05000395/LER-1982-043, Forwards LER 82-043/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 82-043/03L-0.Detailed Event Analysis Encl
ML20070F182
Person / Time
Site: Summer 
Issue date: 12/13/1982
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20070F185 List:
References
NUDOCS 8212200110
Download: ML20070F182 (2)


LER-1982-043, Forwards LER 82-043/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3951982043R00 - NRC Website

text

. _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFICE 764 CotuusiA. SouTM CAnouNA 29218 o. W. DixoN. Jn.

vier passaorav 4

nuca. o.aariOas December 13, 1982 7o

,a

.O 0,/>

e%

Mr. James P. O'Reilly, Director

'^

N U.S. Nuclear Regulatory Commission Teg7 Region II, Suite 3100 101 Marietta Street, N.W.

yd' Atlanta, Georgia 30303

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Thirty Day Written Report LER 82-043 l

Dear Mr. O'Reilly:

Please find attached Licensee Event Report #82-043 for Virgil C.

Summer Nuclear Station.

This Thirty Day Report is required by Technical Specification 6.9.1.13.(a) as a result of entry I

into Action Statement 2 of Technical Specification 3 3.1, Table 3.3-1.2.B, " Reactor Trip Syctem Instrumentation," on November 13, 1982.

Should there be any questions, please call us at your convenience.

Very truly yours, O.

W.

ixo, Jr.

CJM:0WD:dwr Attachment cc:

V.

C.

Summer A.

R.

Koon T.

C.

Nichels, Jr.

G.

D. Mof fatt G.

H.

Fischer Site QA

0. W. Dixon, Jr.

C. L. Ligon (NSRC) i H.

N. Cyrus G. J.

Braddick H.

T.

Babb J. L.

Skolds D.

A.

Nauman J.

B. Knotts, Jr.

M.

B.

Whitaker, Jr.

B.

A.

Bursey W.

A.

Williams, J r.

I&E (Washington)

O.

S.

Bradham Document Management Branch R.

B.

Clary INPO Records Center i

M. N. Browne NPCF Fl' M " # y~

File

@212200110 821213 g

PDR ADOCK 05000395 S

PDR

Mr. James P. O'Reilly LER No.82-043 Page Two December 13, 1982 DETAILED DESCRIPTION OF EVENT On November 13, 1982, with the Plant in Mode 2, the Nuclear Instrumentation Power Range Channel (N42 ) Low Range Trip Setpoint was found set at 50% icstead of the required 25% of Rated Thermal Power.

The discovery was made during the performance of Gurveillance Test Procedure (STP) 310.006, and the bistable was immediately adjusted to the proper setpoint in accordance with Technical Specification 2.2.1.a.

The Channel was not declared inoperable at time of discovery per Technical Specification 3.3 1, Table 3 3-1.2.B, since surveillance testing was in progress, and the bistable was adjusted to the correct setpoint in less than one (1) hour.

PROBABLE CONSEQUENCES There were no adverse consequences from the less conservative setpoint value since the Power Range High Setpoint had previously been adjusted to 25% of Rated Thermal Power for Power Operational Testing on October 18, 1982.

At time of occurrence, the remaining Power Range Channels were operational with the proper trip setpoints.

CAUSE(S) 0F THE OCCURRENCE The cause of this occurrence is attributed to personnel error.

During the performance of the Power Operational Testing Program, the Power Range High Setpoints are adjusted several times for the various plant power levels, and it is believed that the Low Range Bistable was set in error during these perturbations.

IMMEDIATE CORRECTIVE ACTIONS TAKEN Nuclear Instrumentation Power Range Channel (N42) Low Range Trip Setpoint was immediately adjusted to 25% of Rated Thermal Power, and all other setpoints were verified to be correct for that power level.

ACTION TAKEN TO PREVENT RECURRENCE Maintenance personnel have been instructed to exercise caution in adjusting instrument setpoints to their prescribed values. This should prevent recurrences of this nature in the future.