U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENF0PCEMENT Region I Report No. 50-333/79-11 Docket No. 50-333 License No. DPR-59 Priority Category C
Licensee:
Power Authority of the State of New York 10 Columbus Circle New York, New York 10019 Facility Name:
James A. FitzPatrick Nuclear Power Plant Inspection at:
Scriba, New York Inspection conducted: ugust 6-8, 1979 Inspectors:
.b
/
. P. Durr,' Reactor Inspector date signeo
/
data signed date sianed
[.
f
Approved by:
(. E. Tripl,' Chief, Engineering Support Section date signed No. 1, RC&ES Branch Inspection Summary:
'
Inspection on August 6-8,1979 (Report No. 50-333/79-11)
Areas Insoected: Routine, announced inspection by a regional based inspector at the request of NRR to confim that deficient pipe supports identified under the Show Cause Order of March 13, 1979, and Bulletin 79-02 are being properly modified or repaired in accordance with the applicable engineering disposition.
The inspection involved 27 inspector-hours on site by one NRC inspector.
Results: No items of noncompliance were identified in the one area inspected.
1260 050 Region I Form 12 (Rev. April 77)
791102 0
%iU43
.
.
.
DETAILS 1.
Persons Contacted Power Authority of the State of New York
- M. Cosgrove, Site Quality Assurance Engineer
- J. R. Hoddy, Tehnical Services Support (Acting)
- J. D. Leonard, Resident Manager
- R. Liseno, Plant Engineer
- R. J. Pasternak, Superintendent of Power
- denotes those present at the exit interview.
2.
Inspection of Inaccessible Pipe Suppc.'ts The licensee is currently engaged in an extensive repair and modification of safety related pipe supports.
The pipe supports were identified as deficient as a result of review of activities required by the Show Cause Order, dated March 13, 1979, Bulletin 79-02, and the pipe support verifica-tion initiated by the licensee. The licensee has requested approval to restart the facility contingent upon completion of the committments in the August 2, 1979 letter to the NRC.
The purpose of this inspection was to confirm, on a sampling basis, that inaccessible supports identified as deficient have been properly repaired or modified in accordance with the engineering disposition.
The inspection consisted of identifying those deficient supports classified as inaccessible and performing selected dimensional and visual examinations.
The following supports were examined:
System MSK No.
Support No.
Remarks RHR 137E H10-127 Grouted sleeve, analyzed as built condition, OK.
Il4T H10-204 OK 114U H10-213 Visual on UF4 only, vX.
Il4P H10-50 Short sleeve: identified on as built drawings, OK.
Il4M H10-514 OK 1260 051
%
.
HPCI 167A H10-225 Short angle, 'K.
CS ll7A H14-42A OK FPC 113F H19-215N OK FW 134A H29-260 OK MS 127J2 H29-260 OK 127J2 929-262 OK No items of noncompliance were identiftad.
The inspector visually examined the pipe supports H46-282 and H46-284 identified previously as unresolved items (333/79-09-12).
He reviewed the engineering dispositior, of the Work Reques Nos. 2397 and 2398 for complete-ness and adequacy. These items are considered resolved.
The issue remains open pending disposition of the undersize <j bolts which are part of this item.
3.
Unresolved Items Unresolved items art ratters about which more infomation is required to ascertain whether they are acceptable items, itens of noncompliance, or deviations. Unresolved items are discussed in Paragraph 2.
4.
Exit interview The inspector met with representatives of the licensee (denoted in Para-graph 1) on August 8,1979.
He summarized the scope and findings 01 the inspection.
,