05000361/LER-1982-126, Forwards LER 82-126/03L-0.Detailed Event Analysis Submitted

From kanterella
Jump to navigation Jump to search
Forwards LER 82-126/03L-0.Detailed Event Analysis Submitted
ML20066F969
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 11/09/1982
From: Ray H
SOUTHERN CALIFORNIA EDISON CO.
To: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
Shared Package
ML20066F972 List:
References
NUDOCS 8211190248
Download: ML20066F969 (2)


LER-1982-126, Forwards LER 82-126/03L-0.Detailed Event Analysis Submitted
Event date:
Report date:
3611982126R00 - NRC Website

text

e 9 Southern California Edison Company g6

$ AN ONOFME NOCLE AR GENER A TING S T A TION P.O. 8 0 K 128 S AN C LEMENTE. C ALIFORNI A 92672 H. 8. R AY T E L E Pa* 0 N E November 9, 1982 ivar'o= =aaaaa a u m u"oo U. S. Nuclear Regulatory Commission 3

Office of Inspection and Enforcement p

i Region V 2

y(.

1450 Maria Lane, Suite 210 ti 9'

Walnut Creek, California 94596-5368 N

.jg; gg 3

ro Q

g Attention:

Mr. R. H. Engelken, Regional Administrator I

fa p

m 5

Dear Sir:

e-w m

Subject: Docket No. 50-361 30-Day Report Licensee Event Report No.82-126 San Onofre Nuclear Generating Station, Unit 2 Pursuant to Section 6.9.1.13b of Appendix A to Facility Operating License NPF-10 for San Onofre Unit 2, this submittal provides the required written report and copy of Licensee Event Report (LER) for an occurrence involving the containment isolation valves. A completed copy of LER 82-126 is enclosed.

On October 10, 1982, while in Mode 4 during routine Control Room in-spection, mainsteam trap isolation valve 2HV-8249 was observed to have lost position indication. The valve was declared inoperable at 0220 and l

Limiting Condition for Operation (LCO) 3.6.3 Action Stetement b was invoked. As required by this Action Statement, the penetration was isolated by de-energization of the valve and local verification of its closure.

Subsequent investigation revealed that the trouble was due to loosening of the magnetic reed switch assembly 2ZSL-8249-2 on the valve stem. The loosening of this switch assembly allowed it to rotate causing the close limit switch to open due to its misalignment with the magnet. This condition resulted in lost valve position indication in the Control After properly aligning and tightening the switch, the valve was Room.

5023-3-3.30 at 2140 on October 10, declared operable in accordance with As corrective action, Electrical Maintenance has been instructed 1982.

to examine all valves of this type to verify proper reed switch alignment and tightness.

8211190248 821109 PDR ADOCK 05000361 PDR S

MM 83-3 9 s

I Mr. R. H. Engelken November 9,1982 Since the penetration was isolated by de energization of the valve to its closed position, there was no impact on health and safety of plant personnel or the public.

If there are any questions regarding the above, please contact me.

Sincerely, f Wl

Enclosure:

LER 82-126 cc:

A. E. Chaffee (USNRC Resident Inspector, San Onofre Unit 2)

U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Office of Management Information and Program Control Institute of Nuclear Power Operations I

l I

l