U.S. NUCLEAR REGULATORY COMMISSION

'

0FFICE OF INSPECTION Atl0 ENFORCEMENT Region I Report No. 50-293/79-10 Docket No. 50-293 License No.

DPR-35

'

Priority

Category C

Licensee:

Boston Edison Company M/C Nuclear 800 Boylston Street Boston, Massachusetts 02100 Facility Name:

Pilgrim Nuclear Power Station Inspection at: Plymouth, Massachusetts Inspection conducted:May 21-25 & May 29-June 1,1979 Date of Last Physical Security Inspection,:

October 3-6, 1978 j

Inspectors:

h l. d % / 9. m.~.s s

$/10/>$"

R Jones, J sica[SecurityInspector date signed E.b/ A n6 9 /n h.i

/

m, s.

8.* Bailey, Physical Secur,1ty Inspector

' / date signed V

date signed

,

Approved by: k rs, 6M le t.

L

//

"Fi 9mes W. Devlin, Chler, security and

< /date'sigr/ed nvestigations Section, Safeguards Branch Inspection Summary:

Inspection on May 21-25 and May 29 - June 1,1979 (Recort No. 50-293/79-10)

Areas Inspected:

Routine, unannounced physical security inspection by regional based inspectors, of the physical protection program to include Security Plan; Security Program Audit; Security Organization; Physical Barriers (Protected Area and Vital Areas);

Lighting; Access Control (Identification, Authorization and Badging; Search; Escorting; and Vital Areas); Alarm Stations; Detection Aids; Assessment Aids; Communications; Testing and Maintenance; Compensatory Measures; Power Supply; Respnnse; Locks, Keys and Combinations; and Records and Reports.

The inspection involved 122 regular shift and 8 off shift inspector hours onsite as well as 10 inspector hours off site by two NRC inspectors and was begun during regular hours.

Results:

The licensee was found to be in compliance within 15 of the 20 areas examined during the inspection.

Items of noncompliance. were found in the following five (5) areas:

Region I Form 12 8003030 M 7 (Rev. April 77)

.

-

.

.

.

-

.

Inspection Summary

1.

Security Organization - Procedures were not established on site which document the appropriate duties required of guards, watchmen and others responsible for security relating to escorting, key control and security picture badge access control.

(Deficiency)

2.

Physical Barriers - (a) The integrity of the protected area barrier was degra<ied by a glass window.

(Infraction)

(b) The isolation zone was not being maintained.

(Infraction) -(c) A section of the protected area barrier did not contain the required top guard and alarm.

(Infraction)

3 -.

Access Control (Identification, Authorization, and Badging) - Access control records were incomplete.

(Deficiency)

4.

Access Control (Search) - Vehicles entering the protected area were not being properly searched.

(Infraction)

5.

Access Control (Vital Areas) - Compensatory measures had not been implemented to control access to vital areas.

(Infra: tion)

'

.