Integrated Inspection Report 05000266/2025003 05000301/2025003 and 07200005/2025001
ML25350C263
Person / Time
Site: Point Beach  
Issue date: 12/22/2025
From: Sanchez E
NRC/RGN-III/DORS/RPB2
To: Edmonds T
Point Beach
References
IR 2025001, IR 2025003
Download: ML25350C263 (0)


Text

SUBJECT:

POINT BEACH NUCLEAR PLANT - INTEGRATED INSPECTION REPORT 05000266/2025003; 05000301/2025003 AND 07200005/2025001

Dear Thad Edmonds:

On September 30, 2025, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Point Beach Nuclear Plant. On November 19, 2025, the NRC inspectors discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

Due to the temporary cessation of government operations, which commenced on October 01, 2025, the NRC began operating under its Office of Management and Budget-approved plan for operations during a lapse in appropriations. Consistent with that plan, the NRC operated at a reduced staffing levels throughout the duration of the shutdown.

However, the NRC continued to perform critical health and safety functions and make progress on other high-priority activities associated with the ADVANCE Act and Executive Order 14300.

On November 13, 2025, following the passage of a continuing resolution, the NRC resumed normal operations. However, due to the 43-day lapse in normal operations, the Office of Nuclear Reactor Regulation granted the Regional Offices an extension on the issuance of the calendar year 2025, 3rd quarter integrated inspection reports normally issued by November 15, 2025, to December 31, 2025. The NRC will resume the routine cycle of issuing inspection reports on a quarterly basis beginning with the calendar year 2025, 4th quarter integrated inspection reports, which will be issued 45 days after the 4th quarter ends on December 31, 2025.

No findings or violations of more than minor significance were identified during this inspection.

December 22, 2025 This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Elba M. Sanchez Santiago, Chief Reactor Projects Branch 2 Division of Operating Reactor Safety Docket Nos. 05000266; 05000301 and 07200005 License Nos. DPR-24 and DPR-27 Enclosure:

As stated cc w/ encl: Distribution via LISTSERV Signed by Sanchez Santiago, Elba on 12/22/25

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an integrated inspection at Point Beach Nuclear Plant, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

PLANT STATUS

Unit 1 began the inspection period at rated thermal power and remained at or near full power throughout the remainder of the inspection period.

Unit 2 began the inspection period at rated thermal power and remained at or near full power throughout the remainder of the inspection period.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs)in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors performed activities described in IMC 2515, Appendix D, Plant Status, observed risk significant activities, and completed on-site portions of IPs. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:

(1) Unit 2 motor driven auxiliary feedwater system on July 10, 2025
(2) Unit 2 safety injection system on July 14, 2025
(3) G-03 diesel generator starting air system on July 16, 2025
(4) Service water system on July 17, 2025

71111.05 - Fire Protection

Fire Area Walkdown and Inspection Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:

(1) Fire Zones 225, 226, 227, and 228:

D-105 battery room, D-106 battery room, and electrical rooms on July 9, 2025

(2) Fire Zone 151:

Containment spray and safety injection pump area on July 14, 2025

(3) Fire Zones 552, 553, 554, 555:

Service water pump area, circulating water pumphouse, passageway, and forebay on July 15, 2025

(4) Fire Zones 770, 771, 772, 773, 774, 775, 776, and 777:

Diesel generator building on July 16, 2025

Fire Brigade Drill Performance Sample (IP Section 03.02) (1 Sample)

(1) The inspectors evaluated the onsite fire brigade training and performance during an announced fire drill on July 30, 2025.

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01) (1 Sample)

(1) The inspectors observed and evaluated licensed operator performance in the control room during a down power to support turbine-driven auxiliary feedwater pump testing on July 31, 2025, and August 1, 2025.

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1) The inspectors observed and evaluated operator requalification and new license integration on August 19, 2025.

71111.12 - Maintenance Effectiveness

Maintenance Effectiveness (IP Section 03.01) (2 Samples)

The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:

(1) Turbine-driven auxiliary feed system
(2) Control room emergency filtration system

71111.13 - Maintenance Risk Assessments and Emergent Work Control

Risk Assessment and Management Sample (IP Section 03.01) (2 Samples)

The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:

(1) Elevated risk during inverter maintenance and restoration on July 10, 2025
(2) Elevated risk due to emergent work on the rod drive control system on August 28, 2025

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 03.01) (4 Samples)

The inspectors evaluated the licensees justifications and actions associated with the following operability determinations and functionality assessments:

(1) Operability of emergency diesel generator G-01 following step change in coolant conductivity
(2) Operability of containment with elevated hydrogen readings
(3) Operability of rod control system following receipt of urgent failure annunciator
(4) Operability of safety injection valve found with excess packing load

71111.18 - Plant Modifications

Temporary Modifications and/or Permanent Modifications (IP Section 03.01 and/or 03.02) (1 Sample)

The inspectors evaluated the following temporary or permanent modifications:

(1) Containment temperature instrument modification

71111.24 - Testing and Maintenance of Equipment Important to Risk

The inspectors evaluated the following testing and maintenance activities to verify system operability and/or functionality:

Post-Maintenance Testing (PMT) (IP Section 03.01) (8 Samples)

(1) FLEX Charging Pump PMT following 2 year maintenance on July 24, 2025
(2) Swing station battery PMT following battery replacement on July 25, 2025
(3) Repack Unit 1 safety injection pump cross connect valve on August 12, 2025
(4) Repack Unit 1 safety injection pump A discharge valve on August 12, 2025
(5) Service water pump expansion joint replacement on September 23, 2025
(6) Replace residual heat removal to letdown cross connect valve on September 24, 2025
(7) Component cooling water pump following breaker maintenance, pump oil change, and cleaning on September 24, 2025
(8) Rod control system PMT following replacement of logic card on September 30, 2025

Surveillance Testing (IP Section 03.01) (2 Samples)

(1) IT 405A, Auxiliary feedwater pump water supply isolation exercise quarterly test on August 13, 2025
(2) Primary auxiliary building filtration system efficiency testing on September 24, 2025

Inservice Testing (IST) (IP Section 03.01) (2 Samples)

(1) Turbine-driven auxiliary feed pump and valve test on August 1, 2025
(2) Unit 2 containment spray pump and valve test on September 29, 2025

Diverse and Flexible Coping Strategies (FLEX) Testing (IP Section 03.02) (1 Sample)

(1) FLEX 120/240 volt alternating current (VAC) portable generator annual surveillance, work order 40982033

71114.06 - Drill Evaluation

Additional Drill and/or Training Evolution (1 Sample)

The inspectors evaluated:

(1) Point Beach exercise on September 9, 2025

RADIATION SAFETY

71124.03 - In-Plant Airborne Radioactivity Control and Mitigation

Permanent Ventilation Systems (IP Section 03.01) (1 Sample)

The inspectors evaluated the configuration of the following permanently installed ventilation systems:

(1) Primary Auxiliary Building Ventilation

Use of Respiratory Protection Devices (IP Section 03.03) (1 Sample)

(1) The inspectors evaluated the licensees use of respiratory protection devices.

Self-Contained Breathing Apparatus for Emergency Use (IP Section 03.04) (1 Sample)

(1) The inspectors evaluated the licensees use and maintenance of self-contained breathing apparatuses.

71124.04 - Occupational Dose Assessment

Source Term Characterization (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated licensee performance as it pertains to radioactive source term characterization.

External Dosimetry (IP Section 03.02) (1 Sample)

(1) The inspectors evaluated how the licensee processes, stores, and uses external dosimetry.

Internal Dosimetry (IP Section 03.03) (1 Sample)

The inspectors evaluated the following internal dose assessments:

(1) Internal dose assessment performed for an intake on April 1, 2025

Special Dosimetric Situations (IP Section 03.04) (1 Sample)

The inspectors evaluated the following special dosimetric situations:

(1) Noble gas emersion dose

OTHER ACTIVITIES - BASELINE

71151 - Performance Indicator Verification The inspectors verified licensee performance indicators submittals listed below:

MS06: Emergency AC Power Systems (IP Section 02.05) (2 Samples)

(1) Unit 1 (July 1, 2024, through June 31, 2025)
(2) Unit 2 (July 1, 2024, through June 31, 2025)

MS07: High Pressure Injection Systems (IP Section 02.06) (2 Samples)

(1) Unit 1 (July 1, 2024, through June 31, 2025)
(2) Unit 2 (July 1, 2024, through June 31, 2025)

MS08: Heat Removal Systems (IP Section 02.07) (2 Samples)

(1) Unit 1 (July 1, 2024, through June 31, 2025)
(2) Unit 2 (July 1, 2024, through June 31, 2025)

BI01: Reactor Coolant System (RCS) Specific Activity Sample (IP Section 02.10) (2 Samples)

(1) Unit 1 (October 1, 2024, through June 30, 2025)
(2) Unit 2 (October 1, 2024, through June 30, 2025)

OR01: Occupational Exposure Control Effectiveness Sample (IP Section 02.15) (1 Sample)

(1) October 1, 2024, through June 30, 2025 PR01: Radiological Effluent Technical Specifications/Offsite Dose Calculation Manual Radiological Effluent Occurrences (RETS/ODCM) Radiological Effluent Occurrences Sample (IP Section 02.16) (1 Sample)
(1) October 1, 2024, through June 30, 2025

OTHER ACTIVITIES

- TEMPORARY INSTRUCTIONS, INFREQUENT AND ABNORMAL 60855 - Operation of an Independent Spent Fuel Storage Installation

Operation of an Independent Spent Fuel Storage Installation (1 Sample)

(1) The inspectors evaluated the licensees independent spent fuel storage installation (ISFSI) cask loading activities from July 7 through July 11, 2025.

Specifically, the inspectors observed the following activities during the loading of Multi-Purpose Canister (MPC) No. 557:

  • canister fuel loading and verification
  • closure welding and non-destructive evaluations
  • vacuum drying
  • stack-up and download of the MPC from the transfer cask into the storage cask
  • radiological field surveys The inspectors performed walkdowns of the ISFSI pad and haul path, which also included performing independent radiation surveys.

The inspectors evaluated the following:

  • spent fuel selected for loading into dry cask storage during this campaign
  • selected corrective action program documents
  • selected 72.48 screenings
  • changes to the site's 10 CFR 72.212 report since the previous inspection

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On November 19, 2025, the inspectors presented the integrated inspection results to Thad Edmonds, Site Vice President, and other members of the licensee staff.
  • On July 11, 2025, the inspectors presented the ISFSI cask loading inspection results to Thad Edmonds, Site Vice President, and other members of the licensee staff.
  • On September 25, 2025, the inspectors presented the radiation protection inspection results to Thad Edmonds, Site Vice President, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Calculations

HI-2240742

Seismic and Structural Evaluation of Approach Apron

at Point Beach

Calibration

Records

HOL-95601

Relief Valve

2/11/2025

2396325

MPC S/N's 201, 202, 203, & 205 Tracking/Documentation

06/18/2021

2396740

DFC S/N# 26 - Holtec FCR31501057

06/23/2021

2443328

WHSM-17 / WNHOMS-32-033 Concrete Repair

2/07/2022

2507231

P-224 CDW Roughing Vacuum Pump Tripped

2/04/2025

2518574

Hydraulic Oil Leak on HI-TRAN

06/30/2025

2518952

Dislodged Annulus Seal Loaded MPC/HI-TRAC in

Spent Fuel Pool

07/07/2025

Corrective Action

Documents

2519149

Potential FM Intrusion into HI-TRAC Annulus

07/09/2025

2519245

ISFSI Inspection - DFS FME Practices

07/11/2025

Corrective Action

Documents

Resulting from

Inspection

2519253

25 ISFSI Inspection - ISFSI Area Housekeeping

07/11/2025

Engineering

Changes

299638

HI-STORM FW Loading to East ISFSI Pad Approach Aprons

MPC-37 Multi-Purpose Canister Record

07/07/2025

2.48/50.59-1435

HI-STORM FW Overpack Baseplate

01/29/2020

2.48/50.59-1455

HI-STORM FW MPC Guide Tubes

04/22/2020

2.48/50.59-1462

MPC-37 Lid

05/20/2020

2.48/50.59-1551

ECO-100-46-Full Evaluation

09/13/2024

2.48/50.59-1599

ECO-5018-77-Full Evaluation

09/17/2024

FPL-1

Quality Assurance Topical Report

HI-2240509

Fuel Loading Plan for Point Beach (ISFSI)

08/19/2024

Miscellaneous

JNA 24-005

NA Audit JNA 24-005 Independent Spent Fuel Storage

(ISFS)

10/31/2024

3665-0792-24-

095-07092025-01

Helium Leak Test Report for Multi-Purpose Canister (MPC)

Vent and Drain Port Cover Plates

07/09/2025

C03-PT-02

Lid to Shell-1st Fill Layer

07/08/2025

60855

NDE Reports

C03-PT-07

Closure Ring Welds

07/09/2025

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

DOC-103-017R2

Supplied System Name: HI-TRAC VW with Lift Lugs

for Point Beach (LEASED)

FCR-3392-1030

A: HI-TRAN Manual Recovery Without Power

HPP-2951-0200

MPC Loading (ISFSI)

HPP-2951-0300

MPC Sealing, Drying, and Backfilling (ISFSI)

HPP-2951-700

8.8: HI-STORM Vent Surveillance

06/30/2025

HSP-355

Periodic Inspection and Recertification of Special Lifting

Devices

HSP-506

Liquid Penetrant Examination for MPC Field Closure

Welding

MA-AA-110-1000

Rigging Handbook and Inspection Procedure

NP.8.4.7

Control of Safe Load Path and Rigging Manual

NPM 2018-0025

Structural Inspection Year 3

10/05/2022

NPM 2025-0001

Structural Inspection Year 5

2/03/2025

REP-21917-1-

001

Site Load Test Procedure Post Bridge Weld Repair

Procedures

RMP 9120

Auxiliary Building Crane Inspection

2/03/2025

210618-8

ISFSI for New HI-Storm/ Title: Exit Aop 13 C

06/18/2021

210811-15

ISFSI HI-Storm Title: Upper Vent Survey

08/11/2021

220429-10

ISFSI Semi Annual

04/29/2022

220724-01

ISFSI Overview Title: - Exit AOP-13C

07/24/2022

230424-2

ISFSI Semi Annual

04/24/2023

240522-2

ISFSI AOP-13C Exit

05/22/2024

240706-2

ISFSI AOP-13C Exit

07/06/2024

250320-9

ISFSI AOP-13C Exit

03/20/2025

Radiation

Surveys

250416-2

ISFSI Semi Annual

04/16/2025

Self-Assessments 02497351-03

Pre-Inspection Self-Assessment

Work Orders

40997517-01

Z-015 WIRE ROPE INSPECTION

06/04/2025

110E035

P&ID Safety Injection System

71111.04

Drawings

M-207

Service Water System

M-209

P&ID Starting & Service Air System Diesel Generator

Building

Drawings

M-2217

P&ID Auxiliary Feedwater System

CL 10B

Service Water Safeguards Lineup

CL 11A G-03

G-03 Diesel Generator Checklist

CL 13E Part 2

Auxiliary Feedwater Valve Lineup Motor Driven

71111.04

Procedures

CL 7A

Safety Injection System Checklist Unit 2

Modes 1,2,3, and 4 (With Both ECCS Trains Aligned for

Injection)

PFP-0-PAB 26

Pre-Fire Plan Unit 1 & Unit 2 Auxiliary Building 26 Ft

PFP-0-PAB-8

Pre-Fire Plan Primary Auxiliary Building Elevations 8'

and Below

Fire Plans

PFP-0-PAN

Pre-fire Plan Protected Area North (Inside the Fence)

71111.05

Miscellaneous

PBN LOC 25C

2S

Fire Drill

Miscellaneous

PBN LOC 25C

001S

New License Integration

71111.11Q

Procedures

OP 2A Unit 1

Normal Power Operation Unit 1

2503684

Unexpected Start of W-14B

2/13/2024

2503718

2B52-328H W-13B1 CR Recirc Fan Breaker Thermal

Overload Trip

2/14/2024

2514827

CREFS Actuation

05/06/2025

2514954

20 DPM Leakage Upstream of 2AF-59

05/08/2025

2516247

CREFS Mode 5 Partial Activation

05/27/2025

71111.12

Corrective Action

Documents

2517337

C-67-EXT Panel Relay 42-B2X Abnormal Noise

06/12/2025

Work Activity Risk

Management

Plan

2DY-02 Perform 10yr PM per 2RMP 9036-6

Work Activity Risk

Management

Plan

Shifting Instrument Inverters Aligned to an Instrument Bus

71111.13

Miscellaneous

Work Activity Risk

Management

Plan

Troubleshooting and Possible Card Replacement for U2 Rod

Control System Urgent Failure Alarm

Calculations

2003-0014

MOV Operating Parameters

2506691

Review Diagnostic Test Data for 1-SI-00866A Following

Repack

01/29/2025

2511984

Low Level As-Found Inertial Overtorque on 1SI-866A

03/31/2025

2512184

1SI-866B As-Found Test Failure due to Excess Packing

Load

04/01/2025

2513245

Due to Low AL Margin in 1R42 - Increase Thrust in 1R43

04/11/2025

20021

Step Change in Conductivity of Emerg. Diesel Generator

Coolant

07/22/2025

21437

Material Left in Unit 1 Containment

08/13/2025

21441

U1 Containment Entry Aborted due to Lower Explosive Limit

(LEL) Alarm

08/13/2025

Corrective Action

Documents

22288

Unit 2 Rod Control System Urgent Failure

08/26/2025

71111.15

Procedures

CMP 2.2.9

MOV Overthrust/Overtorque Review Guidance

CN-CRA-08-6

Point Beach Units 1 and 2 (WEP/WIS) LOCA Mass and

Energy Release and Containment Response Analysis for the

EPU Program

1B

Calculations

CN-CRA-12-26

Point Beach Units 1 and 2 LOCA Containment Response

Analysis

22756

FSAR Table 14.3.4-29 Update

09/02/2025

Corrective Action

Documents

Resulting from

Inspection

24477

Potential Minor Violation of 10 CFR 50.71(E)

09/25/2025

2013-0188-02

Reduction of CFC Heat Removal Requirement 50.59

Screening

2018-003

10CFR50.59 Evaluation to Correct Errors in the LOCA and

Steam Line Break Containment Response Analyses

(CN-CRA-12-26 and CN-CRA-12-27)

71111.18

Engineering

Evaluations

EC 2015-0031

Evaluation of Increased Containment Post-Accident

Temperature on Previously Qualified EQ Components

2513555

Battery Experienced Catastrophic Failure

04/16/2025

2516913

Z-2005A Did Not Crank Over with Battery

06/05/2025

22767

U2 Rod Control System Additional PMT Needed

09/02/2025

Corrective Action

Documents

23849

2SI-871A CS Suction from RHR Valve Stroke Open was

Outside Acceptance Criteria

09/17/2025

71111.24

Drawings

M-217, Sheet 1

P&ID Auxiliary Feedwater System

107

IT 06

Train A Containment Spray Pump and Valves Unit 2

IT 08A

Cold Start of Turbine-Driven Auxiliary Feed Pump and Valve

Test (Quarterly) Unit 1

IT 405A

2AF-4067, 2P-53 AFP Service Water Supply Isolation

Exercise Test Unit 2 (Quarterly)

IT 520B

Leakage Reduction and Preventive Maintenance Program

Test of 1SI-896A&B, SI Pump Suction Valves and HHSI

System High Flow Test Line (Refueling) Unit 1

NP 7.7.36

Diverse and Flexible Coping Strategies (FLEX) Program

Procedures

OM 3.42

Control of WR SFP Level Instrumentation and Credited

FLEX Equipment

40834723-02

1SI-00829A / Operations PMT Manual Stroke

04/09/2025

40834725-02

1SI-00888A / Operations PMT Manual Stroke

04/09/2025

40881297

Filtration System Efficiency Test

03/06/2024

40951760

1RH-715C Exceeds Admin Limits Leakage

09/03/2025

40964913

D-305; 125V Swing Station Battery is Reaching End of Life

07/06/2025

40973471

2P-011B Change Oil, Flush Bearings and Clean Intake Grills

08/31/2025

40978938

XJ-02974C, P-32C Expansion Joint - 2024 NRC ARD

06/05/2025

40982033-01

0-SOP-FLEX-001 / Z-200A thru I Annual Loaded Run

04/16/2025

40987580-01

Z-2005A 2 Year Maintenance Requirements

06/05/2025

40987580-02

Z-2005A Ops PMT

06/05/2025

40991103

B52-DB50-047 Bkr Maint per RMP 9303 and RMP 9369-1

08/31/2025

41015618-01

Z-2000D; Replace Battery

05/05/2025

41020938-01

Z-2005A Did Not Crank Over with Battery

06/09/2025

Work Orders

41028703

Unit 2 Rod Control System Urgent Failure

08/31/2025

EP Drill Scenario

09/09/2025

Miscellaneous

EPIP 1.2.1

Emergency Action Level Technical Basis

BG AOP-17A

Rapid Power Reduction

71114.06

Procedures

BG EOP-0.2

Natural Circulation Cooldown

2478916

Vendor Calibration Portacount as-Found Out of

Specifications

2/12/2024

2480710

F-021 Unable to Fully Tighten Charcoal Filter Trays

03/06/2024

Corrective Action

Documents

2481790

F-023 PAB Exhaust Charcoal Filter Test Results

03/19/2024

SCBA Qualification Matrix

09/17/2025

71124.03

Miscellaneous

Functional Test Results for SCBA 601

2/20/2024

Functional Test Results for SCBA 617

2/12/2025

Jefferson Fire and Safety Air Quality Analysis Report

06/18/2025

Procedures

PC 75 Part 1

Monthly And Turnaround Maintenance for the Scott 4.5

Self-Contained Breathing Apparatus

Self-Assessments L1A 02496994

Level 1 NRC Inspection Assessment

08/29/2025

Work Orders

40881297

Filter Testing

03/06/2024

Calculations

Internal Dose Assessment

04/12/2025

2476128

Dosimeter Calibrator Not Functioning Properly

01/08/2024

Corrective Action

Documents

2481397

Lapel Sampler Failed during Use

03/14/2024

Miscellaneous

HP-100-100924

Calculation of Shallow Dose Equivalent - Whole Body from

Noble Gases

71124.04

Procedures

HPIP 3.52

Airborne Radioactivity Surveys

Occupational Performance Indicator Data for October 2024

11/05/2024

Occupational Performance Indicator Data for

February/March 2025

04/15/2025

Occupational Performance Indicator Data for June 2025

04/01/2025

RCS Activity PI Data Calculation

11/01/2024

RCS Activity PI Data Calculation

04/02/2025

RCS Activity PI Data Calculation

07/01/2025

ODCM Radiological Effluent Occurrences PI Data

Calculation

11/07/2024

ODCM Radiological Effluent Occurrences PI Data

Calculation

04/12/2025

71151

Miscellaneous

ODCM Radiological Effluent Occurrences PI Data

Calculation

07/11/2025

MSPI Derivation Reports - Unreliability Index for: Emergency

AC Power System, High Pressure Injection System, and

Heat Removal System

09/12/2025

MSPI Derivation Reports - Unavailability Index for:

Emergency AC Power System, High Pressure Injection

System, and Heat Removal System

09/11/2025

71151

Miscellaneous

PBF-1650

MSPI Unavailability and Verification Report for: Emergency

AC Power, High Pressure Injection, and Heat Removal

System from 07/01/2024 through 06/31/2025

4