedure, and noted that the pumps should have been placed in pull-to-lock. Operators placed the standby pumps in pull-to-lock and I&C then completed the procedure. See Section 1R19.
  • On August 5, 2004, Operations and Reactor Engineering personnel were conducting operations in the spent fuel pool to inspect fuel rods from failed fuel assemblies to determine their failure mechanism. During the transfer of a fuel rod into an Individual Rod Inspection Station (IRIS), the fuel rod broke.

Approximately 133 inches of the fuel rod fell into the safety basket, attached to the inspection station, while approximately 13 inches of the fuel rod remained connected to the fuel rod gripper. Fuel inspection operations were stopped and the door was closed at the bottom of the fuel rod gripper to ensure both sections of the broken rod were secured. Recovery plans were formulated to recover the upper and lower fuel rod segments and place them into a failed rod storage canister (FRSC) and to determine the existence of and recover any fuel fragments remaining in the safety basket. On August 6, 2004 the lower section of the failed fuel rod was placed into the FRSC. On August 9, 2004, the upper segment of the failed fuel rod was placed into the FRSC. On August 11, 2004, fuel pellets and/or cladding fragments were identified at the bottom of the safety tube. On August 12, 2004 the safety tube was inverted and the fragments were tipped into a bucket. In all, five fragments were recovered and underwater radiological surveys confirmed there were no more fragments in the safety tube.

The fragments were then transferred to a container (a short section of fuel rod cladding and lower end plug approximately 4 inches long) which was placed into the FRSC.

Unit 3

  • On August 11, 2004, Operations personnel responded to indications of high steam flow on the "A" moisture separator reheater (MSR). Operations responded by securing reheat steam to the "A" and "B" MSRs. The resulting secondary transient caused the control rods to automatically insert which caused a decrease in reactor coolant system temperature and pressure. The operators energized all pressurizer heaters to restore plant pressure and the plant stabilized at 91 percent reactor power. Operations entered OP 3317, "Reheat and Moisture Separator" to remove the MSRs from operation while at power.

Dominion determined that the cause of the high steam flow transient was the closure of two main turbine combined intercept valves due to the failure of a servo valve.

  • On August 30, 2004, Operations personnel responded to a "C" steam generator flow mismatch (i.e., steam flow > feed flow). Operators took manual control of the "C" feed regulating valve (FRV) and matched steam flow, feed flow, and steam generator level in accordance with the alarm response procedure. The operators identified that the Channel 1 computer point had spiked low and then returned to normal. They entered AOP 3571, Instrument Failure Response, and selected the "C" steam generator instrument to Channel 2, and then restored the "C" FRV to automatic control.

b. Findings

No findings of significance were identified.

==1R15 Operability Evaluations (71111.15 - 6 Unit 2 and 8 Unit 3 Samples)

a. Inspection Scope

==

The inspectors reviewed fourteen operability determinations associated with degraded or non-conforming conditions to ensure that operability was justified and that mitigating systems or those affecting barrier integrity remained available and no unrecognized increase in risk had occurred. The inspectors also reviewed compensatory measures to ensure that the compensatory measures were in place and were appropriately controlled. The inspectors reviewed licensee performance to ensure all related TS and FSAR requirements were met. The inspectors reviewed the following degraded or non-conforming conditions:

Unit 2

  • Water Found in "C" Charging Pump Oil (CR-04-06464)
  • Flood Door Found Open Between EDG Enclosures (CR-04-06625)

"C" Service Water Pump Failed In Service Testing (CR-04-07158)

  • Emergency Building Filtration System (CR-04-03329)
  • Lost M&TE Used In The Installation Of MNSA Clamps On The Unit 2 Pressurizer in 2R14 (CR-04-05352)

Unit 3

  • Thermal Performance Test of the 3EGS*E1A & E2A Was Terminated Prior To Completion (CR-04-07596)
  • 125 VDC Battery Cells did not Meet Non Tech Spec Criteria (CR-04-06858)

"B" Train Control Building Chilled Water Valve did not Close Within Required Surveillance Time (CR-04-07851)

"B" Train Charging Pump Component Cooling Water System Relief Valve Leaks By at Approximately One Drop Per Minute (CR-04-07780)

  • Rod Supervision Program Does Not Agree With Rod Position Demand Position and Digital Rod Position Indication (CR-04-07242)

"B" Emergency Diesel Generator Output Breaker Would Not Close (CR-04-07193)

  • Chill Water Valve Indication Fails Surveillance Test (CR-04-07851)

b. Findings

Unit 2 Following the rupture of several atmospheric relief housekeeping boots at Millstone Unit 2, Dominion removed the housekeeping boots, issued CR-04-03329 and performed an operability determination (OD) to establish whether the enclosure building filtration system (EBFS) was operable with the boots removed. Dominion based its OD on the results of a "draw down test" which indicated that, in the absence of housekeeping boots and in a non transient environment, the EBFS system was capable of drawing a vacuum of 2.5 inches of water within the required 60 seconds using a single train of EBFS.

Based on these results, Dominion concluded that the EBFS remained operable following the rupture and subsequent removal of the housekeeping boots. However the inspectors questioned what the effect of steam, increased humidity, an altered flow path and the distribution of debris (scale, dirt, and bird feathers) in the penetration room would have on the post accident operation of the EBFS and found that Dominion had not evaluated these aspects. An unresolved item (URI) is being opened to determine whether these conditions would impact the operability of the system and to determine the significance of any issues. (URI 05000336/2004007-01).

Unit 3 No findings of significance were identified.

1R16 Operator Work-Arounds (71111.16 - 1 Unit 2 and 1 Unit 3 Sample)

Cumulative Effects of Operator Work-Arounds

a. Inspection Scope

The inspectors reviewed the current listing of active operator work-arounds (OWAs) for Millstone Unit 2 and Unit 3. The review was conducted to verify that Dominion procedures and practices provided the necessary guidance to plant personnel, that the cumulative effects of the known OWAs were addressed and that the overall impact on the affected systems was assessed by Dominion. The inspectors independently assessed the cumulative impact of known OWAs to determine if they adversely affected the ability of plant operators to implement emergency procedures, respond to plant transients, or perform normal functions within the expectations of the established Dominion risk models. In support of this assessment, the inspectors reviewed various condition reports regarding OWAs, and verified that OWAs were being identified, tracked, and resolved in Dominion's corrective action program.

b. Findings

No findings of significance were identified.

==1R17 Permanent Plant Modifications (71111.17A - 2 Unit 2 Samples)

a. Inspection Scope

==

The inspectors reviewed two samples of a permanent plant modification on Unit 2. The inspectors performed a walkdown of the area and reviewed the FSAR, licensing and design basis documents, and the engineering disposition. These reviews were conducted to ensure

(1) the modified components remained consistent with the assumptions indicated in the design basis documents,
(2) that system availability, reliability, and functional capability were maintained, and
(3) no unrecognized conditions that significantly affected risk or could place the plant in an unsafe condition were introduced as a result of the modifications. Documents reviewed during the inspection are listed in the Attachment.

Unit 2

  • Charging System (DCR M2-03006)
  • Reactor Regulating System/Atmospheric Reliefs/Condenser Dump Valves (MMOD M2-99056)

b. Findings

1. Charging System

The inspectors identified an unresolved item (URI) related to the application of 10 CFR 50.59 to a permanent modification of the Millstone Unit 2 charging system. During a review of permanent plant modification DCR M2-03006, the inspectors noted that the modification did not contain calculations or test data to verify that the charging system established and maintained an adequate net positive suction head (NPSH) on the system following significant design changes to the system. This issue is addressed in Dominions corrective action program (CR-04-06773). A URI is being opened to track Dominions evaluation of NPSH in the charging system. (URI 05000336/2004007-02).

2. Main Steam Code Safety Valve Operation

Introduction.

A Green non-cited violation of 10 CFR 50 Appendix B, Criterion XVI, Corrective Actions, was identified for the failure to take actions to correct a long-standing design problem whereby main steam safety valves (MSSV) lift following uncomplicated turbine trips/reactor trips from 100% power.

Description.

The inspectors observed that main steam code safety valves had lifted following uncomplicated trips at Unit 2 on March 6, 2004 and March 15, 2004. A review of previous trips found that main steam code safeties had lifted subsequent to several reactor trips in the past. The inspectors questioned Dominion as to the adequacy of the RRS and ASDS system designs since the FSAR indicates these systems are intended to operate to prevent lifting MSSVs following a design basis turbine trip/reactor trip from 100% power.

The inspectors determined that corrective actions taken by Dominion over many years had not corrected the problem of MSSVs lifting following uncomplicated transients. The inspectors determined that cycling the main steam code safety valves following a turbine trip/reactor trip from full power results in an increased likelihood that they may not reseat properly.

Analysis.

The inspectors determined that Dominion's failure to establish and implement adequate corrective actions to prevent the operation of the main steam code safety valves outside of their design constitutes a performance deficiency. Traditional enforcement does not apply because there were no actual safety consequences, impacts on the NRC's ability to perform its regulatory function, or willful aspects to the violation. The finding is more than minor because it affects the equipment performance attribute of the Initiating Event Cornerstone and the objective to limit the likelihood of those events that upset plant stability. Specifically, cycling MSSVs results in a greater likelihood they will not reseat properly during an event. The inspectors determined that this finding was of very low safety significance (Green) through performance of a Phase 1 SDP in accordance with Inspection Manual Chapter (IMC) 0609, Appendix A, "Determining the Significance of Reactor Inspection Findings for At-Power Situations."

Specifically, the finding did not contribute to the likelihood of a primary loss of coolant accident, did not contribute to both the likelihood of a reactor trip and the unavailability of mitigating equipment, and did not increase the likelihood of a fire or internal/external flood. This finding is related to the Problem Identification and Resolution cross-cutting area in that repetitive cycling of MSSVs has not been corrected.

Enforcement.

10 CFR 50 Appendix B, Criterion XVI, Corrective Actions, requires, in part, that Dominion shall take measures to assure that conditions adverse to quality, such as failures, malfunctions, deficiencies, deviations, defective material and equipment are promptly identified and corrected. Contrary to this requirement, Dominion did not take effective corrective action to address repetitive cycling of MSSVs following uncomplicated turbine trips/reactor trips. This violation has been determined to have a very low safety significance since the cycling of MSSVs following turbine trips/reactor trips does not increase the likelihood of a primary system loss of coolant accident, reactor trip initiators, or fire/flooding initiators. This violation is in Dominion's corrective action program (CR-04-02514) and, therefore, is being treated as a non-cited violation, consistent with Section VI.A.1 of the NRC Enforcement Policy.

(NCV 05000336/2004007-03).

==1R19 Post-Maintenance Testing (71111.19 - 4 Unit 2 and 5 Unit 3 Samples)

a. Inspection Scope

==

The inspectors reviewed nine samples of post-maintenance tests (PMT) during this inspection period. The inspectors reviewed these activities to determine whether the PMT adequately demonstrated that the safety-related function of the equipment was satisfied given the scope of the work specified and that operability of the system was restored. In addition, the inspectors evaluated the applicable test acceptance criteria to verify consistency with the associated design and licensing bases, as well as TS requirements. The inspectors also verified that conditions adverse to quality were entered into the corrective action program for resolution. Documents reviewed during the inspection are listed in the Attachment. The following maintenance activities and their post maintenance tests were evaluated:

Unit 2

"A" Control Room Air Conditioning (M2-03-04115)

"A" Enclosure Building Filtration System Fan Dehumidifier Heater (M2-03-03455)

"A" Containment Spray Pump Breaker Preventive Maintenance (M2-02-03953)

  • Replacement of Calibrated Pressurizer Level Control Meter (M2-03-14724)

Unit 3

  • Station Blackout Air Receiver Tank 1B Drain, 3BGA-V023 (M3-03-03273)
  • Service Water to Containment Recirculation Pump Ventilation Cooler Bypass Valve Replacement with a Flange (M3-04-11702)

"B" Diesel Generator Cylinder No. 7 Cover Oil Leak (M3-03-13787)

b. Findings

Unit 2

Introduction.

A Green self-revealing non-cited violation was identified for the failure to adequately implement procedures for Instrumentation and Control (I&C) testing of pressurizer level control circuitry which resulted in an inadvertent start of both standby charging pumps with one charging pump running.

Description.

On July 28, 2004, both standby charging pumps started unexpectedly with one charging pump already running while I&C was performing post-maintenance testing of pressurizer level control circuitry in the Reactor Regulating System (RRS).

I&C generated a work order to replace a pressurizer level instrument and perform a loop calibration of the letdown controls in the RRS. IC2418D, Calibration of Letdown Controls, contained a prerequisite that required, "Unit 2 is shutdown". Additionally, a step within this procedure required placing the charging pump selector switches to "PULL TO LOCK" which would have precluded the standby charging pumps from starting on a RRS test signal. Neither operators nor I&C personnel identified these procedure requirements prior to the conduct of testing. As a result, I&C personnel initiated a test signal that affected both "X" and "Y" RRS channels and caused both standby charging pumps to start. It is noted that this system condition (starting both standby charging pumps with one charging pump already running thereby causing a significant pressure transient in the system) was the identified cause of the failure of the charging system on March 7, 2003. In this event, the highest system pressure recorded was approximately 2413psig (system relief valves are set at approximately 2735psig).

System design changes including charging pump discharge pulsation dampeners, weld reinforcements, piping rerouting, and relief valve modifications taken in response to the March 7, 2003 event appear to have limited the impact on the charging system from this event.

Analysis.

The performance deficiency associated with this event is that I&C technicians and plant operators did not adequately implement a post-maintenance test procedure and it was within Dominion's ability to foresee and control. Traditional enforcement does not apply because there were no actual safety consequences, impacts on the NRC's ability to perform its regulatory function, or willful aspects to the violation. This issue was more than minor because it is associated with the human performance attribute under the Initiating Events cornerstone and the objective to limit the likelihood of those events that upset plant stability. The finding is associated with an increase in the likelihood of initiating events in that both standby charging pumps actually started which was the precursor to the failure of the charging system on March 7, 2003. The inspectors determined that this self-revealing finding was of very low safety significance (Green) through performance of a Phase 1 SDP in accordance with Inspection Manual Chapter (IMC) 0609, Appendix A, "Determining the Significance of Reactor Inspection Findings for At-Power Situations." Specifically, this finding did not contribute to the likelihood of a primary or secondary loss of coolant accident initiator, did not contribute to the likelihood of a reactor trip and the unavailability of mitigation equipment or functions, and did not increase the likelihood of a fire or internal/external flood. This finding is related to the Human Performance cross-cutting area, in that human performance errors resulted in an unexpected start of both standby charging pumps.

Enforcement.

TS 6.8.1a states, in part, that written procedures shall be established, implemented and maintained covering the activities specified in Appendix A of Regulatory Guidance 1.33. Regulatory Guide 1.33, Appendix A, Item 9.a, requires that maintenance that can affect the performance of safety-related equipment should be properly preplanned and performed in accordance with written procedures. Contrary to this requirement, during post-maintenance testing of pressurizer level control circuitry, I&C technicians and operations personnel did not verify all appropriate prerequisites or perform all applicable procedural steps which then resulted in the inadvertent actuation of a safety-related system. This violation has been determined to have a very low safety significance and is in Dominion's corrective action program as CR-04-07015. Therefore, it is being treated as a non-cited violation consistent with Section VI.A.1 of the NRC Enforcement Policy. (NCV 05000336/2004007-04).

Unit 3 No findings of significance were identified.

==1R22 Surveillance Testing (71111.22 - 4 Unit 2 and 5 Unit 3 Samples)

a. Inspection Scope

==

The inspectors reviewed nine samples of surveillance activities to determine whether the testing adequately demonstrated the equipments' operational readiness and its ability to perform its intended safety-related function. The inspectors attended pre-job briefs, verified that selected prerequisites and precautions were met and that the tests were performed in accordance with the procedural steps. Additionally, the inspectors evaluated the applicable test acceptance criteria to verify consistency with associated design basis, licensing bases and TS requirements, and that the applicable acceptance criteria were satisfied. The inspectors also verified that conditions adverse to quality were entered into the corrective action program for resolution. Documents reviewed during the inspection are listed in the Attachment. The following surveillance activities were evaluated:

Unit 2

  • Turbine Driven Auxiliary Feed Pump Surveillance Test (SP-2610B)

"A" Reactor Building Closed Cooling Water Pump Inservice Test (SP-2611A)

Unit 3

"A" Emergency Diesel Generator Service Water Valve Stroke Test (SP-3626.3)

"B" Safety Injection Slave Relay Testing (SP-3646A.9)

"A" Emergency Diesel Generator Operability Tests (SP-3646A.1)

"B" MDAFW Pump Inservice Test (SP-3622.2-001)

b. Findings

Unit 2

1. Main Steam Code Safety Valve Testing

Millstone Unit 2 main steam code safety valve TS surveillance testing is implemented in part by SP-2730B, Main Steam Code Safety Valve Test. The inspectors questioned the following based on a review of the surveillance procedure and supporting documentation:

  • The surveillance procedure contained a conversion factor for the main steam code safety valves that was developed by a 10 CFR Appendix B qualified vendor, however, the developmental data was not available for NRC Inspection and had not been independently reviewed by Dominion. Additionally, the conversion factor does not indicate tolerances such as testing assurance, variation or error related to the development of the conversion factor and the surveillance did not address testing assurance, variation or error related to the measurement and test equipment (MT&E).
  • There was no indication in the Dominion surveillance that the M&TE used during the implementation of the surveillance was calibrated and traceable to a National Bureau of Standards (NIST) standard.
  • Vendor technical materials that were related to the M&TE used in the Millstone Unit 2 surveillance indicated that the M&TE is to be used only for confirming valve set pressure once the valve has been adjusted by the use of full system over pressure ("full lift") testing. Dominion documentation indicates that the M&TE was used on several main steam code safety valves following full valve lifts that resulted from plant transients.

An unresolved item (URI) is being opened to determine how information supplied by Appendix B certified vendors is reviewed, if Dominion can trace the M&TE equipment to a national standard and whether it is acceptable to test main steam code safeties with the test apparatus following an actual lift of the relief valve. (URI 05000336/2004007-05).

2. Trisodium Phosphate Surveillance

Millstone Unit 2 TS 3.5.5, Trisodium Phosphate (TSP), requires a verification that there are 282 cubic feet of active, granulated TSP stored in a designated container within the Millstone Unit 2 containment. The TS surveillances are based on Dominion engineering calculation 97-ENG-1784-M2 and a set of titration curves developed from Dominion Standard 7077-US(B)-001, Titration of Boric Acid with Trisodium Phosphate. The inspectors questioned the effectiveness of the TSP related to it being in a "granulated" state throughout its volume as opposed to the current condition of a coagulated mass.

Additionally, the inspectors questioned if the sampling mechanism and size were adequate. Finally, the inspectors questioned why the engineering calculation used to determine the necessary amount of TSP did not include several volumes of borated water (for example; piping down stream of the blender, EDT, VCT, and PDT) which would contribute to the post accident, containment sump, boric acid concentration. The URI is being opened to address these questions and determine the significance of any issues. (URI 05000336/2004007-06).

Unit 3 No findings of significance were identified.

==1R23 Temporary Plant Modifications (71111.23 - 1 Unit 2 and 2 Unit 3 Samples)

a. Inspection Scope

==

The inspectors reviewed three samples of temporary modifications to verify that the temporary modifications did not affect the safety function of important safety systems.

The inspectors reviewed the temporary modifications and their associated 10 CFR 50.59 screening against the FSAR and TS to ensure the modifications did not affect system operability or availability. Documents reviewed during the inspection are listed in the

.

Unit 2

  • Fuel Handling Building Door Temporary Ventilation Barrier (WC-10-004)

Unit 3

  • Temporary Design Change to Replace the Service Water to Containment Recirculation Pump Ventilation Cooler Bypass Valve with a Flange (DM3-00-0234-04)
  • Temporary Piping Restraints for 3CCI*E1A Service Water Piping (DM3-00-0235-04)

b. Findings

No findings of significance were identified.

Cornerstone: Emergency Preparedness [EP]

1EP6 Drill Evaluation (71114.06 - 1 Unit 2 and 1 Unit 3 Sample)

a. Inspection Scope

The inspectors observed one sample of the conduct of a Unit 2 licensed operator simulator training on September 14, 2004. The inspectors evaluated the Operations crew activities related to evaluating the scenario and making proper classification determinations. Additionally, the inspectors assessed the ability of Dominions evaluators to adequately address deficiencies identified during the exercise.

The inspectors observed one sample of the conduct of a Unit 3 licensed operator training emergency planning drill on August 10, 2004. The inspectors observed the operating crew performance at the simulator and emergency response organization performance at the site emergency operations center and technical support center. The inspectors verified that the classification, notification and protective action recommendations were accurate and timely. Additionally, the inspectors assessed the ability of Dominions evaluators to adequately address deficiencies identified during the exercise. Documents reviewed during the inspection are listed in the Attachment.

b. Findings

No findings of significance were identified.

RADIATION SAFETY

Cornerstone: Occupational Radiation Safety [OS]

2OS3 Radiation Monitoring Instrumentation (71121.03 - 9 Samples)) Unit 2 and Unit 3

a. Inspection Scope

During the period September 13 - 17, 2004, the inspector conducted the following activities to evaluate the operability and accuracy of radiation monitoring instrumentation, and the adequacy of the respiratory protection program for issuing self-contained breathing apparatus (SCBA) to emergency response personnel.

Implementation of these programs was reviewed against the criteria contained in 10 CFR 20, applicable industry standards, and Dominions procedures.

  • The inspector reviewed the operating procedure and current source activities/dose rate characterizations for the Shepherd Model 89 instrument beam calibrators (Serial Nos. 9155 & 9068). The inspector reviewed the calibration records for the Model 530 Electrometer and associated ion chambers used in calibrating the Shepherd calibrators.
  • The inspector reviewed the calibration records for selected survey instruments and contamination monitors including the small article contamination monitors (SAM 9 & 11), personnel contamination monitors (PCM-1B), portal monitors (PM-7), and portable survey instruments (RO-2A, RO-20).
  • The inspector reviewed the relevant procedures and observed a technician calibrating an air sampler (AVS-28A) and two portable radiation survey instruments (RO-2A & RO-20).
  • The inspector observed a technician performing daily functional checks on a variety of contamination monitors and survey instruments located in Unit 3 including a SAM-9, SAM-11, PCM-1B, CM-11, RM-14, and a Teleprobe FH-40-TG. The inspector reviewed the procedure and records associated with performing the instrument daily functional checks, including routine response tests performed on electronic dosimeters.
  • The inspector reviewed the calibration procedure and current calibration data for selected area monitors, including two Unit 3 fuel storage pool area radiation monitors (3RMS-RIY08 and 3RMS-RIY36) and a Unit 3 containment area monitor. The inspector observed an Instrumentation and Control technician calibrating the Unit 3 containment area monitor.
  • The calibration records and pre-operational quality control checks were reviewed for the Fast-Scan whole body counting systems.
  • The inspector reviewed recent contamination sampling results for Units 2 and 3 to determine if the calibration sources used were representative of the radioisotopes found in the plant source term.
  • The inspector evaluated the adequacy of the respiratory protection program regarding the maintenance and issuance of SCBA to emergency response personnel. Training and qualification records were reviewed for three licensed operators from each of the five operating shifts at each unit and for selected radiation protection technicians who would wear SCBAs in the event of an emergency. The inspector, with the assistance of a Fire Brigade member, physically inspected three SCBAs staged for use in each control room, a SCBA staged for use in the Unit 3 auxiliary building, and a SCBA staged in the Unit 2 Technical Services Area. Maintenance and test records were reviewed for selected SCBAs.

b. Findings

No findings of significance were identified.

Cornerstone: Public Radiation Safety [PS]

2PS2 Radioactive Material Processing and Transportation (71122.02 - 6 Samples) Unit 2 and Unit 3

a. Inspection Scope

During the period June 28 - July 1, 2004, the inspector conducted the following activities to verify that Dominions radioactive material processing and transportation programs complied with the requirements of 10 CFR 20, 61, and 71; and Department of Transportation (DOT) regulations contained in 49 CFR 170-189.

Radioactive Waste System Walkdown The inspector walked down accessible portions of the Unit 2 and Unit 3 radioactive liquid and solid waste collection/processing systems with the cognizant system engineer. The inspector evaluated if the systems and facilities were consistent with the descriptions contained in the Updated Final Safety Analysis Report (UFSAR) and Process Control Program, evaluated the general material conditions of the systems and facilities, and identified any changes to the systems. Also, the inspector and the Supervisor of Radioactive Material Controls visually inspected the radwaste storage areas located within the site protected area, including Warehouse No. 9 and the Dominion Radwaste Reduction Facility; and the radwaste storage bunker, located in the owner controlled area.

The inspector discussed with the radioactive waste systems engineer the status of non-operational, retired-in-place, radioactive waste processing equipment, and the administrative and physical controls for various components in these systems. The inspector evaluated any recent changes made to radwaste processing systems and the potential radiological impact, and reviewed the current processes for transferring radioactive resin and sludge to shipping containers and subsequent resin sampling and de-watering.

Waste Characterization and Classification The inspection included a selective review of the waste characterization and classification program for regulatory compliance, including:

  • the radio-chemical sample analysis results for various radioactive waste streams, including spent resins, dry active waste, and mechanical filters
  • the development of scaling factors for hard-to-detect radionuclides
  • methods and practices to detect changes in waste streams
  • classification and characterization of waste relative to 10 CFR 61.55 and to determine the DOT shipment subtype per 49 CFR 173 Shipment Preparation The inspection included a review of radioactive waste program documents and shipment preparation procedures, and in-progress activities for regulatory compliance, including:
  • review of certificates of compliance for in-use shipping casks
  • verification of appropriate NRC (or agreement state) license authorization for shipment recipients for six recent shipments listed in the shipping records section
  • verification that training was provided, in accordance with NRC Bulletin 79-19, and 49 CFR 172 Subpart H, to appropriate personnel directly responsible for classifying, handling, and shipping radioactive materials, or for providing oversight for these activities
  • review of the 2003 Radioactive Effluent Release Report Shipping Records The inspector selected and reviewed records associated with six
(6) non-excepted shipments of radioactive materials made since the last inspection of this area. The shipments were Nos. 04-024-3, 03-082-2, 03-057-3, 03-055-3, 03-024-2, and 02-076-3.

The following aspects of the radioactive waste packaging and shipping activities were reviewed for these shipments:

  • implementation of applicable shipping requirements including proper completion of manifests
  • implementation of specifications in applicable certificates-of-compliance, for the approved shipping casks including limits on package contents
  • classification of radioactive materials relative to 10 CFR 61.55 and 49 CFR 173
  • labeling of containers
  • placarding of transport vehicles
  • radiation and contamination surveys of packages
  • conduct of vehicle checks
  • providing of driver emergency instructions
  • completion of shipping papers

b. Findings

No findings of significance were identified.

OTHER ACTIVITIES

[OA]

4OA1 Performance Indicator Verification (71151 - 2 Unit 2 and 4 Unit 3 Samples)

a. Inspection Scope

The inspectors reviewed six samples of Dominion submittals for the performance indicators (PIs) listed below to verify the accuracy of the PI data reported during the applicable period. The PI definitions and guidance contained in NEI 99-02, "Regulatory Assessment Indicator Guideline", Revision 2, were used to verify the basis for reporting each data element.

Unit 2 Reactor Safety Cornerstone

  • High Pressure Safety Injection System Unavailability Unit 3 Reactor Safety Cornerstone
  • Scrams with Loss of Normal Heat Removal
  • High Pressure Safety Injection System Unavailability
  • Residual Heat Removal System Unavailability The inspectors reviewed licensee event reports, monthly operating reports, control room shift logs, condition reports and NRC inspection reports to identify safety system equipment failures and unavailability that occurred from the third quarter of 2003, through the second quarter of 2004. The inspectors compared this information with Dominion's data reported to the NRC for the performance indicators (PI) listed above to verify that PI reporting and proximity to PI thresholds published on the NRC website were accurate. Documents reviewed during the inspection are listed in the Attachment.

b. Findings

No findings of significance were identified.

4OA2 Identification and Resolution of Problems

1. Daily Review of Problem Identification and Resolution

a. Inspection Scope

As required by Inspection Procedure 71152, "Identification and Resolution of Problems",

and in order to help identify repetitive equipment failures or specific human performance issues for followup, the inspectors performed a daily screening of items entered into Dominion's corrective action program. This review was accomplished by reviewing summary lists of each condition report, attending screening meetings, and accessing Dominion's computerized condition report database.

b. Findings

No findings of significance were identified.

2. Annual Sample Review (1 Unit 2 and 1 Unit 3 Sample)

Unit 2

a. Inspection Scope

The inspectors selected condition reports (CR) associated with the Unit 2 turbine-driven auxiliary feedwater (AFW) pump overspeed condition and excessive discharge check valve chatter for detailed review. While several CRs were reviewed associated with this issue, this inspection constituted one sample. The inspectors reviewed CR-03-11918, CR-03-11922, CR-03-11942, CR-03-11963 and CR-04-05091. The reports were reviewed to ensure that the full extent of the issues were identified, an appropriate evaluation was performed, and appropriate corrective actions were specified, prioritized, and implemented. The inspectors evaluated the reports against the requirements of Dominion's corrective action program as delineated in MP-16-CAP-FAP01.1, "CR Screening and Review," and 10 CFR 50, Appendix B. Documents reviewed during the inspection are listed in the Attachment.

b. Findings and Observations

There were no findings identified. The five CRs reviewed were associated with turbine overspeed events and/or excessive discharge check valve chatter, which occurred during AFW system testing. Although Dominions initial efforts were not effective in identifying the cause and correcting the operational anomalies (resulting in multiple turbine overspeed occurrences), operability of the system was not impacted and an adequate corrective action plan was developed and implemented. For the interim, a previously removed turbine governor was re-installed and tested satisfactorily, and upgraded replacement governors were ordered.

Unit 3

a. Inspection Scope

The inspectors selected three condition reports (CRs) for detailed review. The CRs were associated with unexpected power changes while performing monthly turbine generator valve testing. The CRs were reviewed to ensure that the full extent of the issues were identified, an appropriate evaluation was performed, and appropriate corrective actions were specified and prioritized.

b. Findings

No findings of significance were identified

3. Cross-References to PI&R Findings Documents Elsewhere

Section 1R17 describes a finding for the failure to take effective corrective actions to preclude main steam code safety valves from lifting following design basis turbine trips/reactor trips from 100% power. This issue is attributable to the PI&R cross-cutting area because if left uncorrected it could lead to a more significant event and affect the equipment performance attribute of the Initiating Events Cornerstone. Cycling of main steam code safety valves results in a greater likelihood that the valves will not reseat properly.

4. Radioactive Material Processing and Transportation

Unit 2 and Unit 3

a. Inspection Scope

The inspector reviewed nine

(9) Condition Reports and a Nuclear Oversight Audit Report (MP-03-A07) relating to radioactive material processing and shipment. Through this review, the inspector assessed Dominions threshold for identifying problems, and the promptness and effectiveness of the resulting corrective actions. This review was conducted against the criteria contained in 10 CFR 20.1101(c), TS, and Dominions procedures.

b. Findings

No findings of significance were identified.

5. Radiation Monitoring Instrumentation and Protective Equipment

a. Inspection Scope

The inspector reviewed twenty-five

(25) selected Condition Reports (CR), an I&C Department self-assessment and a Radiation Protection Department self-assessment to evaluate Dominions threshold for identifying, evaluating, and resolving problems in implementing the radiation monitoring and respiratory protection programs. This review was conducted against the criteria contained in 10 CFR 20, TS, and Dominions procedures.

b. Findings

No findings of significance were identified.

4OA3 Event Followup (71153 - 1 Unit 3 Sample)

(Closed) Licensee Event Report (LER) 05000423/2004001-00, Technical Specification Action Statement Not Met

a. Inspection Scope

The inspectors interviewed Dominion personnel and reviewed this LER with its associated condition reports (CR-04-04396, CR-04-08469, and CR-04-08935) to verify that the root cause and corrective actions related to the event described in the LER were adequate.

b. Findings

Introduction.

A Green non-cited violation of TS 3.8.3.2, Onsite Power Distribution -

Shutdown, was identified for the failure to enter TS 3.8.3.2 when it was warranted by plant conditions and the subsequent failure to take TS actions to preclude reactivity additions to the reactor coolant system (RCS).

Description.

On April 30, 2004, with the plant in Mode 5 and with a startup/heatup in progress, an oncoming Shift Manager determined that the previous shift had not performed the required TS 3.8.3.2 limiting condition for operation (LCO) actions, following a failure of a vital inverter. The inverter failure resulted in an electrical lineup that did not meet the TS requirement for one compete train of electrical buses. The required actions were to immediately stop all reactivity additions. The operators entered the appropriate alarm response procedure, but did not complete the procedure which would have directed them to the TS. In addition, the operators failed to stop both the plant heatup and the RCS dilution (hydrazine addition) activities. The plant heatup and dilution activities resulted in positive RCS reactivity additions. CR-04-04396 and LER 05000423/2004001-00 determined the root cause of the event to be a failure to adequately complete the alarm response procedure.

Based on a review of the event, the LER and the associated CRs, the inspectors determined that;

  • the LER did not completely identify the root cause of the event since the LER does not discuss the operators failure to recognize entry was required independent of the failure to complete the alarm procedure,
  • the corrective actions indicated in CR-0404396 were not adequate to prevent recurrence, since they were specific to the failure to complete the alarm response procedure,
  • additional sources of positive reactivity addition (two separate dilutions of the RCS) was not addressed in the LER or CR.

Subsequent to the inspectors review of CR-0404396 and the LER, Dominion issued two additional CRs (CR-0408469 and CR-0408935), in order to revise the stated root cause and to address the RCS dilutions. Dominion also initiated actions to revise the LER and implement additional corrective actions to prevent recurrence.

Analysis.

The inspectors determined that the failure to cease the reactivity addition with a degraded electrical configuration was a performance deficiency. Traditional enforcement does not apply because there were no actual safety consequences, impacts on the NRC's ability to perform its regulatory function, or willful aspects to the violation. The on shift operators did not comply with TS because they failed to recognize the impact of the vital inverter failure on the existing electrical bus configuration and thereby the need to enter TS. The finding is more than minor because it is associated with the human performance attribute of the Mitigating Systems (in this case onsite power distribution) Cornerstone and the objective of ensuring the availability of systems to respond to initiating events to prevent undesirable circumstances. The failure of the vital inverter resulted in an electrical lineup that did not meet the TS requirement for one complete train of electrical buses. Additionally, the failure to recognize the need to enter TS precluded taking corrective actions to prevent adding positive reactivity additions with this electrical lineup. Several positive reactivity additions actually occurred as a result of not taking TS actions.

This finding was assessed using Appendix G, Shutdown Operations Significance Determination Process, of Inspection Manual Chapter 0609, Significance Determination Process (SDP), and was determined to be of very low safety significance (Green). The finding did not increase the likelihood of a loss of Reactor Coolant System (RCS)inventory, degrade Dominions ability to add inventory if needed, or degrade the ability to recover the Residual Heat Removal (RHR) system if it was lost. Finally, the positive reactivity addition from the heatup and the dilution was small compared to the reactivity needed for criticality.

Enforcement.

Technical Specification 3.8.3.2, Onsite Power Distribution - Shutdown, requires, in part, that all reactivity additions be stopped when requirements for one complete train of electrical buses are not met. Contrary to this requirement, Dominion did not recognize the need to enter the TS and thereby failed to take the TS actions to preclude positive reactivity additions while in this electrical configuration. This violation has been determined to have a very low safety significance since the positive reactivity additions were small compared to the reactivity necessary to achieve criticality. Dominion entered this finding into its corrective action program, therefore, this violation is being treated as an NCV, consistent with Section VI.A of the NRC Enforcement Policy (NCV 05000423/2004007-07).

4OA4 Cross Cutting Aspects of Findings

Section 1R19 describes a finding for the failure by Operations and Maintenance to adequately implement a post maintenance test procedure following replacement of a pressurizer level instrument.

Section 4OA3 describes a finding for failure of operators to recognize that a vital invertor equipment failure required entry into TS. As a result, operators did not take TS actions to preclude reactivity additions and several positive reactivity additions occurred.

Section 40A5 describes a finding for failure to adequately implement procedures for venting the reactor coolant system (RCS) and the residual heat removal (RHR) system.

4OA5 Other Activities

1. (Closed) URI 05000423/2004006-02, Air Entrainment of Residual Heat Removal System

Introduction.

A Green non-cited violation was identified for the failure to adequately implement procedures for venting the reactor coolant system (RCS) and the residual heat removal (RHR) system.

Description.

On May 28, 2004, Dominion conducted a quarterly vent and valve lineup surveillance of the "A" train of the RHR system in which air was vented from several vent valves. On June 13, 2004, Dominion repeated the vent for the "A" RHR train.

Again, air was vented from the RHR system but to a lesser extent than described on May 28, 2004. On June 15, 2004, a third venting of the "A" train of the RHR system was conducted with no air vented. Dominion preliminarily determined that the "A" train of the RHR system and portions of both trains of the safety injection (SI) and charging systems may have been adversely affected by entrapped air. CR-04-06166 was written and a team established to determine the root cause and provide a corrective action plan.

Additionally, Engineering was tasked with quantifying the amount of entrapped air that could affect system operability to assess past operability.

The inspectors reviewed the technical evaluation and determined that the amount of air in the RHR system did not adversely impact the RHR pumps, SI pumps, or the charging pumps. The inspectors reviewed the root cause evaluation and determined the cause of the entrapped air was due to securing one of the two RHR pumps on April 28, 2004, during the RCS sweep and vent evolution. Additionally, the inspectors determined that Operations failed to vent the "A" train of the RHR system as required by SP 3610A.3, "RHR System Vent and Valve Lineup Verification" prior to aligning the RHR system to SI mode during plant heatup. Specifically, step 4.1.2 stated, If RHR Train A is being aligned for SI MODE during plant heatup as specified in OP 3310A, Residual Heat Removal System, AND all of the following conditions are satisfied, Go to step 4.1.2.a:

  • RHR Train A has not been run within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
  • RHR Train A has not been swept in accordance with this procedure since any maintenance which drained portions of the train (such as LLRT) was performed OR since any midloop operations were performed.

Contrary to this procedure step, Dominion did not go to step 4.1.2a in SP 3610A.3 even though the "A" RHR train had not been run within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and midloop operations had been performed. Consequently, Dominion did not run the "A" RHR pump as required during the venting of the "A" RHR train which precluded identifying the trapped air in the "A" RHR train prior to aligning the RHR system for the safety injection (SI) mode.

Analysis.

The inspectors determined that the failure to adequately implement procedures for sweeping and venting the RCS and the RHR system was a performance deficiency. Traditional enforcement does not apply because there were no actual safety consequences, impacts on the NRC's ability to perform its regulatory function, or willful aspects to the violation. Dominion did not establish adequate precautions or prerequisites in OP 3218 to prevent securing a running RHR pump during the sweep and vent process and Dominion did not perform the RHR vent and valve lineup verification as required by SP 3610A.3. This resulted in trapping air in the RHR system and portions of the suction piping of both trains of the SI and charging systems. This issue was more than minor because it is associated with the equipment performance attribute of the Mitigating Systems Cornerstone and the objective of ensuring the availability of systems to respond to initiating events to prevent undesirable consequences. The entrapped air had the potential to make the "A" RHR pump, the SI pumps and the charging pumps inoperable. The inspectors determined that the finding was of very low safety significance (Green) through performance of a Phase 1 SDP in accordance with Inspection Manual Chapter (IMC) 0609, Appendix A, "Determining the Significance of Reactor Inspection Findings for At-Power Situations." Specifically, this finding did not represent an actual loss of safety function of the RHR, SI, or charging system since the amount of air subsequently determined to be in these systems would not have prevented them from functioning.

Enforcement.

TS 6.8.1a, Written Procedures, requires, in part, that written procedures be established, implemented, and maintained for activities described in Appendix A of Regulatory Guide (RG) 1.33, "Quality Assurance Program Requirements (Operation)."

Specifically, Section 3 of RG 1.33, Appendix A, "Instructions for energizing, filling, venting, draining, startup, shutdown, and changing modes of operation should be prepared, as appropriate, for the following systems," includes the reactor coolant system. Contrary to this requirement, Dominion failed to establish adequate precautions and prerequisites to prevent plant configuration changes that could lead to air entrainment while conducting OP 3218, "RCS sweep and vent procedure." Additionally, contrary to this requirement, Dominion failed to implement required procedural steps to vent the RHR system as required by SP 3610A.3, "RHR System Vent and Valve Lineup Verification." Together, these circumstances resulted in entrapped air in the "A" train of the RHR system and portions of the SI and charging systems suction piping. This violation has been determined to have very low safety significance and is in Dominion's corrective action program as CR-04-06166. Therefore, this violation is being treated as a non-cited violation (NCV), consistent with Section VI.A.1 of the NRC Enforcement Policy (NCV 05000423/2004007-08).

2. Review of Generic Letter 89-13: Service Water System Problems Affecting Safety-

Related Equipment (TI 2515/159) Heat Sink Performance (71111.07B - 3 Unit 2 Samples)

a. Inspection Scope

The inspectors reviewed Millstone Unit 2 service water (SW) system and component performance which included a review of SW system design requirements, operating, maintenance, and testing procedures. Dominions inspection, cleaning, chemical control, and performance monitoring methods, frequencies, and test results of the SW system and its related components were reviewed to ensure compliance with commitments made in their response to the five recommended actions of Generic Letter (GL) 89-13, "Service Water System Problems Affecting Safety Related Equipment."

The inspectors reviewed design bases summary information including flow calculations and SW-related modifications to ensure that Dominion was maintaining the design bases of the SW system.

The inspectors reviewed system operating, abnormal and emergency procedures, and operator training material associated with the service water system to determine whether the procedures were adequate to ensure that safety-related equipment cooled by the service water system would function as intended, and that operators would perform effectively. In addition, operator logs were reviewed to determine the adequacy of temperature and flow monitoring, and to evaluate operator effectiveness in varying SW system heat exchanger flow rates due to changing climate (temperature) conditions.

During plant tours and procedure and training reviews, the inspectors verified the ability of operators to locally operate SW components. The inspectors reviewed selected SW system maintenance procedures and/or work orders for technical adequacy and proper implementation. The maintenance history and preventive maintenance requirements for selected SW system components were reviewed to determine the effectiveness of corrective and preventive maintenance.

Applicable condition reports (CR), Licensee Event Reports (LER), system health reports and related past self-revealing and NRC-identified inspection findings were sampled to understand the SW system maintenance and operational history, and Dominions response to those identified adverse conditions.

This inspection also fulfilled inspection attributes and requirements for Millstone Unit 2's biennial heat sink inspection (71111.07B). The following heat exchangers were selected for review:

C RBCCW Heat Exchanger X18A C

Vital AC Switchgear Cooler X183 C

"B" Emergency Diesel Generator Heat Exchanger

b. Observations and Findings

No findings of significance were identified.

Overall, the inspectors concluded that Dominions response to GL 89-13 was appropriate and the recommended actions from GL 89-13, in general, have been effectively implemented and maintained. In addition, Dominions operating experience program and procedure have appropriately addressed and incorporated service water items.

The specific responses to the questions directed by TI 2515/159 are contained in the of this report.

4OA6 Meetings, Including Exit

Public Radiation Safety Report Exit Meeting Summary On July 1, 2004, the inspector presented the Unit 2 and Unit 3 inspection results to licensee management and other staff who acknowledged the findings.

Biennial Maintenance Rule Scoping Inspection Exit Meeting Summary On August 20, 2004, the inspectors presented the Unit 2 and Unit 3 inspection results to Mr. J. Alan Price and other member of his staff who acknowledged the findings.

TI-159, GL 89-13 Investigation and Heat Exchanger Performance Inspection Exit Meeting Summary On September 3, 2004, the inspectors presented the Unit 2 inspection results to Mr. Steve Scace and Mr. Steve Sarver and other member of their staff who acknowledged the findings.

Occupational Radiation Safety Report Exit Meeting Summary On September 17, 2004, the inspector presented the Unit 2 and Unit 3 inspection results to licensee management and other staff who acknowledged the findings.

Integrated Report Exit Meeting Summary On October 14, 2004, the resident inspectors presented the overall inspection results to Mr. J. Alan Price and other members of his staff who acknowledged the findings. The inspectors confirmed that proprietary information was not provided or examined during the inspection.

ATTACHMENT:

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee personnel

A. Armagno, Supervisor, Health Physics
K. Beagle, Systems Engineer, Radwaste Systems
J. Bennett, Senior Training Instructor
B. Brown, Licensing
C. Debiasi, Chemist
J. Doroski, Health Physicist
J. Epps, Nuclear Maintenance Planning Supervisor
M. Finnegan, Shift Supervisor, Radiological Protection, Unit 3
J. Firman, Radiation Protection Technician, Instrument Calibration Facility
S. Garvin, Site Fire Protection Supervisor
T. Gleason, Radiation Protection Technician, Instrument Calibration Facility
W. Gorman, Instrumentation & Control Supervisor
I. Haas, Supervisor, Exposure Control & Instrumentation
J. Hochdorfer, Radwaste Operations Supervisor
G. Holtz, Primary Radwaste Shipping Engineer
C. Janus, Maintenance Rule Coordinator
A. Johnson, Supervisor, Radiation Protection Technical Services
A. Jordan, Director, Nuclear Engineering
B. Kaufman, Auditor, Nuclear Oversight
E. Laine, Radiation Protection and Waste Services Manager
R. Leach, Health Physicist, Technical Services
D. MacDonald, Design Engineering
R. McIntosh, Licensing Engineer
K. McQuade, Fire Brigade member
T. Moore, Service Water System Engineer
A. Price, Site Vice President - Millstone
D. Regan, Supervisor, Radiation Protection Support (ALARA)
S. Sarver, Director, Nuclear Station Operations & Maintenance
S. Scace, Director, Nuclear Station Safety and Licensing
G. Sisgoreo, Instrumentation & Control Technician, Unit 3
A. Smith, EDG System Engineer
P. Strickland, Unit 2 Operations Supervisor
P. Tulba, Supervisor, Rad Material Control
K. Yearwood, System Engineering

NRC personnel

B. A. Bickett, Reactor Inspector, Division of Reactor Safety (DRS)
P. C. Cataldo, Senior Resident Inspector, Beaver Valley
G. T. Dentel, Senior Resident Inspector, Seabrook
R. L. Fuhrmeister, Senior Reactor Inspector, DRS
G. K. Hunegs, Senior Resident Inspector, Nine Mile Point 1 & 2
K. M. Jenison, Senior Project Engineer, Division of Reactor Projects (DRP)
S. R. Kennedy, Resident Inspector, Millstone
S. L. Lewis, Reactor Engineer, DRP
K. A. Mangan, Resident Inspector, Millstone
T. A. Moslak, Health Physicist, DRS
M. P. Patel, Reactor Engineer, DRP
S. M. Pindale, Senior Reactor Inspector, DRS
S. M. Schneider, Senior Resident Inspector, Millstone
N. Sieller, Nuclear Safety Professional, DRP
B. D. Welling, Senior Reactor Inspector, DRS

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

Opened

05000336/2004007-01 URI Adequacy of the EBFS OD and the potential risk significance of any degradation in EBFS function (1R15)
05000336/2004007-02 URI Application of 10 CFR 50.59 to a permanent modification of the Millstone Unit 2 charging system (1R17.1)
05000336/2004007-05 URI Adequacy of code safety surveillance testing and the potential risk significance of any degradation in code safety function (1R22.1)
05000336/2004007-06 URI Adequacy of TS 3.5.5 Surveillance Requirements (1R22.2)

Opened and Closed

05000336/2004007-03 NCV Failure to properly establish and implement CFR 50, Appendix B, Criterion XVI, to address repeated lifting of Main Steam Code Safety Valves (1R17.2)
05000336/2004007-04 NCV I&C technicians and operations personnel did not verify all appropriate prerequisites or perform all applicable procedural steps which then resulted in the inadvertent actuation of a safety-related system (1R19)
05000423/2004007-07 NCV Failure to Properly Implement TS 3.8.3.2, Onsite Power Distribution - Shutdown (4OA3)
05000423/2004007-08 NCV Dominion failed to establish precautions and prerequisites to prevent plant configuration changes that could lead to air entrainment in the RHR system (4OA5.1)

Closed

05000423/2004001-00 LER Technical Specification Action Statement Not Met (4OA3)
05000423/2004006-02 URI Air Entrainment of Residual Heat Removal System (4OA5.1)

LIST OF DOCUMENTS REVIEWED