| Title | Inadequate Design Control for Required Service Water Flow to the Emergency Diesel Generators |
| Description | An NRC-identified Green NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, was identified for the failure of the licensee to verify the adequacy of design of the emergency diesel generator (EDG) service water flow. Specifically, from May 1, 1989, until October 28, 2013, Calculation M-89-0008, contained non-conservative values for EDG maximum loading, service water inlet temperatures, and heat exchanger fouling factor, resulting in a non-conservative calculation for required service water flow to the EDG jacket water heat exchanger, which called into question the operability of EDG 3. The licensee re-performed Calculation M-89-0008 and determined EDG 3 was operable. The licensee entered this issue into the corrective action program (CAP) as nuclear condition report (NCR) 592035. The inspectors determined that the failure of the licensee to have an accurate calculation for required service water flow to the EDG jacket water heat exchanger was a performance deficiency. The finding was more than minor because it was associated with the design control attribute of the Mitigating Systems Cornerstone and adversely affects the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the non-conservative calculation called into question the operability of EDG 3. Using IMC 0609, Appendix A, issued June 19, 2012, the SDP for Findings At-Power, the inspectors determined the finding was of very low safety significance (Green) because the finding did not affect the design or qualification of a mitigating structures, systems, and components (SSC), the finding did not represent a loss of system and/or function, the finding did not represent an actual loss of a function of a single train for greater than the technical specification (TS) allowed outage time, the finding did not represent an actual loss of a function of one or more non-TS trains of equipment, and did not screen as potentially risk-significant due to a seismic, flooding, or severe weather initiating event. The finding has a cross-cutting aspect in the area of human performance associated with the resources attribute because the licensee did not have complete, accurate and up-to-date design documentation for EDG service water flow. Specifically, due to the inspector?s questions, Calculation M-89-0008 required revision due to non-conservatisms in August 2013 and in November 2013. |
| Site: | Brunswick |
|---|---|
| Report | IR 05000324/2013005 Section 1R15 |
| Date counted | Dec 31, 2013 (2013Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | J Laughlin M Bates M Catts M Schwieg P Lessard D Jackson G Hopper J Austin J Dodson |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control Technical Specification |
| CCA | H.7, Documentation |
| INPO aspect | WP.3 |
| ' | |