Download: ML18095A435 (3)


Text

~-

I

. Docket Nos.:

50-272 50-311 AUG 2 11990 Public Service Electric and Gas Company ATTN:

Mr. Steven E. Miltenberger Vice President and Chief Nuclear Officer P. 0. Box 236 Hancocks Bridge, New Jersey 08038 Gentlemen:

Subject:

Notice of Violation-Inspection Nos. 50-272/90-200 and 50-311/90-200

.

The subject Salem Maintenance Team Inspection (MTI), identified concerns regarding the failure to maintain design features of the facility that are required to mitigate the consequences of flooding and failures to establish, maintain and follow written procedure Based on our review of these concerns, we h~ve identified apparent violations of NRC requirement Specifically, changes to the facility as described in the Updated Final Safety Analysis Report (FSAR) were made without performing an appropriate written safety evaluatio The changes consisted of modifications to hatch covers that separate the service

  • water rooms on both units from the outside ground leve These covers are required to meet water tightness requirements of the Updated Final Safety Analysis Report, Section Additionally, the MT! determined that water tight doors between the service water valve rooms and the surrounding areas of the auxiliary buildings had not been properly maintained in that latching dogs were inoperable (unmovable with reasonable force applied).

This condition appeared to have existed for an extended period of tim The MT! identified instances where written procedures were not being followed when performing various plant activitie Deficiencies included not performing step-by-step signoffs as required, thread engagements not per site procedure, and removal of piping with an active blocking ta You are required to respond to the enclosed Notice and, in preparing your response, you should follow the instructions specified in the Notic In your response, you should document the actions taken or planned to prevent recurr-enc In particular, you should address the measures established to prevent modifications of the facility without proper safety evaluation, measures taken to ens~re adherence to written procedures, and measures taken to assure an improve the effectiveness of maintenance activitie *

Public Service Electric & Gas Company

The MT! also identified weaknesses involving maintenance activitie These weaknesses are summarized in Appendix We request that you notify us in writing of actions taken or planned in order to enhance maintenance activities relative to the weaknesses described in Appendix Please provide this response within 60 days of receipt of this lette In accordance with 10 CFR 2.790, a copy of this letter and its enclosures will be placed in the NRC Public Document Roo The responses required by this letter and the enclosed Notice are not subject to the clearance procedures of the Office of Management and Budget, otherwise required by the Paperwork Reduction Act of 1980, Public Law No. 96-51 Your cooperation with us in this matter is appreciate Enclosures:

I.*

Appendix A, Notice of Violation Appendix B, Summary of Weaknesses cc w/encl s.:

Sincerely,

~riginaf Signed By;

.i/larvrn W. Hodges Marvin W. Hodges, Director Division of Reactor Safety J. Urban, General Manager, Fuels Oepartment, Delmarva Power & Light C L. K. Miller, General Manager - Salem Operations B. A. Preston, Manager, Licensing and Regulation General Manager - Nuclear Safety Review R. Fryling, Jr., Esquire M. J. Wetterhahn, Esquire S. Ungerer, Manager, Joint Generation Projects Department, Atlantic Electric Company

Licensing Project Manager, NRR D. Wersan, Assistant Consumer Advocate, Office of Consumer Advocate Lower Alloways Creek Township Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector State of New Jersey State of Delaware bee w/encls.:

Region I Docket Room (with concurrences)

Management Assistant, DRMA (w/o encls.)

R. Bellamy, DRSS OFFICIAL RECORD COPY SALEM NOTICE OF VIOLATION - 0002. /17/90

Public Service Electric & Gas Company

bee w/encls. (cont'd.):

DRP Section Chief K. Abraham, PAO (20) SALP Report and (2) All Inspection Reports J. Caldwell, EDO W. Lanning, NRR J. Konklin, NRR T. Gody, NRR M. Hodges, DRS R. Ga 11 o, DRS N. Blumberg, DRS D. Caphton, DRS D. Taylor, DR~

DRS Files (5)

~~

DRS: RI tC/

Caphton/'ajk 08!(&!90 DRS:RI Bessette D.D>

08/16 /90 D~

\\3

""' DRP:RI Gallo Blough 03;\\ ~;90 081/7190 WI~

DRS:RI Hodges 08Pt//90 OFFICIAL RECORD COPY SALEM NOTICE OF VIOLATION - 0002. /16/90