05000361/LER-1982-160, Forwards LER 82-160/01T-0.Detailed Event Analysis Submitted

From kanterella
Jump to navigation Jump to search
Forwards LER 82-160/01T-0.Detailed Event Analysis Submitted
ML20070L554
Person / Time
Site: San Onofre 
Issue date: 12/16/1982
From: Morza H
SOUTHERN CALIFORNIA EDISON CO.
To: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
Shared Package
ML20070L556 List:
References
NUDOCS 8301030179
Download: ML20070L554 (2)


LER-1982-160, Forwards LER 82-160/01T-0.Detailed Event Analysis Submitted
Event date:
Report date:
3611982160R00 - NRC Website

text

.-

0 c

Southern California Edison Company 19 ;

S,G =

S AN ONOFRE NUCLE AR CENER A TING S T A TION p

' l} }

P.O. a u x 12 s S A N C LEMEN T E. C A LIF OR NI A 92672 k//.,;

H. B. R AY frospwont

" " " ~ " " " " ' "

December 16, 1982 U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, CA 94596-5368 Attention:

Mr. R. H. Engelken, Regional Administrator

Dear Sir:

Subject:

Docket No. 50-361 Prompt Report and 14-Day Follow-Up Report Licensee Event Report No.82-160 San Onofre Nuclear Generating Station, Unit 2 This submittal is in accordance with the reporting requirements of Technical Specifications 6.9.1.12.b to Operating License NPF-10 for San Onofre Unit 2, and confirms our December 15, 1982 prompt notification to the NRC of a reportable occurrence involving Limiting Condition for Operation (LCO) 3.3.3.8 associated with the Radioactive Liquid Effluent Monitoring Instrumentation. This letter also represents the required follow-up report and forwards the associated Licensee Event Report (LER), No 82.-160.

On December 1,1982 while in Mode 1, the Turbine Building west sump pumps were cleared for repairs. Temporary pumps were installed to pump down the sump. The flow paths bypassed radiation monitor 2RT-7821, thus rendering it inoperable. LC0 3.3.3.8 Action b allows continued

,i operations for up tc 30 days providing that at least once per 8 hou.rs grab samples are collected and analyzed. Such samples were not taken between December 1,1982 and December 6,1982, when the temporary path was removed and 2RT-7821 restored to operable status. This was identified on December 14, 1982 during routine review of Station Incident Reports (SIR's).

8301030179 821216 PDR ADOCK 05000361 MM S

PDR Ba4%

R. H. Engelken December 16, 1982 The cause of this event was an administrative failure in that appropriate Effluent Monitoring personnel were not notified of the temporary pump installation. Corrective action to prevent recurrence will include a memorandum to operators emphasizing the need to recognize the impact of temporary modifications in any effluent release path that could potentially render a radiation monitor inoperable and to assure that all additional sampling requirements called for by the Technical Specifications are performed.

Public health and safety were not affected by this event since grab samples were taken once a day (instead of every 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />) and indicated no abnormal radioactivity levels.

If there are any questions concerning the above, please contact me.

Sincerely, bh Enclosure: LER 82-160 cc:

A. E. Chaffee (USNRC Resident Inspector, San Onofre Unit 2)

U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement U. S. Nuclear Regulatory Consission Office of Management Information and Program Control Institute of Nuclear Power Operations l

l l