05000387/FIN-2013003-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Inadequate Operability Assessment of Synchroscope Switch |
| Description | Inspectors identified a Green NCV of 10 CFR 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, when PPL performed an inadequate operability determination for a synchroscope switch failure that rendered offsite power and the four emergency diesel generators (EDGs) inoperable. This resulted in PPL being in violation of Unit 1 TSs 3.8.1, 3.8.2, and 3.0.3, and Unit 2 TSs 3.6.4.1 and 3.8.2. PPL entered the issue in their CAP as CR 1703293, re-evaluated past operability and submitted a licensee event report (LER) for the associated condition prohibited by plant Technical Specifications (TS) on July 8, 2013 (ADAMS Accession No. ML13190A104). The performance deficiency was determined to be more than minor since it was associated with the equipment performance attribute of the Mitigating Systems cornerstone and adversely affected its objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding was evaluated using the SDP of IMC 0609.04. The finding was evaluated under both the Mitigating Systems Exhibit of IMC 0609 Appendix A when Unit 1 was at power and Appendix G for the times when one or both units were in a shutdown condition. Under IMC 0609, Appendix A, the finding screened to Green since it was not a design or qualification deficiency and was not a potential or actual loss of system or safety function. Under IMC 0609, Appendix G, Attachment 1, Checklists 5 through 7, the inspectors screened the issue to Green since it affected the requirement for operable DGs under TS 3.8.1 and TS 3.8.2. The inspectors determined that a Phase 2 analysis was not warranted since it did not match those criteria listed for further analysis in these checklists. Specifically, since all automatic transfer functions of off-site power and the EDGs remained functional, inspectors determined that none of the functions evaluated under the SDPs were affected. The finding had a cross-cutting aspect in Problem Identification and Resolution (PI&R), corrective action program (CAP), because PPL staff did not thoroughly evaluate problems such that the resolutions address the causes and extent of conditions, to include properly classifying, prioritizing and evaluating for operability. Specifically, PPL staff did not appropriately evaluate the effect that the synchroscope switch failure had on offsite power and emergency diesel generator operability. |
| Site: | Susquehanna |
|---|---|
| Report | IR 05000387/2013003 Section 1R15 |
| Date counted | Jun 30, 2013 (2013Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | J Greives A Bolger M Gray F Arner J Laughlin P Finney D Orr S Barber R Rolph D Dodson |
| Violation of: | 10 CFR 50 Appendix B Criterion V Technical Specification Technical Specification - Procedures |
| CCA | P.2, Evaluation |
| INPO aspect | PI.2 |
| ' | |
Finding - Susquehanna - IR 05000387/2013003 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Susquehanna) @ 2013Q2
Self-Identified List (Susquehanna)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||