05000395/LER-1982-059, Forwards LER 82-059/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 82-059/03L-0.Detailed Event Analysis Encl
ML20028E169
Person / Time
Site: Summer 
Issue date: 01/13/1983
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20028E170 List:
References
NUDOCS 8301210043
Download: ML20028E169 (3)


LER-1982-059, Forwards LER 82-059/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3951982059R00 - NRC Website

text

-_ _ _ _ _ _ _. _ _ _ _ _

cu SOUTH CAROLINA ELECTmC & GAS COMPANY

^

POST CPPICE 764 COLUMe:A, SOUTH CAROLINA 29218 3

%~.

O. W. DixON, JR.

Vice PnESIDENT January 13, 1983 C'

NUCLEAR OranATeoNS ro Mr. James P.-O'Reilly, Director U.S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street, N.W.

Atlanta, Georgia 30303

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Thirty Day Written Report LER 82-059

Dear Mr. O'Reilly:

Please find attached Licensee Event Report #82-059 for Virgil C. Summer Nuclear Station.

This Thirty Day Report is required by Technical Specification 6.9 1.13.(c) as a result of not performing the surveillance requirements of Technical Specification 4.7.10.2.a, " Plant Systems, Fire : lated Assemblies,"

on December 15, 1982.

Should there be any questions, please call us at your convenience.

Very truly yours,

,h/

i O. W. 41,xon, Jr.

HCF:0WD:dwr Attachment cc:

V.

C.

Summer A. R. Koon T.

C. Nichols, Jr.

G.

D. Moffatt E. C.

Roberts Cite QA 2

0. W. Dixon, Jr.

C. L. Ligon (NSRC)

G. J. Braddick H. N.

Cyrus H. T.

Babb J. L.

Skolds D.

A. Nauman J.

B. Knotts, Jr.

M. B. Whitaker, Jr.

B.

A.

Bursey W.

A.

Williams, Jr.

I&E (Washington)

Document Management Brarach O.

S.

Bradham INPO Records Center R.

B.

Clary NPCF M. N.

Browne OFFICIANP 8301210043 830113 DRADOCK05000g

Mr. James P. O'Reilly LER No.82-059 Page Two January 13, 1983 DETAILED DESCRIPTION OF EVENT On December 15, 1982, with the Plant in Mode 1, a detailed review of fire door surveillance procedures was being performed.

It was discovered that some doors (see Attachment) requiring surveillance had inadvertantly been omitted from the latest revision of the Auxiliary Operator Logs.

As these logs are used by the Auxiliary Operators to ensure that certain plant surveillances are performed, the subject doors were not checked.

Technical Spc+;fication Surveillance Requirement 4.7.10.2.(a) requires these doors to be verified closed once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

1 J

PROBABLE CONSEQUENCES The Plant had previously established a one (1) hour roving fire watch patrol.

This roving one (1) hour fire watch patrol was in effect through December 15, 1982.

Therefore, the chances that any fire cc. curring would have been detected in its early stages and would have been promptly brought under control.

CAUSE(S) 0F THE OCCURRENCE l

During the last revision of the Auxiliary Operator Legs, the subject fire doors were inadvertantly omitted.

Therefore, the doors were not checked.

IMMEDIATE CORRECTIVE ACTIONS TAKEN Upon completion of a temporary log, firewatch personnel checked the identified doors.

The doors were all found to be in the closed position on December 16, 1982.

These doors are verified and logged on a daily basis by firewatch personnel until the issuance of the revised Auxiliary Operator Logs.

ACTION TAKEN TO PREVENT RECURRENCE A revision is underway to incorporate all Plant fire doors onto the Auxiliary Operator Logs.

This will allow the verification that all fire doors are in the correct position once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> as per Technical Specification 4.7.10.2.(a).

The Licensee plans to have this accomplished by January 21, 1983.

1 m

~.

Mr. James P. O'Reilly l

LER No.82-059 r

Page Three i

January 13, 1983 ATTACHMENT FIRE DOORS OMITTED FROM AUXILIARY OPERATORS LOG BUILDING DOOR NO.

Turbine Building 202 Intermediate Building 501 318A I

122 121 210 Penetration Access 204 205 Control Building 704 705 503 504 506 l