Progress Energy Crystal River Nuclear Plant Docket No. 50-302 Operating License No. DPR-72 Ref. 10 CFR 50.55a March 4, 2008 3F0308-0 1 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001

Subject:

Crystal River Unit 3 Day Inservice Inspection (ISI) Summary Report

Dear Sir:

Florida Power Corporation (FPC), doing business as Progress Energy Florida, Inc., Crystal River Unit 3 (CR-3), hereby provides the 90-Day Inservice Inspection (1ST) Summary Report for Refueling Outage (RFO) 15. The report is being submitted in accordance with the requirements of the 1989 Edition of the ASME Boiler and Pressure Vessel Code,Section XI, Article IWA-6000 with no Addenda.

This report addresses ISI examinations and repairs/replacements from the conclusion of RFO 14, December 10, 2005, to the conclusion of RFO 15, December 7, 2007. contains the CR-3 American Society of Mechanical Engineers (ASME),Section XI, NIS-1, Owner's Report for Inservice Inspections. contains MIS-2 Owner's Reports of Repairs or Replacements for ASME Class 1 and Class 2 Components. contains a revised CR-3 ASME,Section XI, NIS-1, Owner's Report for Inservice Inspections for RFO 14. During an American Nuclear Inservice Inspection (ANII) audit, a typographical error concerning the period of inspections was discovered on the MIS-i report for RFO 14. This error does not result in any changes to the technical content of the report.

This letter establishes no new regulatory commitments.

If you have any questions regarding this submittal, please contact Mr. Dennis Herrin, Acting Supervisor, Licensing and Regulatory Programs at (352) 563-4633.

te 47,nJ 5'S 1 /l Engineering Manager SJC/seb Attachments:

1. ASME,Section XI, NIS-1, Owner's Report of Inservice Inspections
2. ASME,Section XI, NIS-2, Owner's Report of Repairs or Replacements for ASME Class 1 and Class 2 Components
3. Corrected ASME,Section XI, NIS-1, Owner's Report of Inservice Inspections for RFO 14 xc: NRR Project Manager Regional Administrator, Region 11 Senior Resident Inspector Progress Energy Florida, Inc.

Aoq-7 Crystal River Nuclear Plant 15760 W. Powerline Street Crystal River, FL 34428

PROGRESS ENERGY FLORIDA, INC.

CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302/LICENSE NUMBER DPR-72 ATTACHMENT 1 COMMERCIAL SERVICE DATE - 03/1 3/1 977 ASME, SECTION XI, NIS-1 OWNER'S REPORT OF INSERVICE INSPECTIONS FOR RFO 15 Table of Contents ASME,Section XI, NIS-1, Owner's Report for Inservice Inspections

  • Summary Report of Examinations, Tests, Results and Corrective Actions Table 1- RFO 15 IWE Examination Summary Table 2- RFO 15 IWL Examination Summary Table 3- RFO 15 Snubber Testing Summary Table 4- RFO 15 Snubber Inspection Summary Table 5- RFO 15 Snubber Elimination Summary Table 6- NIS-2 Owner's Report of Repair or Replacement
  • Inservice Inspection Summary Report Interval 3, Period 3, Refuel Cycle 15

System Acronym System Description CF Core Flooding CH Chilled Water DHI Decay Heat Removal EF Emergency Feedwater FW Feedwater MS Main Steam MU Make Up & Purification RC Reactor Coolant BS Reactor Building Spray DC Decay Heat Closed Cycle Cooling SW Nuclear Services Closed Cycle Cooling RW Nuclear Services & Decay Heat Sea Water HV Heater Vent RV Reheat Vent MC Containment Liner Location Acronym AB Auxiliary Building RB-2 Reactor Building (inside D-Ring)

RB Reactor Building TB Intermediate Building TB Turbine Building

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As Required by the Provisions of the ASME Code Rules 1.Owner Florida Power Corporation. P.O. Box 14042. St. Petersburg FL. 33733-4042 (Name and Address of Owner)

(Name and Address of Plant)

3. Plant Unit- Crystal River Unit 3 4. Owner Certificate of Authorization (if required) N/A S.Commercial Service Date 3/13/1977 6. National Board Number for Unit N/A
7. Components Inspected Components or Manufacturer Manufacturer or State or National Board Appurtenance or Installer Installer Serial No. Province No. No.

Reactor Vessel Babcock & Wilcox 620-0007-St1-52 N/A N-I 17 Pressurizer Babcock & Wilcox 620-0007-59 N/A N-I 18 Steam Generator A Babcock & Wilcox 620-0007-55-1 N/A N-1 19 Steam Generator B Babcock & Wilcox 620-0007-55-2 N/A N-120 Various Piping, Pumps, N/A N/A N/A N/A Valves, Supports and Containment areas.

Reactor Vessel Closure Framatome AN]' CC/CR 001 N/A N/A Head 4 4 4 4 4 1 Note:

____ I ___ I ____ I ___ .1 ___

Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size in the same as this Data Report, (2) informnation in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

FORM NIS-1 (back)

8. Examination Dates: 12/11/2005 to 8/13/2008
9. Inspection Period Identification: Period 2. 12/14/2001 to 4/13/2005 Period 3, 4/14/2005 to 8/13/2008 10 Inspection Interval Identification: Interval 3, 8/14/1998 to 8/13/2008 11 Applicable Edition of Section XI 1989 Addenda N/A 12 Date/Revision of Inspection Plan: 11/2/2005, Revision 6
13. Abstract of Examination and Tests. Include a list of examinations and a statement concerning status of work required for the inspection plan.

See Enclosure

14. Abstract of Results of Examinations and Tests.

See Enclosure

15. Abstract of Corrective Measures.

See Enclosure We certify' that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date 3/4/2008 Signed Progress Energy Florida, Inc. By Michael Brannin/

Owner CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and/or the State or Province of Florida and employed by HSB of CT. have inspected the components described in this Owner's Data Report during the period 12-11-2005 - to 08-13-2008 and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Data Report in accordance with the Inspection Plan and as required by the ASME code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examination and corrective measures described in this Owner's Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a 9ý-

lossofny nd rising from or connected with this inspection.

CA e Commissions NB12597ANI FL 535 Inspector's Signature dý'National Board, State, Province, and No.

Date 2- LA 2008

PROGRESS ENERGY FLORIDA, INC.

CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302/LICENSE NUMBER DPR-72 90 DAY INSERVICE INSPECTION Summary Report of Examinations, Tests, Results and Corrective Actions

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 1 of 27 Summary Report of Exam inations, Tests, Results and Corrective Actions Introduction The following report documents the American Society of Mechanical Engineers (ASME)

Section XI Code, Jnservice Inspection (ISI) Examinations and Repairs/Replacements performed during the third period of the third interval during Refueling Outage 15 (RFO 15). RFO 15 was the only outage for the third period of the -third inspection interval. Examinations performed during this period satisfy the requirements of the ASME Section XI Code, 1989 Edition without Addenda.

Nuclear Regulatory Commission (NRC) regulations (10 CFR50.55a) require that ISI examinations be performed in accordance with the latest edition and addenda of the ASME Code Section XI, incorporated by reference, 12 months prior to the start of the 120-month interval.

This report documents the examination activities conducted during this period. The detailed records of these examinations are on file and available at the plant site for review. ASME Code Cases utilized by Florida Power Corporation, doing business as Progress Energy Florida, Inc.,

during this period are documented within this report and have been approved for use either through the inclusion in the NRC Regulatory Guide 1.147, Revision 15 or by NRC approved Relief Requests.

Examinations Components A summary listing of examinations conducted on ASME Class 1, 2, and 3 components is provided in Attachment 1 to FORM NIS-1, Owners Report for Inservice Inspections. These inspections were conducted in accordance with the 1989 Edition without Addenda of the ASME Code,Section XI, TWA-2432, Inspection Program B.

Reactor Vessel Examinations Ultrasonic examinations were conducted on reactor vessel shell welds in accordance with 10CFR50.55a augmented requirements for examination Category B-A as specified in the 1989 Edition of the ASME Section XT Code. Specific examinations conducted are provided in Attachment I to FORM NIS-1. There were no unacceptable indications observed during these examinations. This constitutes completion of the 10-Year inspection interval examination requirements for the reactor vessel.

Steam Generator Eddy Current Inspections Eddy current examination was conducted on 100% of the tubes in-service in both steam generators during RFO 15. A separate summary report for these examinations is submitted to the NRC as required in Improved Technical Specification (ITS) 5.7.2.c. This report documents these examinations as part of the NIS- 1 report only.

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 2 of 27 Containment Inspection Program The Crystal River Unit 3 (CR-3) Contaimnment Inspection Program implements an examination/testing schedule for ISI inspection of the primary containment pressure boundary in accordance with ASME Section XI, 1989 Edition, no Addenda and incorporates the requirements of the ASME Section XI, 1992 Addenda of Subsections IWE & TWL.

IWE Prozram For RFO 15, the primary containment liner (IWE Class MC Components) was examined. This work was comprised of visual examination of all accessible metal containment liner plates, penetrations and associated attachments. Each of the areas as listed below was examined utilizing visual (VT-3 and General) methods.

Upon completion of the work scope, visual inspection resulted in certain locations requiring further investigation utilizing the more detailed visual (VT-i) method on suspect conditions.

The Responsible Professional Engineer (structural) reviewed each of the indications as presented and signed off the corresponding examination data sheet as part of the JWE/IWL examination.

These indications were further documented on non-conformance reports and dispositioned as minor in nature. These indications do not adversely affect the overall structural integrity of the Reactor Building (RB) Containment structure nor prevent it from performing its intended design function. No further scope increases were required. Results of the visual inspections are on file and available upon request and summarized below.

Table 1 - IWE Examination Summary Component ID lComponent Description Summary No

[CExamT Category I4 Ite 1T Locationiý Az _Report No Results Examination

ýBasement Liner Embedded in 24' Visual Examination of RBLP-1001 Concrete El 1.

1.1049 E-A El.I I RB EL 93'-0" 0 to 90 VT-07-064- Acceplt IWE Surfaces (General)

ýBasemenit Liner Visual (VT-3)

Embedded in 24" Examination of IWE RBLP-1001 Concrete EI.12.0182 E-A E1.12 RB EL93'-0" 0 to 90 VT-07-088 Accept Surfaces RB Wall Liner Plate - NCR 257242 - Visual Examination of RBLP-1002 10,to 90, EI1.11. 1023 E-A ELI I RB-95'-l 19' 0 to 90 1VT-07-041 Accept IWE Surfaces (General)

Visual (VT-3)

RB Wall Liner Plate - NCR 257242 - Examnination of IWE RBLP-1002 01 to 900 EI.12.0156 E-A E1.12 RB-95'-t 19' 0 to 90 VT-07-065 Accept Surfaces 0 Visual (VT-t)

RB Wall Liner Plate - NCR 257242 - Examination of VT-3 RBLP-1002 00 to 901 EI.12.0156 E-A E1.12 RB-95'-t 19' 0 to 90 VT-07-166 IAccept indications.

RE Wall Liner Plate - NCR 257242 - Visual Examination of RBLP-1003 10'to 90' ELI1.tl1024 E-A E1.11 RB-119'-160' 10 to 90 VT-07-042 Accept IWE Surfaces (General)

Visual (VT-3)

RB3Wall Liner Plate - NCR 257242 - Examination of IW E RBLP-1003 06 to 900 E1.12.0157 E-A Et1 BI19'-160' 0 to 90 VT-07-066 Accept Surfaces

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 3 of 27 Table 1 - IWE Examination Summary (continued)

ID~nn j rmpnetlDesritij Sumnr No I Exameor Item ] Location ] Az jReport No Results Examination Visual (VT-I)

ýRBWatt Liner Plate - NCR 257242 - Examination of VT-3 RBLP-1003 00 to 900 E1.12.0157 F-A- E1.12 RB-I 19'-160' 0 to 90 VT-07-306 Acceplt indications.

IRB0 Watt Liitcr Plate -

Visual Examination of RBLP-1004 0 to 90, E~l.1.1025 F-A E1l1t R-B-160-'-242' 0Oto 90 VT-07-043 Accept IWE Surfaces (General)

Visual (VT-3)

RB Watt Liner Plate - Examination of IWE RBLP-1004 ý00to 900 - E.12.0158 E-A E1.12 RB-160'-242' 0 to 90 VT-07-067 Accept Surfaces RB Watt Liner Plate -

0' to 900 / Crane Runaway Support Visual Examination of RBLP-1005 Gallery E~l.1.1026 F-A E1.11 RB-242'-250' Oto9O VT-07-044 Accept IWE Surfaces (General)

RB Watt Liiter Plate -

00 to 900 / Crane Visual (VT-3)

Runaway Support Examination of ]WE RBLP-1005 Gallery EI.12.0159 F-A E1.12 RB-242'-250' 0 to 90 VT-07-068 Accept Surfaces RB Dome Litter Plate - Visual Examination of RBLP-1006 010*o900 FIt 1.1027 F-A Fill1 R13-250' Oto 90 VT-07-045 Accept IWE Surfaces (General)

Visual (VT-3)

ýRBDome Litter Plate - Examination of IWE RBLP-1006 00 to 900 1.12.0160 E-A E1.12 RB-250' 0 to 90 VT-07-069 Accep~t Surfaces

ýBasement Liner Embedded in 24' Visual Examination of RBLP-2001 Concrete EI~l.1.1028 E-A F1ll1 RB EL 93'-0" VT-07-046 _Accept IWE Surfaces (General)

ýBasemettt Liner Visual (VT-3)

Embedded in 24" Examination of IWE RBLP-2001 Concrete E1. 12.0161 E-A E1.12 RB EL93'-0" VT-07-070 I Accept Surfaces RB Wall Liner Plate - Visual Examination of RBLP-2002 1900 to 1800 F1.11. 1029 E-A Fl.Ill RB-95'-1 19' 90Oto 180 VT-07-047 Accept IWE Surfaces (General)

Visual (VT-3)

RB Walt Liner Plate - NCR 257242 - Examination of IWE RBLP-2002 ý900 to 1800 E1. 12.0162 F-A El. 12 RB-95'-1 19' 90Oto 180 VT-07-071 Accept Surfaces Visual (VT-I)

RB Wall Liner Plate - NCR 257242 - Examination of VT-3 RBLP-2002 ý90010t1800 E1. 12.0162 F-A FEl.12 RB-9S'-l 19' 9010o 180 VT-07-210 Accept indications.

RB Watt Liner Plate - NCR 257242 - Visual Examination of RBLP-2003 190010to1800 E~l.1.1030 F-A Fl.ItI RB-I 119'-160' 901to 180 VT-07-048 Accept IWE Surfaces (General)

Visual (VT-3)

RB Watt Litter Plate - NCR 257242 - Examination of IWE RBLP-2003 90010t 180F.12.0163 F-A EI.12 RB- 119'- 160' 90Oto 180 VT-07-072 Accept Surfaces Visual (VT-I)

ýRBWatt Liner Plate - NCR 257242 - Examination of VT-3 RBLP-2003 90010t 1800 E1.12.0163 F-A El. 12 RB- 119'-160' 90Oto 180 VT-07-307 Accept indications.

RB Watt Litter Plate - NCR 257242 - Visual Examittation of RBLP-2004 190010o1800 FLI 1.1031 F-A Fl.ItI RB- 160'-242' 90Oto 180 VT-07-049 A_,

ccept IWE Surfaces (General)

Visual (VT-3)

RB Watt Litter Plate - NCR 257242 - Examination of IWE RBLP-2004 IgoE.12.0164 9010 180 F-A E1.12 RB- 160'-242' 901to 180 VT-07-073 Acceplt Surfaces Visual (VT-I)

RB Watt Liner Plate - NCR 257242 - Examination of VT-3 RBLP-2004 ý90010t1800 FI.12.0164 F-A El. 12 RB-1 60'-242' 9010o 180 VT-07-308 Accept tndtcattons.

RB Watt Liner Plate -

90' to 1800 / Crante Visual Examination of RBLP-2005 RuttawaySupt. GalleryL E1.11.1032 F-A FLItI RB-242'-250' 9010o180 VT-07-050 Accept IWE Surfaces (Getteral)

RB Watt Liner Plate - Visual (VT-3) 90'0t0 180' /Crane Examination of IWE RBLP-2005 Rutnaway Supt. Gallery El. 12.01_65 F-A F1.12 RB-242'-250' 9010o 180 VT-07-074 Accept Surfaces RB Dome Liner Plate - Visual Examitnatiott of RBLP-2006 190010o 1800 Fl. 11. 1033 F-A El. ItI RB-250' 9010o 180 VT-07-051I Accept IIWE Surfaces (General)

Visual (VT-3)

RB3Dome Liner Plate - Examination of IW E RBLP-2006 ý90010t1800 1.12.0166 F-A El. 12 RB-250' 9010o 180 VT-07-075 Accept Surfaces

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 4 of 27 Table 1 - IWE Examination Summary (continued)

Component ID jComponent Descriptionj Summary No Exam 1eut 1xmiatoAz Category jItem ILocation jReport No[ ReutExmaio

ýBasement Liner Embedded in 24' Visual Examination of RBLP-3001 Concrete ELI 1.1034 E-A ELIIt RB EL 93'-0" VT-07-052 Accept tWE Surfaces (General)

ýBasement Liner Visual (VT-3)

Embedded in 24" Examination of IWE RBLP-3001 Concrete E1.12.0167 E-A E1.12 RB EL 93'-0' VT-07-076 Acceplt Surfaces RB Wall Liner Plate - NCR 257242 - Visual Examination of RBLP-3002 11800to 2700 ELI 1.1035 E-A E 1.i1 RB-95'-1 19' 180 to 270 VT-07-053 Accept IWE Surfaces (General)

Visual (VT-3)

RB Wall Liner Plate - NCR 257242 - Examination of IWE RBLP-3002 1800 to 2700 E1. 12.0168 1 E-A E1.12 RB-95'-1t9' 180 to 270 VT-07-0_77 Accept_ Surfaces Visual (VT-I)

RB Wall Liner Plate - NCR 257242 - Examination of VT-3 RBLP-3002 11800 to 2700 E1.12.0168 E-A E1.12 RB-95'- 119' 180 to 270 1VT-07-202 Accept! indications.

RB Wall Liner Plate - NCR 257242 - Visual Examination of RBLP-3003 180010to2700 ELI 1.1036 E-A ELIlI RB- 1t9'-160' 180 to 270 VT-07-054 Accept tWE Surfaces (General)

Visual (VT-3)

RB Wall Liner Plate - NCR 257242 - Examination of IWE 0 0 RBLP-3003- 180 to 270 E1.12.0169 E-A EI.t2 RB-1 19'-160' 180to270 VT-07-078 Acceplt Surfaces Visual (VT-I)

RB Wall Liner Plate - NCR 257242 - Exam-ination of VT-3 RBLP-3003 11800to 2700 E1. 12.0169 E-A El. 12 RB-119'- 160' 180 to 270 VT-07-309 I Accept indications.

RB Wall Litter Plate - Visual Examination of RBLP-3004 1800 to 2700 El. 11.1037 E-A ELIlI RB-160'-242' 180 to 270 VT-07-055 Accept tWE Surfaces (General)

Visual (VT-3)

RB Wall Litter Plate - Examination of IWE RBLP-3004 180010to2700 Et1.12.0170 E-A E1.12 RB-160'-242' 180 to 270 VT-07-079 Accept Surfaces RB Wall Liner Plate -

1800 to 2700 / Crane Visual Examination of RBLP-3005 Runaway Supt Gallery El.11l.1038 E-A El1.11I RB-242'-250' 180 to 270 VT-07-056 Accept IWE Surfaces (General)

RB Wall Liner Plate - Visual (VT-3) 1800 to 2700 / Crane Examination of IWE RBLP-3005 Runaway Supt GalleryL E1.12.0171 E-A E1.12 RB-242'-250' 18010o270 VT-07-080 Accept Surfaces RB Dome Liner Plate - Visual Examination of RBLP-3006 11800 to 2700 El.l 11.1039 E-A E1.11 RB-250' 18010o270 VT-07-057 Accept IWE Surfaces (General)

Visual (VT-3)

RB Dome Liner Plate - Examination of IW E RBLP-3006 180010to2700 E1.12.0172 E-A EI.12 RB-250' 18010o270 1VT-07-081 Accept Surfaces Basement Liner Embedded in 24" Visual Examination of RBLP-4001 Concrete El.11l.1040 E-A EI.11 RBEL93'-0" VT-07-058 Accept IWE Surfaces (General)

Basement Liner Visual (VT-3)

Embedded in 24" Examination of IWE RBLP-4001 lConcrete E1.12.0173 E-A El. 12 1RB EL 93'-0" VT-07-082 Accept Surfaces RB Wall Liner Plate - NCR 257242 - Visual Examination of RBLP-4002 2700 to 3600 EI1.11.1041 E-A ELI I RB-95'-1 19' 300 to 360 VT-07-059 A~ccept_ IWE Surfaces (General)

Visual (VT-3)

RB Wall Liner Plate - NCR 257242 - Examination of IWE RBLP-4002 270010o3600 E1.12.0174 E-A EI.12 RB-95'-1 19' 300 to 360 VT-07-083 Accept Surfaces Visual (VT-I)

RB Wall Liner Plate - NCR 257242 - Examination of VT-3 RBLP-4002 1270010o3600 EI.12.0174 E-A E1.12 RB-95'- 119' 300 to 360 VT-07-211 Accept indications.

RB Wall Liner Plate - NCR 257242 - Visual Examination of 0 0 RBLP-4003 270 to 360 El 1.

1.1042 E-A ELI I RB-1 19'-160' 280 to 300 VT-07-060 Accept IWE Surfaces (General)

Visual (VT-3)

RB Wall Liner Plate - NCR 257242 - Examination of IWOE RBLP-4003 2700 to 3600 E1.12.0175 E-A EI.12 RB-I 19'-160' 28010o300 1VT-07-084 Accept Surfaces Visual (VT-I)

RB Wall Liner Plate - NCR 257242 - Examination of VT-3 RBLP-400 200 to 3600 E1.12.0175 0-A E1.12 RB-I 119'-160' 28010o300 VT-07-310 Accept indications.

RB Wall Liner Plate - Visual Examintation of RBLP-4004 270010to3600 E01.

11. 1043 E-A 01.11 RB-160'-242' 270 to 280 VT-07-061 Accept lWE Surfaces (General)

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 5 of 27 Table 1 - IWE Examination Summary (continued)

Component IExamI ID lComponent Description Summary No jCategory Item Location Az I Report No Results Examination Visual (VT-3)

RB Wall Liner Plate - Examination of IWE PBLP-4004 ý2700 to 3600 E1. 12.0176 E-A El. 12 RB-1 60'-242' 270 to 280 VT-07-085 Accept Surfaces RB Wall Liner Plate -

2700 to 3600 / Crane Visual Examination of RBLP-4005 Runaway Supt Gallery El1.1 1.1044 E-A El .11 RB-242'-250' 300 10360 VT-07-062 Accept IWE Surfaces (General)

RB Wall Liner Plate - Visual (VT-3) 2700 to 3600 / Crane Examination of IWE RBLP-4005 Rustaway Supt Gallery E1.12.0177 E-A E1.12 RB-242'-250' 300to360 VT-07-086 Accept Surfaces RB Dome Liner Plate - Visual Examination of RBLP-4006 2700 to 3600 E1.l 11.1045 E-A E1.I1I RB-250' 270 to 280 VT-07-063 Accept IWE Surfaces (General)

Visual (VT-3)

RB; Dome Liner Plate - Examination of IWE RBLP-4006 2700 to 3600 El. 12.0178 E-A EI.12 RB-250' 27010o280 VT-07-087 Accept Surfaces Visual (VT-3)

Moisture Moisture Barrier AZ Moisture NCR 256012 - Examination of Moisture Barrier 00 - 3600 (95 RB) E5.30.0001 E-D E5.30 Barrier VT-07-136 I Accept Barrier Visual (VT-I)

Moisture Moisture Barrier AZ Moisture NCR 256012 - Examination of VT-3 Barrier 00 - 3600 (95 RB) E5.30.0001 E-D E5.30 Barrier VT-07-148 Accept indications.

20", Type VII, Visual (VT-3)

Chemical Cleaning Containment Examination of Pressure PEN-I 19 Pen. E8.10.0005 E-G E8.10 Penetration 29D-55M VT-07-141 Accept Retaining Bolting 20", Type VII, Visual (VT-3)

Chemical Cleansing Containment Examination of Pressure PEN-120 Pen. E8.10.0006 E-G E8. 10 Penetration 32D-35M VT-07-142 -Accept Retaining Bolting Visual (VT-3) 12", Type VII, Containment Exanilnation of Pressure PEN-216 Electrical Pen. Spare E8.10.0001 E-G E8.10 Penetrations 90 VT-07-137 Accept Retaining Bolting Visual (VT-3) 12", Type VII, Containment Examinatiotn of Pressure PEN-217 Electrical Pen. Spare E8.10.0002 E-G E8.10 Penetration 95 VT-07-138 Accept Retaining Bolting Visual (VT-3)

Equipment Access Equipment NCR 257242 - Examination of Pressure PEN-222 Hatch E8.10.0003 E-G E8.10 Access Hatch 150 VT-07-139 Accept Retaining Bolting Visual (VT-l)

Equipment Access Equipment NCR 257242 - Examination of VT-3 PEN-222 Hatch ES. 10.0003 E-G ES. 10 Access Hatch 150 VT-07-311I Accept indications.

Visual (VT-3)

Equipment Access Equipment Examination of Pressure PEN-222 Hatch E8.10.0003 E-G E8.10 Access Hatch I50 VT-07-339 Accept Retaining Bolting Visual (VT-3) 34", Type VIII, Fuel Examination of Pressure PEN-348 Transfer Tuhe #2 E8.10.0004 E-G E8.10 Transfer Tube VT-07-140 Accept Retaining Bolting Visual (VT-3) 34", Type VIII, Fuel Examination of Pressure PEN-436 Transfer Tube #1 E8.10.0007 E-G _E8.10 Transfer Tube VT-07-143 Accept RetaimningBolting _

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 6 of 27 IWL Prazram For RFO 15, the primary containment pressure boundary (concrete containment IWL components) was examined. The 16 designated locations represent' the complete concrete containment. Each of these areas, as listed below, was visually examined utilizing the visual (VT-3) method.

Upon completion of the work scope, visual inspection resulted in certain locations requiring further investigation utilizing the more detailed visual (VT-i) method on suspect conditions.

The Responsible Professional Engineer (structural) reviewed each of the indications as presented and signed off the corresponding examination data sheet as part of the IWE/JWL examination.

These items were further documented on non-conformance reports and dispositioned as minor in nature and do not adversely affect the overall structural integrity of the Reactor Building (RB)

Containment structure nor prevent it from performing its intended design function. No further scope increases were required. Results of the visual inspections are on file and available upon request and summarized below.

Table 2 - IWL Examination Summary Copoent' CcIDP Component Description [ Summary No 1jCategory Exam Item

ýiRepor Location [ Az No Status Examination NCR 160D to VT 256010- Visual Examination of RBCN-000 I Concrete Surface L1.11.000 1 L-A LIII EL. 95' to EL. 119' 300D 097 Accept Concrete (VT-3)

NCR Visual (VT-I1) 160D to VT-OS- 256010- Examination of VT-3 RBCN-0001 Concrete Surface Ll. 11.0001 L-A LIII EL. 95'to EL. 119' 3000 201 Accept indications.

NCR 300D to VT-OS- 256010- Visual Examination of R.ECN-0002 Concrete Surface L1.11.0002 1 L-A LIII1 EL. 95'to EL. 119' 45D 098 Accept Concrete (VT-3)

NCR Visual (VT-I) 300D to VT-OS- 256010- Examination of VT-S RBCN-0002 Concrete Surface L1.11.0002 L-A LIII EL. 95' to EL. 119' 450 118 Aýccept_ indications.

NCR 45D to VT-OS- 256010- Visual Examinution of RBCN-0003 Concrete Surface L1.1l.0003 L-A LIII EL. 95'to EL. 119' 160D 099 Accept Concrete (VT-3)

NCR Visuaul(VT-I) 45D to VT-OS- 256010- Examination of VT-S RBCN-0003 Concrete Surface LI1.11l.0003 L-A LIII EL. 95'to EL. 119' 160D0 130 Accept indications.

45D0t0 VT-OS- Visual Examination of RBCN-0003 Concrete Surface L .1l.0003 L-A LIII EL. 9S to EL. 119' 1600 131 Accept Concrete (VT-3) 2500 to VT-OS- Visual Examination of RBCN-0004 Concrete Surface Lt111.0004 L-A Lt.III EL. I tO to EL. 143' 3000 100 - Accept Concrete (VT-3)

Concrete Surface; Only accessible via fuel NCR transfer tube inspection 2600 to VT-OS- 256010- Visual Examination of RBCN-0005 opening. LtIl1.O005 L-A LIII EL. I 19'to EL. 129' 2800 101 Accept_ Concrete (VT-3)

Concrete Surface; Only accessible via fuel NCR Visual (VT-I) transfer tube inspection 2600 to VT 256010- Examination of VT-S R BCN-0005 opening. L1.11.0005 L-A LtItl EL. I 19'to EL. 129' 2800 304 Accept indications.

NCR 3000 to VT-OS- 256010- Visual Examination of RBCN-0006 Concrete Surface LI1.11.0006 L-A LtLtI EL. I 19'to EL. 143' 1050 102 Accept Concrete (VT-3)

NCR Visual (VT-1t 3000 to VT-OS- 256010- Examination of VT-S RBCN-0006 Concrete Surface L1.11. 0006 L-A LtLtl EL. I I19'to EL. 143' 105D 203 Accept indications.

EL. 118' 4" to EL. 1400 to VT-OS- VisuaulExamination of RBCN-0007 Concrete Surface LI1.11.0007 L-A LtIt1 146' 1600 103 -Accept__ Concrete (VT-3)

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 7 of 27 Table 2 - IWL Examination Summary (continued)

Component ID

[Summary Component Description No Exam Category Item Ij Locution Az Report No Status Examination NCR 205D to VT 256010- Visual Examination of RBCN-0008 Concrete Surface LI.II.0008 L-A LIII1 EL. 143'to EL. 167' 300D 104 Accept Concrete (VT-)

NCR Visual (VT-I) 2050 to VT 256010- Examination of VT-3 RBCN-0008 Concrete Surface LI1.11. 0008 L-A LI. I I EL. 143' to EL. 167' 300D 300 Accept indications.

EL. 162'to EL. 200' 250D to VT Visual Examination of RBCN-0009 Concrete Surface L1.It1.0009 L-A Lt.t 11 4" 300D 105 Accept Concrete (VT-3)

Visual (VT-t)

EL. 162' to EL. 200' 250D to VT Examination of VT-3 RBCN-0009 Concrete Surface L1.I1.0009 L-A LtItI 4" 300D 302 Accept indications.

NCR EL. I 19'to EL. 267' 180D to VT 256010- Visual Examination of R.BCN-0010 Concrete Surface Ll. 11.00t1 L-A LtItI 6" 240D 106 Accept Concrete (VT-3)

NCR Visual (VT-t1)

EL. I t9' to EL. 267' 1800 to VT 256010- Examinution of VT-3 RBCN-0010 Concrete Surface L~l.l110t1 L-A LIII1 6" 2400 288 Accept indications.

NCR 2400 so VT 256010- Visual Examination of R-BCN-00I I Concretc Surface Ll.I 11.0011 L-A Lt.tII EL. 167' to 267'6" 300D 107 Accept Concrete (VT-3)

NCR Visual (VT-I1) 2400 to VT 256010- Examination of VT-3 RBCN-00 I I Concrete Surface - LI.I 11.00111 LA Lt.tIl EL. 167' to 267'6" 300D 227 Accept indications.

NCR EL. 148' to EL. 267' 300D to VT 256010- Visual Examination of R.BCN-0012 Concrete Surface -Ll.I11.0012 L-A Lt.t11 6" 0D 108 Accept Concrete (VT-3)

NCR Visual (VT-I)

EL. 148' to EL. 267' 300D to VT 256010 - Examination of VT-3 RBCN-0012 Concrete Surface LI.II.0012 L-A ULII 6" 00 230 AccegL. indicutions.

NCR EL. 149' to EL. 267' ODto VT 256010- Visual Examination of RBCN-00 13 Concrete Surface Ll. 11.0013 L-A LIAt 6" 600 109 Accept Concrete (VT-3)

NCR Visual (VT-I)

EL. 148' to EL. 267' 00 to VT 256010 - Examination of VT-3 RBCN-0013 Concrete Surface LI .I1.0013 L-A LIII1 6" 600 229 1 Accept indications.

NCR EL. 1 19' to EL. 276' 600Dto VT 256010 - Visual Examination of RBCN-00 14 Concrete Surface LII 1.0014 L-A LIII 6" 1200 110 Accept Concrete (VT-3)

NCR Visual (VT-I)

EL. 119' to EL. 276' 600 to VT 256010- Examination of VT-3 RBCN-00 14 1Concrete Surface Ll.I11.0014 L-A LIII1 6" 1200 228 _ Accept indications.

NCR EL. 11I9'to EL. 267' 1200 to VT 256010- Visual Examination of RBCN-0015 Concrete Surface Ll.I11.0015 LA LI.I 11 6" 1800 III Accept Concrete (VT-3)

NCR Visual (VT-I)

EL. 11I9'to EL. 267' 1200 to VT 256010- Examination of VT-3 RBCN-0015 Concrete Surface L~llAO1001 L-A Ll.III 6" 1800 289 Accept indications.

RBCN-00 16 (Buttress I to Buttress I to Buttress VT Visual Examination of Buttress 21 Concrete Surface Ll.I 11.0016 L-A L1.11 2 112 Accept Concrete (VT-3)

RBCN-0016 (Buttress 2 to Buttress 210oButtress VT Visual Examination of Buttress 3) Concrete Surface Ll. 11.0017 L-A LI. I1 3 113 Accept Concrete (VT-3) _

RBCN-0016 (Buttress 3 to Buttress 3 to Buttress VT Visual Examination of Buttress 4) Concrete Surface LI. .11.0018 L-A LI. 11 4 114 Accept Concrete (VT-3)

RBCN-0016 NCR (Buttress 410o Buttress 4 to Buttress VT 256010 - Visual Examination of Buttress 5) Concrete Surface Ll.I 11.0019 L-A ILIII1 5 115 Acet Concrete (VT-3)

RBCN-0016 NCR Visual (VT-I)

(Buttress 4 to Battress 4 to Bautress VT 256010 - Examination of VT-3 Buttress 5) Concrete Surface Ll.I 1.,0019 L-A -LII11 5 165 1 Accept indications.

PBCN-0016 (Buttress 5 to Buttress 5 to Buttress VT Visual Examination of Buttress 6) Concrete Surface Ll. 11.0020 L-A LIII1 6 116 Accept Concrete (VT-3)

RBCN-00 16 (Buttress 6 to Buttress 6 to Buttress VT Visual Examination o Buttress I) 1Concrete Surface LI.I 1.0021 I L-A I LII I 1 117 Accept Cnrt(T3

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 8 of 27 In addition to these visual examinations, the 30h year (8th) tendon surveillance was performed between October and November 2007.

The surveillance was conducted by Precision Surveillance Corporation (PSC) between October and November 2007 with CR-3 site overview utilizing SP-182, "Reactor Building Structural Integrity Tendon Surveillance Program," as the controlling site procedure. The actual procedures used for testing activities were contained in the PSC Inservice Inspection Manual for Progress Energy Crystal River Unit 3 (N1002), Revision 0. This 3 0oth year surveillance met all the requirements of ASME Section XI, Subsection IWL, as modified by 10CFR5O.55a. The results of this surveillance have shown that the CR-3 containment structure has not experienced abnormal degradation and is projected to meet its minimum design criteria until the end of its current forty-year life.

Code Compliance IWL-2400: Schedule CR-3 performed the Structural Integrity Test in November of 1976. The code required 30oth year surveillance was to be performed in November of 2006 plus/minus 1 year. Since the 30th surveillance was performed between October and November 2007 this requirement was met.

IWL-25 10: Examination of Concrete The concrete was visually examined (VT-3) during the 30' year surveillance period. For areas that required further evaluation, a detailed visual exam (VT-i) was performed. The data was reviewed by the Responsible Professional Engineer (RPE) and found to be acceptable.

IWL-2520: Examination of Unbonded Post-Tensioning Systems The random selection for CR-3 resulted in three Dome, three Vertical and five Horizontal tendons being selected. These tendons were D 129, D212, D23 8, 12V0 1, 45V20, 6 1V 17, 46H2 1, 42H46, 51H34, 62H30 and 13H36. It was later determined that 12V0l (identified as a control tendon) was retensioned during the prior surveillance. Per IWL-2521 (b), 61V08 was selected as a substitute control tendon. Although not identified as an exempted tendon the IWL-2524 and IWL-2525 examinations were performed on the original selected tendon (12V01).

IWL-2522: Tendon Force Measurements Tendon force measurements were performed on the selected sample and adjacent tendons as required. All vertical and dome tendons tested this inspection period, were found to have forces greater than 95% of the corresponding predicted force. Of the hoop tendons, 42H46 and 5 1H34 were observed with forces above 95% of their predicted force. Tendons 62H30, 46H21 and 13H36 were found to have forces below 95% but above 90% of their corresponding predicted forces. While monitoring the forces of tendons adjacent to the respective surveillance tendons, PSC Condition Reports FN1002-001, 002, 003, 006, 007, 008, 009, 011 and 012 were generated to document the conditions and were dispositioned by CR-3 engineering in CR-3 Nuclear Condition Reports (NCRs) 251318 and 252558. After the completion of testing the adjacent tendons, all tendons with an as-found force below 95% were restored to an as-left force -0%,

+6% of their corresponding predicted force in accordance with PSC Procedure 5Q9.0. The acceptance criteria of IWL-322 1.1 were met for all the tendons with the exception of tendon 62H30, 131136, and 46H21. The analyses of the as-found lift-off forces contained in the PSC final report, demonstrate that the as-found condition is acceptable for these tendons. Part of the analysis is a discussion on the calculation of the predicted base value for each tendon.

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 9 of 27 Historically, CR-3 has found numerous tendons below 95% of predicted base value, but demonstrated the acceptability of the containment with the as-found condition.

IWL-2523: Tendon Wire and Strand Sample Examination and Testing Tendons D238, 61V17 and 51H34 were detensioned and a wire removed for testing. The acceptance criteria of IWl-322 1.2 were met for all wire samples.

IWL-2524: Examination of Tendon Anchorage Areas A VT-i visual examination was performed for all tendons when the end cap was removed. The detailed inspections did not reveal any cracks in the concrete adjacent to the bearing plates nor in any of the anchorage components. There were several instances of missing or broken wires observed. These instances were compared against the acceptance criteria contained in IWL-3321.3 and SP-182 and found to be acceptable. Therefore no further analysis was required for these conditions.

IWL-2525: Examination of Corrosion Protection Medium and Free Water There were no instances of free water in the corrosion protection medium. The acceptance criteria of IWL-3221.4 were met for all samples taken.

IWL-2526: Removal and Replacement of Corrosion Protection Medium The amount of grease removed and replaced was recorded for each tendon.

10CFR5 0.5 Sa (b)(2)(viii): Examination of Concrete Containments (A) During the visual exam, all grease caps were examined for leakage and deformation. No grease leakage or deformation was observed. Minor weepage continues to be observed on the intermediate building buttresses. See (D) (3) below for further discussion.

(B) The evaluation of the trend data does not indicate an adverse trend.

(C) The elongation of any tendon during restressing did not vary from previously recorded results by more than 10% and therefore was acceptable.

(D) The following items shall be included in the RFO 15 NIS-1I report:

(1) The presence of water in the grease sample. There was no water recorded for this surveillance.

(2) The absolute difference between the amount of grease removed and the amount replaced did not exceed 10% of the net duct volume in any of the tendons.

(3) Detection of grease leakage (if found). During the tendon accessibility walkdown, PSC noted that small grease/oil leaks were occurring on multiple tendon caps, which were located inside existing structures that adjoin the containment building (adjacent to main steam and feedwater penetrations). The substance displacing from the tendon cap is actually the oil portion from the original P2 grease that has separated. This is a common occurrence that has been noted throughout many plants that perform tendon surveillances. This condition does not correspond to the system's degradation. A small amount of oil can cause a large aesthetically unpleasing condition. On buttresses without any coating, the oil is absorbed into the concrete, leaving very little signs of leakage. However, in the existing condition, the coated surface does not allow for the absorption to occur. Therefore, the oil continues to displace down the buttress face. PSC recommends this condition be monitored and cleaned on a periodic basis. Gasket replacement can be performed on the tendon cap, however the oil will continue to leak from the cap based on PSC's experience. The labor and material required for

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 10 of 27 the gasket replacement is not cost effective and PSC does not recommend performing such a task.

Based on the evaluation of the Inservice Inspection results of the 3 0 th Year Containment TWL Tendon Surveillance performed at CR-3 it has been determined that the containment structure meets the code requirements and that the containment structure has experienced no abnormal degradation of the post-tensioning system. The containmnent post-tensioning system is performning in accordance with the design requirements and is expected to continue to do so for its current forty-year life.

Snubbers The CR-3 Snubber Inspection Program for the third period of the third inspection interval implements the requirements of the 1989 Edition of the ASME Section XI Code with the 1988 Addenda to ASME/ANSI OM-1987, Part 4 (OM-4). Relief Request 98-001-SS, Revision 1, approved August 5, 1999, authorizes the use of an examination/testing snubber program based on a 24 month outage cycle for refueling, and applicable examination/testing results to determine continued inspection cycles. Relief Request 98-010-11, Revision 1, approved August 5, 1999, authorizes the use of ASME Section XI Code Case N-508-1. Prior to the completion of RFO 15, the CR-3 snubber population consisted of 231 locations within the plant. This includes 16 Non-Safety Related and 215 Safety-Related/Safety-Significant snubber locations. During RFO 15, as part of a continuing snubber reduction project, twelve locations had their snubbers removed permanently from the plant. The Inspection & Testing of snubbers satisfies the ITS requirements of 5.6.2.9 (a). A 100% visual examination was scheduled and performed in RFO 15.

Non-Safety Related locations are not addressed by the ASME Section XI or OM-4 Code requirements. As such, they are not included as part of the visual frequency calculation. However 100% of the Non-Safety Related locations were also visually inspected in RFO 15.

Functional test sampling: Snubbers have been categorized in five (5) separate populations; small bore snubbers, medium bore snubbers, and large bore snubbers, subdivided into accessible and inaccessible (Note: no accessible large bore population exists). The initial sample selection for these populations was performed by generating a randomly selected representative sample of each configuration, operating environment, range of size and capacity of each type/group of snubber. In addition, four snubbers were tested under an Augmented Test Plan.

Confirmation of Functional0perabilit The initial 10% functional test scope sample totaled 24 snubbers, the breakdown is as follows:

Accessible Small-Bore Snubber population - 9 required; Accessible Medium-Bore Snubber population - 3 required; Accessible Large-Bore Snubber population - N/A; Inaccessible Small-Bore Snubber population - 8 required; Inaccessible Medium-Bore Snubber population - 3 required; Inaccessible Large-Bore Snubber population - 1 required.

All snubbers tested under the Initial Sample Plans had satisfactory/acceptable results. No scope expansion was required.

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page I11 of 27 The functional testing was performed per procedure SP-200, "Functional Testing of Hydraulic Snubbers." Additionally, snubbers re-installed into these locations had final as-lefiiVT-3 visual inspections performed to verify that both the operability and installation were correct per the design drawings and to provide a pre-service baseline. The snubbers tested are listed in Table 3.

Table 3 - Snubber Testing Summary As-[

New FoundI Original Se-rial Serial Report AsLf Initial Sample - Accessible Small Hydraulic Snubbers (Required 9)

Initial Sample - Small DCR- FT Hyd Test Plan, Replace 33E 750113 888599 0019 11/18/2007 SAT EC#t64167 Initial Sample - Small Hyd Test Ptan, DCR- FT Rebuild/Replace EC#

33W 750118 888600 0020 11/18/2007 SAT ___________64167 Initial Sample - Small H-ydTest Plan, EFH- FT Rebuild/Replace EC#

110 760108 888608 0002 11/5/2007 SAT 64167 Initial Sample - Small Hyd Test Plan, EFH- FT Rebuild/Replace EC#

144 750116 888609 0003 11/5/2007 SAT 64167 Initial Sample - Small Hyd Teat Plan, FWH- FT Rebuild/Replace EC#

139 740051 888615 0006 11/6/2007 SAT 64167 FWH- FT Initial Sample - Small 150 30500067/001 888617 0008 11/6/2007 SAT Hyd TestPlan, MSH- FT Initial Sample - Small 122 03615923/019 888728 0004 11/5/2007 SAT Hyd Test Plan, Initial Sample - Small Hyd Test Plan, MSH- FT Rebuild/Replace EC#

128 740070 1 1888721 0005 1 11/5/2007 SAT 64167 Initial Sample - Small Hyd Test Plan, FT Rebuild/Replace ECN SWR-18 1730081 888641 0001 11/5/2007 SAT ___________64167 Initial Sample - Accessible Medium Hydraulic Snubbers (Required 3)

Initial Sample -

Medium Hyd Test MSH- FT Plan, Rebuild/Replace 224 720062A 888779 0010 11/7/2007 SAT ______EC#f 64167 Initial Sample -

Medium Hyd Test Plan, Replace EC#

MSH- FT 64167 [Last 5x10, no 229 - 720065 888809 0007 11/6/2007 SAT spare]

Initial Sample -

Medium Hyd Test MSH_ FT Plan, Rebuild/Replace 235 720068 888808 0030 11/25/2007 SAT ___________EC# 64167

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 12 of 27 Table 3 - Snubber Testing Summary (continued)

T T As-1 INew Found Original Serial Serial Report Rsls A-et Dt _____________

Mark No No No WO No No Dtl____ Rpr o _____ eulsCmet Initial Sample - Inaccessible Small Hydraulic Snubbers (Required 8)

Initial Sample - Small Hyd Test Plan, FT Rebuild/Replace EC#

CFH-16 720104 888598 0021 11/18/2007 SAT 64167 Initial Sample - Small Hyd Teat Plan, FT Rebuild/Replace EC#

MUH-32 750140 888752 0027 11/22/2007 SAT 64167 FT-07 Initial Sample - Small MUJH-33 04616483/011 888818 0022 11/20/2007 SAT Hyd Test Plan, FT-07 Initial Sample - Small MUH-36 30500067/03 888819 0029 11/22/2007 SAT Hyd Teat Plan, Initial Sample - Small Hyd Test Plan, FT Rebuild/Replace EC#

RCH-80 1750106 888631 10009 11/7/2007 SAT 64167 FT Initial Sample - Small RCH-86 03616013/005 888630 0012 11/11/2007 SAT Hyd Test Plan, Initial Sample - Small Hyd Test Plan, SWH- FT Rebuild/Replace EC#

493L 750103 _ __ 888639 0024 11/21/2007 SAT _ ____64167 Initial Sample - Small SWFI- FT Hyd Test Plan, Replace 493U 730231 888640 0025 11/21/2007 SAT EC# 64167 Initial Sample - Inaccessible Medium Hydraulic Snubbers (Required 3)

Initial Sample -

DHH- T-07-Medium Hyd Test DHH- T-07-Plan, Rebuild/Replace 26V 720098A 888601 0028 11/22/2007 SAT -EC# 64167 Initial Sample -

FWH- T-07-Medium Hyd Teat FWH-FT07Plan, Rebuild/Replace 131 730026 888613 0026 11/22/2007 SAT EC# 64167 Initial Sample -

Medium Hyd Test MSH- FT Plan, Rebuild/Replace 164 720077 _____ 888771 0011 11/1120 SAT ___________ ____EC# 64167 Initial Sample - Inaccessible Large Hydraulic Snubbers (Required 1) 618 I1 RCH- F FT-07 1j____ [ ]Initial Sample - Large-Bore Test Plan, 5-yr 11

ý16676624 ____ 888629 [0023 11/14/2007 SAT IIRebuild Augmented Test Samples ________

NCR# 253886 - Test, FWH- FT tightened sigtttglass, 164 760007 _____ 1152889 0014 11/13/2007 SAT and re-install NCR# 253725-No RCH- FT Fluid, Replace EC#~

530 26342 888820 0013 11/13/2007 SAT ______ ____64167 FT-07 FT NCR#I 253367- Test RCH-69 730133 1760192 11150780 10017 111/16/2007 1SAT 10018 111/16/2007 1SAT Iand Replace IFT FT-07 N R# 253727 - Test RCH-73 730147 730145 11151995 0015 11/16/2007 1UNSAT 0016 11/16/2007 1SAT Iatd Replace

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 13 of 27 Confirmationof Visual Operabilitv The required RFO 15 Visual Inspection scope consisted of 100% of the installed population. The inspections included the recording of all installation data and any unacceptable/unsatisfactory inservice and operability conditions. Additionally, 100% of the Non-Safety population was visually inspected.

The Safety Related/Safety Significant snubbers were inspected per procedure SP-201, "Hydraulic Snubbers Visual Inspection," and were reviewed and evaluated by the Inservice Inspection (ISI)/Engineering Programs and Design Engineering.

Additionally, Non-Safety as-found visual inspections were performed and documented under a separate Augmented Examination Scope in accordance with procedure PM-ill, "Check of Hydraulic Pipe Snubbers."

A listing of the snubbers visually inspected is found in Table 4.

Table 4 - Snubber Inspection Summary As- ý Found As-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WO No No Date Results No Date Results VT BSH-14 30500067/09 N/A 0277 11/19/2007 SAT VT BSH-15 730114 N/A 0262 11/18/2007 SAT VT BSH-19 30500067/04 N/A 0213 11/6/2007 SAT VT BSR-31 720115 N/A 0003 10/29/2007 SAT VT BSR-35 750073 N/A 0004 10/29/2007 SAT _____

VT CFH-14 740047 _______ N/A 0214 11/6/2007 SAT VT CFH-15 750046 N/A 0215 11/6/2007 SAT 888598-01, - VT VT CFH-16 720104 30600572/006 02 0080 11/5/2007 SAT 0255 11/16/2007 SAT VT CFH-17 730018 N/A 0149 11/5/2007 SAT VT CFH-18 720083 _______ N/A 0150 11/5/2007 SAT VT VT CFH-19 720105 N/A 0151 11/5/2007 SAT 0305 11/26/2007 SAT VT DCR-31 750105 N/A 0005 10/29/2007 SAT DCR- 888599-01, - VT VT 33E 750113 30700257/017 02 0006 10/29/2007 SAT 0259 11/18/2007 SAT DCR- 888600-01, - VT VT 33W 750118 30700257/018 02 0007 10/29/2007 SAT 0260 11/18/2007 SAT VT DHH-17 720136 ______ N/A 0216 11/5/2007 SAT _____ _____

VT DHH-18 30500067/06 _______ N/A 0217 11/5/2007 SAT _____ _____

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 14 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found As-Left Mark Original Serial Report As-Found Report As-Left No No New SerialNo WO No No Date Results No Date Results VT DHH-23 740097 N/A 0203 11/8/2007 SAT VT DHH-25 30500067/10 N/A 0199 11/12/2007 SAT DHH- VT 26H 30500067/08 N/A 0200 11/9/2007 SAT DHH- 888601-01, - VT VT 26V 720098A 30700296/015 02 0245 11/7/2007 SAT 0276 11/20/2007 SAT VT DHH-27 720103 N/A 0201 11/8/2007 SAT ____ ____

888602-01, - VT VT DHH-35 750101 30700257/019 02 0175 11/6/2007 SAT 0209 11/12/2007 SAT VT DHH-36 720128 N/A 0176 11/6/2007 SAT VT DHH-37 750120 _______ N/A 0248 11/8/2007 SAT_____

888603-01, - VT VT DHH--38 720130 30700257/020 02 0192 11/8/2007 SAT 0210 11/12/2007 SAT VT DHH-39 750104 N/A 0127 11/4/2007 SAT______

888604-01, - VT VT DHR-18 760176 30700257/001 02 0008 10/29/2007 SAT 0065 11/1/2007 SAT VT DHR-21 760027 N/A 0009 10/29/2007 SAT _____

DHR- VT 24L 730128 N/A 0205 11/8/2007 SAT DHR- VT 24U 750134 N/A 0204 11/8/2007 SAT____

888605-01, - VT VT DHR-28 730229 30700257/002 02 0010 10/29/2007 SAT 0239 11/14/2007 SAT VT DHR-31 750078 N/A 0011 10/29/2007 SAT 888606-01, - VT VT DHR-37 750114 30700257/003 02 0012 10/29/2007 SAT 0066 11/1/2007 SAT 888607-01, - VT VT DHR-49 750110 30700257/004 02 0001 10/31/2007 SAT 0002 10/31/2007 SAT EFH- VT 109 740004 N/A 0016 10/29/2007 SAT EFH- 888608-01, - VT VT 110 760108 30700257/006 02 0017 10/29/2007 SAT 0139 11/4/2007 SAT EFH- VT 141 750122 N/A 0018 10/29/2007 SAT EFH- 888611-01, - VT VT 143 730148 30700257/007 02 0019 10/29/2007 SAT 0125 11/7/2007 SAT EFH- 888609-01, - VT VT 144 750116 30700257/008 02 10020 10/29/2007 SAT 0140 11/4/2007 SAT VT EFH-27 730217 N/A 0273 11/19/2007 SAT VT EFH-28 730230 _______ N/A 0274 11/19/2007 SAT VT EFH-92 04616483/009 N/A 0013 10/29/2007 SAT 888612-01, - VT VT EFH-93 730223 30700257/005 02 10014 10/29/2007 SAT 0238 11/14/2007 SAT VT VT EFH-94 760193 _ _____ 1151795 0138 10/30/2007 DEGR 0297 11/23/2007 SAT VT EFH-95 750071 _ _____ N/A 0015 10/29/2007 SAT ____ _____

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 15 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found As-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WO No No Date Results No Date Results FWH- VT 122 730020 N/A 0152 11/5/2007 SAT FWH- VT 123 03616013/014 N/A 0153 11/5/2007 SAT FWH- VT 124 30500001/02 N/A 0154 11/5/2007 SAT FWH- VT 125 730022 N/A 0195 11/12/2007 SAT FWH- VT 128 760036 N/A 0246 11/7/2007 SAT FWH- VT 130 04616373/007 N/A 0147 11/5/2007 SAT FWH- 888613-01, - VT VT 131 730026 30600313/004 02, -03 0155 11/5/2007 SAT 0280 11/21/2007 SAT FWH- VT VT 132 720088 30600572/010 888614 0156 11/5/2007 SAT 0290 11/23/2007 SAT FWH-- VT 133 720087 N/A 0256 11/15/2007 SAT FWH- VT 138 03616013/009 N/A 0021 10/29/2007 SAT FWH- 8886 15-01, - VT VT 139 740051 30700296/007 02 0022 10/29/2007 SAT 01I79 11/7/2007 SAT FWH- VT VT-07-1 140 740092 1151795 0181 10/30/2007 DEGR 0298 11/23/2007 SAT FWH- VT 141 740068 N/A 0023 10/29/2007 SAT FWH- VT 142 740058 N/A 0024 10/29/2007 SAT FWH- VT 143 30500067/07 N/A 0025 10/29/2007 SAT EWH- VT 144 30500067/002 N/A 0026 10/29/2007 SAT FWH- VT 145 740079 N/A 0027 10/29/2007 SAT FWH- VT 146 740049 N/A 0028 10/29/2007 SAT FWH- VT VT 147A 760071 1002989-05 0029 10/29/2007 SAT 0303 11/26/2007 SAT FWH- 888616-01, - VT VT 148 740066 30600231/012 02 10030 10/29/2007 SAT 0287 11/22/2007 SAT FWH- VT 149 03616013/010 ______ N/A 0031 10/29/2007 SAT FWH- VT VT 150 30500067/001 ______ 888617-01 0032 10/29/2007 SAT 0185 11/8/2007 SAT FWH- VT 151 760006 - _______ N/A 0033 10/29/2007 SAT FWH- VT 152 0361013/007 N/A 0034 10/29/2007 SAT______

FWH- VT 153 30400010/02 N/A 0035 10/29/2007 SAT _____ ___

FWH- VT 154 30400010/03 N/A 0036 10/29/2007 SAT _____

FWH- VT 155 30400010/08 N/A 0037 10/29/2007 SAT _____ ___

FWI-- VT 156 30400010/10 ________ N/A 0038 10/29/2007 1SAT ___________

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 16 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found As-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WQ No No Date Results No Date Results FWH- VT 157 30400010/09 N/A 0039 10/29/2007 SAT ____ _________

FWH- VT 158 04616373/005 N/A 0040 10/29/2007 SAT _____

FWH- 888618-01, - VT VT 159 740056 30600572/005 02 0041 10/29/2007 SAT 0264 11/19/2007 SAT FWH- VT 160 740067 N/A 0042 10/29/2007 SAT _____

FWH- VT 161 30400010/04 N/A 0043 10/29/2007 SAT FWH- 888619-01, - VT VT 162 740055 3060023 1/008 02 0044 10/29/2007 SAT 0288 11/22/2007 SAT FWH- VT 163 740073 N/A 0045 10/29/2007 SAT FWH- VT VT 164 760007 1152889 0182 11/7/2007 UNSAT 0251 11/15/2007 SAT FWH- VT 165 03615923/017 N/A 0046 10/29/2007 SAT FWH- VT VT 166 30500067/05 1002989-05 0047 10/30/2007 SAT 0263 11/19/2007 SAT FWH- VT 167 03615923/020 N/A 0048 10/30/2007 SAT FWH- VT 168 03616013/013 N/A 0049 10/30/2007 SAT FWH- VT 169 740062 ________ N/A 0050 10/30/2007 SAT FWH- VT 170 760047 N/A 0051 10/30/2007 SAT FWH- VT 171 740053 N/A 0052 10/30/2007 SAT HVR- VT ION 760098 N/A 0054 10/30/2007 SAT HVR- VT lOS 760089 N/A 0055 10/30/2007 SAT VT HVR-1 3 760106 N/A 0056 10/30/2007 SAT Permanently VT HVR-14 720134 Deleted 888763-01 0057 10/30/2007 SAT Permanently VT HVR-15 730127 Deleted 1000482-01 0058 10/30/2007 SAT Permanently VT HVR-16 740001 Deleted 1000484-01 0059 10/30/2007 SAT Permanently VT HVR-17 730142 Deleted 888762-01 0060 10/30/2007 SAT VT HVR-4 04616483/007 N/A 0053 10/30/2007 SAT MSH- VT 117 760190 N/A 0061 10/30/2007 SAT MSH- 888761-01, - VT VT 118 750042 30600707/038 02 0062 10/30/2007 SAT 0299 11/25/2007 SAT MSH- 888760-01, - VT VT 119 79000088 30600707/039 02 0063 10/31/2007 SAT 0187 11/8/2007 SAT MSH- 888755-01, - VT VT 120 750043 30600707/040 02 0064 10/30/2007 SAT 0212 11/12/2007 SAT MSH- 888754-01, - VT VT 121 740089 30600231/007 1 02 10067 10/30/2007 SAT 0188 11/8/2007 SAT

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 17 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found IAs-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WO No No Date Results No Date Results MSH- VT VT 122 03615923/019 888728-01 0068 10/30/2007 SAT 0186 11/8/2007 SAT MSH- 888726-01, - VT VT 123 1730121 30700296/009 02 0069 10/30/2007 SAT 0289 11/23/2007 SAT MSH- VT 124 740091 ______ N/A 0070 10/30/2007 SAT MSH- 888722-01, - VT VT 125 720099 30600231/001 02 0071 10/30/2007 SAT 0301 11/25/2007 SAT MSH- VT 126A 730119 _______ N/A 0072 10/30/2007 SAT MSH- 888721-01, - VT VT 128 1740070 30700296/014 02 0073 10/30/2007 SAT 0173 11/6/2007 SAT MSH- VT 139 04616373/003 N/A 0218 11/6/2007 SAT MSH- VT VT 147 720075 _______ 1151795 0157 11/5/2007 DEGR 0294 11/23/2007 SAT MSH- 8887 19-01, - VT VT 149 720074 30600231/016 02 0158 11/5/2007 SAT 01I98 11/12/2007 SAT MSH- VT 150 730019 N/A 0159 11/5/2007 SAT ____

MSH- VT 159 03615643/030 _______ N/A 0247 11/7/2007 SAT MSH- 888765-01, - VT VT 160 720081 04616493/079 02 0160 11/5/2007 SAT 0270 11/19/2007 SAT_

MSH- Permanently VT 161 046163731/004 Deleted 888768-01 0161 11/5/2007 SAT MSH- VT 162 30500001/26 N/A 0162 11/5/2007 SAT MSH- 888771-01, - VT VT 164 720077 30600231/013 02 0146 11/4/2007 SAT 0180 11/7/2007 SAT MSH- VT 165 720082 N/A 0143 11/4/2007 SAT MSH- VT 166 02615453/02 _______ N/A 0163 11/5/2007 SAT MSH- VT 167 740036 N/A 0164 11/5/2007 SAT MSH- 888774-01, - VT VT 168 730120 04616593/10 02 0165 11/5/2007 SAT 0272 11/19/2007 SAT MSH- VT-07-.

170 04616453/010 N/A 0166 11/5/2007 SAT MSH- Permanently VT 205 04616483/010 Deleted 1000476-01 0074 10/30/2007 SAT____

MSH- Permanently VT 206 750079 Deleted 1000478-01 0075 10/30/2007 SAT MSH- 888775-01, - VT VT 207 25609 04616483/010 02 0076 10/30/2007 SAT 0211 11/12/2007 SAT MSH- Permanently 1000479 VT 208 730112 Deleted (Hang) 0077 10/30/2007 SAT MSH- Permanently VT 209 760105 Deleted 888776-01 0078 10/30/2007 SAT MSH- Permanently VT 211 760180 Deleted 888788-01 0079 10/30/2007 SAT MSH- VT 212 1730131 1_____ 1__ N/A 10081 110/30/20071 SAT ___________

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 18 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found oAs-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WO No No Date Results No Date Results MSH- VT 213 730029 N/A 0082 10/30/2007 SAT MSH- VT 214 760088 N/A 0083 10/30/2007 SAT MSH- VT 223 720062 N/A 0084 10/30/2007 SAT ____

MSH- 888779-01, - VT VT 224 720062A 30700210/017 02 0085 10/30/2007 SAT 0184 11/7/2008 SAT MSH- 888643-01,- VT VT 225 760191 30600707/041 02 0086 10/30/2007 SAT 0302 11/25/2007 SAT MSH- 888773-01, - VT VT 226E 760078 30700296/016 02 0087 10/30/2007 SAT 0252 11/15/2007 SAT MSH- 888781-01,- VT VT 226W 760077 30700296/017 02 0088 10/31/2007 SAT 0253 11/15/2007 SAT MSH- VT 2M2S7 720069 N/A 0089 10/31/2007 SAT MSH- IVT 228 720064 N/A 0090 10/31/2007 SAT MSH- 888809-01, - VT VT 229 720065 30600313/003 02 0091 10/31/2007 SAT 0111 11/7/2007 SAT MSH- VT 230 04616413/03 N/A 0092 10/31/2007 SAT MSH- VT 231 30500001/01 ________ N/A 0093 10/31/2007 SAT MSH- VT 232 720086 ________ N/A 0094 10/31/2007 SAT MSH- VT 233 840001 ______ N/A 0095 10/31/2007 SAT ____

MSH- VT 234 760067 ______ N/A 0096 10/31/2007 SAT MSH- 888808-01, - VT VT 235 720068 30600572/009 02 0097 10/31/2007 SAT 0300 11/25/2007 SAT MSH- VT 237 760068 N/A 0098 10/31/2007' SAT MSH- VT 238 720066 N/A 0099 10/31/2007 SAT ____

MSH- 888807-01, - VT VT 239 740094 30600231/017 02 0100 10/31/2007 SAT 0304 11/26/2007 SAT MSH- VT 240 730025 N/A 0101 10/31/2007 SAT____

MSH- 888625-01, - VT VT 243 750040 30600313/002 02 0167 11/5/2007 SAT 0271 11/19/2007 SAT MSH- VT 248 760198 N/A 0102 10/31/2007 SAT MSH-Permanently VT 2M4S9 720127 Deleted 1000480-01 0103 10/31/2007 SAT MSH- VT VT 250 730027 ______ 1151795 0183 10/30/2007 DEGR 0296 11/23/2007 SAT MSH- 888626-01, - VT VT 251 730138 30600572/007 02 0104 10/31/2007 SAT 0295 11/23/2007 SAT MSH- VT 252 750130 N/A 0105 10/31/2007 SAT MSH- VT 253 730028 N/A 0106 10/31/2007 SAT______

MSH- VT 254 730136 ________ N/A 0107 10/31/2007 SAT ___________

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 19 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found As-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WO No No Date Results No Date Results MSH- VT 255 04616483/014 N/A 0108 10/31/2007 SAT MSH- VT 567L 730227 N/A 0219 11/7/2007 SAT MSH- VT 567U 730226 N/A 0220 11/7/2007 SAT MSH- VT 568L 04616483/013 N/A 0221 11/7/2007 SAT _____

MSH- IVT 568U 04616483/015 ______ N/A 10222 11/7/2007 SAT MSH- VT 575 740087 N/A 0168 11/5/2007 SAT MSH- VT 576L 04616483/016 _______ N/A 0244 11/7/2007 SAT____

MSH- VT 576U 04616483/012 _______ N/A 0240 11/7/2007 SAT MSH- VT 581 730039 N/A 0144 11/4/2007 SAT____

MSH- 888627-01, - VT VT 664 25607 30700257/014 02 0110 10/31/2007 SAT 0243 11/14/2007 SAT MSH- 888753-01, - VT VT 665 25610 30700257/015 02 10109 10/31/2007 SAT 0189 11/9/2007 SAT MUR- 1888752-01, - VT VT 32 750140 30700257/009 02 0169 11/5/2007 SAT 10279 11/20/2007 SAT MUH- VT IVT 33 04616483/011 888818-01 0223 11/7/2007 SAT 0281 11/21/2007 SAT MUH- VT 34 04616323/019 N/A 0196 11/9/2007 SAT M UH- VT 35 740003 N/A 10207 11/9/2007 SATI MUH- VT VT 36 30500067/03 888819-01 0265 11/19/2007 SAT 0292 11/23/2007 SAT MUH- Permanently VT 37 730141 Deleted 888821-01 0266 11/19/2007 SAT MUH- IVT 38 04616483/006 N/A 0267 11/19/2007 SAT MUH- IVT 39 760194 N/A 0268 11/19/2007 SAT MUH- IVT 40 720131 N/A 0224 11/6/2007 SAT ____

MUH- IVT 51 04616353/021 N/A 0261 11/18/2007 SAT MUH- VT 80 720125 N/A 0194 11/12/2007 SAT MUH- 888822-01, - VT VT 82 740007 30700296/001 02 0190 11/9/2007 SAT 0191 11/11/2007 SAT VT RCH-29 750082 N/A 0122 11/3/2007 SAT RCH- VT 47N 740069 N/A 0225 11/6/2007 SAT RCH- VT 47S 740080 N/A 10226 1 11/6/2007 SAT VT RCH-48 720139 N/A 10227 I 11/6/2007 SAT

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 20 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found As-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No Wo No No Date Results No Date Results VT RCH-49 740065 N/A 0202 11/8/2007 SAT RCH- 888820-01, - VT VT 530 126342 30700257/016 02 0131 11/6/2007 UNSAT 0242 11/14/2007 SAT RCH- 888628-01, - VT VT 531 25594 30700257/023 02 0134 11/3/2007 SAT 0241 11/14/2007 SAT VT RCH-55 03616013/012 N/A 0145 11/4/2007 SAT VT RCH-58 03616013/015 N/A 0141 11/4/2007 SAT VT RCH-60 720111 N/A 0137 11/3/2007 SAT RCH- VT 614 16676626 N/A 0197 11/12/2007 SAT RCH- VT VT 618 16676624 888629-01 0206 11/12/2007_ SAT 0254 11/15/2007 SAT RCH- VT 619 16676623 N/A 0269 11/19/2007 SAT ____

RCH- VT 620 16676627 N/A 0278 11/20/2007 SAT VT RCH-63 760094 N/A 0249 11/8/2007 SAT VT RCH-64 760041 N/A 0250 11/8/2007 SAT VT RCH-65 760197 ______ N/A 0228 11/6/2007 SAT VT RCH-66 730228 N/A 0229 11/6/2007 SAT VT RCH-67 750100 N/A 0128 11/3/2007 SAT VT RCH-68 750137 N/A 0126 11/3/2007 SAT VT V RCH-69 730133 760192 1150780 0124 11/3/2007 UNSAT 0V285 11/22/2007 SAT VT RCH-70 750119 N/A 0129 11/3/2007 SAT RCH- VT 71L 730076 N/A 0136 11/3/2007 SAT RCH- VT 71 U 750083 N/A 0135 11/3/2007 SAT VT VT RCH-73 730147 730145 1151995 0133 11/6/2007 UNSAT 0284 11/22/2007 SAT VT RCH-74 730139 N/A 0123 11/3/2007 SAT VT VT RCH-76 730014 1151795 0230 11/6/2007 DEGR 0293 11/23/2007 SAT VT RCH-77 730129 N/A 0231 11/6/2007 SAT VT RCH-78 730124 N/A 0232 11/6/2007 SAT VT RCH-79 730150 N/A 0233 11/6/2007 SAT 888631-01, - VT VT RCH-80 750106 30700257/021 02 0130 11/3/2007 SAT 0306 11/29/2007 1SAT

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 21 of 27 Table 4 - Snubber Inspection Summary (continued)

As-Found As-Left Mark Original Serial Report As-Found Report As-Left No No New Serial No WO No No Date Results No Date Results 888632-01l/ VT VT RCH-81 750132 30700257/022 796855 0132 11/3/2007 SAT 0307 11/29/2007 SAT VT RCH-84 750076 N/A 0171 11/5/2007 SAT VT VT RCH-86 03616013/005 888630-01 0172 11/5/2007 SAT 0193 11/11/2007 SAT VT RCH-89 760186 N/A 0170 11/5/2007 SAT VT RCH-90 750077 N/A 0142 11/4/2007 SAT _______________

888633-01, - VT VT RVR-3E 1840002 30700210/016 02 0112 10/31/2007 SAT 0235 11/12/2007 SAT RVR- 888634-01, - VT VT 3W 760034 30700210/018 02 0113 10/31/2007 SAT 0236 11/12/2007 SAT 888635-01, - VT VT RVR-4E 910002 30700210/019 02 0114 10/31/2007 SAT 0234 11/12/2007 SAT RVR- 888636-01, - VT VT 4W 740093 30700210/002 02 0115 10/31/2007 SAT 0237 11/12/2007 SAT RVR- VT 5N 99614230/054 N/A 0116 10/31/2007 SAT VT RVR-5S 99614230/055 N/A 0117 10/31/2007 SAT RVR- VT 6N 99614230/056 N/A 0118 10/31/2007 SAT VT RVR-6S 99614230/053 ________ N/A 0119 10/31/2007 SAT SWH- 888638-01, - VT VT 483 730144 30700257/010 02 0208 11/12/2007 DEGR 0291 11/23/2007 SAT SWI-- 888639-01, - VT VT 493L 750103 30700257/011 02 0257 11/18/2007 DEGR 0282 11/21/2007 SAT SWI-- 888640-01, - VT VT 4931U 730231 30700257/012 02 0258 11/18/2007 SAT 0283 11/21/2007 SAT 888641-01, - VT VT SWR-18 730081 30700296/002 02 0120 10/31/2007 SAT 0148 11/5/2007 SAT SWR- VT 423 760199 N/A 0275 11/19/2007 SAT SWR- 888642-01, - VT VT 425 750115 30700257/013 02 0177 11/6/2007 SAT 0286 11/22/2007 SAT SWR- VT 440 740011 ______ N/A 0178 11/6/2007 SAT VT SWR-91 760042 ______ N/A 0121 10/31/2007 SAT _____ ___

Snubber Reduction As a continuing snubber reduction project, twelve (8 Safet y-Related/Safety-Significant and 4 Non-Safety Related) locations had their snubbers removed permanently from the plant under Design Engineering Changes (EC) 52000, 5993 5, 64167, 65794 and 65795.

A listing of the snubbers permanently removed from the plant is found in Table 5.

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 22 of 27 Table 5 - Snubber Elimination Summary Mark No Original Serial No New Serial No WO No" Comments HVR-14 720134 Permanently Deleted 888763-01 Replace Snubber with Strut EC# 65795 HVR-15 730127 Permanently Deleted 1000482-01 Replace Snubber with Strut EC# 65795 HVR-16 740001 Permanently Deleted 1000484-01 Replace Snubber with Strut EC# 65795 HVR-17 730142 Permanently Deleted 888762-01 Replace Snubber with Strut EC# 65795 MSH-1 61 04616373/004 Permanently Deleted 888768-01 Replace Snubber with Strut EC# 65795 MSH-205 04616483/010 Permanently Deleted 1000476-01 Eliminate Snubber EC# 65794 MSH-206 750079 Permanently Deleted 1000478-01 Eliminate Snubber EC# 65794 MSH-208 730112 Permanently Deleted 1000479 Replace Snubber with Strut EC# 65795 MSH-209 760105 Permanently Deleted 888776-01 Eliminate Snubber EC# 65794 MSH-21 1 760180 Permanently Deleted 888788-01 Eliminate Snubber EC# 65794 MSH-249 720127 Permanently Deleted 1000480-01 Replace Snubber with Strut EC# 65794 MUH-37 730141 Permanently Deleted 888821-01 Replace Snubber with Strut EC# 65795 Component Supports There were one hundred and ten (110) component supports examined during RFO 15 to meet the requirements of ASME Code Section XI as modified by ASME Code case N-491-1, "Alternative Rules for Examination of Class 1, 2, 3, and MC Component Supports of Light Water Cooled Power Plants." A summary listing of these exams is provided in Attachment 1 to FORM NIS- 1 Owner's Report for Inservice Inspections.

Pressure Testing Pressure testing was conducted on 10 systems to meet the ASME Section XI Code Requirements as amended by ASME Code Case N-498-1 during RFO 15. These are documented in to FORM NIS- 1 Owner's Report for Inservice Inspections. Pressure testing for applicable Repairs/Replacements of ASME Class 1 and 2 components are documented on the applicable NIS-2 forms attached to this report. A summary of these Repairs/Replacements is provided in Table 6 of this document.

Repair and Replacement There were seventeen (17) ASME Class 1 and thirty eight (38) ASME Class 2 Repair/Replacements performed since the last summary report. A summary listing of these Repair/Replacements is provided in Table 6 of this document. Additionally, the NIS-2 Owners Report of Repairs or Replacements documenting these Repair/Replacements for ASME Class 1 and Class 2 components are included with this report.

Augmented Plan Examinations Augmented inspections were performed on Inconel 600 inspections. These exams consisted of visual exams performed on 40 components which consist of reactor coolant system and pressurizer locations. No evidence of leakage was identified.

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 23 of 27 Code Cases and Relief Requests This section documents all ASME Section XI Code Cases and NRC approved Relief Requests applicable to the reporting period.

Section XI Code Cases N-416-2 Alternative Pressure Test Requirements for Welded Repairs or Installation of Replacement Items by Welding, Class 1, 2, and 3 (with hold times of IWA-5213)

N-460 Alternative Examination Coverage for Class 1 and Class 2 Welds N-463-1 Evaluation Procedures and Acceptance Criteria for Flaws in Class 1 Ferritic Piping That Exceed the Acceptance Standards of IWB-35 14.2 N-49 1-2 Alternative Rules for Examination of Class 1, 2, and 3 and MC Component Supports of Light Water Cooled Power Plants N-498-4 Alternative Rules for 10-Year Hydrostatic Testing for Class 1, 2, and 3 Systems (with times of IWA-52 13)

N-508-1 Rotation of Serviced Snubbers and Pressure Relief Valves for the Purpose of Testing N-509 Alternate Rules for the Selection and Examination of Class 1, 2, and 3 Integrally Welded Attachments N-521 Alternative Rules for Deferral of Inspections of Nozzle-to-Vessel Welds, Inside Radius Sections, and Nozzle-to-Safe End Welds of a Pressurized Water Reactor (PWR) Vessel N-522 Pressure Testing of Containment Penetration Piping N-524 Alternative Examination Requirements for Longitudinal Welds in Class 1 and 2 Piping N-533-1 Alternative Requirements for VT-2 Visual Examination of Class 1 Insulated Pressure Retaining Bolted Connections. (Conditionally Accepted)

N-566-1 Corrective Action for Leakage Identified at Bolted Connections,Section XI, Division I N-598 Alternative Requirements to Required Percentages of Examinations N-613 Ultrasonic Examination of Penetration Nozzles in Vessels, Examination Category B-D, Item Nos. B3.10 and B3.90, Reactor Nozzle-to-Vessel Welds, Figs. IWB-2500-7(a), (b), and (c),Section XI Division I

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 24 of 27 N-616 Alternate Requirements for VT-3 Visual Examination of Classes 1, 2, and 3 Insulated Pressure Retaining Bolted Connections,Section XI, Division 1 (Conditionally Accepted)

N-624 Successive Inspections,Section XI, Division 1 N-648 Alternate Requirements for Inner Radius Examination of Class I Reactor Vessel Nozzles,Section XI Division N-649 Alternate Requirements for IWE-5240 Visual Examination,Section XI, Division 1 N-652 Alternate Requirements to Categorize B-G-1, B-G-2, and C-D Bolting Examination Methods and Selection Criteria,Section XI, Division 1 N-663 Alternate Requirements for Classes 1 and 2 Surface Examinations,Section XI, Division 1 Relief Requests 98-001-11 Inside diameter Ultrasonic examination of the Core Flood Nozzles using enhanced UT as described in B&W Topical Reports BAW-2228-A and BAW-2228P 98-002-11 Surface Examination of Reactor Coolant Pump casing scroll welds. Applicable to RCP- 1A only 98-008-1I Request to use the 1989 Addenda of ASME Section XI for examination category B-G-1I for the examination of reactor vessel closure nuts; Item B6. 10 98-0 12-Il Request for relief from performing the Code required VT-3 examination on metal containment seals and gaskets. (ASME Section XI, 1992 Edition) 98-013-11 Request for relief from the provisions of Paragraph IWA-2300 in accordance with CP-189 as amended by ASME Section XI. (ASME Section XI, 1992 Edition) 98-0 14-Il Request for relief from requirement to perform pre-service inspection of new paint or coatings 98-015-I1 Request for relief from performing the Code required visual examination on paint or coatings prior to removal 98-0 16-Il Request for relief from performing the VT-2 visual examination in connection with system pressure testing following repair, replacement or modification under Article IWE-5000 98-017-11 Request for relief from the requirement of Paragraphs IWE-2420(b) and IWE-2420(c) to perform successive examinations of repairs

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 25 of 27 98-018-11 Request for relief from performing bolt torque or tension tests on bolted connections that have not been disassembled and reassembled during the inspection interval 98-001-SS Request to use the 1988 Addenda to the 1987 ASME GM Code for definition of Examination Interval, Subsequent Examination Schedule and Examination Sample Size 03-001-I1 Relief from ASME Code,Section XI, Appendix VII, Supplement 10 3F1 104-02 Crystal River Unit 3 - Third 10-Year Inservice Inspection Program - Request for Approval of Risk-Informed Inservice Inspection Program for Class 1, ASME Code, Category B-J and B-F Piping Welds

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-0 1 Page 26 of 27 TABLE 6 NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT The following NIS-2 forms are attached in compliance with the requirements of Article IWA-6220 of ASME Section X1, 1989 Edition without Addenda.

Class 1 NIS-2 Reports ________

Work Description Repaired/

Order # Replacement 796747 RCV-9, Rotated spare from stock (parts replaced). Replaced flange Replacement bolting.______ ___

796748 RCV-8, Rotated spare from stock (parts replaced). Replaced flange Replacement bolting.______ ___

785441 RCV-10 & RCV- 11, Rotated spares from stock (parts replaced in RCV- Replacement 10). Replaced flange bolting. ________

888598 CFH-16 Replaced Snubber with new model Replacement 888603 DHH-38 Replaced Snubber with new model Replacement 888752 MUH-32 Replaced Snubber with new model Replacement 888821 MUH-37 Replaced Snubber with Strut Replacement 888822 MUH-82 Replaced Snubber with new model Replacement 888820 RCH-530 Replaced Snubber with new model Replacement 888628 RCH-531 Replaced Snubber with new model Replacement 888631 RCH-80 Replaced Snubber with new model Replacement 888632 RCH-81 Replaced Snubber-with new model Replacement 801715 MUHE-iC piping flange studs & nuts Replacement 894115 RC Letdown Line Reroute Replacement 1000474 Pressurizer and Hot Leg Surge Nozzle Weld Overlay Weld Repairs Repaired 1000472 Pressurizer Relief Nozzles and Spray Nozzle Overlay Weld Repairs Repaired 1000471 Pressurizer Vent Nozzle, Thermowell Nozzle, and Sensing Nozzles Repaired Class 2 NIS-2 Reports ________

Work Description Repaired Order # Replacement 612143 MUFL-3A, Replaced nuts Replacement 856521 DHP-1B3, bolting replacement Replacement 789395 SWV-616, Replaced valve and pipe. Replacement 789397 SWV-618, Replaced valve and pipe. Replacement 885131 Implement EC 60076 for SWR-235 Replacement 901641 Add Shear Lugs to EFH-121 per EC 59936 Replacement 888614 FWH-132 Replacement 901640 Modify EFH-120 Replacement 901639 Remove EFH-118 Replacement 888614 FWH-120A Replacement 888613 FWH-131 Replacement 888601 DHH-26V Replacement

U. S. Nuclear Regulatory Commission Attachment 1 3F0308-01 Page 27 of 27 TABLE 6 NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT (continued)

The following NIS-2 forms are attached in compliance with the requirements of Article IWA-6220 of ASME Section X1, 1989 Edition without Addenda.

Cl~ 2 NIS-2 R~nnrt'~ Ienntinuerll Work Description Repaired /

Order # Replacement 888604 DHR-18, Replacement 888605 DHR-28, Replacement 888606 DHR-37, Replacement 888607 DHR-49, Replacement 888616 FWH-148, Replacement 888619 FWH-162, Replacement 888726 MSH-123 Replacement 888722 MSH-125 Replacement 888721 MSH-128 Replacement 888719 MSH-149 Replacement 888765 MSH-160 Replacement 888768 MSH-161 Replacement 888771 MSH-164 Replacement 888774 MSH-168 Replacement 888625 MSH-243 Replacement 888638 SWH-483 Replacement 888639 SWH-493L Replacement 888640 SWH-493U Replacement 885130 SWR-233 Replacement 888642 SWR-425 Replacement 885123 DHP-1B3 stuffing box head assembly Replacement 1002989 Leading Edge Flowmeter FW-1-FX Replacement 1002989 Leading Edge Flowmeter FW-2-FX Replacement 1159274 CIV-40 replaced valve and pipe Replacement 1013710 MUV-53 replace valve Replacement 1158205 LRV-50 Valve disc replaced. Replacement

PROGRESS ENERGY FLORIDA, INC.

CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302/LICENSE NUMBER DPR-72 Inservice Inspection Summary Report Interval 3, Period 3, RFO 15 (122 Pages)

out]

.G Attachment I L

Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY. AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description B4.1.76 MKA61 TO MK55 PIPE TO PIPE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments OWN VT-07-293 Accept 893554 ITEM: AUG7.7 Summary No. Component ID Description System System Description EA-03-609 RCRE-1 RX Vessel Head and 69 CRDMS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-162 Accept 893554 CATEGORY: B-A ITEM: B1.11 Summary No. Component ID Descriptio n System System Description B1.1.1 MK A7 TO B1 REACTOR PRESSURE VESSEL RC REACTOR COOLANT CIRCUMFERENTIAL SHELL WELD Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-045 Accept 899103 Summary No. Component ID Description System System Description B1.1.4 MI(Al TO A2 REACTOR PRESSURE VESSEL RC REACTOR COOLANT CIRCUMFERENTIAL SHELL WELD Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-048 Accept 899103 Summary No. Component ID Description System System Description 131.2.1 MKB1 TO A6 REACTOR PRESSURE VESSEL RC REACTOR COOLANT CIRCUMFERENTIAL SHELL WELD Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-054 Accept 899103 Wednesday, February 13, 2008Pae1o12 Page 1of122

Grou Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-A ITEM: BI.11 Summary No. Component ID Description System System Description B 1.2.3 MK86 TO 87 REACTOR PRESSURE VESSEL RC REACTOR COOLANT CIRCUMFERENTIAL SHELL WELD Workscope Report t Jo. Exam Status Work Order No. Comments ISI VE-07-0 56 Accept 899103 ITEM: B 1.12 Summary No. Component ID Description .System System Description B1.1.2 MKA1 TO Al W-X AXIS REACTOR PRESSURE VESSEL .RC REACTOR COOLANT LONGITUDINAL SHELL WELD Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-046 Accept 899103 Summary No. Component ID Description System System Description B1.1.3 MKA1 TO Al Y-Z AXIS REACTOR PRESSURE VESSEL RC REACTOR COOLANT LONGITUDINAL SHELL WELD Workscooe Report No Exam Status Work Order No. Comments ISI VE-07-047 Accept 899103 Summary No. Component ID Description System System Description B1.1.5 MKA2 TO A2 X-Y AXIS REACTOR PRESSURE VESSEL RC REACTOR COOLANT LONGITUDINAL SHELL WELD Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-049 Accept 899103 Summary No. Component ID Description System System Description B1.1.6 MKA2 TO A2 W-Z AXIS REACTOR PRESSURE VESSEL RC REACTOR COOLANT LONGITUDINAL SHELL WELD Workscope Report No., Exam Status Work Order No. Comments ISI VE-07-050 Accept 899103 Wednesday, February 13, 2008 Pg Page 2 oof 122 2

"G~ Gusa Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-A ITEM: B1.21 Summary No. Component ID Description System System Description 131.2.2 MK36 TO 6 REACTOR PRESSURE VESSEL RC REACTOR COOLANT LONGITUDINAL SHELL WELD Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-055 Accept 899103 ITEM: B1.30 Summary No. Component ID Description System System Description Bi .3.1A MK7 TO 86 REACTOR PRESSURE VESSEL FLANGE RC REACTOR COOLANT TO SHELL Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-057 Accept 899103 CATEGORY:, B-B ITEM: B2.11 Summary No. Component ID Description System System Description B2.1.1 .A MK5 TO 1 UPPER HEAD TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-276 Accept 893554 ISI UT-07-277 Accept 893554 ISI UT-07-278 Accept 893554 Summary No: Component ID Description System System Description 132.1.1.13 MK5 TO 1 UPPER HEAD TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-279 Accept 893554 IS' UT-07-280 Accept 893554 ISI UT-07-281 Accept 893554 Wednesday, February 13, 2008Pae3o12 Page 3 of 122

Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY. B-B ITEM: B2. 11 Summary No. Component ID Description System System Description B2.1.1.C MK5 TO I UPPER HEAD TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-282 Accept 893554 SIs UT-07-283 Accept 893554

'SI UT-07-284 Accept 893554 ITEM: B2.12 Summary No. Component ID Description System System Description B2.1.2 MK1 TO 1 LONGITUDINAL SHELL WELD RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments ISI UT-07-285 Accept 893554 IS' UT-07-286 Accept 893554 IS' UT-07-287 Accept 893554 CATEGORY: B-D ITEM: B3.100 Summary No. Component ID Description System System Description B1.4.1B MK1 7-86 WAXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-059 Accept 899103 Summary No. Component ID Description *System System Description 131.4.213 MK17-86 Y AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-061 Accept 899103 Wednesday, February 13, 2008Pae4o12 Page 4 of 122

Nucal*s Lo~ 3t~ Attachment 1 roll o'

(2 Un Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-D ITEM: B3.100 Summary No. Component ID Description System System Description Bi .4.31B MK18-86/87 W-X AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments IS] VE-07-063 Accept 899103 Summary No. Component ID Description System System Description 131.4.413 MK1 8-86/87 X-Y AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No! Comments ISI VE-07-065 Accept 899103 Summary No. Component ID Description System System Description B11.4.513 MK18-86/87 Y-Z AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-067 Accept 899103 Summary No. Component ID Description System Systemn Description 131.4.613 MK1 8-86/87 Z-W AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-069 Accept Summary No. Component ID Description System System Description 813.4.713 MK19 TO 86/87 X AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-071 Accept 899103 Summary No. Component ID Description System System Description Bi .4.8B MKI9 TO 86/86 Z AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-073 Accept 899103 Wednesday, February 13, 2008Pae5o12 Page 5of122

K ie 6 0i.U Attachment 1 P~(L Inser vice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY. B-D ITEM: B3.110 Summary No. Component ID Description System System Description B2.2.2A MK31 TO 5 X-Y AXIS NOZZLE TO HEAD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-066 Accept 893554 IS' UT-07-295 Accept 893554 ITEM: B3.120*

Summary No. Component ID Description System System Description 132.2.213 MK31 TO 5 X-Y AXIS NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-067 Accept 893554 IS! UT-07-296 Accept 893554 ITEM: B3.130 Summary No. Component ID Description System System Description B3.2.4 MK70 TO 8 SG B NOZZLE TO HEAD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments isI UT-07-063 Accept 893554 ITEM: B3.140 Summary No. Component ID Description System System Description B3.2.4.1 MK70 TO 8 SG B NOZZLE INNER RADIUS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-062 Accept 893554 Wednesday, February 13, 2008Pae6o12 Page 6 of 122

Group Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-D ITEM: B3.90 Summary No. Component ID Description System System Description B1.4.1A MK17-86 WAXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-058 Accept 899103 Summary No. Component ID Description Systemn Systemn Description B1.4.2A MK17-86 YAXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-060 Accept 899103 Summary No. Component ID Description System System Description B1.4.3A MK1 8-86/87 W-X AXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-062 Accept . 899103 Summary No. Component ID Description Systemn System Description Bi .4.A MK1 8-86/87 X-Y AXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-064 Accept 899103 Summary No. Component ID Description System System Description 81 .4.5A MK18-86/87 Y-Z AXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-066 Accept 899103 Summary No. Component ID Description System System Description Bi .4.6A MK18-86/86 Z-W AXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-068 Accept 899103 Wednesday, February 13, 2008Pae7o12 Page 7 of 122

NIar 6 nL"Ie afor Attachment 1

" ~GGUUj1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-D ITEM: B3.90 Summary No. Component ID Description *System System Description 81.4.7A MK19 TO 86/87 X AXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-070 Accept 1899103 Summary No. Component ID Description System System Description 81 .4.8A MK1 9 TO 86/86 Z AXIS NOZZLE TO SHELL RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-072 Accept 899103 CATEGORY: B-E ITEM: B4.12 Summary No. Component ID Description System System Description 131.5.1.38 CRDM Nozzle #38 CRDM Head Penetration C-7 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments SI VT-07-167 Accept 893554 Summary No. Component ID Description Systemn Systemn Description 831.5.1.39 CRDM Nozzle #39 CRDM Head Penetration C-9 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-168 Accept 893554 Summary No. Component ID Describtion System System Description

81. 5.1.51 CRDM Nozzle #51 CRDM Head Penetration C-il1 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments isI VT-07-169 Accept 893554 Wednesday, February 13, 2008 Pg 8oof 122 Page 2

Nuclar A rv~1 Gqciatoi Attachment 1 (GUUP Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.12 Summary No. Component ID Description System System Description B1 .5.1.58 CRDM Nozzle #58 CRDM Head Penetration B-8 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments IS! VT-07-170 Accept 893554 Summary No. Component ID Description System System Description B1.5.1.62 CRDM Nozzle #62 CRDM Head Penetration B-6 RC REACTOR COOLANT Workscooe Report No Exam Status Work Order No. Comments ISI VT-07-171 Accept 893554 Summary No. Component ID Description System System Description B1.5.1.63 CRDM Nozzle #63 CRDM Head Penetration 8-10 RC REACTOR COOLANT Workscope Report Ng. Exam Status Work Order No. Comments ISI VT-07-172 Accept 893554 ITEM: B4.13 Summary No. Component ID Description System System Description B1.5.2.00 INCORE INST. NOZ. INCORE INSTRUMENTATION NOZZLES RC REACTOR COOLANT WELD IN REACTOR (52)

VESSEL Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 1044554-03 Summary No. Component ID Description System System Description 8135.2.01. MK #181 INSTRUMENTATION NOZZLE #1 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#01)

Wednesday, February 13, 2008Pae9o12 Page 9 of 122

G Poup Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1.5.2.02 MK# 182 INSTRUMENTATION NOZZLE #2 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#02)

Summary No. Component ID Description System System Description B1 .5.2.03 MK# 182 INSTRUMENTATION NOZZLE #3 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#03)

Summary No. Component ID Description System System Description B1 .5.2.04 MK# 182 INSTRUMENTATION NOZZLE #4 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#04)

Summary No. Component ID Description System System Description 131.5.2.05 MK# 183 INSTRUMENTATION NOZZLE #5 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#05)

Summary No. Component ID Description System System Description B1.5.2.06 MK# 182 INSTRUMENTATION NOZZLE #6 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#06)

Wednesday, February 13, 2008 Pg 10 Page 0oof 122 2

  • t6 out Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description 131.5.2.07 MK# 183 INSTRUMENTATION NOZZLE #7 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#07)

Summary No. Com~ponent ID Description System System Description B1.5.2.08 MK# 182 INSTRUMENTATION NOZZLE #8 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#08)

Summary No. Component ID Description System System Description B1.5.2.09 MK# 183 INSTRUMENTATION NOZZLE #9 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT- 07-144 Accept 893554

(#09)

Summary No. Component ID Description System System Description 131.5.2.10 MK# 183 INSTRUMENTATION NOZZLE #10 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#10)

Summary No. Component ID Description Systemn System Description 131.5.2.11 MK# 183 INSTRUMENTATION NOZZLE #11 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#11)

Wednesday, February 13, 2008 Pg 111oof 122 Page 2

J"G I tIoud Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1.5.2.12 MK# 183 INSTRUMENTATION NOZZLE #12 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#12)

Summary No. Component ID Description System System Description B1.5.2.13 MK# 183 INSTRUMENTATION NOZZLE #13 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#13)

Summary No. Component ID Description System System Description B31.5.2.14 MK# 183 INSTRUMENTATION NOZZLE #14 RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#14)

Summary No. Component ID Description System System Description B1.5.2.15 MK# 183 INSTRUMENTATION NOZZLE #15 RC REACTOR COOLANT Workscope Report No. *Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#15)

Summary No. Component ID Description System System Description 131.5.2.16 MK# 183 INSTRUMENTATION NOZZLE #16 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#16)

Wednesday, February 13, 2008 Pg 12 Page 2o 2 of 122

Gstle Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description 131.5.2.17 MK# 183 INSTRUMENTATION NOZZLE #17 RC REACTOR COOLANT Workscope RepotNo Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#17)

Summary No. Component ID Description System System Description B1.5.2.18 MK# 183 INSTRUMENTATION NOZZLE #18 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#18)

Summary No. Component ID Description System System Description B1.5.2.19 MK# 183 INSTRUMENTATION NOZZLE #19 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-1144 Accept 893554

(#19)

Summary No. Component ID Description System System Description B1.5.2.20 MK# 183 INSTRUMENTATION NOZZLE #20 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#20)

Summary No. Component ID Description System System Description B1.5.2.21 MK# 184 INSTRUMENTATION NOZZLE #21 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#21)

Wednesday, February 13, 2008 Pg 133oof 122 Page 2

Nuissr G 1(,ra~

o Attachment 1 (3uup Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 'I CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1 .5.2.22 MK# 184 INSTRUMENTATION NOZZLE #22 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#22)

Summary No. Component ID Description System System Description B1.5.2.23 MK# 184 INSTRUMENTATION NOZZLE #23 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#23)

Summary No. Component ID Description System System Description B 1.5.2.24 MK# 184 INSTRUMENTATION NOZZLE #24 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#24)

Summary No. Component ID Description System System Description B1.5.2.25 MK# 183 INSTRUMENTATION NOZZLE #25 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 893554

(#25)

Summary No. Component ID Description System System Description B1.5.2.26 MK# 183 INSTRUMENTATION NOZZLE #26 RC REACTOR COOLANT Workscope Report No. Exam Status . Work Order No. Comments AUG VT-07-144 Accept 785469

(#26)

Wednesday, February 13, 2008 Page Pg 14 4oof 122 2

Nuclear Go fcaliop Attachment 1 1 oull Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1 .5.2.27 MK# 184 INSTRUMENTATION NOZZLE #27 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#27)

Summary No. Component ID Description System System Description B1.5.2.28 MK# 184 INSTRUMENTATION NOZZLE #28 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#28)

Summary No. Component ID Description System System Description B1.5.2.29 MK# 184 INSTRUMENTATION NOZZLE #29 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept .785469

(#29)

Summary No. Component ID Description System System Description B1.5.2.30 MK# 185 INSTRUMENTATION NOZZLE #30 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#30)

Summary No. Component ID Description System System Description B1 .5.2.31 MK# 185 INSTRUMENTATION NOZZLE #31 RC REACTOR COOLANT Workscope Report No Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#31)

Wednesday, February 13, 2008 Page Pg 155o of 122 2

\lear J"6 et.

u Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1.5.2.32 MK# 184 INSTRUMENTATION NOZZLE #32 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#32)

Summary No. Component ID Description System System Description 131.5.2.33 MK# 184 INSTRUMENTATI ON NOZZLE #33 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#33)

Summary No. Component ID Description System System Description B1.5.2.34 MK# 184 INSTRUMENTATION NOZZLE #34 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#34)

Summary No. Component ID Description System System Description 51.5.2.35 MK# 184 INSTRUMENTATION NOZZLE #35 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#35)

Summary No. Component ID Description System System Description B1.5.2.36 MK# 185 INSTRUMENTATION NOZZLE #36 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#36)

Wednesday, February 13, 2008 Pg 166oof 122 Page 2

Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1.5.2.37 MK# 185 INSTRUMENTATION NOZZLE #37 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#37)

Summary No. Component ID Description System System Description B1.5.2.38 MK# 185 INSTRUMENTATION NOZZLE #38 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#38)

Summary No. Component ID Description System System Description B1.5.2.39 MK# 184 INSTRUMENTATION NOZZLE #39 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#39)

SummarV No. Component ID Description System System Description B1.5.2.40 MK# 184 ' INSTRUMENTATION NOZZLE #40 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#40)

Summary No. Component ID Description System System Description B1.5.2.41 MK# 184 INSTRUMENTATION NOZZLE #41 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG \VT-07-144 Accept 785469

(#41)

Wednesday, February 13, 2008PaeIf12 Page 17 of 122

PNudeIar 13Graaop Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description 131.5.2.42 MK# 184 INSTRUMENTATION NOZZLE #42 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#42)

Summary No. Component ID Description System System Description B1.5.2.43 MK# 184 INSTRUMENTATION NOZZLE #43 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#43)

Summary No. Component ID Description System System Description B1.5.2.44 MK# 185 INSTRUMENTATION NOZZLE #44 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#44)

Summary No. Component ID Description System System Description 131.5.2.45 MK# 185 INSTRUMENTATION NOZZLE #45 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#45)

Summary No. Component ID Description System System Description B1.5.2.46 MK# 185 INSTRUMENTATION NOZZLE #46 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#46)

Wednesday, February 13, 2008 Page Pg 188oof 122 2

LN~~03Gout Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description B1 .5.2.47 MK# 184 INSTRUMENTATION NOZZLE #47 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#47)

Summary No. Component ID Description System System Description B1.5.2.48 MK# 185 INSTRUMENTATION NOZZLE #48 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#48)

Summary No. Component ID Description System System Description 131.5.2.49 MK# 185 INSTRUMENTATION NOZZLE #49 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#49)

Summary No. Component ID Description System System Description 131.5.2.50 MK# 184 INSTRUMENTATION NOZZLE #50 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#50)

Summary No. Component ID Description System System Description 131.5.2.51 MK# 185 INSTRUMENTATION NOZZLE #51 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#5 1)

Wednesday, February 13, 2008 Page 19 Pg 9oof 122 2

c~ Nucl ear G3ietefa o!

Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-E ITEM: B4.13 Summary No. Component ID Description System System Description Bi .5.2.52 MK# 185 INSTRUMENTATION NOZZLE #52 RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-144 Accept 785469

(#52)

ITEM: B4.20 Summary No. Component ID Description System System Description B2.3.1 TOP, MIDDLE, PRESSURIZER HEATER BUNDLES RC REACTOR COOLANT BOTTOM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-371 Accept 893554 CATEGORY: B-F ITEM: B5.40 Summary No. Component ID Description System System Description B4. 1.1 MK45 TO 9 SPRAY NOZZLE TO SAFE-END WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-156 .Accept 893554 Summary No. Component ID Description System System Description B4. 1.10 MK8 TO 37 NOZZLE TO SAFE-END WELD RC REACTOR COOLANT WorIkscope Report No. Exam Status Work Order No. Comments AUG VT-07-1 53 Accept 893554 Summary No. Component ID Description System System Description B4.1.2 MK45 TO9 PRESSURIZER SPRAY NOZZLE TO SAFE- RC REACTOR COOLANT END WELD Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-155 Accept 893554 Wednesday, February 13, 2008 Pg Page 20 0oof 122 2

LNG8GI clea Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-F ITEM: B5.40 Summary No. Component ID Description System System Description B4.1.9 MK8 TO 37 NOZZLE TO SAFE-END RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-154 Accept 893554 CATEGORY: B-G-1 ITEM: B6.10 Summary No. Component ID Description System System Description B 1.8.4.4 0 26-207-41 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-236 Accept 1003165 Summary No. Component ID Description System System Description B 1.8.4.41 26-207-42 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments 151 VT-07-237 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.42 26-207-43 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-238 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.43 26-207-44 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-239 Accept 1003165 Wednesday, February 13, 2008 Page Pg 21 1oof 122 2

Ll"G 'Cla o' Uý'~

iL. Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.10 Summary No. Component ID Description System System Description B1 .8.4.44 26-207-45 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-261 Accept 1003165 Summary No. Component ID Description System System Description B1 .8.4.45 26-207-46 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-262 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.46 26-207-47 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-263 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.47 26-207-48 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-264 Accept 1003165 Summary No. Component ID Description System System Description B 1.8.4.48 26-207-49 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-265 Accept 1003165 Summary No. Component ID Description System System Description B1 .8.4.49 26-207-50 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-266 Accept 1003165 Wednesday, February 13, 2008 Pg 22 Page 2oof 122 2

NILdcear GrIcefaor Attachment 1 Groupp Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-I ITEM: B6.10 Summary No. Component ID Description System System Description B1 .8.4.50 26-207-5 1 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-267 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.51 26-207-52 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments isI VT-07-268 Accept 1003165 Summary No. Component ID Description System System Descrip~tion B3.8.4.52 26-207-53 CLOSURE HEAD NUT RC REACTOR COOLANT Workscoroe Report Np. Exam Status Work Order No. Comments ISI VT-07-269 Accept \1003165 Summary No. Component ID Description System System Description B1 .8.4.53 26-207-54 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-270 Accept 1003165 Summary No. Component ID Description System System Description 131.8.4.54 26-207-655 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments isI VT-07-271 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.55 26-207-56 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-272 Accept 1003165 Wednesday, February 13, 2008 Pg 23 Page 3oof 122 2

Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-1 ITEM: B6.10 Summary No. Component ID Description System System Description B1 .8.4.56 26-207-57 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-273 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.57 26-207-58 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-274 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.58 26-207-59 CLOSURE HEAD NUT RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments ISI VT-07-275 Accept 1003165 Summary No. Component ID Description System System Description B1.8.4.59 26-207-60 CLOSURE HEAD NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments iSI VT-071-276 Accept 1003165 ITEM: B6.200 Summary. No. Component ID Description System System Description B5.2.15 RC-PU-381 NUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-301 Accept 893554 Wednesday, February 13, 2008 Page Pg 24 4oof 122 2

Sear Lirta or Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-1 ITEM: B6.30 Summary No. Component ID Description System System Description B 1.8.1.40 25-207-41 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-068 Accept 1003165

'SI UT-07-1 46 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.41 25-207-42 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments 151 UT-07-069 Accept 1003165 ISI UT-07-147 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.42 25-207-43 CLOSURE STUD RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments ISI UT-07-070 Accept 1003165 Is[ UT-07-148 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.43 25-207-44 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-071 Accept 1003165 ISI UT-07-149 Accept 1003165 Wednesday, February 13, 2008 Pg Page 25 5oof 122 2

Nuclear G uanca~o Attachment 1 Group I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.30 Summary No. Component ID Description System System Description B1 .8.1.44 25-207-45 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-074 Accept 1003165 ISI UT-07-1 50 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.45 25-207-46 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-075 Accept 1003165 ISI UT-07-151 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.46 25-207-47 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-076 Accept 1003165 ISI UT-07-152 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.47 25-207-48 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-077 Accept 1003165 ISI UT-07-153 Accept 1003165 Wednesday, February 13, 2008 Pg 26 Page 6oof 122 2

NI-la Moit row Gou Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.30 Summary No. Component ID Description System System Description B1 .8.1.48 25-207-49 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments 1St UT-07-078 Accept 1003165

'SI UT-07-1 54 Accept 1003165 Summary No. Component ID Description System System Description B1 .8.1.49 25-207-50 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments I1S . UT-07-079 Accept 1003165 IS' UT-07-1 551' Accept 1003165 Summary No. Component ID Description System System Description 131.8.11.50 25-207-51 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-080 Accept 1003165 ISI UT-07-1 56 Accept 1003165 Summary No. Component ID Description System System Description B1 .8.1.51 25-207-52 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-081 Accept 1003165 ISI UT-07-1 57 Accept 1003165 Wednesday, February 13, 2008 Pg Page 27 7oof 122 2

Kusaw b 'u.a Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.30 Summary No. Component ID Description System System Description B1.8.1 .52 25-207-53 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-082 *Accept 1003165 151 UT-07-1 58 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.53 25-207-54 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-083 Accept 1003165 ISI UT-07-159 Accept 1003165 Summary No. Component ID Description System System Description B1 .8.1.54 2-055CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-084 Accept 1003165 IS! UT-07-160 Accept 1003165 Summary No. Component ID Description System System Description Bi .81.55 25-207-56 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments SIs UT-07-085 Accept 1003165 IS! UT-07-161 Accept 1003165 Wednesday, February 13, 2008 Page Pg 28 8oof 122 2

Nula Grou. ap Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-1 ITEM: B6.30 Summary No. Component ID Description System System Description B1.8.1.56 25-207-57 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-086 Accept .1003165 IS' UT-07-1 62 Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.57 25-207-58 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-087 Accept 1003165 is] UT-07-163 . Accept 1003165 Summary No. Component ID Description System System Description B1.8.1.58 25-207-59 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-088 Accept 1003165 ISI UT-07-164 Accept .1003165 Summary No. Component ID Description System System Description B1.8.1.59 25-207-60 CLOSURE STUD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-089 Accept 1003165 SIs UT-07-165 Accept 1003165 Wednesday, February 13, 2008 Pg 29 Page 9oof 122 2

Nuclear Attachment 1 Inservice Inspection Report Interval 3, Period 3, RFOI 5 CLASS: I CATEGORY: B-G-1 ITEM: B6.40 Summary No. Component ID Description System System Description 131.9.1 .15 STUD 15 REACTOR THREADS IN FLANGE RC REACTOR COOLANT VESSEL THREADS IN FLANGE Workscope Report No. Exam Status Work Order No. Comments ISI . UT-07-230 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.22 STUD 22 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-191 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.23 STUD 23 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. -Exam Status Work Order No. Comments 151 UT-07-192 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.24 STUD 24 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-193 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.25 STUD 25 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-194 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.26 STUD 26 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-195 Accept 893554 Wednesday, February 13, 2008 Page Pg 30 0oof 122 2

Nula Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.46 Summary No. Component ID Description System System Description B1.9.1.27 STUD 27 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-196 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.28 STUD 28 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-197 Accept 893554 Summary No. Component ID Description .System System Description 131.9.11.29 STUD 29 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status, Work Order No. Comments ISI UT-07-198 Accept 893554 Summary No. Component ID Description System System Description 131.9.11.30 STUD 30 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-199 Accept 893554 Summary No. Component ID Description System System Description B1 .9.1.31 STUD 31 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-200 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.32 STUD 32 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-201 Accept 893554 Wednesday, February 13, 2008 Page Pg 311oof 122 2

Nula Grout]a Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-1 ITEM: B6.40 Summary No. Component ID Description System System Description B1 .9.1.33 STUD 33 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-202 Accept 893554 Summary No. Component ID Description System System Description B 1.9.1.34 STUD 34 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-203 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.35 STUD 35 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-204 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.36 STUD 36 THREADS IN FLANGE RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments ISI UT-07-205 .Accept .893554 Summary No. Component ID Description System System Description 131.9.11.37 STUD 37 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-206 Accept 893554 Summary No. Component ID Description System System Description B1 .9.1.38 STUD 38 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-207 Accept 893554 Wednesday, February 13, 2008 Page Pg 32 2oof 122 2

N Isaa 13Ou a Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-I ITEM: B6.40 Summary No. Component ID Description System System Description B1.9.1.39 STUD 39 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-208 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.40 STUD 40 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-209 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.41 STUD 41 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-21 0 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.42 STUD 42 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-21 1 Accept 893554 Summary No. Component ID Description System System Description B1 .9.1.43 STUD 43 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-212 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.44 STUD 44 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-213 Accept 893554 Wednesday, February 13, 2008 Page Pg 33 3oof 122 2

N S ~iud 0 Attachment 1

(~~bbUI Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-1 ITEM: B6.40 Summary No. Component ID Description System System Description 131.9.1.45 STUD 45 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-214 Accept 893554 Summary No. Component ID Description System Systemn Description B1.9.1.46 STUD 46 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-215 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.47 STUD 47 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-216. Accept 893554 Summary No. Component ID Description System System Description 81.9.1.48 STUD 48 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-217 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.49 STUD 49 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISt UT-07-218 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.50 STUD 50 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-219 Accept 893554 Wednesday, February 13, 2008 Pg Page 34 4oof 122 2

N'C~

1 3oJ Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.40 Summary No. Component ID Description System System Description B1 .9.1.51 STUD 51 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments 1St UT-07-220 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.52 STUD 52 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-221 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.53 STUD 53 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-222 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.54 STUD 54 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-223 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.55 STUD 55 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments I1S UT-07-224 Accept 893554 Summary No. Component ID Description System System Description 131.9.1.56 STUD 56 THREADS IN FLANGE R~C REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-225 Accept 893554-Wednesday, February 13, 2008 Pg 35 Page 5oof 122 2

ear5 "GGru l"Clfapf Ub Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY:, B-G-1 ITEM: B6.40 Summary No. Component ID Description System System Description B1.9.1.57 STUD 57 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments SI UT-07-226 Accept 893554 Summary No. Component ID Description System System Description B1 .9.1.58 STUD 58 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No.. Exam Status Work Order No. Comments ISI UT-07-227 Accept 893554 Summary No. Component ID Description System System Description 61.9.1.59 STUD 59 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No Exam Status Work Order No. Comments ISI UT-07-228 Accept 893554 Summary No. Component ID Description System System Description B1.9.1.60 STUD 60 THREADS IN FLANGE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-229 Accept 893554 ITEM: B6.50 Summary No. Component ID Description- System System Description B1.10.1.41 14/27-207-41 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI \/T-07-232 Accept 1003165 Summary No. Component ID Description System System Description B 1.10.1.42 14/27-207-42 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments isI VT-07-233 Accept 1003165 Wednesday, February 13, 2008 Page 36 Pg of 122 6o 2

Nuclar Graou Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.50 Summary No. Component ID Description System System Description B1.110.1.43 14/27-207-43 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments 151 \/T-07-234 Accept 1003165 Summary No. Component ID Description System System Description B 1.10.1.44 14/27-207-44 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments I51 \VT-07-235 Accept 1003165 Summary No. Component ID Description System System Description 131.10.1.45 14/27-207-45 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments is] \/T-07-245 Accept 1003165 Summary No. Component ID. Description System System Description B31.10.11.46 14/27-207-46 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-246 Accept 1003165 Summary No. Component ID Description System System Description 131.10.11.47 14/27-207-47 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments IS[ \/T-07-247 Accept 1003165 Summary No. Component ID Description System System Description B1.10.1.48 14/27-207-48 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-248 Accept 1003165 Wednesday, February 13, 2008 Page Pg 37 7oof 122 2

Nuclear 6 i~ aop Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-1 ITEM: B6.50 Summary No. Component ID Description , System System Description B1.10.1.49 14/27-207-49 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-249 Accept 1003165 Summary No. Component ID Description System System Description B31.10.1.50 14/27-207-50 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-250 Accept . 1003165 Summary No. Component ID Description System System Description 131.10.1.51 14/27-207-51 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-251 Accept 1003165 Summary No. Component ID Description System System Description B31.10.1.52 14/27-207-52 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-252 Accept 1003165 Summary No. Component ID Description System System Description B1.10.1.53 14/27-207-53 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-253 Accept 1003165 Summary No. Component ID Description System System Description B1 .10.1.54 14/27-207-54 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-254 Accept 1003165 Wednesday, February 13, 2008 Page Pg 38 8oof 122 2

Gru Nuclea Gewml or Attachment 1 Inservice Inspection Report Interval 3, Period. 3, RFOI 5 CLASS: 1 CATEGORY: B-G-I ITEM: B6.50 Summ~ary No. Component ID Description System System Description B1.10.1.55 14/27-207-55 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments IS[ VT-07-255 Accept 1003165 Summary No. Component ID Description System System Description B1.10.1.56 14/27-207-56 CLOSURE WASHER AND BUSHING RC REACTOR COOLANTr Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-256 Accept 1003165 Summary No. Component ID Description System System Description B1.10.1.57 14/27-207-57 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-257 Accept1036 Summary No. Component ID Description System System Description Bi.10.1.58 14/27-207-58 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-258 Accept 1003165 Summary No. Component ID Description System System Description B1.10.1.59 14/27-207-59 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-259 Accept 1003165 Summary No. Component ID Description System System Description 131.10.1.60 14/27-207-60 CLOSURE WASHER AND BUSHING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI \/T-07-260 Accept 1003165 Wednesday, February 13, 2008 Pg 39 Page 9oof 122 2

Nuclear 3e afov Attachment 1 (2 oU Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-2 ITEM: B7.20 Summary No. Component ID Description System System Description B2.5.4 MvK75 & 76 HTR BOLTING RC REACTOR COOLANT STUD/NUT Workscope Report No. Exam Status Work Order No. Comments 151 VT-07-209 Accept 893554 ITEM: B7.30 Summary No. Component ID Description System System Description B3.10.3 SG B INSP. COVER UPPER HANDHOLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments.

IS! VT-07-325 Accept 893554 Summary No. Component ID Description System System Description B3.10.4 SO B INSP. COVER LOWER HANDHOLE BOLTING RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments ISI VT-07-188 Accept 893554 Summary No. Component ID Description System System Description B3.10.8 MK1 11/109 SO-B LOWER MANWAY BOLTING .RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-189 Accept 893554 ITEM: B7.50 Summary No. Component ID Description System System Description B4.12.3 MUHE-1C FLANGE TO FLANGE BOLTING MU MAKE UP & PURIFICATION Workscope Report No. .Exam Status Work Order No. Comments ISI VT-07-224 Accept 893554 Wednesday, February 13, 2008 Pg Page 40 0o 2 of 122

LO,.OI Nuclear P

Gi?9rl o Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-G-2 ITEM: B7.50 Summary No. Component ID Description System System Description B4.12.4 MUHE-1C - FLANGE FLANGE TO FLANGE BOLTING MU MAKE UP & PURIFICATION BOLTING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-317 Reject 893554 Acceptable for use as is per engineering evaluation.

Evaluation Leakage deemed non RCS, condensation caused rust. Rust on bolting is acceptable for use as-is.

Disposition Acceptable:

ITEM: B7.60 Summary No. Component ID Description System System Description 135.1.01 RC-PU-3A1 RCP SEAL FLANGE BOLTING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-173 Accept 893554 Summary No. Component ID Description System System Description B5.3.02 RC-PU-3A2 BOLTING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-174 Accept 893554 Summary No. Component ID Description System System Description B5.3.03 RC-PU-3B1 BOLTING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI \/T-07-175 Accept 893554 Summary No. Component ID Description System System Description B5.3.04 RC-PU-3B2 BOLTING RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments isI VT-07-176 Accept 893554 Wednesday, February 13, 2008 Pg 41 Page 1oof 122 2

Nuclear Gtarop Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-2 ITEM: B 7.70 Summary No. Component ID Description System System Description B6.9.03 RCV-8 VALVE BOLTS, STUDS, AND NUTS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-333 Accept 00796747-08 Summary No. Component ID Description System System Description B6.9.05 RCV-9 VALVE BOLTS, STUDS, AND NUTS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-279 Accept 00796747-08 Summary No. Component ID Description System System Description B6.9.29 MUV-497 STUD\NUT .MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments isI VT-07-283 Accept 893554 Summary No. Component ID Description System System Description B6.9.31 MUV-38 STUD\NUT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-290 Accept 893554 Summary No. Component ID Description System System Description B6.9.33 MUV-498 STUD\NUT MU MAKE UP & PURIFICATION Workscope Report t Exam Status Work Order No. Comments ISI VT-07-2Z Accept 893554 Summary No. Component ID Description System System Description B6.9.35 MUV-504 STUD\NUT MU MAKE UP & PURIFICATION Workscope Report I Jo. Exam Status Work Order No. Comments ISI VT-07-2;23 Accept 893554 Wednesday, February 13, 2008 Page 42 Pg 2oof 122 2

N...ClIar CT13 0!a Attachment 1

'"G 6 Goup Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-G-2 ITEM: B 7.70 Summary No. Component ID Description System System Description B6.9.37 MUV-505 STUD\NUT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-222 Accept 893554 CATEGORY: B-H ITEM: B8.30 Summary No. Component ID Description System System Description B3.7.1 A MK95 TO 7 SG A RCSG-1A SUPPORT SKIRT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments is] MT-07-001 Accept 893554 IS' MT-07-002 Accept 893554 CATEGORY: B-J ITEM: MRP200405 Summary No. Component ID Description System System Description B4.1 .78 MK 49 TO53 PIPE TO ELBOW WELD RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments OWN VT-07-244 Accept 893554 Summary No. Component ID Description System System Description B4.1 .80 MK46 TO 47 HPI NOZZLE TO SAFE-END WELD RC' REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments OWN VT-07-286 Accept 893554 Summary No. Component ID Description System System Description B4.1 .86 MKA61 TO MK55 PIPE TO PIPE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments OWN VT-07-242 Accept 893554 Wednesday, February 13, 2008Pae4of12 Page 43 of 122.

KNuIea Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-J ITEM: MRP200405 Summary No. Component ID Description System System Description B4.1 .88 MK 49 TO 53 PIPE TO ELBOW WELD RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments OWN VT-07-285 Accept .893554 Summary No. Component ID Description System System Description B4. 1.90 MK 46 TO 47 HPI NOZZLE TO SAFE-END WELD RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. *Comments OWN VT-07-284 Accept 893554 CATEGORY: B-K-I ITEM: B 10.10 Summary No. Component ID Description System System Description B4.9.3 CFH-5/CFH-15 INTEGRAL ATTACHMENT CF CORE FLOODING Workscope Report No. Exam Status Work Order No. Comments 131 PT-07-034 Accept 893554 CATEGORY: B-L-1 ITEM: B12.10 Summary No. Component ID Description System System Description B5.6.01 RC-PU-3A1 REACTOR COOLANT PUMP TOP CASING RC REACTOR COOLANT WELD Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-041 Accept 1053942 Summary No. Component ID Description System System Description B5.6.02 RC-PU-3A1 REACTOR COOLANT PUMP BOTTOM RC REACTOR COOLANT PUMP CASING WELD Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-040 Accept 1053942 Wednesday, February 13, 2008 Pg 44 Page 4oof 122 2

Bdar 1" ~G6 'Ie O 1 Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: B-M-1 ITEM: B 12.30 Summary No. Component ID Description System System Description B6.6.01 .01 RCV-10 VALVE FLANGE TO BODY WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments SIs PT-05-001 Accept 893554 SIs PT-05-026 Accept 893554 Summary No. Component ID- Description System System Description B6..6.01.02 RCV-10 VALVE BODY TO PILOT VALVE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI PT-05-018 Accept 893554 ISI PT-05-027 Accept 893554 Summary No. Component ID Description System System Description B6.6.4 RCV-9 -VALVE FLANGE TO BODY WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-037 Accept 00796747-08 ITEM: B 12.40 Summary No. Component ID Description System System Description B6.6.7 DHV-3 VALVE BODY VALVE BODY TO CANOPY WELD DH DECAY HEAT REMOVAL WELD Workscooe Report No. Exam Status Work Order No. Comments ISI UT-07-183 Accept 893554 Wednesday, February 13, 2008 Pg 45 Page 5oof 122 2

Nuclear 6anerafof Attachment I

  • N 2t(ru Inservice Inspection Report Interval 3, Period 3, RFOI5, CLASS: I CATEGORY. B-N-I ITEM: B13.10 Summary No. Component ID Description System System Description B1.15.1.A RCRE-1 REACTOR REACTOR VESSEL EXPOSED VESSEL RC REACTOR COOLANT VESSEL INTERIOR INTERIOR Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-051 Accept 893554 CATEGORY. B-N-2 ITEM: B 13.60 Summary No. Component ID Description System System Description B1.16.2 RPV ACCESSIBLE INTERIOR ATTACHMENTS RC REACTOR COOLANT WELDS Workscope Report No. . Exam Status Work Order No. Comments ISI VE-07-052 Accept 893554 CATEGORY: B-N-3 ITEM: B13.70 Summary No. Component ID Description System System Description B1.17.1 RPV ACCESSIBLE CORE SUPPORT STRUCTURE RC REACTOR COOLANT SURF Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-053 Accept 893554 CATEGORY: B-P ITEM: B15.00.BP Summary No. Component ID Description System System Description B15.100.1 Reactor Coolant Bolted Reactor Coolant Bolted Connections RC REACTOR COOLANT Connections Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-372 Accept 893554 Summary No. Component ID Description System System Description B15.100.1A RCT-1 VESSEL CLASS I INSULATED BOLTED RC REACTOR COOLANT MANWAY TO FLANGE CONNECTION Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-164 Accept 867731 Wednesday, February.13, 2008 Page 46 of 122

Nuclear

'a .0 Attachment 1 (1~rulI Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY. B-P ITEM: B15.OO.BP Summary No. Component ID Description System System Description B15.100.113 RCRE-1 VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT HEAD FLANGE CONNECTION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-178 Accept 867731 Summary No. Component ID Description System System Description B15.100.1C RCSG-1B VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT LOWER INSPECTION CONNECTION COVER FLANGE Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-179 Accept 867731 Summary No. Component ID Description System System Description B15.100.1D RCSG-1 B VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT LOWER MANWAY CONNECTION FLANGE Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-180 Accept 867731 Summary No. Component ID Description System System Description B15.100.1E RCSG-1B VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT UPPER HAND HOLE CONNECTION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-127 Accept 867731 Summary No. Component ID Description System System Description B15.100.1F RCSG-1B VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT UPPER MANWAY CONNECTION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-186 Accept 867731 Summary No. Component ID Description System System Description B15.100.1G RCSG-1A LOWER CLASS 1 INSULATED BOLTED RC REACTOR COOLANT INSPECTION COVER CONNECTION FLANGE Workscooe Report No. Exam St -atus Work Order No. Comments ISI VT-07-181 Accept 867731 Wednesday, February 13, 2008 Page 47 of 122

N dear e Is a e Attachment 1 Grout)

Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY. B-P ITEM: B15.OO.BP Summary No. Component ID Description System System Description B15.100.1H RCSG-1A VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT LOWER MANWAY CONNECTION FLANGE Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-146 Accept 867731 Summary No. Component ID Description System System Description B15.100.11 RCSG-1A VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT UPPER HAND HOLE CONNECTION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-133 Accept 867731 Summary No. Component ID Description System System Description B15.100.1J RCSG-1A VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT UPPER MANWAY CONNECTION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-187 Accept 867731 Summary No. Component ID Description System System Description B15.100.iL RCV- 10 VALVE CLASS 1 INSULATED BOLTED RC REACTOR COOLANT FLANGE CONNECTION CONNECTION BOLTING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-161 Accept 867731 Summary No. Component ID Description System System Description B15.100.1M RCV-1 1 VALVE CLASS 1 INSULATED BOLTED RC REACTOR COOLANT FLANGE CONNECTION CONNECTION BOLTING Workscooe Report No. Exam Status Work Order No. Comments ISI VT-07-182 Accept 867731 Wednesday, February 13, 2008 Page Pg 48 8oof 122 2

Gow~alo

'"G Group u Attachment 1 0 0 W Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: B-P ITEM: B15.OO.BP Summary No. Component ID Description System System Description B 15.100.1 N RCT-1 VESSEL CLASS 1 INSULATED BOLTED RC REACTOR COOLANT HEATER BUNDLE CONNECTION BOLTING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-183 Accept 867731 Summary No. Component ID Description System System Description B15.100.1P RCV-38 VALVE CLASS 1 INSULATED BOLTED RC REACTOR COOLANT BONNET BOLTING CONNECTION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-184 Accept 867731 Summary No. Component ID Description System System Description B15.100.2 ALL CLASS 1 CLASS 1 SYSTEM LEAKAGE TEST RC REACTOR COOLANT PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-373 Accept 893554 ITEM: B15.70 Summary No. Component ID Description System System Description B15.100.3 DHV-3 DHV-3 CANOPY-TO-BONNET WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-374 Accept 893554 CATEGORY: F-A ITEM: FI.IOA Summary No. Component ID Description System System Description MUH-5 MUH-5 ROD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-190 Accept 893554 Wednesday, February 13, 2008 Pg 49 Page 9oof 122 2

. Nula 6 uýG Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY. F-A ITEM: FI.IOA Summary No. Component ID Description System System Description MUH-7 MU H-7 ROD MU MAKE UP & PURIFICATION Workscope Report INo Exam Status Work Order No. Comments ISI VT-07-218 Accept 893554 ITEM: FI.IOB Summary No. Component ID Description System System Description DHH-7 DHH-7 ANCHOR DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-1150 Accept 893554 Summary No. Component ID Description System System Description MUH-65 MUH-65 ANCHOR MU MAKE UP & PURIFICATION Workscope ReportN 10. Exam Status Work Order No. Comments ISI VT-07-1t 37 Accept 893554 Summary No. Component ID Description System System Description MUH-66 MUH-66 GUIDE MU MAKE UP & PURIFICATION Workscope Report No Exam Status Work Order No. Comments ISI VT-07-198 Accept 893554 Summary No. Component ID Description System System Description MUH-68 MUH-68 ANCHOR MU MAKE UP & PURIFICATION Workscope Report No Exam Status Work Order No. Comments ISI VT-07-199 Accept 893554 Summary No. Component ID Description System System Description RCH-TYP-123-1 RCH-TYP-1 23-1 RESTRAINT RC REACTOR COOLANT Workscope Report INo Exam Status Work Order No. Comments ISI VT-07-324 Accept 893554 Wednesday, February 13, 2008 Pg 500o Page 2 of 122

NIL Sulcaf r Attachment 1 (3 UU Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY. F-A ITEM: FI.1OC Summary No. Component ID Description System System Description CFH-10 CFH-10 SPRING CAN CF CORE FLOODING Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-299 Reject 893554 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description CFH-14 CFH-14 SNUBBER CF CORE FLOODING Workscope Report No. Exam Status Work Order No. Comments SIs VE-07-037 Accept 893554 Summary No. Component ID Description System System Description DHH-12 DHH-12 SPRING CAN DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-318 Accept 893554 Summary No. Component ID Description System System Description MUH-1 MUH-1 SPRING CAN MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-305 Eval 893554 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description MUH-37 MUH-37 SNUBBER MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments PSI VT-07-319 Accept 888821-01 Summary No. Comoonent ID Description System System Description MUH-62 MUH-62 SPRING CAN MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-196 Accept 893554 Wednesday, February 13, 2008 Page Pg 51 1oof 122 2

Nuclear 6 "ccatior Attachment I j4Gt3(jOull Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: F-A ITEM: F1.1OC Summary No. Component ID Description System System Description MUH-70 MUH-70 SPRING CAN MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-200 Eval 893554 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description RCH-44 RCH-44 SPRING CAN RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. - Comments isI VT-07-292 Accept 893554 Summary No. Component ID Description System System Description RCH-45 RCH-45 SPRING CAN RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments IS! VT-07-193 Accept 893554 Summary No. Component ID Description System System Description RCH-46 RCH-46 SPRING CAN RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-332 Accept 893554 Summary No. Component ID Description System System Description RCH-48 "RCH-48 SNUBBER RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-042 Accept 893554 Summary No. Cc)mponent ID Description System System Description RCH-69R CH-69 SNUBBER RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-043 Accept 893554 Wednesday, February 13, 2008 Pg 52 Page 2oof 122 2

C,"N tissu Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: F-A ITEM: F1.40 Summary No. Component ID Description System System Description RCT-i ROT-i ANCHOR RC REACTOR COOLANT Workscoo~e Report No. Exam Status Work Order No. Comments SIs VT-07-331 Accept 893554 CATEGORY: R-A ITEM: B9.21 Summary No. Component ID Description System System Description B4.5.289 (RI-ISI) MU-269A ELBOW TO PIPE WELD 03MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-227 Accept 893554 SIs UT-05-228 Accept 893554 ISI UT-05-229 Accept 893554 Summary No. Component ID Description System System Description B4.5.644 (RI-ISI) B4.05.644 PIPE TO PIPE WELD 03MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-230 Accept 893554 ISI UT-05-231 Accept 893554 SIs UT-05-232 Accept 893554 Wednesday, February 13, 2008 Pg 53 Page 3o 2 of 122

Nucliear "I~

A6 A. Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: R-A ITEM: RI.11-2 Summary No. Component ID Description System System Description B4.5.247 (RI-ISI) 80 TO 83 ELBOW TO PIPE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments SIs UT-07-188 Accept 893554 ISI UT-07-1 90 Accept 893554 Summary No. Component ID Description System System Description B4.5.252 (RI-ISI) 83 TO 82 WJ-3B3 PIPE TO PIPE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-187 Accept 893554 ISI UT-07-189 Accept 893554 Summary No. *Component ID Description System System Description B4.5.255 (RI-ISI) DH-1 26B ELBOW TO PIPE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-054 Accept 893554 Summary No. Component ID Description System System Description B4.5.384 (RI-ISI) MK93 TO 98 PIPE TO ELBOW WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-245 Accept 893554 ISI UT-07-246 Accept 893554 Wednesday, February 13, 2008 Pg 54 Page 4oof 122 2

K\£155 Genwtio LOG 'Out G(.

Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: R-A ITEM: R1.11-2 Summary No. Component ID Description System System Description B4.5.385 (RI-ISI) MK 98 TO 101 ELBOW TO TEE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-247 Accept 893554

'SI UT-07-248 Accept 893554 Summary No. Component ID Description System System Description B4.5.393 (RI-ISI) DH-1 1 PIPE TO REDUCER WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-249 Accept 893554 ISI .UT-07-250 Accept 893554 Summary No. Component ID Description System System Description B4.5.394 (RI-ISI) DH-12 REDUCER TO ELBOW WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-251 Accept 893554 ISI UT-07-252 Accept 893554 Summary No. Component ID Description System System Description B4.5.56 (RI-ISI) DH-126A PIPE TO ELBOW WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-053 Accept 893554 ITEM: R1.15-2 Summary No. Component ID Description System System Description B1.6.1 (RI-ISI) MK89 TO 17 WAXIS NOZZLE TO SAFE-END WELD CF CORE FLOODING Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-074 Accept 899103 Wednesday, February 13, 2008 Page 55 of 122

Nuclear 6 raor s Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: '1 CATEGORY. R-A ITEM: R1.15-2 Summary No. Component ID Description System System Description B1.6.3 (RI-ISI) MK89 TO 17 YAXIS NOZZLE TO SAFE-END WELD CF CORE FLOODING Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-075 Accept 899103 Summary No. Component ID Description System System Description B4.1.27 (RI-ISI) MK34 ON MKA32 NOZZLE TO SAFE-END WELD DH DECAY HEAT DECAY PIPING WELD Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-139 Accept 893554 ISI UT-07-1 40 Accept 893554 ISI UT-07-141 Accept 893554 ISI UT-07-142 Accept 893554 IS' UT-07-143 Accept 893554 151 UT-07-144 Accept 893554 ISI UT-07-145 Accept 893554 ITEM: R1.20-4 Summary No. Component ID Description System System Description B4.5.1 (RI-ISI) WJ-1-1 MK19 TO MK32 NOZZLE TO PIPE WELD RC RE'ACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-077 Accept Summary No. Component ID Description System System Descripto B4.5.102.12 (RI-ISI) MU85-235 ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order'No. Comments ISI UT-07-056 Accept 893554 Wednesday, February 13, 2008 Page 56 of 122

fears 0bi b. Crao

'"G~ G-u Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: I CATEGORY: R-A ITEM: R1.20-4 Summary No. Component ID Description Systerr System Description B4.5.108.14 (RI-ISI) MU85-270 TEE TO REDUCER WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-036 Accept 893554 Is' UT-07-037 Accept 893554

'SI UT-07-038 Accept 893554 Summary No. Component ID Description System System Description B4.5.108.17 (RI-ISI) MU85-277 ELBOW TO VALVE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-090 Accept 893554 isI UT-07-091 Accept 893554 ISI UT-07-1 86 Accept 893554 Summary No. Component ID Description System System Description 134.5.18 (RI-ISI) WJ-4-2 PIPE TO NOZZLE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments IS[ VE-07-078 Accept Summary No. Component ID Description System System Description B4.5.198 (RI-ISI) 19 TO 32 NOZZLE TO PIPE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-080 Accept Wednesday, February 13, 2008 Pg 57 Page 7oof 122 2

Nuclea 3 nra0f Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 1 CATEGORY: R-A ITEM: R1.20-4 Summary No. Component ID Description System System Description B4.5.221 (RI-ISI) MK38 TO MK18 PIPE TO NOZZLE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-076 Accept Summary No. Component ID Description System System Description B4.5.231 (RI-ISI) 38 TO 18 PIPE TO NOZZLE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-079 Accept Summary No. Component ID Description System System Description B4.5.246 (RI-ISI) 38 TO 18 PIPE TO NOZZLE WELD RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-081 Accept CLASS: 2 CATEGORY: C-A ITEM: C1.10 Summary No. Component ID Description System System Description C1.1.5 D-H COOLER A S-F DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-001 Accept 997520 isI UT-07-043 Accept 997520 Wednesday, February 13, 2008 Page Pg 58 8oof 122 2

Nuda Gr oup Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-A ITEM: C1.20 Summary No. Component ID Description System System Description C1.1.6 D H COOLER B SHELL TO HEAD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-290 Accept 997520

'SI UT-07-291 Accept 997520 IS] UT-07-292 Accept 997520 CATEGORY: C-B ITEM: C2.21 Summary No. Component ID Description System System Description C1.2.3 DH COOLER A INLET NOZZLE TO SHELL WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-003 Accept 997520 IS' UT-07-005 Accept 997520 ISI UT-07-047 Accept 997520 Summary No. Component ID Description System System Description C1.2.7 DH COOLER A NOZZLE TO SHELL WELD DH DECAY HEAT REMOVAL OUTLET Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-001 Accept 997520 ISI UT-07-044 Accept 997520 SIs UT-07-045 Accept 997520 Wednesday, February 13, 2008 Pg 59 Page 9o 2 of 122

Nuclear 6 s.a or Attachment 1 Grout)

Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-B ITEM: C2.22 Summary No. Component ID Description System System Description C1 .2.3.1 DH COOLER A INLET NOZZLE INNER RADIUS DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISi UT-07-002 Accept 997520 ISI UT-07-046 Accept 997520 Summary No. Component ID Description. System System Description C1.2.4.1 DH COOLER B NOZZLE INNER RADIUS DH DECAY HEAT REMOVAL OUTLET Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-288 Accept 997520 ISI UT-07-289 Accept 997520 Summary No. Component ID Description System System Description C1 .2.7.1 DH COOLER A NOZZLE INNER RADIUS DH DECAY HEAT REMOVAL OUTLET Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-003 Accept 997520 151 UT-07-048 Accept 997520 CATEGORY: C-C ITEM: C3.20 Summary No. Component ID Description System System Description C2.5.18 MSH-244 INTEGRAL ATTACHMENT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-031 Accept 893553 Wednesday, February 13, 2008 Pg 60 Page 0o 2 of 122

Nuclear U M.la o~

L~~~f ot3G0 Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-C ITEM: C3.20 Summary No. Component ID Description System 'System Description C2.5-2 MSH-161 INTEGRAL ATTACHMENT MS MAIN STEAM Workscope Rep~ort No. Exam Status Work Order No. Comments ISI MT-07-026 Accept* 893554 Summary No. Component ID Description System System Description C2-5.3 MSH-154 INTEGRAL ATTACHMENT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-023 Accept 893554 Summary No. Component ID Description System System Description C2.5-4 MSH-242 INTEGRAL ATTACHMENT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-008 Accept 893554 Summary No. Component ID Description System System Description C2..5.42 FWH-163 INTEGRAL ATTACHMENT FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT 028 Accept 893553 Summary No. Component ID Description System System Description C2.5.43 FWH-1 61 INTEGRAL ATTACHMENT FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-027 Accept 893553 Summary No. Component ID Description System System Description C2.5.68 DHH-663 INTEGRAL ATTACHMENT DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-047 Accept 997520 Wednesday, February 13, 2008 Pg Page 61 1oof 122 2

Nuclear

  • ~ (p Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-C ITEM: C3.20 Summary No. Component ID Description System System Description C2.5.69 MUH-943 INTEGRAL ATTACHMENT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-012 Accept 997520 Summary No. Component ID Description System System Description C2.5.75 DHH-645 INTEGRAL ATTACHMENT DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments SIs PT-07-046 Accept 997520 Summary No. Component ID Description System System Description C2.5.90 MUH-897 INTEGRAL ATTACHMENT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-014 Accept 997520 Summary No. Component ID Description System System Description C2.5.91 DHH-518 INTEGRAL ATTACHMENT DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-043 Accept 997520 Summary No. Component ID Description System System Description C2.5.92 MUH-927 INTEGRAL ATTACHMENT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments is[ PT-07-044 Accept 997520 Wednesday, February 13, 2008 Pg 62 Page 2oof 122 2

Nuclea Goffo Attachment 1 GrOU Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-C ITEM: C3.20 Summary No. Comp~onent ID Description System System Description C2.5.96 EFH-121 INTEGRAL ATTACHMENT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments PSI MT-07-016 Accept 901641-01 PSI VT-07-287 Accept 901641-01 CATEGORY: C-D ITEM: C4.40 Summary No. Component ID Description System System Description c4.2. 10 97-10 STUD MVS MAIN STEAM Workscope Report Exam Status Work Order No. Comments ISI UT-07-0 Accept 893553 Summary No. Component ID Description System System Description C4.2.7 97-07 STUD MVS MAIN STEAM Workscope ReportN Jo. Exam Status Work Order No. Comments ISI UT-07-0 51 Accept 893553 Summary No. Component ID Description System System Description C4.2.8 97-08 STUD MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-052 Accept 893553 Summary No. omponent ID Description System Systemn Description C4.2.9 97'-09 STUD MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-049 Accept 893553 Wednesday, February 13, 2008 Pg 63 Page 3oof 122 2

Ntcdear 3 quwt oo Attachment 1 Gruup Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: AUG7.1 Summary No. Component ID Description System System Description C2.1.1565 DH-12A ELBOW TO PIPE WELD OH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-009 Accept 997520 ISI UT-07-01 5 Accept 997520 Summary No. Component ID Description System System Description C2.1.194A DH-69G ELBOW TO TEE WELD OH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments AUG PT-07-021 Accept 997520 AUG UT-07-1 23 Accept 997520 AUG UT-07-1 24 Accept 997520 Summary No. Component ID Description System System Description X121 .020 BS-FW-6 PIPE TO VALVE WELD BS REACTOR BUILDING SPRAY Workscope Report No. Exam Status Work Order No. Comments AUG PT-07-049 Accept 997520 AUG UT-07-239 Accept 997520 AUG UT-07-240 Accept 997520 AUG UT-07-24 1 Accept 997520 Wednesday, February 13, 2008 Page 64 Pg 4oof 122 2

Nula

-enraor4 Attachment I LOGru Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: AUG7.I Summary No. ' Component ID Description System System Description X121 .050 BS-6-C PIPE TO ELBOW WELD BS REACTOR BUILDING SPRAY Workscope Report No. Exam Status Work Order No. Comments AUG PT-07-007 Accept 997520 AUG UT-07-031 Accept 997520 AUG UT-07-032 Accept 997520 Summary No. Component ID Description System System Description X121 .290 85S46-A PIPE TO ELBOW WELD BS REACTOR BUILDING SPRAY Workscope Report No Exam Status Work Order No. Comments AUG UT-07-127 Accept 997520 AUG UT-07-1 28 Accept 997520 Summary No. Component ID 'Description System System Description X1 22. 170 BS-4-B PIPE TO REDUCER WELD BS REACTOR BUILDING SPRAY Workscope Report No Exam Status Work Order No. Comments AUG PT-07-005 Accept 997520 Summary No. Component ID Description System System Description X122. 190 BS-F W-47 FLANGE TO VALVE WELD BS REACTOR BUILDING SPRAY Workscope Report No. Exam Status Work Order No. Comments AUG PT-07-006 Accept 997520 Summary No. Component ID Description System -System Description X122.220 BS-39-A PIPE TO ELBOW WELD BS REACTOR BUILDING SPRAY Workscope Report N. Exam Status Work Order No. Comments AUG PT-07-004 Accept 997520 Wednesday, February 13, 2008 Pg 65of122 Page 5o 2

6 il~ sa0

.cI'iraup Gimeau or Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.11 Summary No. Component ID Description System System Description C2.1.105 DH-136B PIPE TO ELBOW WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-033 Accept 893554 IS' UT-07-055 Accept 893554 Summary No. Component ID Description System System Description C2.1.106 DH-134A PIPE TO ELBOW WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-042 Accept 893554 ISI UT-07-231 Accept 893554 ISI UT-07-232 Accept 893554 Summary No. Component ID Description System System Description C2.1.181 DH-47 ELBOW TO VALVE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-05-024 Accept 997520 ISI UT-07-274 Accept 997520 ISI UT-07-275 Accept 997520 SIs UT-07-297 Accept 997520 Wednesday, February 13, 2008 . Page Pg 66 6oof 122 2

eneratf G3 Guanio Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I TEM: C5.I11 Summary No. Component ID Description System System Description C2.1.182 DH-32A TEE TO PIPE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments I1S PT-07-010 Ac cept 997520 isI UT-07-019 Ac cept 997520 IS' UT-07-020 Ac cept 997520 IS' UT-07-02 1 Aci cept 997520 Summary No. Component ID Description System System Description C2.1.183 DH-44 ELBOW TO VALVE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments SIs PT-05-025 Accept 997520 IS' UT-07-022 Accept 997520 IS' UT-07-023 Accept 997520 IS' UT-07-024 Accept 997520 Summary No. Component ID Description System System Description C2.1 .2079 MU-289A PIPE TO REDUCER WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments

'SI PT-07-035 Accept 893554 Is' UT-07-059 Accept 893554

'SI UT-07-060 Accept 893554

'SI UT-07-061 Accept 893554 Wednesday, February 13, 2008 Pg 67 Page 2 7oof 122

Nuclear G 'Iefaliof Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5. 11 Summary No. Component ID Description Sy~stem System Description C2.1 .43 DH-49 ELBOW TO PIPE WELD DH DECAY HEAT REMOVAL Workscooe Report No. Exam Status Work Order No. Comments ISI UT-07-006 Accept 893354 IS' UT-07-01 2 Accept 893354 Summary No. Component ID Description System System Description C2.1 .485 DH-37A ELBOW TO PIPE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-008 Accept 997520

'SI UT-07-01 4 Accept 994520 Summary No. Component ID Description System System Description C2.1. 513 DH-41A ELBOW TO PIPE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-038 Accept 997520 ISI UT-07-1 37 Accept 997520

'SI UT-07-1 38 Accept 997520 Wednesday, February 13, 2008 Pg Page 68 8oof 122 2

K luear Group Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.I11 Summary No. Comiponent ID Description System System Description C2.1.517 DH-43B ELBOW TO PIPE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-039 Accept 997520 ISI UT-07-168 *Accept 997520 ISI UT-07-169 Accept 997520 ISI UT-07-170 , Accept 997520 ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1009 MU-75C ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-267 Accept ISI UT-05-268 Accept Summary No. Component ID Description System. System Descripti on C2.1.1028 MU-69A REDUCER TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments isI PT-07-032 Accept 997520 ISI UT-07-1 35 Accept 997520 ISI UT-07-1 36 Accept 997520

-Wednesday, February 13, 2008 Pg 699o Page 2 of 122

  • ~r~II~IGroup Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1029 MU-69B ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-020 Accept 997520 ISI UT-07-039 Accept 997520 Summary No. Component ID Description System System Description C2.1.1030 MU-69C PIPE TO TEE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-018 Accept 997520 ISI UT-07-1 33 Accept 997520 ISI UT-07-1 34 Accept 997520 Summary No. Component ID Description System System Description C2.1.1037 MU-99 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscooe Report No. Exam Status Work Order No. Comments ISI PT-07-019 Accept 997520 isI UT-07-040 Accept 997520

'ISI UT-07-041I Accept 997520 Wednesday, February 13, 2008 Pg Page 700oof 122 2

t Nuclear Groull Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I

.ITEM: C5.21 Summary No. . Component ID Description System System Description C2.1.1040 MU-100 PIPE TO VALVE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SIs PT-05-022 Accept Single-Sided Exam due to Valve Configuration ISI UT-05-240 Accept ISI UT-05-241 Accept ISI UT-05-242 Accept Summary No. Component ID Description System System Description C2.1.1057 MU-1 05B PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscooe Report No. Exam Status Work Order No. Comments ISI UT-05-243 Accept ISI UT-05-244 *Accept ISI UT-05-245 Accept Summary No. Component ID Description System System Description C2.1.1058 MU-i1050 ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-246 Accept ISI UT-05-247 Accept ISI UT-05-248 Accept Wednesday, February 13, 2008 Page Pg 71of1221o 2

Kludear Attachment 1 LOG~~ Grup2 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.;

Summary No. Component ID Description System System Description C2.1.1060 MU-1 05F TEE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments IS' PT-07-028 Accept 997520 IS' UT-07-1 14 Accept 997520 IS' UT-07-115 Accept 997520

'SI UT-07-1 16 Accept 997520 Summary No. Component ID Description System System Description C2.1. 1061 MU-1 67 ELBOW TO FLOW ELEMENT WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments IS' PT-07-01 7 Ac cept 997520 ISI UT-07-1 12 Ac cept 997520 IS' UT-07-113 Ac cept 997520' ISI UT-07-294 Ac cept 997520 Summary No. Component ID Description System System Description C2.1.1070 MU-61B ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SIs PT-07-029 Accept 997520 IS' UT-07-1 09 Accept 997520 ISI UT-07-1 10 Accept 997520 ISI UT-07-1 11 Accept 997520 Wednesday, February 13, 2008 Pg 72 Page 2oof 122 2

Gn dsai Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1. 1082 MU-62L ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-024 Accept 997520 ISI UT-07-072 Accept 997520 ISI UT-07-073 Accept 997520 Summary No. Component ID Description System System Description C2.1.1099 MU-63E TEE TO PIPE WELD MU MAKE UP &PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-249 Accept ISI UT-05-250 Accept ISI UT-05-251 Accept Summary No. Component ID Description System System Description C2.1.1119 MU-85-96 PIPE TO ELB3OW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SIs UT-07-042 Accept 997520 ISI UT-07-242 Accept 997520 Wednesday, February 13, 2008 Pg 733oof 122 Page 2

." f,a 0

'If Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1132 MU-85-29 FLOW ELEMENT TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-016 Accept 997520 ISI UT-07-033 Accept 997520 ISI UT-07-034 Accept 997520 ISI UT-07-035 Accept 997520 Summary No. Component ID Description System System Description C2.1.1143 MU-85-41 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No.. Comments ISI UT-05-252 Accept ISI UT-05-253 Accept ISI UT-05-254 Accept Summary No. Component ID Description System System Description C2.1.1144 MU-85-43 ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI .UT-05-255 Accept ISI UT-05-256 Accept ISI UT-05-257 Accept Wednesday, February 13, 2008 Pg 74 Page 4oof 122 2

Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1159 MU-85-1 30 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments IS' PT-07-01 3 Accept 997520 IS' UT-07-265 Accept 997520 SIs UT-07-266 Accept 997520 Is' UT-07-267 Accept 997520 Summary No. Component ID Description System System Description C2. 1.1176 MU-85-64 ELBOW. TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SIs PT-07-030 Accept 997520 is] UT-07-106 Accept 997520 is' UT-07-107 Accept 997520 IS' UT-07-108 Accept 997520 Summary No. Component ID .Description System System Description C2.1.1178 MU-85-66 ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments

'SI PT-07-027 Accept 997520 IS' UT-07-103 Accept 997520 IS' UT-07-1 04 Accept 997520.

is] UT-07-105 Accept 997520 Wednesday, February 13, 2008 Page Pg 75 5oof 122 2

Nucle ar Giouupfo Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1326 MU-140YF VALVE TO VALVE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-05-023 Accept Summary No. Component ID Description System System Description C2.1.1333 MU-140AFF ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-031 Accept 997520 ISI UT-07-1 22 Accept 997520 ISI UT-07-243 Accept 997520 ISI UT-07-244 Accept 997520 Summary No. Component ID Description System System Description C2.1.1367 MU-380 PIPE TO REDUCER WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-264 Accept ISI UT-05-265 Accept ISI UT-05-266 Accept Wednesday, February 13, 2008 Pg 76 Page 6oof 122 2

Attachment 1 Inservice Inspection Report Interval 3, Period 3, RFQI 5 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1385 3496-MU-i19R PIPE TO FLOW ORAFICE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SIs PT-07-009 Accept *997520 IS' UT-07-268 Accept 997520 ISI UT-07-269 Accept 997520 IS' UT-07-270 Accept 997520 Summary No. Component ID Description' System System Description C2.1.1530 DH-122C PIPE TO ELBOW WELD DH DECAY HEAT REMO)VAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-209 Accept ISI UT-05-21 0 Accept Summary No. Component ID Description System System Description C2.1.1531 DH-122B ELBOW TO PIPE WELD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI UT-05-211 Accept ISI UT-05-212 Accept Summary No. Component ID Description System System Description C2.1.1591 MU-i -Wi TEE TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-166 Accept 997520 ISI UT-07-1 67 Accept 997520 Wednesday, February 13, 2008 Pg 77 Page 7o 2 of 122

N cie Attachment 1 0~ - )o Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F7-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1611 MU-8-Wl 7 ELBOW TO PIPE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status- Work Order No. Comments ISI PT-07-045 Accept 997520 ISI UT-07-262 Accept 997520 ISI UT-07-263 Accept 997520 Summary No. Component ID Description System System Description C2.1.1642 MU-i 6-W48 TEE TO TEE WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-011 Accept 997520 ISI UT-07-271 Accept 997520 ISI UT-07-272 Accept 997520 ISI UT-07-273 Accept 997520 ISI UT-07-293 . Accept 997520 Summary No. Component ID Description System System Description C2.1.1672 MU-23-W89 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI UT-07-125 Accept 997520 SI UT-07-126 Accept 997520 Wednesday, February 13, 2008 Pg 788o Page 2 of 122

KNda Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-I ITEM: C5.21 Summary No. Component ID Description System System Description C2.1.1676 MU-85-593 PIPE TO REDUCER WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-036 Accept 893554 ISI UT-07-096 Accept 893554 ISI UT-07-097 Accept 893554 ITEM: C5.30 Summary No. Component ID Description System System Description C2.1 .1377 3496-MU-il1 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SIs PT-07-022 Accept 997520 Summary No. Component ID Description System System Description C2.1.1387 3496-MU-21 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-015 Accept 997520 Summary No. Component ID Description System System Description C2.1.1415 3498-MU-3 PIPE TO ELBOW WELD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI PT-07-026 Accept 997520 Wednesday, February 13, 2008 Pg 79 Page 9oof 122 2

NurIsar Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2.1.118 MS-30D SWEEPOLET TO FLANGE WELD MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-005 Accept 893553 Sweepolet to flange configuration did not allow scans in addition to 45 degree angle to be used.

IS' UT-07-092 Accept 893553 Summary No. Component ID Description System System Description C2.1.119 MS-31 PIPE TO ELBOW WELD MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-011 Accept 893554 is] UT-07-098 Accept 893554 Summary No. Component ID Description System System Description C2. 1.121 MS-278 PIPE TO VALVE WELD MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-003 Accept 893553 ISI UT-07ý1 17 Accept 893553

'SI UT-07-1 18 Accept 893553 SIs UT-07-1 19 Accept 893553 ISI UT-07-1 20 Accept 893553 Wednesday, February 13, 2008 Pg 80 Page 0oof 122 2

cGomeraI~d Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2.1.122 MS-42C SWEEPOLET TO FLANGE WELD MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments SIs MT-07-009 Accept 893553 ISI UT-07-057 Accept 893553

'Is UT-07-058 Accept 893553 Summary No. Component ID Description System System Description C2.1.136 FW-1 28A PIPE TO TEE WELD EW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-015 Accept 893554 ISI UT-07-1 31 Accept 893554 ISI UT-07-1 32 Accept 893554 Summary No. Component ID Description System System Description C2.1.137 FW-23 ELBOW TO PIPE WELD FW FEEDWATER Workscooe Report No. Exam Status Work Order No. Comments ISI MT-07-013 Accept 893554 SI.i UT-07-1 00 Accept 893554 Summary No. Component ID Description System S~ystem Description C2.1.138 FW- 1 26A ELBOW TO PIPE WELD FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-012 Accept 893554 151 UT-07-099 Accept 893554 Wednesday, February 13, 2008 Page Pg 81 1oof 122 2

  • ~I~JI(i6 LOA oup Nuclear 6 eta Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2.1.139 FW-1 25A ELBOW TO PIPE WELD FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-017 Accept 893554 IS' UT-07-129 Accept 893554 IS' UT-07-130 Accept 893554 Summary No. Component ID Description System System Description C2.1.140 FW-18 ELBOW TO PIPE WELD FW FEEDWATER Workscope -Report No. Exam Status Work Order No. Comments

'SI .MT-07-029 Reject 893554 Indication was removed via surface conditioning. Component is free of recordable indications.

IS' MT-07-035 Reject 893554

's] MT-07-036 Reject 893554

's] MT-07-037 Accept 893554 Is' UT-07-233 Accept* 893554

'SI UT-07-234 Accept 893554 IS' UT-07-264 Info 893554 Wednesday, February 13, 2008 Pg 82 Page 2oof 122 2

Nuclear Attachment 1 G

'ouj Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2

- ITEM: C5.51 Summary No. Component ID Description System System Description C2.1.156 FW-48 ELBOW TO PIPE WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-018 Accept 893554 151 UT-07-121 Accept 893554 is[ UT-07-1 84 Accept 893554 Summary No. Component ID Description System System Description C2.1.157 FW-1 41 A PIPE TO ELBOW WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments is] MT-07-034 Accept 893553

'SI UT-07-255 Accept 893553 IS' UT-07-256 Accept 893553 Summary No. Component ID Description System System Description C2.1.158 FW-45AF PIPE TO ELBOW WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments 1SI MT-07-020 Accept 893553 isI UT-07-253 Accept 893553 IS' UT-07-254 Accept 893553 Wednesday, February 13; 2008 Pg 83 Page 3oof 122 2

NbýGroup Attachment 1 0 0*,-i Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2.1.160 FW-61 SF PIPE TO ELBOW WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments SI. MT-07-022 Accept 893553 IS' UT-07-1 77 Accept 893553 Is' UT-07-1 78 Accept 893553 ISI UT-07-1 79 Accept 893553 Summary No. Component ID Description System System Description C2.1.23 FW MK124 TO FW TEE TO PIPE WELD EW FE ED WATER MK121 Workscope Report No. Exam Status Work Order No. Comments SIs MT-0J7-019 Accept 893553

'SI UT-07-1 71 Accept 893553

'SI UT-07-1 72 Accept 893553 ISI UT-07-1 73 Accept 893553 Summary No. Component ID Description System System Description C2.1.290 MS-30F SWEEPOLET TO FLANGE WELD MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-006 Accept 893553 ISI UT-07-093 Accept 893553 Wednesday, February 13, 2008 Pg 84 Page 4oof 122 2

  • ~r~ji~i6 up Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2.1 .360 FW-129D (25A) PIPE TO ELBOW WELD FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments IS! MT-07-014 Accept 893554 ISI UT-07-101 Accept 893554 ISI UT-07-1 02 Accept 893554 Summary No. Component ID Description , System System Description C2.1 .366 FW MK120 TO FW PIPE TO CAP WELD FW FEEDWATER MK127 Workscope Report No. Exam Status Work Order No. Comments ISMT-07-030 Accept 893554 ISI UT-07-235 Accept 893554 ISI UT-07-236 Accept- 893554 Summary No. Component ID Description System System Description C2.1.462 FW-49 ELBOW TO PIPE WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-024 Accept 893354 ISI UT-07-237 Accept 893354 ISI UT-07-238 Accept 893354 Wednesday, February 13, 2008 Page 85 Pg 5oof 122 2

Nuclear Gan afo0 G5pup Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2.1 .475 FW-61 H F REDUCER TO PIPE WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-032 Accept 893553

'SI UT-07-259 Accept 893553 IS' UT-07-260 Accept 893553 is' UT-07-261 Accept 893553 Summary No. Component ID Description System System Description C2.1.7 MS-18 NOZZLE TO ELBOW WELD MS MAIN STEAM Workscope Report No. Exam Status Work Order No. comments ISI MT-07-025 Accept 893554 IS' UT-07-1 74 Accept 893554 SIs UT-07-1 75 Accept 893554 IS' UT-07-1 76 Accept 893554 Summary No. Component ID Description System System Description C2.1.8 MS-283 PIPE TO VALVE WELD MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-007 Accept 893553 ISI UT-07-094 Accept 893553 ISI UT-07-095 Accept 893553 Wednesday, February 13, 2008 Page.

Pg 86 6oof 122 2

LN 3-Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.51 Summary No. Component ID Description System System Description C2. 1.911 FW-85-088 ELBOW TO PIPE WELD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-033 Accept 893553 ISI UT-07-257 Accept 893553 IS' UT-07-258 Accept 893553 Summary No. Component ID Description System System Description C2.1 .921 UNKNOWN PIPE TO TEE WELD EF EMERGENCY FEEDWATER Workscope Report Np. Exam Status Work Order No. Comments ISI MT-07-021 Accept 893553 SIs UT-07-1 80 Accept 893553

'SI UT-07-1 81 Accept 893553 IS' UT-07-1 82 Accept 893553 ITEM: C5.81 Summary No. Component ID Description System System Description C2.3.1 1 MS-42J PIPE TO SWEEPOLET WELD MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-01 0 Accept 893553 ISI UT-07-064 Accept 893553 ISI UT-07-065 Accept 893553 ISI UT-07-1 85 Accept 893553 Wednesday, February 13, 2008 Pg 87 Page 7oof 122 2

Group .Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-F-2 ITEM: C5.81 Summary No. Component ID Description System System Description C2.3.9 MS-17D PIPE TO SWEEPOLET WELD MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI MT-07-004 Accept 893553 CATEGORY: C-H ITEM: C7.GO.CH Summary No. Component ID Description System System Description C7.100.1 RCSG-1A MS FROM RCSG-IA MIS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments isI VT-07-353 Accept 893554 Summary No. Component ID Description System System Description 07.100.12 DHP-1 B ALL DHP-1B COMPONENTS DH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS, Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-038 Accept 858724 Summary No. Component ID Description System System Description C7.100.13 System Pressure Test CLASS 2 REACTOR COOLANT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-365 Accept 8994687 Summary No. Component ID Description System System Description C7.100.16 CET- B ALL CET-i B COMPONENT CF CORE FLOODING PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-129 Eval 893554 Acceptable for use as is.

Wednesday, February 13, 2008 Pg Page 88 8oof 122 2

I~1~IGrout) Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-H ITEM: C7.OO.CH Summary No. Component ID Description System System Description C7.100.18 BSP-1 B ALL BSP-1 B COMPONENTS BS REACTOR BUILDING SPRAY PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-037 Accept 858724 Summary No. Component ID Description System System Description C7.100.2 RCSG-1B MS FROM RCSG-1B MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-354 Accept 893554 Summary No. Component ID Description System System Description C7.100.20 CET-lA CFT-1A COMPONENTS CIF CORE FLOODING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-1126 Eval 893554 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description C7.1 00.21 MUHE-1A ALL SW SUPPLY / RETURN TO LETDOWN SW NUCLEAR SERVICES PRESSURE COOLERS CLOSED CYCLE COOLING RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-344 Accept 893554*

ISI VT-07-375 Accept 893554*

Summary No. Component ID Description System System Description C7.100.23 DHV-5 ALL "A"TRAIN DH TO RB DH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments isI VT-07-123 Accept 893554 Wednesday, February 13, 2008 Pg 899F2 Page of 122

NIL-cear t., raior Group Attachment I L*

Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-H ITEM: C7.00.CH Summary No. Component ID Description System System Description C7.100.24 DHV-6 ALL "B" TRAIN DH TO RB DH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-208 Accept 00899469-01 Summary No. Component ID Description System System Description C7.100.25 DHV-4 ALL DH DROPLINE TO DHP-1A DH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-120 Accept 893554 Summary No. Component ID Description System System Description C7.100.26 DHV-4 ALL DH DROPLINE TO DHP-1B DH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments.

ISI VT-07-121 Accept 893554 Summary No. Component ID Description System System Description C7.100.28 FWV-44 PEN-424 ALL EF TO RCSG-1A EF EMERGENCY FEEDWATER PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-360 Accept 893554 Summary No. Component ID Description System System Description C7.100.29 FWV-43 PEN-109 ALL EF TO RCSG-1 B EF EMERGENCY FEEDWATER PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments SI VT-07-363 Accept 893554 Wednesday, February 13, 2008 Pg 90 Page 0oof 122 2

Nuclear 6 nc at or Attachment 1 Gou"P Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-H ITEM: C7.OO.CH Summary No. Component ID Description System System Description C7.100.3 RCSG-1A FW-TO RCSG-1A FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-355 Accept 893554 Summary No. Component ID Description System System Description C7.100.32 EFV-58 ALL "A" TRAIN EF (EFP-3) TO RCSG-1A EF EMERGENCY FEEDWATER PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-342 Accept, 893553 Summary No. Component ID Description System System Description C7.100.33 EFV-57 ALL "A" TRAIN EF (EFP-3) TO RCSG-1 B EF EMERGENCY FEEDWATER PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments SI VT-07-343 Accept 893553 Summary No. Component ID Description System System Description C7.100.34 PEN-333 CLASS 2 MU INSIDE REACTOR BUILDING MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-366 Accept 899468 Summary No. Component ID Description System System Description C7.100.35 PEN-333 CLASS 2 MU OUTSIDE REACTOR MU MAKE UP & PURIFICATION.

BUILDING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-348 Accept 899468 ISI VT-07-370 Accept .899468 Wednesday, February 13, 2008 Page Pg 91 1oof 122 2

NudIar Gri aou Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-H ITEM: C7.OO.CH Summary No. Component ID Description System System Description C7.100.36 DH-49-FE CLASS 2 DH INSIDE REACTOR BUILDING DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-352 Accept 893554 Summary No. Component ID Description System System Description C7.100.37 DHV-91 ALL DHV-91 TO DHV-93 DH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-122 Accept 893554 Summary No. Component ID Description System System Description C7.100.38 SVWV-37 ALL SW TO AHE-iB SW NUCLEAR SERVICES PRESSURE CLOSED CYCLE COOLING RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-207 Accept 893554 ISI VT-07-350 Accept 893554 Summary No. Component ID Description System System Description C7.100.39 SWV-39 ALL SW TOAHF-1C SW NUCLEAR SERVICES PRESSURE CLOSED CYCLE COOLING RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments isI VT-05-208 Accept 893554 ISI VT-07-351 Accept 893554 Summary No. Component ID Description System System Description C7.100.4 RCSG-1 B FW TO RCSG-1IB FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-361 Accept 893554 Wednesday, February 13, 2008 Page Pg 92 2oof 122 2

GlIsa Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY. C-H ITEM: C7.OO.CH Summary No. Component ID Description System System Description C7.100.40 WDSU-1 RB SUMP TO ISOLATION VALVES OH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments iSi VT-07-125 Accept 893554 Summary No. Component ID Description System System Description C7.100.41 MUV-582 HPI RECIRC TO SUMP MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments SI VT-07-349 Accept 899468 Summary No. Component ID Description System System Description C7.100.5 RCP-1A SW TO RCP-1A SW NUCLEAR SERVICES CLOSED CYCLE COOLINGr Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-341 Accept 893554 / 985664-02 Summary No. Component ID Description System System Description C7.100.6 DRRD-1 ALL SW TO DRRD-1 SW NUCLEAR SERVICES PRESSURE CLOSED CYCLE COOLING RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-347 Accept 893554 / 785454 /

984864 ISI VT-07-376 Accept 893554 / 785454 /

984864 Summary No. Component ID Description System System Description C7.100.7 RCP-1B SW TO RCP-1B SW NUCLEAR SERVICES ICLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-340 Accept 893554 / 695063-02 Wednesday, February 13, 2008 Pg 93 Page 3oof 122 2

Nlda b1Gonea Group 0f Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: C-H ITEM: C7.OO.CH Summary No. Component ID Description System System Description C7.100.8 RCP-1C SW TO ROP-1C. SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-346 Eval 893554 / 985663 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description C7.100.9 RCP-1D SW TO RCP-1 D SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-345 Eval 893554 / 985663- Acceptable for use as is.

02 CATEGORY: F-A ITEM: F1.20A Summary No. Component ID Description System System Description BSH-541 BSH-541 ROD BS REACTOR BUILDING SPRAY' Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-217 Eval 603856-03 Acceptable for use as is per engineering evaluation.

Evaluation .2' gap between base plate and ceiling on one end of plate. AISC ASD 9th edition, section M4.4 page 5-90, permits a Disposition gap allownace for less than 1/4. As per evaluation BSH-5411"is acceptable for use in the 'as is' condition."

Acceptable:

Summary No. Component ID Description System System Description DHH-554 DHH-554 ROD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-214 Accept Summary No. Component ID Description System System Description DHH-558 DHH-558 ROD DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-002 Eval 997520 One bolt does not have proper thread engagement. Acceptable as per calculation S-94-0088.

Wednesday, February 13, 2008 Pg 94 Page 4oof 122 2

Nuclear Go'ca.aof Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: F-A SITEM: FI.20A Summary No. Component ID Description System System Description DHH-588 DHH-588 ROD OH DECAY HEAT REMOVAL Workscope Report Exam Status Work Order No. Comments 151 VT-07-0 Accept 997520 Summary No. Component ID Description System System Description DHR-26 DHR-26 STRUT DH DECAY HEAT REMOVAL Workscope ReportN Jo. Exam Status Work Order No. Comments 151 VT-07-0; 29 Eval 997520 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description DHR-38 DHR-38 RESTRAINT OH DECAY HEAT. REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-013 Eval 997520 In field conditions; no washers present. 1/8" air gap between nut and clamp. Item A is 5 degrees off of horizontal. Conditions are acceptable as per engineering evaluation.

Summary No. Component ID Description System System Description DHR-45 DHR-45 STRUT OH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-215 Accept Summary No. Component ID Description System System Description EFH-120 EFH-120 STRUT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments PSI VT-07-277 Accept 901640-01 Summary No. Ccomponent ID Description System System Description EFH-121 ElFH-121 STRUT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments PSI VT-07-278 Accept 901641-01 Wednesday, February 13, 2008 IPage 95 of 122

Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY. F-A ITEM: FI.20A Summary No. Component ID Description System System Description EFH-127 EFH-1 27 ROD EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments I51 VT-05-211 Accept 893553 Summary No. Component ID Description System System Description MSH-1 61 MSH-161 STRUT MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-040 Accept 888768 PSI VT-07-320 Accept 888768 Summary No. Component ID Description System System Description MSH-242 MSH-242 RESTRAINT IMS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-192 Accept 893554 Summary No. Component ID Description System System Description MSH-247 MSH-247 RESTRAINT IMS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-191 Accept 893554 Summary No. Component ID Description System System Description MSH-28 MSH-28 RESTRAINT MVS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-238 Accept 893553 Wednesday, February 13, 2008 Page Pg 96 6oof 122 2

Attachment 1 16 00 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: F-A ITEM: FI.20A Summary No. Component ID Description System System Description MUH-577 MUH-577 RIGID ROD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-254 Accept Summary No. Component ID Description System System Description MUH-578 MUH-578 RIGID ROD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-218 Accept Summary No. Component ID Description System System Description MUH-61 3 MUH-61 3 RESTRAINT MU MAKE UP & PURIFICATION Workscope Report 1o. Exam Status Work Order No. Comments ISI VT-07-0 17 Eval 997520 Condition is acceptable for use as is as per engineering evaluation.

Summary No. Component ID Description System System Description MUH-637A MUH-637A STRUT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-018 Eval 997520 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description MUH-761 MUH-761 STRUT MU MAKE UP & PURIFICATION Workscope Report Exam Status 'Work Order No. Comments ISI \VT-07-0: Accept 997520 Summary No. Component ID Description System System Description MUH-792 MUH-792 RESTRAINT MU 'MAKE UP & PURIFICATION Workscope ReportN Jo. Exam Status Work Order No. Comments ISI VT-07-0 19 Eval 997520 Acceptable for use as is per engineering evaluation.

Wednesday, February 13, 2008 Pg 97 Page 7oof 122 2

N enati Group0 Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: F-A ITEM: F1.20A Summary No. Component ID Description System System Description MUH-827 MUH-827 STRUT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-256 Accept Summary No. Component ID Description System System Description MUH-828 MUH-828 RIGID ROD MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-220 Accept Summary No. Component ID Description System System Description SWH-269 SWH-269 U-BOLT SW *NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-226 Accept 893554 Summary No. Component ID Description System System Description SWH-277 SWH-277 RIGID ROD SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-195 Accept 893554 Summary No. Component ID Description System System Description SWH-301 SWH-301 RIGID ROD SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscooe Report No. Exam Status Work Order No. Comments ISI VT-07-225 Accept 893554 Summary No. Component ID Description System System Description SWH-383 SWH-383 RESTRAINT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-134 Accept 893554 Wednesday, February 13, 2008 Pg 98 Page 8oof 122 2

6 coup Attachment 1' Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY. F-A ITEM: FI.20A Summary No. Component ID Description System System Description SWR-234 SWH-234 STRUT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-217 Eval 893554 Acceptable for use as is per engineering evaluation.

ITEM: F1.20B Summary No. Component ID Description System System Description DHH-643 DHH-643 GUIDE DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments IS! VT-07-024 Accept 997520 Summary No. Component ID Description System System Description EFH-130 EFH-130 RESTRAINT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments SIs VT-05-213 Accept 893553 Summary No. Component ID Description System System Description MUH-1024 MUH-1024 U-BOLT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-243 Accept Summary No. Component ID Description System System Description MUH-1030 MUH-1 030 U-BOLT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-245 Accept Summary No. Component ID Description System System Description MUH-1032 MU H-1032 RESTRAINT MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comm'ents ISI VT-05-244 .Accept Wednesday, February 13, 2008 Page 99 Pg 9oof 122 2

I L""Icraf0r Iear Attachment I 0G b6" Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY. F-A ITEM: FI.20B Summary No. Component ID Description System System Description MUH-1039 MUH-1039 BOX GUIDE MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-151 Accept 893554 Summary No. Component ID Description System System Description MUH-579 MUH-579 SLIDING GUIDE MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-255 Accept Summary No. Component ID Description System System Description MUH-580 MUH-580 SLIDING GUIDE MU MAKE UP & PURIFICATION Workscope Report to. Exam Status Work Order No. Comments ISI VT-05-2 19 Accept Summary No. Component ID Description System System Description SWH-299 SWH-299 BOX GUIDE SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments isI VT-05-246 Accept 893554 Summary No. )mponent ID Description System System Description SWH-304 IVH-304 BOX GU IDE SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments SI VT-07-194 Accept 893554 ITEM: FI.20C Summary No. Component ID Description System System Description DHH-556A DHH-556A SPRING CAN DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments isI VT-07-005 Accept 997520 Wednesday, February 13, 2008Pae10o12 Page 100 of 122

Attachment 1 Inservice Inspection Report Interval 3, Period 3, RFOI15 CLASS: 2 CATEGORY: F-A ITEM: F1.20C Summary No. Component ID Description System System Description DHH-560 DHH-560 SPRING CAN DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-004 Accept 997520 Summary No. Component ID Description System System Description DHH-592A DHH-592A SPRING CAN DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-012 Accept 997520 Summary No. Component ID Description System System Description DHH-622 DHH-622 SPRING CAN OH DECAY HEAT REM OVAL Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-030 Accept 997520 Summary No. Component ID Description System System Description EFH-1 EFH-1 SPRING CAN EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-216 Accept 893554 Summary No. Component ID Description System System Description FWH-120 FWH-120 CONSTANT FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-152 Accept 888614 PSI VT-07-336 Accept 888614 Wednesday, February 13, 2008Pae11o12 Page 101 of 122

K tisar L OG Attachment I 6ruu` Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 2 CATEGORY: F-A ITEM: F1.20C Summary No. Component ID Description System System Description FWH-133 FWH-1 33 SNUBBER. FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-038 Accept 893554 Summary No. Component ID Description System System Description FWH-147A FWH-147A SNUBBER FW FEEDWATER Workscope Report No. Exam Status Work Order No. Comments isI VE-07-039 Accept 1002989 Summary No. Component ID Description System System Description MSH-148 MSH-148 CONSTANT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-321 Accept 893554 Summary No. Component ID Description System System Description SWH-276 SWH-276 VAR SPRING SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-326 Accept 893554 ITEM: F1.40 Summary No. Component ID Description System System Description DHHE-1B DHHE-1B SUPPORT .DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments isI VT-07-291 Accept 997520 Summary No. Component ID Description System System Description MUFL-3A MUFL-3A ANCHOR MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-135 Accept 997520 Wednesday, February 13, 2008Pae12o12 Page 102 of 122

Nuclea Group~ Attachment 1 Inservice Inspection Report Inter val 3, Period 3, RFOI 5 CLASS: 2 CATEGORY. F-A ITEM: F1.40 Summary No. Component ID Description System System Description MUP-1 A MUP-1A ANCHOR MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Ordeý No. Comments ISI VT-07-0111 Accept 997520 CLASS: 3 CATEGORY: D-A ITEM: D1.10 Summary No. Component ID Description System System Description D1.100.1 RCSG-1A RCSG-1A INSTRUMENTATION MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments is] VT-07-356 Accept 893554 Summary No. Component ID Description System System Description D1.100.14 EFP-1 EFP-1 RECIRC COMPONENTS EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments SI SlVT-07-031 Accept 893553 Summary No. Component ID Description . System System Description D1.100.17 SWP-1A ALL SWP-1A COMPONENTS SW NUCLEAR SERVICES PRESSURE CLOSED CYCLE COOLING RETAINING COMPONENTS Workscope Report t Jo. Exam Status Work Order No. Comments SIs VT-07-0 33 Eval 836710 Acceptable for use as is per engineering evaluation. Water in trench is not from SW system. The water is backflush from a drain in the dry sump.

Summary No. Component ID Description System System Description D1.100.2 RCSG-1 B RCSG-1B3 INSTRUMENTATION MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-362 Accept 893554 Wednesday, February 13, 2008Pae13o12 Page 103 of 122

. (AGrout Nuclear Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: D-A ITEM: D1.10 Summary No. Component ID Description System System Description D1.100.3 EFP-2 AS TO EFP-2 AS AUXILIARY STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-380 Accept 872186-01 Summary No. Component ID Description System System Description D1.100.30 RWP-3B ALL RWP-3B TO DCHE-1 B RW NUCLEAR SERVICE &

PRESSURE DECAY HEAT SEA WATER RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-089 Accept 858725-0 1 Summary No. Component ID Description System System Description D1.100.31 RWP-2B ALL RWP-2B TO RWV-35 RW NUCLEAR SERVICE &

PRESSURE DECAY HEAT SEA WATER RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-040 Accept 849759 Summary No. Component ID Description System System Description D1.100.33 DHV-93 ALL DECAY HEAT TO RCf F-1 OH DECAY HEAT REMOVAL PRESSURE RETAINING COMPONENTS Workscooe Report No. Exam Status Work Order No. Comments ISI VT-07-124 Eval 893554 Acceptable for use as is per engineering evaluation. Valve replaced during REOlS.

Summary No. Component ID Description System System Description D1.100.36 EFP-3 ALL PRESSURE EFP-3 DIESEL JACKET COOLANT DJ DIESEL, JACKET COOLANT RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-025 Accept 816928 Wednesday, February 13, 2008Pae14o12 Page 104 of 122

Nuclea,3 Groupo Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY. D-A ITEM: D1.10 Summary No. Component ID Description System System Description D1 .100.38 EGDG-1B ALL EGDG-1 B JACKET COOLANT DJ DIESEL, JACKET COOLANT PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-006 Accept 819850 Summary No. Component ID Description System System Description D1.100.40 EFV-11 ALL EFP-2 COMPONENTS EF EMERGENCY FEEDWATER PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-378 Accept 872186-01

  • Summary No. Component ID Description System System Description D1. 100.41 EFV-32 ALL EFP-2 COMPONENTS EF EMERGENCY FEEDWATER PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments is[ VT-07-379 Accept 872186-01 Summary No. Component ID Description System System Description D1 .100.42 EFP-3 ALL PRESSURE EFP-3 RECIRC COMPONENTS EF EMERGENCY FEEDWATER RETAINING COMPON ENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-026 Accept 816928 Summary No. Component ID Description System System Description D1 .100.45 PEN-338 MAKE-UP TO REACTOR COOLANT MU MAKE UP & PURIFICATION PUMPS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-368 Accept 899468 Wednesday, February 13, 2008Pae15f12 Page 105 of 122

Nuclear Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: D-A ITEM: D1.10 Summary No. Component ID Description System System Description D1 .100.46 PEN-377 MAKE-UP FROM REACTOR COOLANT MU MAKE UP & PURIFICATION PUMPS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-358 Accept 899468 Summary No. Component ID Description System System Description D1.100.47 RCV-84 CLASS 3 REACTOR COOLANT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-359 Accept 899468 Summary No. Component ID Description System System Description D1.100.8 RCT-1 CLASS 3 REACTOR COOLANT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-357 Accept 899468 ITEM: D1.20 Summary No. Component ID Description System System Description D2.5.20 MSH-21 1 INTEGRAL ATTACHMENT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-322 Accept 893553 Summary No. Component ID Description System System Description D2.5.39 EFH-84 INTEGRAL ATTACHMENT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-149 Accept 893553 Summary No. Component ID Description System System Description D2.5.4 SWH-209 INTEGRAL ATTACHMENT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-028 Accept 997520 Wednesday, February 13,2008Pae16o12 Page 106 of 122

Nucdear in~ tit Gro0 Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: D-A ITEM: DI.20 Summary No. Component ID Description System System Description D2.5.40 EFH-83 INTEGRAL ATTACHMENT. EF EMERGENCY FEEDWAT ER Workscope Report No. Exam Status Work Order No. Comments 151 VT-07-145 Accept 893553 Summary No. Component ID Description System System Description D2.5.5 SWH-37 INTEGRAL ATTACHMENT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscooe Report No. Exam Status Work Order No. Comments ISI VT-07-215 Accept 997520 Summary No. Component ID Description System System Description D2.5.67 RW-27 INTEGRAL ATTACHMENT RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-007 Accept 997520 ITEM: DI.20A Summary No. Component ID Description System System Description D2.5.89 SWT-1 INTEGRAL ATTACHMENT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-016 Accept 997520 ITEM: DI.20B Summary No. Component ID Description System System Description D2.5.93 RWP-3A INTEGRAL ATTACHMENT RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-009 Accept 997520 Wednesday, February 13, 2008Pae17o12 Page 107 of 122

GuupGso Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: D-A ITEM: DI.20B Summary No. Component ID Description System System Description D2.5.94 RWP-2B INTEGRAL ATTACHMENT RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-015 Accept 997520 ITEM: DI.20C Summary No. Component ID Description System System Description D2.5.96 SWP-1A INTEGRAL ATTACHMENT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments SI VT-07-01 0 Eval 997520 Acceptable for use as is per engineering evaluation.

ITEM: DI.20D Summary No. Component ID Description System System Description D2.5.79 SWHE-1A INTEGRAL ATTACHMENT RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-003 Accept 997520 CATEGORY: D-B ITEM: D2.10 Summary No. Component ID Description System System Description D1 .100.18 SWP-1 B ALL SWP-11B COMPONENTS SW NUCLEAR SERVICES PRESSURE CLOSED CYCLE COOLING RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments isI VT-07-039 Accept 849759 Summary No. Component ID Description System System Description D1.100.28 RWP-2A ALL RWP-2A TO RWV-38 RW NUCLEAR SERVICE &

PRESSURE DECAY HEAT SEA WATER RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-034 Accept 836710 Wednesday, February 113, 2008 ,Page 108 of 122

Group Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: D-B ITEM: D2.10 Summary No. Component ID Description System System Description D1.100.29 RWP-3A ALL RWP-3A TO DCHE-11A RW NUCLEAR SERVICE &

PRESSURE DECAY HEAT SEA WATER RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-032 Accept 867053 CATEGORY: D-C ITEM: D3.10 Summary No. Component ID Description System System Description D1.100.5 SFP-1A ALL SEP-1A COMPONENTS SF SPENT FUEL COOLING PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-035 Accept 839971 Summary No. Component ID Description System System Description D1 .100.50 SFV-53 SF TO SF POOLS SF SPENT FUEL COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-036 Accept 839971 Summary No. Component ID Description System System Description D1 .100.6 SFP-1 B ALL SFP-1 B COMPONENTS SF SPENT FUEL COOLING PRESSURE RETAINING COMPONENTS Workscope Report No. Exam Status. Work Order No. Comments ISI VT-07-377 Accept 893554 Wednesday, February 13, 2008Pge19o12 Page 109 of 122

N le Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: F-A ITEM: FI.30A Summary No. Component ID Description System System Description DCR-41 DCR-41 STRUT DC DECAY HEAT CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-258 Accept Summary No. Component ID Description Systemn System Description DCR-42 DCR-42 STRUT DC DECAY HEAT CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-216 Accept Summary No. Component ID Description System System Description DHR-55 DHR-55 STRUT DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-094 Accept 997520 Summary No. Component ID Description System System Description DHR-60 DHR-60 RESTRAINT DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-093 Accept 997520 Summary No. Component ID Description System System Description MSH-208 MSH-208 STRUT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments PSI VT-07-219 Accept 1000479-06 Summary No. Cc)mponent ID Description System System Description MSH-249 SH-249 STRUT MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments PSI VT-07-231 Accept 1000480-01 Wednesday, February 13, 2008Pae10o12 Page 110 of 122

Group Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY. F-A ITEM: FI.30A Summary No. Component ID Description System System Description RWH-1 26 RWH-1 26 STRUT RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments

'SI VT-07-338 Accept 893554 Summary No. Component ID Description System System Description RWH-13 RWH-13 ROD RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-223 Accept Summary No. Component ID Description System System Description RWH-24B RWH-24B ROD RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments SIs VT-05-224 Accept Summary No. Component ID Description System System Description RWH-63 RWH-63 RESTRAINT RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments isI VT-05-225 Accept Summary No. Component ID Description System System Description SWH-1 0 SWH-10 ROD SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-096 Accept 997520 Summary No. Component ID Description System System Description SWH-22 SWH-22 RESTRAINT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-001 Reject 771829 Acceptable for use as per AR 219138. To be repaired via EC66369.

Wednesday, February 13, 2008Pae Page 111of122 11o12

Gfiup Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: F-A ITEM: FI.30A Summary No. Component ID Description System System Description SWR-31 SWR-31 STRUT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments tSI VfT-07-091 Accept 997520 Summary No. Component ID Description System System Description SWR-82 SWR-82 STRUT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-021 Accept 997520 Summary No. Ccmponent ID Description System System Description SWR-9 SVVR-9 STRUT SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscooe Report No. Exam Status Work Order No. Comments ISI VT-05-242 Accept ITEM: FI.30B Summary No. Component ID Description System System Description DHH-626A DHH-626A RESTRAINT DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-090 Eval 997520 Acceptable for use as is per engineering evaluation.

Summary No. Component ID Description System System Description EFH-525 EFH-525 RESTRAINT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-240 Accept 893553 Summary No. Component ID Description System System Description EFH-593 EFH-593 RESTRAINT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-213 Accept 893553 Wednesday, February 13, 2008Pae 12o12 Page 112 of 122

Nroup Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: F-A ITEM: -FI.30B Summary No. Component ID Description System System Description EFH-595 EFH-595 RESTRAINT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-212 Eval 893553 - Acceptable for use as is per engineering evaluation.

Summary No. Coimponent ID Description System System Description EFH-597 EFH-597 RESTRAINT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-214 Accept 893553 Summary No. Component ID Description System System Description EFH-78 EFH-78 ANCHOR EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-241 Accept 893553 Summary No. Ccimponent ID Description System System Description' EFH-83 EFH-83 RESTRAINT EF EMERGENCY FEEDWATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-239 Accept 893553 Summary No. Component ID Description System System Description MSH-1 82 MSH-1 82 ANCHOR Ms. MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments PSI VT-07-303 .Eval 01 000485-1 Acceptable for use as is per engineering evaluation.

Summary No. Ccmponent ID Description System System Description RW-27 RtV-27 ANCHOR RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-221 Accept Wednesday, February 13, 2008Pae13o12 Page 113 of 122

Nuclear Gioicrafor Attachment 1 Group Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: F-A ITEM: F1.30B Summary No. Component ID Description System System Description RW-50 RW-50 ANCHOR RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-222 Accept Summary No. Component ID Description System System Description SWH-209 SWH-209 ANCHOR SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments SIs VT-07-027 Accept 997520 Summary No. Ccomponent ID Description System System Description SWH-560 NH-560 ANCHOR SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-228 Accept ITEM: FI.30C Summary No. Component ID Description System System Description DHH-61 5 DHH-615 SPRING CAN DH DECAY HEAT REMOVAL Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-095 Accept 997520 Summary No. Component ID . Description .System- System Description MSH-211 MSH-211 SNUBBER MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments ISI VE-07-044 Accept 893553 Summary No. Component ID Description System System Description MSH-248 MSH-248 SNUBBER MS MAIN STEAM Workscope Report No. Exam Status Work Order No. Comments isI VE-07-041 Accept 893553 Page 114 of 122 February 13, Wednesday, February Wednesday, 2008 13, 2008 Page 114 of 122

Nuclmr LN~t 3,;Goup Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: F-A ITEM: F1.30C Summary No. Component ID Description System System Description SWH-1 82 SWH-1 82 SPRING CAN SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI I VT-07-020 Accept 997520 ITEM: F1.40 Summary No. Component ID Description System System Description MUHE-2A MUHE-2A ANCHOR MU MAKE UP & PURIFICATION Workscope Report No. Exam Status Work Order No. Comments ISI. VT-07-092 Accept 997520 Summary No. Component ID Description System -System Description RWP-2B3 RWP-28 ANCHOR RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments SIs VT-05-226 Accept Summary No. Component ID Description System System Description RWP-3A RWP-3A ANCHOR RW NUCLEAR SERVICE &

DECAY HEAT SEA WATER Workscope Report No. Exam Status Work Order No. Comments 1St VT-05-227 Accept Summary No. Component ID Description System System Description SFH-1 SFE-1A NCORSF SPENT FUEL COOLING Workscope Report No. Exam Status Work Order No. Comments ISt VT-07-008 Accept 997520 Summary No. Component ID Description System System Description SWHE-1A SWHE-1A ANCHOR SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments 151 VT-05-229 Accept Wednesday, February 13, 2008 Page 115 of 122

Gnuraio Attachment 1

(.ruup Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: 3 CATEGORY: F-A ITEM: F1.40 Summary No. Component ID Description System System Description SWHE-1 C SWHE-1C ANCHOR SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-07-023 Accept 997520 Component consists of both front and rear supports.

Summary No. Component ID Description System System Description SWP-1 B(N) SWP-1B(N) ANCHOR SW. NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments isI VT-05-230 Accept Summary No. Component ID Description System System Description SWP-1 B(S) SWP-1 B(S) ANCHOR SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-231 Accept Summary No. Component ID Description System System Description SWT-1 SwT-1 ANCHOR SW NUCLEAR SERVICES CLOSED CYCLE COOLING Workscope Report No. Exam Status Work Order No. Comments ISI VT-05-232 Accept CLASS: 4 CATEGORY: F-A ITEM: FI.30A Summary No. Component ID Description System System Description RCH-32 RCH-32 STRUT RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments ISI V--3 Accept 893554 Wednesday, February 13, 2008Pae16o12 Page 116 of 122

Gr oup' Attachment 1 Inservice Inspection Report Interval 3, Pe6riod 3, RF015 CLASS: AUG CATEGORY. AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description X007 MK #45 PRESSURIZER SPRAY NOZZLE SAFE- RC REACTOR COOLANT END (MK # 45)

Workscope Report 40. Exam Status Work Order No. Comments AUG VT-07-1 85 Accept 893554 Summary No. Component ID Description System System Description X008 MK #46 PRESSURIZER SPRAY NOZZLE PIN RC REACTOR COOLANT (INTERNAL)

Workscope Report No. Exam Status Work Order No. Comme'nts AUG VT-07-157 Accept 893554 Summary No. Component ID Description System System Description X009 MK # 78 RCT-1 VENT PRESSURIZER VENT NOZZLE RC .REACTOR COOLANT NOZZLE Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-1 58 Accept 893554 Summary No. Component ID Description System System Description X010A MK #2 A - HOT LEG VENT NOZZLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-335 Accept 893554 Summary No. Component ID Description System System Description X01013 MK #2 B - HOT LEG VENT NOZZLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-205 Accept 893554 Summary No. Component ID Description System System Description X01 1A MK #8 A - HOT LEG PRESSURE TAP NOZZLE (2) RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-240 Accept 893554 Wednesday, February 13, 2008Pae17o12 Page 117 of 122

.G 1, 'ii.

11881 Gro~up Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: AUG CATEGORY. AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description X011B MK #8 B - HOT LEG PRESSURE TAP NOZZLE (2) RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-327 Accept 893554 Summary No. Component ID Description System System Description X012A MK #10 A - HOT LEG HL TEMPERATURE RC REACTOR COOLANT CONNECTION Workscooe Report qo. Exam Status Work Order No. Comments AUG VT-07-2 20 Accept 893554 Summary No. Component ID Description System System Description X012B MK #10 B - HOT LEG HL TEMPERATURE RC REACTOR COOLANT CONNECTION Workscop~e Report No. Exam Status Work Order No. Comments AUG \/T-07-328 Accept 893554 Summary No. Component ID Description System System Description X013A MK # 12 'A - HOT LEG RTE MOUNTING BOSS (2) RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No.. Comments AUG VT-07-221 Accept 893554 Summary No. Component ID Description System System Description X013B MK #12 B - HOT LEG RTE MOUNTING BOSS (2) RC REACTOR COOLANT Workscooe Report No. Exam Status Work Order No. Comments AUG \/T-07-329 Accept 893554 Wednesday, February 13, 2008Pae18o12 Page 118 of 122

Grout] Attachment 1 Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: AUG CATEGORY: AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description X014A MK # 17 A - HOT LEG FLOW METER NOZZLE (2) RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG PT-07-048 Accept 893554 Acceptable for use as is per engineering evaluation, AUG VT-07-337 Eval 893554 Summary No. Component ID Description System System Description X014B MK #17 B - HOT LEG FLOW METER NOZZLE (2) RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-330 Accept 893554 Summary No. Component ID Description System Systemn Description X015A MIK # 64 B1 COLD LEG DRAIN NOZZLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-206 Accept 893554 Summary No. Component ID Description System System Description X015B MK #64 All COLD LEG DRAIN NOZZLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-334 Accept 893554 Summary No. Component ID Description System System Description X015C MK #64 A2 COLD LEG DRAIN NOZZLE RC. REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-316 Accept 893554 Wednesday, February 13, 2008Pae19o12 Page 119 of 122

Groutl Attachment I Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: AUG CATEGORY: AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description X016 MK #88 B2 LETDOWN SAFE END RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-204 Accept 893554 Summary No. Component ID Description .System System Description X017 RCRE-l REACTOR VESSEL HEAD RC REACTOR COOLANT PENETRATIONS (69)

Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-163 Accept 893554 Summary No. Component ID Description System System Description X018A MK #58 B31LCL RTE MOUNTING BOSS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-243 Accept 893554 Summary No. Component ID Description System System Description X018B MK #58 B2 LCL RTE MOUNTING BOSS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-295 Accept 893554 Summary No. Component ID Description System. System Description X018C MK #58 Al LCL RTE MOUNTING BOSS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-297 Accept 893554 Summary No. Component ID Description System System Description X018D MK #58 A2 LCL RTE MOUNTING BOSS RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-315 Accept 893554 Wednesday, February 13, 2008Pae10o12 Page 120 of 122

Nuciear 6 nerafo! Attachment I 6 OUP Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: AUG CATEGORY: AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description X019A MK# 41 Al PRESSURE TAP NOZZLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-296 Accept 893554 Summary No. Component ID Description .System System Description X019B MK #41 Al COLD LEG RETURN PRESSURE TAP RC REACTOR COOLANT NOZZLE Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-281' Accept 893554 Summary No. Component ID Description System System Description X019C MK #41 A2 COLD LEG RETURN PRESSURE TAP RC REACTOR COOLANT NOZZLE Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-280 Accept 893554 Summary No. Component ID Description System System Description X019D MK #41 A2 COLD LEG PRESSURE TAP NOZZLE RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-314 Accept 893554 Summary No. Component ID Description System System Description X020A MK# 11 Al LCL TEMPERATURE CONNECTION RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-298 Accept 893554 Summary No. Component ID Description System System Description X020B MK#11 B2 LCL TEMPERATURE CONNECTION RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-294 Accept 893554 Wednesday, February 13, 2008Pae11o12 Page 121 of 122

Nula Geme afot Attachment I (2rout Inservice Inspection Report Interval 3, Period 3, RF015 CLASS: AUG CATEGORY: AUG ITEM: AUG7.5 Summary No. Component ID Description System System Description X020C MK#11 A2 LCL TEMPERATURE CONNECTION RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-313 Accept 893554 Summary No. Component ID Description System System Description X020D MK #11 131LCL TEMPERATURE CONNECTION RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-241 Accept 893554 Summary No. . Component ID Description System System Description X021A MK# 22 RCSG-1A PRIMARY DRAIN RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-159 Accept 893554 Summary No. Component ID Description System System Description X021 B MK #22 RCSG-1B PRIMARY DRAIN RC REACTOR COOLANT Workscope Report No. Exam Status Work Order No. Comments AUG \/T-07-160 Accept 893554 Summary No. Component ID Description System System Description X026 RCT-1 RCT-1 STEAM SPACE 1-600 PIPING RC REACTOR COOLANT CONNECTIONS Workscope Report No. Exam Status Work Order No. Comments AUG VT-07-207 Accept 893554 Wednesday, February 13, 2008Pge12o12 Page 122 of 122

PROGRESS ENERGY FLORIDA, INC.

CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302/LICENSE NUMBER DPR-72 ATTACHMENT 2 ASME, SECTION XI, NIS-2 OWNER'S REPORTS OF REPAIR OR REPLACEMENT FOR ASME CLASS 1 AND CLASS 2 COMPONENTS (112 Pages)

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI 1.- Owner Progress Energy Florida, Inc. Date 12/18/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address

2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 796747 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant
  • 5. (a) Applicable Construction Code B31 .1 19 67 Edition, No Addenda, No -Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 .89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Valve Disc Dresser ADJ-47 n/a VI s/n BU031,48 n/a Replaced No-Valve Disc Dresser ADP-89 n/a VI s/n BU03149 n/a Replacement No Vive Nozzle Dresser AAE-19 n/a VI s/n BU03148 n/a Replaced No VIve Nozzle Dresser ADI-24 n/a VI s/n BU03149 n/a Replacement No Bolts n/a n/a n/a n/a n/a Replaced No Hex Screws n/a n/a n/a HT 64983 n/a Replacement No Nuts n/a n/a n/a n/a n/a Replaced No Nuts n/a n/a n/a HT 223422 n/a Replacement No

7. Description of Work Relief Valves RCV-9 rotated from stock and bolting replaced.
8. Tests Conducted: Hydrostatic LI] Pneumatic E] Nominal Operating Pressure El Other El Pressure 2150 psi Test Temp. 528 o NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 796747 Applicable Manufacturer's Data Reports to be attached.

See EC 65877 for cap screws' reconciliation.

ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A .Expiration Date N/A:

Signed *'*1 ŽJ Z ISI Engiineer Date 'o2O7j

,,'e'wpn-ror Owner's' Designee, Title' CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and.

employed by THE HARTFORD STEAM BOILER I & I COMPANY of

- HARTFORD, CT. have inspected the components described in this Owner's Report during the period R6-g 6 -0)? to /-ý -/9-) ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corretv measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, Commissions _AA /Z2HI A AJZ Inspector's Signature el National Board, State, Province, and Endorsements Date________Q20 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 12/17/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3

.Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 796748 Address Repair Organization, P.O. No., Job N. etc.

3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FIL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant

.5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, No Addenda, No Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No

6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes

-Component: ;...Manufacturer,......1 Serial No... No.. Identification 'Built or.Replacement -rN Valve Disc Dresser ADJ-47 n/a. Vlv s/n BL8.900 n/a ,Replaced No Valve Disc-Dese ADP-89 n/a VIv s/n BL8899 n/a Replacement No Bolts n/a n/a n/a n/a n/a Replaced No Hex Screws n/a n/a n/a HT 64983 n/a Replacement No Nuts n/a n/a n/a n/a n/a Replaced No N uts n/a n/a n/a HIT 223422 n/a Replacement No

7. Description of Work Relief Valves RCV-8 rotated from stock and bolting replaced.
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure Other El Pressure 2150 psi Test Temp. 528 O NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 796748 Applicable Manufacturer's Data Reports to be attached.

See EC 65877 for cap screws' reconciliation.

ASME Section Xl Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___Expiration Date N/A Signed ISI Engineer Date 20~Z

/r ' '`Owrt-er or Owner%~ Designee, Title (

CERTIFICATE OF INSERVICE INSPECTION

.1,the undersigned,, holding. a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the

.State-or Province of-: .. ý-ýFLORIDA . -- -- n employed by THE HPARTFORD STEAM BOILER I & I COMPANY of.

HARTFORD..CT. have inspected the components described, in thisOwner's Report during the period I IYA -0O) tofýeo-t3) ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any-manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspectionn.,

__________________ Commissions FIL i9 Inspector's Signat National Board, State, Province, and Endorsements Date ___ __20 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 12113/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 785441 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name -

15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A

4. Identification of System Reactor Coolant
5. .(a) Applicable Construction Code USAS B31 .7 19 'ý68 Editipn, -No Addenda, No Code Cate (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 8 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components
  • *. ASME Code National Repaired, .Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Com pone nt Manufacturer Serial No. No. Identification Built or Replacement or No)

RCV 10 0 Dresser....../ n/a. ~n/a n/d' Replaced* No main Disc RCV-1 0 Dresser ACG43/49883 n/a n/a n/a Replacement No Main Disc Flange stud n/a n/a n/a n/a n/a Replaced No Flange stud n/a n/a n/a n/a n/a Replacement No

7. Description of Work Rotated RCV-1 0 and RCV-1 1 from stock. RCV-1 0 disc replaced by Wyle Lab using PE part.
8. Tests Conducted: Hydrostatic Li Pneumatic E] Nominal Operating Pressure 0 Other E] Pressure 2150 psi Test Temp. 528 o NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 785441 Applicable Manufacturer's Data Reports to be attached.

ASME Section Xl Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Date

'___Expiration N/A Signed ISI Engineer Date 20 D2

/""ýQrw-orOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued b~y the National Board of Boiler and Pressure Vessel Inspectors and the

,State..or Province of FLORIDA.. and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, ýT. have inspected the components described in this Owner's Report during the period IR1 to)2.Jj3A&7L, and state that to the best of my knowledge'and belief, the Owner has performed examinations anten corrective mea64s described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, ,

CIKP46tiftgnature omsin National Soad 8tate, Province, and Endorsements Date U~- L-3 20b.

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/18/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888598 Address Repair Organization', P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Core Flood (CF)
5. (a) Applicable Construction Code ANSI B31." 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board ~ Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

CFH-16 Power Piping 720104 N/A N/A N/A Replaced No CFH-1 6 Lisega 30600572/006 1N/A N/A N/A IReplacement No

7. ecito fWr Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber per EC#

ofWork Desciptin 64157.

8. Tests Conducted: Hydrostatic El Pneumatic Li Nominal Operating Pressure E]

Other El Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QIA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888598 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorizaliao No. IN -___Expiration Date N/A Signed_ 64 c z ISI Engineer Date Ala L,, / 7 206; OwnerW~Owner's Designee, T1ie CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. ,Fhave inspected the components described in this Owner's Report during the period I /Ca to lL!1IJ/0L., and state that to the best of my knowledge and belief, the Owner has performed examinations and lak6 n corrective mebsufes described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be kiable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inseci,7 W/ k -Commissions FL 124 N, B, A, I

' In p&c r's Signature National Board, State, Province, and Endorsements Date Nb q _20V 72 Note: Note:

Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI 1.- Owner Progress Energy Florida, Inc. Date 11 1, / -

Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address

2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888603 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat (DH)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

DHH-38 Power Piping 720130 N/A N/A N/A Replaced No DHH-38 Lisega. 3070257/020 N/A N/A N/A Replacement No

7. of ork Dscritio Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber, per EC#
7. Dscritio of ork 64157.
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure [:]

Other El Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12182)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888603 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed iL~.-/SI I Enciineer Date Amy,.. /W ,06 Owner or Ownier's Designee, Titl~i CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. have inspected the components described in this Owner's Report during the period 11147to LIIIN 167, and state that to the best of my knowledge and belief, the Owner has performed examinations ana t~ken corrective meadsuees described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this

/I' Ilsk ~) ____ Commissions FL 124 N, B, A.I F/ l~srg~o-rs Signature National Board, State, Province, and Endorsements Date NO t 2007 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2.

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/20/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 888752 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, F'L 34428. Authorization No. N/A Address Expiration Date N/A
4. Identification of System Make Up (MU)
5. (a) Applicable Construction Code ANSI B31.; 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section X1 Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MUH-32 Power Piping 750140 N/A N/A N/A Replaced N/A MUH-32 Lisega 30700257/009 N/A N/A N/A Replacement N/A

.7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167

8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure LI 0

Other E] Pressure psi. Test Temp. F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888752 / EC# 64167 ASME Section Xl Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ~L 61,=Z- / 181 Engilneer Date 7,7 kjo~ 2y, 2067 Owiner or Owner sesg-, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. have inspected the components described in this Owner's Report during the period to//, i~, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measi res described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions FL 124 N. B. A. I lnspectbr~s Signature National Board, State, Province, and Endorsements Date 40Vk22L 20n,-

Note: Note:

Upon completion of the document, it is a completed GA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/23/2007 Name P.O.-Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888821 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name .

15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A

4. Identification of System Make Up (MU)
5. (a) Applicable Construction Code ANSI B31:* 19 67 Edition, N/A Addenda, N/A Code Case

.(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None

6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MUH-37 Power Piping 730141' N/A (Snubber) N/A Replaced N/A MUH-37 Lisega N/A N/A (Strut) N/A Replacement N/A dýJio Aj'rqj

7. Description of Work Replace Power Piping SInubber with a new Lisega Strut per Cr 7
8. Tests Conducted: Hydrostatic E] Pneumatic L] Nominal Operating Pressure LI Other El Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888821 / EC# 65795 ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _ 0 ý Q::==4 ISI Engineer Date /A10-y 2 T,200 Owner or Owner's Desigvlee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Repot duing he-prio - t/~ L and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective me~sti res described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be Ii ble in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspectio

_________________________________Commissions FL 124 N, B, A, I sp tor' 'Signature National Board, State, Province, and Endorsements Date NOkV Z4, 20 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001 .

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/11/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FIL 34428 W.0. # 888822 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Make Up (MU)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MUH-82 Power Piping 740007 N/A N/A N/A Replaced N/A MUH-82 Lisega 30700296/001 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure El Other El Pressure psi Test Temp. o NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8'/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12182)

Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888822 / EC# 64167 ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp. N/A Certificate of Authorization No. N/A  := -Expiration Date N/A Sigined (Z ,,r OwiRUi or Owner's Designee, Title

)L -- = / ISI Engineer ,Date Al 3 , )7e , 20-7.

IA CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT have inspected the components described in this Owner's Report during the period f 11117 to /W,67 ,.and state that to the best of my knowledge and belief, the Owner has performed examinations and tAkdn corrective me~suires described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspectiop_

_______________________________Commissions FL 124 N, B, A, I eor's Signature National Board, State, Province, and Endorsements Date N~1 .2OjD7 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/13/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FIL 34428 W.0. # 888820 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant (RC)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

RCH-530 ITT Grinnell 26342 N/A N/A N/A Replaced N/A RH30 Lisega 30700257/016 N/A N/A N/A Replacement N/A

7. Description of Work Replace ITT Grinnell Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure El Other E] Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001 .

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888820 / EC# 64167 ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 6 i ._Li.79 ISI Engineer -Date /oi 0, 19 , 20 6 Ow6ie or Owner's Designed, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, XgT. have inspected the components described in this Owner's Report during the period ULIfJ2. ....... tojj~ and state that to the best of my knowledge and belief, the Owner has performed examinations anb tdken corrective mesr dscribed in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manaear any personal injury or property damage or a loss of any kind arising from or connected with this ipC o m m is s o nmssos FL 124 N, B, A. I I1n e tloirs -Signature National Board, State, Province, and Endorsements Date ~~L .20" Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 11/13/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FIL 34428 W.0. # 888628 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant (RC)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

RCH-531 ITT Grinnell 25594 N/A N/A N/A Replaced N/A RCH-531 Lisega 30700257/023 N/A N/A N/A Replacement N/A

7. Description of Work Replace ITT Grinnell Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure El Other E] Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888628 / EC# 64167 ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 6 , ) i - ISI Engineer- Date &)Lbt,. 1 20 0"7~z Own-bror Owner's Designel~, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. ýT. have inspected the components described in this Owner's Report during the period ill167 too 1A , and state that to the best of my knowledge and belief, the Owner has performed examinations anak~en corrective meabdres described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall *e iaý in any m r for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions FL 124 N. B, A. I

/ "'-inspeq ors Signature National Board, State, Province, and Endorsements Date ___VI__S7 20(2-Note: Note:

Upon completion of the document, it is a completed.OA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/6/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0.# 888631 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant (RC)
5. (a) Applicable Construction Code ANSI B-31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

RCH-80 Power Piping 750106 N/A N/A N/A Repiaced N/A RCH-80 Lisega 30700257/02 1 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure El Other El Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888631 / EC# 64167 ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 1 0- ISI Enciineer Date 4/00:I. 7 ,20 07 Owne'l-6r Owner's Designee, T/fe CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period_ 10t i, toI 117to 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall 4e liable in a y manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspect

___ ___ ___ ___ ___ __Commissions FIL 124 N. B, A, I

'npeorsSignature National Board, State, Province, and Endorsements DateN 1 7 2007~

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/29/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888632 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant (RC)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

RCH-81 Power Piping 750132 N/A N/A N/A Replaced N/A RCH-81 Lisega 30700257/022 1N/A N/A N/A IReplacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E) Pneumatic E] Nominal Operating Pressure EL Other E] Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8'/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888632 / EC# 64167 ASME Section XI Class 1.

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A .__ Expiration Date N/A Sionnt- *2 7.4-1Q ISI Engineer -Date  ;:, . 1 ,2068~

Owner or Owner's Def gnee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period ii' Z-V -a' to It 1tý , and state that to the best of my knowledge and belief,'the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, k-1%Y 7A'Xý -: Commissions J 2S 4&i Inspector's SEi-gnature National Board, State, Province, and Endorsements Date -2O0_LV Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI 1.- Owner Progress Energy Florida, Inc. Date 12/7/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address

2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 801715 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Makeup and Purification
5. ,(a) Applicable Construction Code ANSI B31.: 19 67 Edition, No Addenda, No Code.Case (b) Applicable. Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes.

Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Flange n/a - n/a n/a n/a n/a. Replaced No>-

Studs Flange n/a n/a n/a HT 8991340 n/a Replacement No Studs Flange n/a n/a n/a n/a n/a. Replaced No Nuts Flange n/a n/a n/a HT 7201928 n/a Replacement No Nuts

7. Description of Work Replaced flange bolting materials on MUHE-iC.
8. Tests Conducted: Hydrostatic E] Pneumatic L] Nominal Operating Pressure 0 Other E] 0 Pressure psi Test Temp. F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 801715 ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization. No. N/A ___Expiration Date N/A Signed -- I ;F ISI Enqineer Date ~ ' ,20 07

./ -*' Ipri or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of .FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT.. have inspected the components described in this Owner's Report during the period /1/AA toD 191Wand state that to the best of my knowledge and belief, the Owner has performed examinations and talken corrective meaE-u~e-sdescribed in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be I any m)nner for any personal injury or property damage or a loss of any kind arising from or connected with this inspectio i / /t Commissions FL 124 N, B, A, I rpr Si a-ture National Board, State, Province, and Endorsements Dateb~ 1- -20o7 Note: Upon completion of the document, it is a completed CIA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 3 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 1/1 7/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 3 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0.#894115 Address Repair Organization, P.O. No., Job N.etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant (Letdown Line)
5. ;-(a) Applicable Construction Code ANSI 831:, 19ý 67- Edition, No Addenda, -No' Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacemfents' 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components
  • ASME Code National Repaired, Stamped Name of Name of Manufacturer Board *Other Year Replaced, * (Yes Component
  • Manufacturer Serial No. No. .Identification Built or Replacement or No)

Pipe and *n/a . n/a n/a . n/a.., n/a Replaced * .No Fittings ________

Hanger n/a n/a n/a n/a n/a Replaced No RCH-637 RCV-46 & n/a n/a n/a n/a n/a Replaced No RCV-47 Pipe, valves See attached table for list of replacement parts. n/a Replacement No hanger I

7. Description of Work Replaced 2-1/2" and 1-1/2" piping and fittings, valves RCV-46 & RCV-47, and hanger RCH-637.
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure ED Other [] Pressure psi Test Temp. ______

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 3 FORM NIS-2 (Back)

9. Remarks WO# 894115 Code Case N416-2 invoked ASME Section Xl Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME"Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A - Expirationý Date N/A ISI Eniin eerIr DatI e .2 , 2O-3 .20.0

,o' Ovdier orOwn-er'sDesignee,11tle CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and~the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY ... of HARTFORD. CT. have inspected the components described in this Owner's Report during the period 10-, 'A- '"'Y to I- Oand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,-

__________________ Commissions FL 1:ý tZ1f

/ Inspector's Si 6ture National Board, State, Province, and Endorsements Date Z,:? 200'?

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 3 of 3 1 Owner Progress Energy Florida, Inc. Date 1/17/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 3 of 3 Address

2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 894115 Address Repair Organization, P.O. No., Job N.. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Reactor Coolant (Letdown Line)
5. (a) Applicable Construction Code ANSI B31.* 19 67 Edition, No Addenda, No Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Replacement Components Heat /Lot Catalog ID 7 Q Description PO Serial No.

1592012 1 PIPE, SEAMLESS, 1-1/2 NIPS, SCH 160 TP316 311862 507577 9220149558 - 1 VALVE, GLOBE, 1-1/2 IN, BW,SCH 160 311167 S/N 71175-2 RCV-46 9220149558 1 VALVE, GLOBE, 1-1/2 IN, BW,SCH 160 311167 S/N 71175-1 RCV-47 9220151171 1 ELBOW, PIPE, 1-1/2 NIPS IN, WP316 SCH 160 308874 MN1GU-1 9220151174 1 TEE, PIPE, 1-1/2 X 1 IN, WP316 SCH 160 308874 LZRZ2 9220151177 1 ANGLE, STAINLESS, STRUCTURAL 308874 OK5L RCH-637 9220151179 1 PLATE, STRUCTURAL, 1/8" THIC 308874 25F9 RCH-637 9220151181 1 TUBING, STRUCTURAL, S30400, 2" X2"X 1 /" 308874' '604592 RCH-637 9220151182 1 BAR, FLAT, 4" X 3/4", ASTM A 308874 429570 RCH-637 9220151183 1 BAR, FLAT, 1" X 1/4", ASTM A 308874 548234 RCH-637.

9220156304 1 PIPING, SUBASSEMBLY, MAKE-UP SK-M006 324082*

9220156353 1 PIPING, SUBASSEMBLY, MAKE-UP SK-M007 324082 *

__________ 2-1/2 TEE HT# QC524/MGZB-1 ___ _________

2-1/2 REDUCER HT# QC524/MGZB-1____

2-1/2 90 DEG ELBOW HT# QE174/NUFX ___

1-1/2 90 DEG ELBOW HT# L44882/MNGU-1 ___

1-1/2 PIPE HT# 507577 3/32 TIG WIRE HT# 234108

    • **Heat Numbers for M007 Spool Piece

_________ ______2-1/2 PIPE HT#37982

________ _____2-1/2 90 DEG ELBOW HT#QC524/MGZB-1 ___ _________

________ _____3/32 TIG WIRE HT#234108 ___ _________

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 1/24/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 1000474-08, -09, -10 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
I4.
;. Identification of System Reactor Coolant - Surge Line Nozzles on Hot Leg and Pressurizer:.,- , , ,;

.(a).Applicable.Construction Code USAS B31.7 .19. 68, Edition, June 1968 ,Errata,ý. No. CodeCase

()Applic~ableý Edition: of.Section XI Utilized for Repairs or Replacements -19 89 ,:Addenda. No.,

-6. l.dentifidation 'of Compone66nts Repaired or Replaced and Replacement Componenits Code" National,. Repaired, Stamped Name of Name of Manufacturer Board *' Other Year Replaced, '(Yes Component' Manufacturer Serial No. No. Identification Built or Replacement .or No)

Pressurizer Babcock & 620-0007m-59'ý /a Overlay of n/a Repaired. ~ Yes; Surge Line Wilcox nozzle, safe-

  • Nozzle end & welds Hot Leg Babcock & Part No. 25 n/a Overlay of n/a Welding Yes Surge Line Wilcox *,nozzle, pipe & performed then Nozzle welds removed due to defects in overlay. Repair

___________~~~~~ ______ ~~~~~deferred.

____________________ 1____

7. Description of Work See identification above for each nozzle. Justification for actions taken on hot leg side in EC65878.
8. Tests Conducted: Hydrostatic E] Pneumatic EII Nominal Operating Pressure Z Other L] Pressure psi Test Temp. -F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y2 in. x I1I in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1000474 Relief Request 07-003-RR Code Case N416-2 invoked ASME Section Xl Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair cc

)nforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A

.Certificate of Authorization No. N/A ___Expiration Date N/A Sionpnd ISI *Engineer Dat 2 0 6~

Z) Y' om& ~or Owner's Designee, Title CERTIFICATE OF INSERVJCE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State o'r Province of FLORIDA and.

employed by THE HARTFORD STEAM BOILER I & I COMPANY of -

HARTFORD, CT. II have inspected the components described in this Owner's Report during the period 1, - I 1 totl ý-- oSand O' state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this 2e L\-e 2--- .. Commissions FL kJ( 11TQ0 AIJI-Inspector's Signature/ National Board, State, Province, and Endorsements Date 'K3c 20 0 "

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RD C-N GGC-OOO 1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 1/28/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1000472-04 thru -08 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System ,. .Reactor.Coolant - Relief nozzles (3 ea) and spray nozzle 5 (a) Applicable Construction Code USAS B3-1..1 19 68 Edition, June.1968 Errata .. No . > Code Case.

.(b) Applicable Edition of Section X1 Utilized-.for.Repairs or Replacements, 19 89 Addenda:., No ;i

6. Identification of Componbhts ~Reoaired or Replacebd and Replacement Components ASME National . . Repaired, Stamped Name of - Name of Manufacturer Board Other Year .Replaced, . (Yes

-Component. Manufactu'rer Serial No. No. Identification Built or Replacement or No)

Pressurizer.j-Babcock ....... 620-0007-'59' N-i 18 n/a '1971 'Repaired .Yes i Relief Nozzle Wilcox,- .

Pressurizer Babcock & 620-0007-59 N-i118 n/a 1971 Repaired Yes Relief Nozzle Wilcox

  1. 2 __________

Pressurizer Babcock & 620-0007-59 N-i118 n/a 1971 Repaired Yes Relief Nozzle Wilcox

  1. 3 __________ _______

Pressurizer Babcock & 620-0007-59 N-I118 n/a 1971 Repaired Yes Spray Nozzl . ilo Overlay welding of alloy 82/182 welds on relief valve nozzles (including flanges), and spray nozzle

7. Description of Work (including piping and alloy 600 safe end).
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure E Other EL Pressure psi Test Temp. -F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-

NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1000472 Relief Request 07-003-RR Code Case N416-2 invoked ASME Section XI Class 1 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp. N/A

'Certificate of Authorization No. N/A ____Expiration Date N/A Signed 12n ISI Engineer Date Z ,20 6

,0o/7A0,neror Owfier's Designee,'Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned; holding. a valid commission issued-by the; National-Board. of-Boiler and Pressure Vessel Inspectorsand the'.,

State or Province of FLORIDA . and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. have inspected the components described in this Owner's Report during the period _t. Z.6r- %-I to 1.-3 t- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

>x u. /z1:--*i Commissions FL VlA ,A~1 vn. LJ K)

IInspector's Sjgfature National Board, State, Province, and Endorsements 2

Date 0% -............ 20 d Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 3 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 2/4/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 3 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1000471 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System, Reactor Coolant
5. (a) Applicable Construction Code. ASME 111 19 65 Edition, S'67 Addenda, No Code Case (b) Applicable Edition of- Section XI Utilized for Repairs or Replacements 19 89 Addenda- No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Pressurizer Areva 8018667-001-02 n/a n/a n/a 'Replacement No Sample-Noz. ____ __

Pressurizer Areva 8018667-001-03, n/a n/a, n/a Replacement No Vent Nozzle ____ _______ ____

Pressurizer Areva 8018667-001-04 n/a n/a n/a Replacement No Nozzle 4 ___ ___ ___

Pressurizer Areva 8018667-001-01 n/a n/a n/a Replacement No Nozzle 5 ____ ____

Pressurizer Areva 8018667-001-05 n/a n/a n/a Replacement No Nozzle 6 _______ __________ ______ __ _______ _ ___

Pressurizer Areva 24984 n/a n/a n/a Replacement No Thermowell

7. Description of Work Replaced 5 nozzles and 1 Thermowell on Pressurizer
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure 0 Other El Pressure psi Test Temp. oF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 3 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 2/4/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 2 of 3 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1000471 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FIL 34428 Authorization No. N/A Address Expiration Dat -e N/A
4. Identification of System Reactor Coolant
5. (a) Applicable Construction Code ASME 111 19 65 Edition, S'67 Addenda, No Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda No.

A Idpntific~tinn of (~omoone.nt~ RAn~imd or R~ol~ir~d ~nd R~olac.Am~nt ComnonRnts ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes

-Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Pressurizer Babcock & Part # 30 N-I 18 n/a n/a "'Replaced:. Yes Samo~le Noz. Wilcox _____ I__________

Pressurizer Babcock & Part # 78 N-i 18 n/a n/a Replaced Yes Vent Nozzle Wilcox _______________

Pressurizer Babcock & Part # 30 N-1 18 n/a n/a Replaced Yes Nozzle 4 Wilcox_______________

Pressurizer Babcock & Part # 30 N-I 18 n/a n/a Replaced Yes Nozzle 5 Wilcox_______ _______

Pressurizer Babcock & Part # 30 N-i 18 n/a n/a Replaced Yes Nozzle 6 Wilcox___________________________________

Pressurizer Babcock & Part # 29 N-i 18 n/a n/a Replaced Yes Thermnowell Wilcox ______ ______________ _______ ____

Sheet 3 of 3 FORM NIS-2 (Back)

9. Remarks WO # 1000471, Engineering Change # 65876 Relief Requests 07-001-RR and 07-002-RR NCR 264576 identifies an apparent documentation error on the weld control record for the vent nozzle J-Groove weld. This was discovered when processing this NIS-2. The record indicates an incorrect welding procedure. This will be resolved through the CAP process.

ASME Section XI Class 1, Code Cases N416-2 and N638-1 invoked CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.. -

Type dode Symbol Stamp N/A Certificate of Authorization No. N/A *Expiration Date N/A Signed bzz7=--2&ý E 3'~.#~e~i~*r OwersDesignee, Title L-ISI Engjineer Date _20 A3 CERTIFICATE.OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period I-ti-v6 i to e~ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,A Commissions FL .1, Fc 0A~Ak.T Inspect Signature Natiorial Board, State, Province, and Endorsements Date 2 .. i........ 20dY Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 5/3/2006 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 'of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0.# 612143 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Makeup & Purification (MU)
5. (a) Applicable Construction Code USAS B331.1 19 67 Edition, None Addenda, None Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Bolting N/A N/A N/A N/A N/A Replaced No (Nuts) _____ I_________ I_______

Bolting N/A N/A N/A N/A N/A Replacement No (Nuts) _____

7. Description of Work Replaced bolting material (nuts) on MUFL-3A Filter Housing.
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure Other [I Pressure N/A psi Test Temp. N/A o NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks W.0. # 612143 ASME Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ci... -~ e: 7V.Z , / SI Engqineer Date Mft, 3,0 g

&-Owner's Designee, rfle olwnr CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period 4(- i- 2-p &. to and state that to the best of my knowledge and belief, the Owner has w6~c~,

performed examinations and taken corrective measdres described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this insp~Peftroy

--7c~ Commissions FL 218 N,A,I lnspegt~pls Signature National Board, State, Province, and Endorsements Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 12/31/07' Name P.O. Box 14042, St. Petersburg, Ff. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 856521 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat
5. (a) Applicable Construction Code. AN-SI B31., 19 67 Edition,:ý No ýAddenda, No Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda No
6. Identif ication of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial N,o:' 1 No.' Identification Built or Replacement or No)

Casing n/a n/a - n/a. n/a' n/a- Replaced' No Studs (4ea) _______

Casing n/a n/a n/a Heat LTV n/a Replacement No Studs (4ea)

7. Description of Work Replaced 4 casing studs on DHP-1 B
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure EL Other E] Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 856521 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A - Expiration Date N/A Signed z ISI Enaoineer Date 20 2

//16VPe-ror owne?s Designee, Tille.,

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors andithe State or Province of FLORIDA II-and, employed by THE -HARTFORDSTEAM BOILER I & I COMPANY of HARTFORD. CT. have inspected the components described in this Owner's Report during the period 'Y- Y'- Q') to a- 5/- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection 7A~e ,~'~ Commissions FL OR 1A 4 )

V-Insrpecrrs ifite National Board, State, Province, and Endorsements Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 1/8/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 789395 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water
5. '(a) Applic.able Construction Code ,ANSI B31.: 19 67 Edition, No Addenda, No Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Pipe n/a n/a n/a /an/a Replaced No Pipe n/a n/a n/a HT #A83600 n/a Replacement No Valve n/a n/a n/a n/a n/a Replaced No Valve Velan 991121-3 n/a n/a n/a Replacement No

7. Description of Work Replaced valve SWV-61 6 and associated piping
8. Tests Conducted: Hydrostatic E] Pneumatic L] Nominal Operating Pressure ED Other EL Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8'/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 789395 (WO 785454-01 for VT-2)

Code Case N41 6-2 invoked ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ISI En ineer Datee ~ 20A~

n~ei'-or Owner's Designee, Title' CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period tr (o0- to jSziand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this ino n p ' e ta Com missio ns FL I ) 6jO ý- q r)

I ns'pecto r's ig no---e' National Board, State, Province, and Endorsements Date ?_____ 20 0 V Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 1/8/08 Name P.O. Box 14042, St. Petersburg, Ff. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 789397 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water.
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, No Addenda, No Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Pipe n/a .n/a n/a n/a n/a Replaced No Pipe n/a n/a n/a HT #A83600 n/a Replacement No Valve n/a n/a n/a n/a n/a Replaced No Valve Velan 051019-2 n/a n/a n/a Replacement No

7. Description of Work Replaced valve SWV-618 and associated piping.
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure 0 Other E] Pressure psi Test Temp. 0F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 789397 (WO 785454-0 1 for VT-2)

Code Case N41 6-2 invoked ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of.Authorization No. N/A r:

AV 1.

n + KI/A SigneddLý ý,Q SI Enoineer Date _065ý ISI Enaineer

,, -1, e rO nirsDsgeTt6 A'"

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA .and employed by THE HARTFORD STEAM BOILER I & I CO MPANY of..

HARTFORD, CT. have inspected the components described in this Owner's Report during the period 1 0' to to0) OY , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection~

_______________ Commissions FL 2 Inspector's Signatre National Board, State, Province, and Endorsements Date Y__0 Y_

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/27/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 885131 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water (SW)
5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, N/A Addenda, N/A Code Case

-(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None

6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

SWR-235 N/A N/A N/A N/A N/A Repaired N/A

7. Description of Work Add shear lugs to process piping for support SWH-235
8. Tests Conducted: Hydrostatic E] Pneumatic [] Nominal Operating Pressure El Other El Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 885131 / EC# 60076 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair c onforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. -N/A ___ Expiration Date N/A Signed ý -- ISI Engineer Date &J)0 CL) 20 -07 Owner or Owner's Desigfiee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of

-HARTFORD,IT. . .Ihave inspected the components described in this Owner's Report during the period M,316 tofiJ2,716Y and state that to the best of my knowledge and belief, the Owner has performed examinations anddtaen corrective mea'sures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable i an manner for any personal injury or property damage or a loss of any kind arising from or connected with this if(1(/1/o 5 i w Commissions FL 124 N,B,A,I

/ inspe~o-r's Signature National Board, State, Province, and Endorsements Date NOL27L 200-7 Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/20/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 901641 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Emergency Feedwater (EF)
5. (a) Applicable Construction Code ANSI B331: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

EFH-121 N/A -Owner N/A N/A N/A N/A Repaired N/A Fab.

7. Description of Work Added Shear Lugs per EC# 59936.
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure E]

Other E] Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001 .

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 901641 / EC# 59936 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms nostoherlsfte to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A ISI Engineer Date Aln.tp 'X-e 2047 OwnýTror Owner's [Tsignee, Tritle CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTORD,ýT.have inspected the components described in this Owner's Report during the period )ja-/ to! fal 97 , and state that to the best of my knowledge and belief, the Owner has performed examinations and ta en corrective me sures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liabei ymanrfr any personal injury or property damage or a loss of any kind arising from or connected with this

_______________________Commissions FL 124 N, B, A, I lnspet~fsSigntureNational Board, State, Province, and Endorsements Dated0\1 21 20 07 Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/25/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888614 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Feedwater (FW)
5. (a) Applicable Construction Code ANSI B31:* 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

FWH-132 Power Piping 720088 N/A N/A N/A Replaced N/A FWH-132 Lisega 30600572/010 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber, attachment bracket and pipe clamp per EC# 59935.
8. Tests Conducted: Hydrostatic E Pneumatic E] Nominal Operating Pressure LI Other [1 Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888614 / EC# 59935 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed "'~4 L .- iIS[ Engineer Date AJd,2. ZS- ,200-7 Owne-ror Owners'Designee/itle CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. .. have inspected the components described in this Owner's Report during the period 47 to114 toand state that to the best of my knowledge and belief, the Owner has performed examinations anO ta~ken corrective measre dscribed in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be Iible in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection

_______________________________Commissions FL 124 N, B, A, I nsprc)rs Signature National Board, State, Province, and Endorsements Date 90y 14 2O.DL_

Note: Upon completion of the document, it is a completed CIA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/19/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 901640 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Emergency Feedwater (EF)
5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

EFH-1 20 Power Piping N/A N/A N/A N/A Replaced N/A EFH-120 Bergan Patterson N/A N/A N/A N/A Replacement N/A

7. Description of Work Replaced Strut and relocated to a new clamp per EC# 59936..
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure EL Other F1 Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

ONote: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 901640 / EC# 59936 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. ŽLA,~

N ___ Expiration Date N/A Signed _4 6L ISI Engineer Date A)0 1 1. 2067 Owner or Owner's Designee, Tiffle CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT.. . ~ have inspected the components described in this Owner's Report during the period 11?/0 toJ4(ZqW , and state that to the best of my knowledge and belief, the Owner has performed examinations ant tatken corrective mehsdreg described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,.

Commissions FL 124 N, B, A, I IsApdctor Sign6ature National Board, State, Province, and Endorsements Date Nb 0i 2007 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/29/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0.# 901639 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Emergency Feedwater (EF)
5. (a) Applicable Construction Code ANSI B31.' 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

EFH-1 18 N/A - Strut N/A N/A N/A N/A Replaced N/A

7. Description of Work Permanently Remove Strut and abandoned piping clamp and structural attachment per EC# 59936.
8. Tests Conducted: Hydrostatic El Pneumatic El Nominal Operating Pressure E]

Other E] Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 901639 / EC# 59936 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed (ý Cý a =7= ISI Engineer Date 11 IZS 20 07 Owner or Owner's DesignEK~ Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period ..JL.4.............. to II/7L , and state that to the best of my knowledge and belief, the Owner has performed examinations and ta en corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, A y l , Commissions FL 124 N, B, A. I VsI56Fq/ S ignature National Board, State, Province, and Endorsements Date NO ý 200~7...

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 11/27/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888614 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Feedwater (FW)
5. (a) Applicable Construction Code ANSI B331: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

FWH-120A Power Piping N/A N/A N/A N/A Replaced N/A FWH-120A Lisega / Progress N/A N/A N/A 2007 Replacement N/A Energy

7. Description of Work Replace clamp and constant support attachment items per EC# 59935..
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure [-]

Other El Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888614 / EC# 59935 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Signed -/<7-1 61-!-,

Ow`1`116-or Owner's Desigg~e, Title ISI Engineer Date /L1..I ......... 2007.......

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA n and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT.. have inspected the components described in this Owner's Report during the period iJIW07L~ toll )?c ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

(//7I1Iltt ______ Commissions FL 124 N.B, A. I Inspector's! Signature National Board, State, Province, and Endorsements Date NO(Y V _ 2O.D7.

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/22/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888613 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Feedwater (FW)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

FWH-131 Power Piping 730026 N/A N/A N/A Replaced N/A FWH-131 Lisega 3060031 3/004 N/A N/A N/A IReplacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167.
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure El Other E] Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888613 / EC# 64167 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Signed (/" ISI Engineer Date Z~~j

-Z ,20 07 Owner or Owner's Designee, Tit~h CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. -9have inspected the components described in this Owner's Report during the period 1401 to=117L.., and state that to the best of my knowledge and belief, the Owner has performed examinations anH taken corrective mdas'ures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be Ii beInaymnefoay personal injury or property damage or a loss of any kind arising from or connected with this inspectioin, Commissions FL 124 N. B. A. I lnspebcrol's Signature National Board, State, Province, and Endorsements Datefly23 20C37 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/20/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 888601 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat (DH)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

DHH-26V Power Piping 720098A N/A N/A N/A Replaced No DHH-26V Lisega 30700296/015 N/A N/A N/A Replacement No

7. Description of Work Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber per EC#

64157.

8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure L]

Other [] Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888601 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Signed _ --  ?,L c5"-J ISI.Engineer Date 0Uouj '. 20 7 Owner or Owner's Designee, TO, CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period 40- totffm/kn, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective me~sures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,_______________

Commissions FIL 124 N, B, A, I fnsi~e~tors/SignaureNational Board, State, Province, and Endorsements Date NOV . 20.!7 Note: Note:

Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 11/1/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888604 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat (DH)
5. (a) Applicable Construction Code ANSI B31.' 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

DHR-18 Power Piping 760176 N/A N/A N/A Replaced No DHR-18 Lisega J 30700257/001 1N/A N/A N/A Replacement No

7. Description of Work Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber per EC#

64157.

8. Tests Conducted: Hydrostatic LII Pneumatic E] Nominal Operating Pressure [L]

Other 0 Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888604 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Date N/A

~zzzzII

___Expiration Signed- ISI Encgineer Date 44.Z 206!

Owne'trf Own'§`F's Designee, Title/

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. , . have inspected the components described in this Owner's Report during the period _ ,116 to &/W/4J I and state that to the best of my knowledge and belief, the Owner has performed examinations and tak6n ebrrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this o//49& -Commissions insec77 FL 124 N. B. A. I 1ý..ffid~orsgigntureNational Board, State, Province, and Endorsements DateM V 2-L 2007 Note: Upon completion of the document, it is a completed GA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/15/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888605

.Address Repair Organization, P.O. No., Job N. etc.

3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat (DH)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

DHR-28 Power Piping 730229 N/A N/A N/A Replaced No DHR-28 Lisega 30700257/002 1N/A N/A N/A IReplacement No

______________ I. ____________________ U A___________ U ________________ A _______ L ___________________ A ____________

Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber per EC#

7. Description of Work 64157.
8. Tests Conducted: Hydrostatic LI Pneumatic El Nominal Operating Pressure ElJ Other F1 Pressure 0 psi Test Temp. F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. xl11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888605 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of A ~thio 'zation No. N/A ___ Expiration Date N/A ISI Engineer Date A)ci.II /T , 2007 Owner or Owners Designe~e,Titl1 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. .I - have inspected the components described in this Owner's Report during the period Z V/2 to -W," and state that to the best of my knowledge and belief, the Owner has performed examinations an dtaik*'en corrective rea sures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall b lib anfr any personal injury or property damage or a loss of any kind arising from or connected with this

_______________________________Commissions FL 124 N, B, A, I

% IsE¶'Signtre National Board, State, Province, and Endorsements DatemblisL 20D7 Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.-

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Riequired by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 11/1/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888606 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat (DH)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

DHR-37 Power Piping 750114 N/A N/A N/A Replaced No DHR-37 Lisega 30700257/003 N/A N/A N/A Replacement No Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber per EC#

7. Description of Work 64157.
8. Tests Conducted: Hydrostatic E] Pneumatic L]I Nominal Operating Pressure [L]

Other 0 Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888606 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of A tho 'zation No- N/A Expiration Date N/A Signed_6 1 Crwher o6r Owner's Destgnee, Title ISI Engineer Date A~/o. 20. 07 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of

.HARTFORD, CT. have inspected the components described in this Owner's Report during the period JQA Z to tt,4ý and state that to the best of my knowledge and belief, the Owner has performed examinations and takeb corrective mea ursdescribed in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this fI/YA'Af~i/JCommissions FIL 124 N, B, A. I_____

1/0' ' nspegfors-Signature National Board, State, Province, and Endorsements Date 2007L Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 10/30/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888607 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. .Identification of System Decay Heat (DH)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

DHR-49 Power Piping 750110 N/A N/A N/A Replaced No DHR-49 ILisega 30700257/0041 N/A N/A N/A IReplacement No

7. Description of Work Replace existing Power Piping Hydraulic Snubber with a new Lisega Hydraulic Snubber per EC# 64157.
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure El Other El Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. xl11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (112/82)

Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888607 / EC# 64157 Applicable Manufacturer's Data Reports to be attached.

ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Auth1

  • in
  • No. NA Expiration Date N/A Signed_ Z l OWiner or Owner's Designee, Title/

k ISI Enclineer Date /I613 _,20,07 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period 14/t6 tof;#I&W , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions FL 124 N. B. A, I Ins ecor's Signature National Board, State, Province, and Endorsements DateWt 31 20_03 Note: Upon completion of the document, it is a completed QIA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/23/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888616 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Feedwater (FW)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

FWH-148 Power Piping 740066 N/A N/A N/A Replaced N/A FWH-148 ILisega 130600231/012 N/A N/A N/A IReplacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic LI Pneumatic EL Nominal Operating Pressure DI Other El Pressure psi Test Temp. 0 F

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888616 / EC# 64167 ASME Section X1 Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _ ý,5z z {5L=,

OwneTrhor Owner's Designee, TitI(r ISI Engineer Date 000yj a23 200 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD.QT. thave inspected the components described in this Owner's Report during the period 12p/7 toil~g.?4L7, and state that to the best of my knowledge and belief, the Owner has performed examinations aný ta~en corrective me sdres described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this

//IJJLti 7/J Mi/ Commissions FL 124 N, B,A.I

/ , 141YErC/Ors"Signature National Board, State, Province, and Endorsements Date 140 2 2007 Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/23/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0.# 888619 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Feedwater (FW)
5. (a) Applicable Construction Code ANSI B331: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes

-Component Manufacturer Serial No. No. Identification Built or Replacement or No)

FWH-162 Power Piping 740055 N/A N/A N/A Replaced N/A FWH-1 62 Lisega 3060023 1/008 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic L] Nominal Operating Pressure [-]

Other LI Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001 .

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888619 / EC# 64167 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N6 Expiration Date N/A Sioned L - .ISI Engineer -Date Akoij. 91 ~ 20 "

Ow-ner r Owner's Designee, T/4e CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. have inspected the components described in this Owner's Report during the period .L(/z.1),'? to/I.-aX, and state that to the best of my knowledge and belief, the Owner has performed examinations arid tAken corrective measues described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be Ii ble in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, Commissions FL 124 N. B, A. I In tors Wignature National Board, State, Province, and Endorsements Date 20,23j Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/25/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888726 Addrp.ss Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31." 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-1 23 Power Piping 730121 N/A N/A N/A Replaced N/A MSH-123 ILisega 130700296/009- N/A N/A N/A IReplacemnen Ný/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic [] Nominal Operating Pressure E]

Other E] Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888726 / EC# 64167 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed -cIIýf 6-\ 4~- ISI Engineer Date ______________ 2007 Owner or Owner's Desi fiee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. pT. have inspected the components described in this Owner's Report during the period 11_ýO/ to J1WQ and state that to the best of my knowledge and belief, the Owner has performed examinations and ten corrective meisutei described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be Ii ble in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this insp/ectio___ __ Com m issions F IL124 N.B ,A. I 4sffiyd'Pý Signature National Board, State, Province, and Endorsements Date /4/2lA 20 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

-I Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/25/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888722 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31:- 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-125 Power Piping 720099 N/A N/A N/A Replaced N/A MSH-125 Lisega 30600231/001 N/A N/A N/A Replacement N/A

______________ .1. ____________________ +/- A L ________________ £ _______ L .1____________

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic Ei Nominal Operating Pressure E]

Other LI Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888722 / EC# 64167 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A -Expiration Date N/A Signed _ 1! (Y-Owner or Owner's-esigrjee, Title ISI Engineer Date AJO u. :2 . 20 07~

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report uigthepriod gtheperiodto 1 1j , and state that to the best of my knowledge and belief, the Owner has performed examinations ana taken corrective measure-sdescribed in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

____________________ Commissions FL 124 N, B, A, I Ihsp&&to6fSignature National Board, State, Province, and Endorsements I

Date jjb..26 2067.

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI 1 Owner Progress Energy Florida, Inc. Date 11/6/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1lof 2 Address

2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888721 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-1 28 Power Piping 740070 N/A N/A N/A Replaced N/A MSH-1 28 Lisega 30700296/014 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure E]

Other El Pressure psi Test Temp. -F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888721 / EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. NA..Expiration Date N/A Signed - '2 16,. ( ) ~ ISI Engineer Date ot o&j 7

51, 200!

Ownerdor Owne5r's DesigneTt~

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period 16L47 to[/I1/O7 _, and state that to the best of my knowledge and belief, the Owner has performed examinations and t'akd n corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

________________________Commissions FL 124 NK B, A, I lhspý61'or Signature National Board, State, Province, and Endorsements Date 140VLý 20O-7 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc.

Name Date l/I/1 /'07Z P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address

2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888719 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31:* 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-1 49 Power Piping 720074 N/A N/A N/A Replaced N/A MSH-149 Lisega. 30600231/016 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure []

Other El Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888719 / EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. Expiration Date N/A SigneddCJZý-A= ISI Engineer Date AA0~. /-3 ,2 6O 7 Owner or Owiner's DV1gnee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT 0 7-6 have inspected the components described in this Owner's Report duringgthep riodiod1727 to C , and state that to the best of myknowledge and belief, the Owner has performed examinations and takef corrective mers-ur~esdescribed in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal iniury or property damage or a loss of any kind arising from or connected with this 17X 6/',VR - Commissions FL 124 N, B, A. I In e4 or's Signature National Board, State, Province, and Endorsements Datewo 13 -20A Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/19/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888765 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A, Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-1 60 Power Piping 720081 N/A N/A N/A Replaced N/A MSH-160 Lisega 0461 6493/079 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic El Pneumatic L] Nominal Operating Pressure L-I Other Eli Pressure psi Test Temp. DF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8'/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888765 / EC# 64167 ASME Section X1 Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp -N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Signed_ ISI Engineer Date A.)x,o, 1~ 20 017 Owner or Owner's Designe6, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT.. . have inspected the components described in this Owner's Report during the period I to/" 1(9/7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be ha he in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,'--?

_____________________ Commissions FL 124 N, B, A, I

'inspbc' rA Signature National Board, State, Province, and Endorsements Date ~ ~~ 2007 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/23/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888768 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-161 Lisega 04616373/00 N/A N/A N/A Replaced N/A 4

MSH-1 61 Lisega N/A - Strut N/A N/A N/A Replacement N/A

7. Description of Work Replace Lisega Snubber with a new Lisega Strut per EC# 65795
8. Tests Conducted: HydrostaticEl Pneumatic El Nominal Operating Pressure [_1 Other E] Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2

FORM NIS-2 (Back)

9. Remarks WO # 888768 / EC# 65795 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Signed (Z r,ý4) Liiii ISI Engineer Date XL,, 2001 N7-er or-Owner's Design;' -$Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT,. have inspected the components described in this Owner's Report during the period L$4ZZ/67 to I Wl, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective mc'asu'res described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be lial le in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

/iKIIYJ)____ Commissions FL 124 N, B.A, I I ` InsWIr's- Signature National Board, State, Province, and Endorsements Date 06-. 2QJLZ_

Note: Upon completion of the document, it is a completed GA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 11/7/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888771 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MVSH-1 64 Power Piping 720077 N/A N/A N/A Replaced N/A MSH-1 64 ILisega 130600707/038 1N/A IN/A IN/A IReplacement IN/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure EL Other E Pressure psi Test Temp. O NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888771 / EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. NIa. Expiration Date N/A Signed _I ISI Engineer Date A-)&v . 20 0 owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, C1. have inspected the components described in this Owner's Report during the period --I f ýL........... to 11/17a nd state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective mea'sufes described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this ins/cio ( Com missions FL 124 N,B A , ,I I IffsI56c)6r's Signature National Board, State, Province, and Endorsements Date N 1........2067.

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.,

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/20/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888774 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date ,N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-1 68 Power Piping 730120 N/A N/A N/A Replaced N/A MSH-1 68 Lisega 04616593/10 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure El Other E] Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2'of 2 FORM NIS-2 (Back)

9. Remarks WO # 888774 /EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ~ )r/ISI Engilneer Date Qp 20o0.

Owner or Owner's Designee, Titlt CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT, have inspected the components described in this Owner's Report during the period 4!.3 /07 to 1j ,07.., -and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective me~surbs described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neith rer the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be Ii Ole in any manner for pesoa injury or property damage or a loss of any kind arising from or connected with'this inspection, 7

_______________________Commissions FL 124 N. B, A, I "Insp~dfor'slignature National Board, State, Province, and Endorsements*

Date UOV'20 2007 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/19/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888625 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Main Steam (MS)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

MSH-243 Power Piping 750040 N/A N/A N/A Replaced N/A MSH-243 Lisega 130600313/002 1N/A N/A N/A Replacement N/A

_____________ I ___________________ .L ______________ __________ L ________________ L _______ L __________________ I ___________

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic EII Pneumatic E] Nominal Operating Pressure El Other EL Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888625 / EC# 64167 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 71I.L6 2 /SI Ownier or Owner's Designe~r Title Engineer -Date P-JOV 092067' CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT.,/ have inspected the components described in this Owner's Report during the period tor tot(i&f. and state that to the best of my knowledge and belief, the Owner has performed examinations and aWen corrective mehs~res described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be ~~l pn man ~fo any personal injury or property damage or a loss of any kind arising from or connected with this

/#1 fjZ~fi1Y/7 Commissions FL 124 N,B,A. I

/ 'Insf~c~tt rs~ignature National Board, State, Province, and Endorsements Date W1V 200-Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section X1

1. Owner Progress Energy Florida, Inc. Date 11/23/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888638 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water (SW)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

SWH-483 Power Piping 730144 N/A N/A N/A Replaced N/A SWH-483 ILisega 130700257/010 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure Li]

0 Other E] Pressure psi Test Temp. F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11, ,in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to, be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM. NIS-2 (Back)

9. Remarks WO # 888638 / EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed/ ISI Enciineer Date / Z2- ,2 Owner or Owner's DesigrjP4, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. . have inspected the components described in this Owner's Report during the period J1.L/i1Z............... to L//4Z417 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken -corrective medsurbs described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

________________________ Commissions FL 124 N, B, A, I 11fspectoll Signature National Board, State, Province, and Endorsements Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 11/22/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888639 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water (SW)
5. (a) Applicable Construction Code ANSI B31:, 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

SWH-493L Power Piping 750103 N/A N/A N/A Replaced N/A SWH-493L Lisega 30700257/011 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic LI Pneumatic E] Nominal Operating Pressure EL Other L] Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888639 / EC# 64167 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ~SI I2--.Engineer Date AVaL', Z% ,200-7 Owner or Owner's Designte, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORDFCT. IIhave inspected the components described in this Owner's Report during the period Wo 7 .. to t&.ja7,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective me~sdres described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspect _______________

Commissions FL 124 N, B, A. I ln~ctor's Signature National Board, State, Province, and Endorsements Date_______2_ 2007' Note: Upon completion of the document, it is a completed QIA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/22/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888640 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water (SW)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

SWH-493U Power Piping 730231 N/A N/A N/A Replaced N/A SWH-493U Lisega. 30700257/012 N/A N/A N/A Replacement N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic E] Pneumatic L] Nominal Operating Pressure [LI Other El Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888640 / EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed <21I4 6* 2 ..-. ISI Engineer Date A-A0 Ll ZJ , 20 07 Owner or Owner's Desi~fiee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period !If R......... tolj , , and state that to the best of my knowledge and belief, the Owner has performed examinations anfd taken corrective m) s res described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions FL 124 N. B, A, I fnspor-'s Signature National Board, State, Province, and Endorsements Date 140y2L 2007 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/27/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FIL 34428 W.0. # 885130 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water (SW)
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

SWR-233 N/A N/A N/A ýN/A N/A Repaired N/A

7. Description of Work Add shear lugs to process piping for support SWH-233
8. Tests Conducted: Hydrostatic L Pneumatic E] Nominal Operating Pressure [I Other E] Pressure psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

V~

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 885130 / EC# 60076 ASME Section X1 Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair c onforms nom to oterlso h the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A___ExiaonDt N/

ISI Engineer Date k)ý 2067 Owner or Owner's Ddsignee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of

,HARTFORD, CT. have inspected the components described in this Owner's Report during the period _LU413 toi(/274? ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in ny manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,____________

Commissions FL 124 N. B. A. I Inspeefor's Signature National Board, State, Province, and Endorsements Date 20 1)720 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 11/23/2007 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.0. # 888642 Address Repair Organization, P.O. No., Job N. -etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Service Water (SW)
5. (a) Applicable Construction Code ANSI B31:" 19 67 Edition, N/A Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement; or No)

SWR-425 Power Piping 750115 N/A N/A N/A Replaced N/A SWR-425___ Lisega____ 130700257/013 N/A N/A N/A ,Replacemen~t N/A

7. Description of Work Replace Power Piping Snubber with a new Lisega Hydraulic Snubber per EC# 64167
8. Tests Conducted: Hydrostatic El Pneumatic EL Nominal Operating Pressure EL Other EL Pressure psi Test Temp. OF____

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8'/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QIA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 888642 / EC# 64167 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed_~ 2~ h Ow'h~r or Owner's Designeek'Title ISI Engineer Date // /2.3 206 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT.. have inspected the components described in this Owner's Report during the period i~fij&/

41441)7 ..... to and state that to the best of my knowledge and belief, the Owner has performed examinations and t~en corrective me~ue dscribed in this Owner's Report in~accordlance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable ip any manner for any personal injury or property damage or a loss of any kind arising from or connected with this

___ ___ ___ Commissions FL 124 N, B, A, I

% lnspe toWs Signature National Board, State, Province, and Endorsements DateNO V-23 2V Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 9/19/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W.O.#885123 and 1056081 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Decay Heat
5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, No Addenda, None Code Case (b) Applicable'Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda None
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Bellows N/A N/A N/A N/A N/A Replaced No Pump Seal Mechanical A. W. Chesterton 8812 N/A N/A N/A Replacemnent No Seal

7. Description of Work The bellows seal on the pump shaft is being replaced by a mechanical cartridge seal per EC65264
8. Tests Conducted: Hydrostatic E]i Pneumatic E] Nominal Operating Pressure ED Other El Pressure 160 psi Test Temp. 98 O NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed OA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 885123 and 1056081 ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A

,Certificate of Authorization No. N/A Expiration Date N/A Siged 42:ý ::ý .- "O.o' ISI Engineer Date Li= 20..L2.

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period :Z300 tc2ZL&7, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall b~e liabje in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions FL 12g 1QR,4A

' l'ng¶oI)Signature National B6&rd' Stbite, Province, and Endorsements Date a 2J 20,0 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 1/14/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3

.Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1002989 Address Repair Organization, P.O. No., Job N. etc.

3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Feedwater
5. (a) Applicable Construction Code ANSI B31.: 19 67 Edition, No Addenda, No Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired,. Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No) 18" Pipe n/a n/a. n/a n/a n/a Replaced .No Cast Steel Caldon, Inc 17932 n/a Heat V2153 n/a Replacement No spool _______ ____

18" Pipe Caldon, Inc 17932 n/a Heat 17417.9 n/a Replacement No add on

7. Description of Work Replace feedwater pipe with flow metering spool piece FW71 -FX
8. Tests Conducted: Hydrostatic Li Pneumatic Li Nominal Operating Pressure Other EL Pressure 946 psi Test Temp. 258 OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1002989 Code Case N416-2 invoked ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. :N/A Expiration Date N/A 5hin~d

  • ~IS

$7 'w~r~re6or Owner's'Designee, Title En2zDatee0r 15UFnninppr Date 20 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Ins pectors and the State or Province of .FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period ! Z - Z,S- ýj-) to _j' i'4-o0Y ands§tate that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

  • <~ /4.Commissions FL .ý 0 J,  ? __ _

ffispebtor's Signature National Board, State, Province, and Endorsements Date /~~' 20O~

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 2/14/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1002989 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A

.Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A

4. Identification of System Feedwater
5. (a) Applicable Construction Code ANSI B31., 19 67 Edition, No Addenda, No Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, 'Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No) 18" Pipe n/a n/a n/a n/a n/a -Replaced No Cast Steel Caldon, Inc 17933 n/a V2159 n/a Replacement No spool _______

18" Pipe Caldon, Inc 17933 n/a Heat 174179 n/a Replacement No add on

7. Description of Work Replace feedwater pipe with flow metering spool piece FW-2-FX
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure Other El Pressure 997 psi Test Temp. 377 . F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1002989 Code Case N416-2 invoked ASME Section Xl Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Signeed~

/r,-5vreror Own~er's Designee, Titfe CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA and employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD. CT. have inspected the components des-cribed in this Owner's Report during the period ,ZJ i 6- to L Oand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, Commissions FL 46IZ~,~

ge-ctor's Signature National Board, State, Province, and Endorsements Date qf 2 20 Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OO0i.

ISheet 1of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 12/19/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1159274 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Industrial Cooler Water

,5. (a) Applicable Construction Code ANSI B31.: 19 67 -Edition, No Addenda, No- Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19 `89 Addenda No.'

6. Identification of Components Repaired or Replaced and Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufac~turer- Board Other Year Replaced, (Yes Component Manufacturer Serial-No. No. Identification Built or Replacement or No)

Valve' Crane n/a n/a n/a' :hrna Replaced No Valve Crane n/a n/a P0 A331 11 n/a Replacement No Pipe 2-1/2" n/a n/a n/a n/a n/a Replaced No Pipe 2-1/2" n/a n/a n/a HT 364333 n/a Replacement No

7. Description of Work Replace valve CIV-40 and associated piping.
8. Tests Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure Other [I Pressure 0 52 'psi Test Temp. 70 F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2/in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1159274 Code Case N416-2 invoked ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of;Authorization No. N/A ___Expiration Date N/A Sine ISI Engineer Date 2ý L)'7Z..

/7't-ADvw-er orOwrier's Designee¶-Title CERTIFICATE OF.INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or,Prýovince of FLORIDA and employed by 'THE HARTFORD STEAM BOILER I & I COMPANY Of.

HARTFORD, CT. have inspected the components described in this Owner's Report during the period Hi ZA 4-01 to I OT, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures -described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.I By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection, S

>(>4j A ---. Commissions FIL )d3J '7 Inspector's Sign,99¶r National Board, State, Province, and Endorsements Date 1/'2 6 7__

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner -Progress Energy Florida, Inc. Date 2/14/08 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant -Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1013710 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FIL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Make-up and Purification
5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, No Addenda, No Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced and Replacement Components

- 1 - -ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Valve Rockwell-Mfg. N/A N/A N/A N/A Replaced No Valve Rockwell Edward ZA01 8 N/A N/A 1980 Replacement No

7. Description of Work Replaced valve MUV-53
8. Tests Conducted: Hydrostatic U Pneumatic E] Nominal Operating Pressure 0 Other LI Pressure 2850 psi Test Temp. 73 o NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1013710 EC # EQVR 68701 Code Case N416-2 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Sge SI Engineer Date S ~*,20 d I CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of . FLORIDA and.

employed by THE HARTFORD STEAM BOILER I & I COMPANY of HARTFORD, CT. have inspected the components described in this Owner's Report during the period I (- -Z 7$- 6-1 toZý-rPf -0V and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection,

~--~2 -Commissions FL T Inspecto~psýignature National Board, State, Province, and Endorsements Date qj, 200 K Note: Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

Sheet 1 of 2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Progress Energy Florida, Inc. Date 12/31/07 Name P.O. Box 14042, St. Petersburg, Fl. 33733-4042 Sheet 1 of 2 Address
2. Plant Crystal River Unit 3 Name 15760 W. Powerline Street, Crystal River, FL 34428 W. 0. # 1158205 Address Repair Organization, P.O. No., Job N. etc.
3. Work Performed by Crystal River Unit 3 Type Code Symbol Stamp N/A Name 15760 W. Powerline Street, Crystal River, FL 34428 Authorization No. N/A Address Expiration Date N/A
4. Identification of System Leak Rate Test
5. (a) Applicable Construction Code ANSI B31 .1 19 *67 Edition, No Addenda, No Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 89 Addenda No
6. Identification of Components Repaired or Replaced an d Replacement Components ASME Code National Repaired, Stamped Name of Name of Manufacturer Board Other Year Replaced, (Yes Component Manufacturer Serial No. No. Identification Built or Replacement or No)

Valve Disc n/a n/a n/a n/a n/a. .Replaced No Valve Disc n/a n/a n/a P0 ME6283 n/a Replacement No

7. Description of Work Replaced disc in valve LRV-50.
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure El Other E] Pressure psi Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2 in. x 11 in.,

(2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82)

Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-0001.

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks WO # 1158205 ASME Section XI Class 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the repair or replacement ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A ___ Expiration Date N/A Sig9ned ISI Engineer Date 5 A'S < /,20 0ý7 o"' 6wp~r or Own~r's Designee, TI'tle CERTIFICATEOF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued. by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FLORIDA -and~

employed by ,THE HARTFORD STEAM BOILER I & I COMPANY -of HARTFORD, CT. have inspected the components described in this Owner's Report during the period I-'  ? to fA*3ý -Q), and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this insp ec tio n, 5 < O aC o ms i nF L j Inspector's Signp, re National Board, State, Province, and Endorsements Datek,+/-20 0Y Note: Note:

Upon completion of the document, it is a completed QA record and is to be transmitted in accordance with RDC-NGGC-OOO1.

PROGRESS ENERGY FLORIDA, INC.

CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302/LICENSE NUMBER DPR-72 ATTACHMENT 3 CORRECTED ASME, SECTION XI, MIS-i, OWNER'S REPORT OF INSERVICE INSPECTIONS FOR RFO 14

NIS-1 Page I of 2 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As Required by the Provisions of the ASME Code Rules L Owner rioriua rower kýumorarion,.Or. Box 1~U404. St. reter-sburtz rL. 337331-4042 (Name and Address of Owner)

2. P taut (Name and Address of Plant)
3. Plant Unit Crystal River Unit 3 4. Owner Certificate of Authorization (if required) N/A S.Commercial Service Date 3/1 3/1 977 6. National Board Number for Unit N/A
7. Components Inspected Components or Manufacturer Manufacturer or State or National Board Appurtenance or Installer Installer Serial No. Province No. No.

Reactor Vessel Babcock & Wilcox 620-0007-51-52 N/A N-I 17 Pressurizer Babcock & Wilcox 620-0007-59 N/A N-I 18 Steam Generator A Babcock & Wilcox 620-0007-55-1 N/A N-1 19 Steam Genemator B Babcock & Wilcox 620-0007-55-2 N/A N- 120 Various Piping, Pumps, N/A N/A N/A N/A Valves, Supports and Containment areas.

Reactor Vessel Closure Fmamatome ANP CC/CR 001 N/A N/A Head Note: Supplemental sheets to form of lists, sketches, or drawings may be used, provided (1) size in the same as this Data Report, (2) information in items I through 600n this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

NIS-I Page 2 of 2 FORM NIS-1 (back)

8. Examination Dates: 11/5/2003 - to 12/10/2005
9. Inspection Period Identification: I'erkdL2. 2)14i'fXcll to !N,-Y-n05 Period 3. 4/1412005 to 8/13/2008.

10 Inspection Interval Identification: Interval 3, 8/14/1998 to 8/11N0-00 I I Applicable Edition of Section XI 1989 Addenda N/A 12 Date/Revision of Inspection Plan: 11/2/2005. Revision 6

13. Abstract of Examination and Tests. Include a list of examinations and a statement concerning status of work required for the inspection plan.

See Enclosure

14. Abstract of Results of Examinations and Tests.

See Enclosure

15. Abstract of Corrective Measures.

See Enclosure We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code.

Section XI.

Certificate of Authorization No. (if applicable) __N/A ____Expi ration Date N/A Date 2/2/2006 Signed Progress Energy Florida, Inc. By Matthew Denny/ C 'I Owner 0)

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boilef-pd ressure Vessel Inspectors and/or the State or Province of Florida and employed by HS13 /' of CT. have inspecqtl 9_h mponents described in this Owner's D ta ptduig h pro 11-5-2003 to-_1ý 0?0- r state that to the best of my knowledge and belief, the Owner has performed xamirinaticins and tesfRK i*6t nTorrective measures described inthis Owner's Data Report in accordan'e--Vv-tl the Inspection Plan and as required by the ASME code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examination and corrective measures described in this Owner's Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a losso n kid aisincqfromnor connected with this inspection.

_Zmmissions FL218 NIA Inspector's S atiure National Board, State, Province, and No.

ILStZrQ 4AA)

Date)ý7 4,ý 4 2006