11-02-2017 | On May 3, 2017 with the unit shutdown for refueling outage, while performing plant procedure 3.M.3-27, "480V Bus B6 Transfer Test, UV, Degraded Voltage and Timing Relays Calibration and Annunciator Verification," the time delay Agastat relay 27A-B1X/TDDO opened instantaneously, instead of with a time delay. This relay is set to drop out after a 1.25 second time delay after being de-energized. This condition was discovered during the plant's refueling outage when conditions were such that the equipment normally energized/activated by this time delay relay was not required to be operable.
Pilgrim Nuclear Power Station is submitting this Licensee Event Report in accordance with 10 CFR 50.73(a)(2)(i)(B) - Operation or condition prohibited by Technical Specifications; and in accordance with10 CFR 50.73(a)(2)(v)(B), (C) and (D) - Any condition that could have prevented the fulfillment of the safety function of structures or systems that are needed to remove residual heat, control the release of radioactive material and mitigate the consequences of an accident.
This event was not risk significant. There was no threat to public health and safety from this condition. |
---|
|
---|
Category:Letter
MONTHYEARL-24-002, Late LLRW Shipment Investigation Report Pursuant to 10 CFR 20, Appendix G2024-02-0202 February 2024 Late LLRW Shipment Investigation Report Pursuant to 10 CFR 20, Appendix G ML23342A1182024-01-0909 January 2024 Independent Spent Fuel Storage Installation Security Inspection Plan L-23-019, Proof of Financial Protection 10 CFR 140.152023-12-18018 December 2023 Proof of Financial Protection 10 CFR 140.15 ML23334A1822023-11-30030 November 2023 Biennial Report for the Defueled Safety Analysis Report Update, Technical Specification Bases Changes, 10 CFR 50.59 Evaluation Summary, and Regulatory Commitment Change Summary November 2021 Through October 2023 L-23-012, Master Decommissioning Trust Agreement Changes for Indian Point Nuclear Generating Units 1, 2 and 3, Pilgrim Nuclear Power Station, Palisades Nuclear Plant and the Non-Qualified Trust for Big Rock Point2023-11-13013 November 2023 Master Decommissioning Trust Agreement Changes for Indian Point Nuclear Generating Units 1, 2 and 3, Pilgrim Nuclear Power Station, Palisades Nuclear Plant and the Non-Qualified Trust for Big Rock Point ML23306A0992023-11-0202 November 2023 and Indian Point Energy Center, Notification of Changes in Schedule in Accordance with 10 CFR 50.82(a)(7) L-23-011, 10 CFR 72.48 Biennial Change Summary Report2023-10-27027 October 2023 10 CFR 72.48 Biennial Change Summary Report IR 05000293/20234012023-08-31031 August 2023 NRC Inspection Report No. 05000293/2023401 & 2023001 (Cover Letter Only) IR 05000293/20230022023-08-0404 August 2023 NRC Inspection Report No. 05000293/2023002 L-23-008, Correction to Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations Holtec Decommissioning International, LLC (HDI)2023-05-23023 May 2023 Correction to Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations Holtec Decommissioning International, LLC (HDI) ML23136A7792023-05-15015 May 2023 Annual Radiological Environmental Operating Report, January 1 Through December 31, 2022 ML23135A2152023-05-15015 May 2023 Annual Radioactive Effluent Release Report, January 1 Through December 31, 2022 L-23-004, HDI Annual Occupational Radiation Exposure Data Reports - 20222023-04-24024 April 2023 HDI Annual Occupational Radiation Exposure Data Reports - 2022 L-23-003, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations2023-03-31031 March 2023 Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations ML23088A0382023-03-29029 March 2023 Stations 1, 2, & 3, Palisades Nuclear Plant, and Big Rock Point - Nuclear Onsite Property Damage Insurance ML23069A2782023-03-13013 March 2023 Request for Scoping Comments Concerning the Environmental Review of Monticello Nuclear Generating Plant, Unit 1 Subsequent License Renewal Application ML22361A1022023-02-24024 February 2023 Reactor Decommissioning Branch Project Management Changes for Some Decommissioning Facilities and Establishment of Backup Project Manager for All Decommissioning Facilities IR 05000293/20220042023-02-15015 February 2023 NRC Inspection Report No. 05000293/2022004 ML22356A0712023-01-31031 January 2023 Issuance of Exemption for Pilgrim Nuclear Power Station ISFSI Regarding Annual Radioactive Effluent Release Report - Cover Letter ML22347A2782022-12-21021 December 2022 Independent Spent Fuel Storage Installation Security Inspection Plan Dated December 21, 2022 L-22-042, Oyster, Pilgrim, Indian Point, Palisades and Big Rock Point - Proof of Financial Protection 10 CFR 140.152022-12-14014 December 2022 Oyster, Pilgrim, Indian Point, Palisades and Big Rock Point - Proof of Financial Protection 10 CFR 140.15 L-22-041, Supplemental Information to Enhance Exemption Request Detail for Pilgrim ISFSI Annual Radioactive Effluent Release Report Due Date Extension2022-12-0909 December 2022 Supplemental Information to Enhance Exemption Request Detail for Pilgrim ISFSI Annual Radioactive Effluent Release Report Due Date Extension IR 05000293/20220032022-11-18018 November 2022 NRC Inspection Report No. 05000293/2022003 L-22-036, Decommissioning Trust Fund Agreement2022-11-0808 November 2022 Decommissioning Trust Fund Agreement ML22276A1762022-10-24024 October 2022 Decommissioning International Proposed Revisions to the Quality Assurance Program Approval Forms for Radioactive Material Packages ML22266A1922022-09-23023 September 2022 and Pilgrim Nuclear Power Station - Request to Withdraw Prior Submissions from NRC Consideration ML22272A0352022-09-22022 September 2022 S. Lynch-Benttinen Letter Regarding U.S. Citizen Intent to Sue U.S. Fish and Wildlife and NOAA Fisheries Representing the Endangered Species (Na Right Whale) Which Will Be Adversely Affected by Holtec International Potential Actions ML22269A4202022-09-22022 September 2022 Citizen Lawsuit ML22241A1122022-08-29029 August 2022 Request for Exemption from 10 CFR 72.212(a)(2), (b)(2), (b)(3), (b)(4), (B)(5)(i), (b)(11), and 72.214 for Pilgrim ISFSI Annual Radioactive Effluent Release Report IR 05000293/20220022022-08-12012 August 2022 NRC Inspection Report No. 05000293/2022002 ML22215A1772022-08-0303 August 2022 Decommissioning International (HDI) Proposed Revisions to the Quality Assurance Program Approval Forms for Radioactive Material Packages ML22206A1512022-08-0101 August 2022 NRC Office of Investigations Case Nos. 1-2022-002 & 1-2022-006 ML22221A2592022-08-0101 August 2022 LTR-22-0217-1-NMSS - Town of Duxbury Letter Opposing the Irradiated Water Release from Pilgrim (Docket No. 05000293) ML22193A1662022-07-28028 July 2022 LTR-22-0154-1 - Heather Govern, VP, Clean Air and Water Program, Et Al., Letter Regarding Radioactive Wastewater Disposal from the Pilgrim Nuclear Power Station (Docket No. 05000293) ML22175A1732022-07-28028 July 2022 LTR-22-0153-1 - Response Letter to D. Turco, Cape Downwinders, from A. Roberts, NRC, Regarding Holtec-Pilgrim Plans to Dump One Million Gallons of Radioactive Waste Into Cape Cod Bay ML22154A4882022-06-0101 June 2022 Letter from Conservation Law Foundation Regarding Irradiated Water Release from Pilgrim ML22154A1622022-05-26026 May 2022 Letter and Email from Save Our Bay/Diane Turco Regarding Irradiated Water Release from Pilgrim ML22136A2602022-05-16016 May 2022 Submittal of Annual Radiological Environmental Operating Report for January 1 Through December 31, 2021 ML22136A2572022-05-16016 May 2022 Submittal of Annual Radioactive Effluent Release Report for January 1 Through December 31, 2021 ML22102A0932022-05-12012 May 2022 LTR-22-0067 Response to Matthew P. Levesque, President, Barnstable Town Council Regarding Irradiated Water Release from Pilgrim IR 05000293/20220012022-05-11011 May 2022 NRC Inspection Report No. 05000293/2022001 ML22104A0542022-04-30030 April 2022 LTR-22-0093 Response to Sheila Lynch-Benttinen, Regarding Irradiated Water Release from Pilgrim L-22-026, Occupational Radiation Exposure Data Report - 20212022-04-29029 April 2022 Occupational Radiation Exposure Data Report - 2021 ML22152A2592022-04-25025 April 2022 Zaccagnini Letter Dated 04/25/22 ML22152A2642022-04-19019 April 2022 Flynn Letter Dated 04/19/22 ML22091A1062022-04-0101 April 2022 Nuclear Onsite Property Damage Insurance (10 CFR 50.54(w)(3)) L-22-022, and Indian Point Nuclear Generating Stations 1, 2, & 3 - Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations - Holtec.2022-03-25025 March 2022 and Indian Point Nuclear Generating Stations 1, 2, & 3 - Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations - Holtec. ML22130A6762022-03-14014 March 2022 Decola Ltr Dtd 03/14/22 Re Potential Discharge of Radioactive Water from Pilgrim Nuclear Power Station ML22041B0762022-03-0707 March 2022 03-07-22 - Letter to the Honorable William R. Keating, Responds to Letter Regarding Proposed Release of Irradiated Water at Pilgrim Nuclear Power Station Into Cape Cod Bay ML22054A2962022-02-23023 February 2022 Annual ISFSI Radioactive Effluent Release Report for 2021 2024-02-02
[Table view] Category:Licensee Event Report (LER)
MONTHYEARML18179A1632018-06-21021 June 2018 Retraction of Licensee Event Report 2018-002-00, Diesel Generator a Inoperability, a Condition Prohibited by the Plant Technical Specifications 05000293/LER-2017-0132018-01-25025 January 2018 1 OF 4, LER 17-013-00 for Pilgrim Nuclear Power Station Regarding Reportable Conditions Involving Standby Gas Treatment System and Secondary Containment lnoperability Not Reported During the Previous Three Years 05000293/LER-2017-0122017-11-13013 November 2017 Start-Up Transformer Degraded Voltage Relay Found Outside Technical Specification Limit, LER 17-012-00 for Pilgrim Nuclear Power Station Regarding Start-Up Transformer Degraded Voltage Relay Found Outside Technical Specification Limit 05000293/LER-2017-0112017-08-15015 August 2017 Simultaneously Opened Reactor Building Airlock Doors Caused Loss of Secondary Containment, LER 17-011-00 for Pilgrim Nuclear Power Station Regarding Simultaneously Opened Reactor Building Airlock Doors Caused Loss of Secondary Containment 05000293/LER-2017-0102017-08-0707 August 2017 Air Accumulation Creates Small Void in Core Spray Discharge Piping, LER 17-010-00 for Pilgrim re Air Accumulation Creates Small Void in Core Spray Discharge Piping 05000293/LER-2017-0012017-07-17017 July 2017 Reactor Building Isolation Dampers Failed to Isolate, LER 17-001-01 for Pilgrim Nuclear Power Station Regarding Reactor Building Isolation Dampers Failed to Isolate 05000293/LER-2017-0092017-07-17017 July 2017 Supplement to Potential Primary Containment System Inoperability Due to Relay Concerns, LER 17-009-00 for Pilgrim Nuclear Power Station Regarding Potential Primary Containment System lnoperability Due to Relay Concerns 05000293/LER-2017-0082017-06-30030 June 2017 Supplement to 480V Bus B6 Auto Transfer Function Degraded Due to Time Delay Relay Failure, LER 17-008-00 for Pilgrim re 480V Bus B6 Auto Transfer Function Degraded Due to Time Delay Relay Failure 05000293/LER-2017-0072017-06-22022 June 2017 Supplement to Potential Inoperability of Safety Relief Valve 3A, LER 17-007-00 for Pilgrim Regarding Potential Inoperability of Safety Relief Valve 3A 05000293/LER-2016-0102017-06-14014 June 2017 MSIV Inoperability Led to a Condition Prohibited by the Plant s Technical Specifications, LER 16-010-01 for Pilgrim Nuclear Power Station re MSIV Inoperability 05000293/LER-2017-0062017-06-13013 June 2017 Source Range Monitor Inoperable During Fuel Movement, LER 17-006-00 for Pilgrim Nuclear Power Station Regarding Source Range Monitor Inoperable During Fuel Movement 05000293/LER-2017-0052017-06-0707 June 2017 10 CFR 50, Appendix J, Option B, Leak Rate Criteria Exceeded, LER 17-005-00 for Pilgrim Regarding 10 CFR 50, Appendix J, Option B, Leak Rate Criteria Exceeded 05000293/LER-2017-0042017-06-0202 June 2017 Secondary Containment Testing Led to Loss of Safety Function to Both Trains of Standby Gas Treatment System, LER 17-004-00 for Pilgrim Nuclear Power Station Regarding Secondary Containment Testing Led to Loss of Safety Function to Both Trains of Standby Gas Treatment System 05000293/LER-2017-0022017-05-25025 May 2017 Isolation of HPCI, LER 17-002-00 for Pilgrim Regarding Isolation of HPCI 05000293/LER-2017-0032017-05-25025 May 2017 Supplement to Suppression Pool Declared Inoperable Due to High Water Level, LER 17-003-00 for Pilgrim Nuclear Power Station Regarding Pressure Suppression Pool Declared Inoperable Due to High Water Level 05000293/LER-2016-0082016-12-0909 December 2016 Emergency Diesel Generator 'A' Past Inoperability, LER 16-008-00 for Pilgrim Nuclear Power Station Regarding Emergency Diesel Generator 'A' Past Inoperability 05000293/LER-2016-0072016-11-0404 November 2016 Manual Reactor Scram Due To Feedwater Regulating Valve Malfunction, LER 16-007-00 for Pilgrim Nuclear Power Station Regarding Manual Reactor Scram Due To Feedwater Regulating Valve Malfunction 05000293/LER-2016-0032016-07-11011 July 2016 Spent Fuel Storage Design Feature Exceeded, LER 16-003-00 for Pilgrim Nuclear Power Station Regarding Spent Fuel Storage Design Feature Exceeded 05000293/LER-2016-0042016-07-11011 July 2016 Salt Service Water Pump B Past Operability - Operation or Condition Prohibited by Technical Specifications, LER 16-004-00 for Pilgrim Nuclear Power Station Regarding Salt Service Water Pump B Past Operability - Operation or Condition Prohibited by Technical Specifications 05000293/LER-2016-0022016-06-20020 June 2016 Online Maintenance Test Configuration Prohibited By Technical Specifications, LER 16-002-00 for Pilgrim Nuclear Power Station Regarding Online Maintenance Test Configuration Prohibited By Technical Specifications 05000293/LER-2016-0012016-06-0909 June 2016 Both Emergency Diesel Generators Inoperable, LER 16-001-00 for Pilgrim Nuclear Power Station Regarding Both Emergency Diesel Generators Inoperable ML13149A1722013-05-26026 May 2013 E-mail from Micheal Mulligan to R.Guzman, Pilgrim Evacuation Plan Broken During Blizzard Nemo and Unenforced by the Nrc. ML0613706222006-05-11011 May 2006 LER 06-01-000, Pilgrim Re Manual Scram Due to High Offgas Recombiner Temperature Resulting from Inadequate Preventive Recombiner Preheater Pressure Control Valve Controller ML0416706152004-06-0808 June 2004 LER 99-008-01 for Pilgrim Regarding Automatic Scram at 100 Percent Power Due to Turbine Trip ML0207700612002-02-27027 February 2002 LER 99-003-01 for Pilgrim Nuclear Power Station Re Local Leak Rate Test Results Exceeding Allowable Technical Specification Leakage Rates 2018-06-21
[Table view] |
comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555.0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Pilgrim Nuclear Power Station 05000-293 2017 -01
BACKGROUND
Bus B6 supplies 480V vital power to the low pressure coolant injection (LPCI) valves that open to facilitate LPCI injection flow into the recirculation piping during the plant response to a postulated design basis event.
Power to Bus B6 is normally fed from Bus B1 (train A). Bus B2 (train B) is the back-up power feed to Bus B6. Bus B6 is designed to automatically transfer power to the opposite train power feed in the event of loss of power or degraded voltage on the feed providing power to Bus B6.
EVENT DESCRIPTION
On May 3, 2017 with the unit shutdown for refueling outage, while performing plant procedure 3.M.3-27, "480V Bus B6 Transfer Test, UV, Degraded Voltage and Timing Relays Calibration and Annunciator Verification," the time delay Agastat relay 27A-B1X/TDDO opened instantaneously, instead of with a time delay. This relay is set to drop out after a 1.25 second time delay after being de-energized. This condition was discovered during the plants refueling outage when conditions were such that the equipment normally energized/activated by this time delay relay was not required to be operable.
The 27A-B1X/TDDO relay is used only in the degraded voltage scheme and works in conjunction with relay 27-B1X/TDE. The 27A-B1X/TDDO relay picks up instantly when relays 27A-B1/1 and 27A-B1/2 sense a degraded voltage condition. Contact 3/5 of relay 27A-B1X/TDDO closes instantly energizing relay 27- B1X/TDE. The 27-B1X/TDE relay contact closes on a 1 second delay, then trips breaker 52-601 and closes breaker 52-602. The time delay of the 27A-B1X/TDDO relay keeps the degraded voltage relay trip on the 27-B1X/TDE relay for 1.25 seconds, to ensure relay 27-B1X/TDE remains energized and performs the portion of the bus transfer in which 52-601 opens and 52-602 closes.
This transfer between breakers52-601 and 52-602 works synchronously with the transfer between breakers52-102 and 52-202. The complementary relay (27A-B1Z) in this portion of the transfer logic also stays energized for 1.25 seconds on a momentary degraded voltage condition causing breakers52-102 and 52- 202 to transfer.
In this particular case, there was the potential that if relay 27A-B1X TDDO dropped out instantly on a degraded voltage condition, but the degraded voltage condition then cleared during the 1.00 second time delay to energize (TDE) for 27-B1X TDE (such that it does not energize), then breaker 52-601 would remain closed and 52-602 would remain open (i.e., no bus transfer to B2). At the same time, the complementary bus B1 breaker 52-102 relay 27A-B1Z, holding energized during the 1.25 seconds that the bus B1 degraded voltage clears, would allow that portion of the transfer scheme to operate correctly, and breaker 52-102 would open and 52-202 would close. This set of conditions would have left bus B6 De-Energized with both bus B1 and bus B2 back to normal voltage.
- 008 comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555.0001, or by e-mail to NEOB-10202, (3150.0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Pilgrim Nuclear Power Station 05000-293 2017 - 01 Thus, with contact 3/5 of relay 27A-B1X TDDO opening instantaneously instead of with a 1.25 second time delay, this portion of the transfer scheme to transfer bus B6 to bus B2 with bus B1 powering B6, for a temporary degraded voltage on bus B1, was inoperable. For any other condition of degraded voltage on bus B1 (that did not clear during the transfer), or for a significant or total loss of Bus B1 voltage, the transfer scheme to bus B2 would have functioned normally.
In addition, the ability to perform a manually controlled operation to transfer bus B6 from B1 to bus B2 under these degraded voltage conditions was available per PNPS Procedure 2.4.B.6 "Loss of bus B6". This transfer would re-power the LPCI injection valves from either bus B1 or B2 as needed.
CAUSE OF THE EVENT
The offsite vendor concluded after examinations and analysis of the time delay relay 27A-B1X/TDDO that the latch spring has an intermediate position. During energizing, the latch spring goes to the intermediate position and causes the diaphragm plunger to not fully pick up and the air system is not fully charged.
Therefore, at de-energization, it requires less time for the diaphragm plunger to pull the latch spring from the intermediate position back to the normally open position; thus creating less time delay as observed in plant testing.
CORRECTIVE ACTIONS
The Agastat time delay relay 27A-B1X/TDDO was replaced, restoring the degraded voltage protection functionality for the condition where bus B6 is being powered by bus B1.
SAFETY CONSEQUENCES
This Agastat time delay relay 27A-B1X/TDDO was installed during PNPS Refueling Outage 20 and therefore had only been installed for one cycle. This condition was discovered during the refueling outage when conditions were such that the equipment normally energized/activated by this time delay relay were not required to be operable, however based on the offsite vendor examinations and analysis this condition most likely existed during PNPS Cycle 21.
If during plant operation a bus B1 degraded voltage condition had occurred, manual actions could have been taken to transfer bus B6 from bus B1 to bus B2 per procedure PNPS 2.4.B.6, "Loss of bus B6." This transfer would re-power the LPCI injection valves and provide power to other primary containment isolation valves.
There are no consequences to the general safety of the public, nuclear safety, industrial safety and radiological safety from this event.
- 008 comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
Pilgrim Nuclear Power Station 05000-293 2017 -01 - 008
REPORTABILITY
Pilgrim Nuclear Power Station is submitting this Licensee Event Report (LER) in accordance with 10 CFR 50.73(a)(2)(i)(B) — Operation or condition prohibited by Technical Specifications; and in accordance withl0 CFR 50.73(a)(2)(v)(B), (C) and (D) — Any condition that could have prevented the fulfillment of the safety function of structures or systems that are needed to remove residual heat, control the release of radioactive material and mitigate the consequences of an accident.
PREVIOUS EVENTS
A review of PNPS LERs for the past five years identified LER 2015-004-00 "480V Bus B6 Auto Transfer Function Degraded" also documented a failure of relay 27A-B1X/TDDO. In the 2015 failure, the relay contact 3/5 never closed to initiate the transfer logic to trip open breaker 52-601 and close breaker 52-602.
REFERENCES:
CR-PNP-2017-4768 CR-PNP-2015-3454
|
---|
|
|
| | Reporting criterion |
---|
05000293/LER-2017-010 | Air Accumulation Creates Small Void in Core Spray Discharge Piping LER 17-010-00 for Pilgrim re Air Accumulation Creates Small Void in Core Spray Discharge Piping | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-011 | Simultaneously Opened Reactor Building Airlock Doors Caused Loss of Secondary Containment LER 17-011-00 for Pilgrim Nuclear Power Station Regarding Simultaneously Opened Reactor Building Airlock Doors Caused Loss of Secondary Containment | | 05000293/LER-2017-001 | Reactor Building Isolation Dampers Failed to Isolate LER 17-001-01 for Pilgrim Nuclear Power Station Regarding Reactor Building Isolation Dampers Failed to Isolate | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-012 | Start-Up Transformer Degraded Voltage Relay Found Outside Technical Specification Limit LER 17-012-00 for Pilgrim Nuclear Power Station Regarding Start-Up Transformer Degraded Voltage Relay Found Outside Technical Specification Limit | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-002 | Isolation of HPCI LER 17-002-00 for Pilgrim Regarding Isolation of HPCI | 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | 05000293/LER-2017-013 | 1 OF 4 LER 17-013-00 for Pilgrim Nuclear Power Station Regarding Reportable Conditions Involving Standby Gas Treatment System and Secondary Containment lnoperability Not Reported During the Previous Three Years | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | 05000293/LER-2017-003 | Supplement to Suppression Pool Declared Inoperable Due to High Water Level LER 17-003-00 for Pilgrim Nuclear Power Station Regarding Pressure Suppression Pool Declared Inoperable Due to High Water Level | 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-004 | Secondary Containment Testing Led to Loss of Safety Function to Both Trains of Standby Gas Treatment System LER 17-004-00 for Pilgrim Nuclear Power Station Regarding Secondary Containment Testing Led to Loss of Safety Function to Both Trains of Standby Gas Treatment System | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | 05000293/LER-2017-005 | 10 CFR 50, Appendix J, Option B, Leak Rate Criteria Exceeded LER 17-005-00 for Pilgrim Regarding 10 CFR 50, Appendix J, Option B, Leak Rate Criteria Exceeded | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded | 05000293/LER-2017-006 | Source Range Monitor Inoperable During Fuel Movement LER 17-006-00 for Pilgrim Nuclear Power Station Regarding Source Range Monitor Inoperable During Fuel Movement | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-007 | Supplement to Potential Inoperability of Safety Relief Valve 3A LER 17-007-00 for Pilgrim Regarding Potential Inoperability of Safety Relief Valve 3A | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-008 | Supplement to 480V Bus B6 Auto Transfer Function Degraded Due to Time Delay Relay Failure LER 17-008-00 for Pilgrim re 480V Bus B6 Auto Transfer Function Degraded Due to Time Delay Relay Failure | 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2017-009 | Supplement to Potential Primary Containment System Inoperability Due to Relay Concerns LER 17-009-00 for Pilgrim Nuclear Power Station Regarding Potential Primary Containment System lnoperability Due to Relay Concerns | 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
|