05000293/LER-2010-001, Regarding Single Train of Reactor Building Closed Cooling Water System Inoperable for Time Period Exceeding Technical Specification Limits

From kanterella
(Redirected from 05000293/LER-2010-001)
Jump to navigation Jump to search
Regarding Single Train of Reactor Building Closed Cooling Water System Inoperable for Time Period Exceeding Technical Specification Limits
ML100740345
Person / Time
Site: Pilgrim
Issue date: 03/11/2010
From: Bronson K
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER 10-001-00
Download: ML100740345 (6)


LER-2010-001, Regarding Single Train of Reactor Building Closed Cooling Water System Inoperable for Time Period Exceeding Technical Specification Limits
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
2932010001R00 - NRC Website

text

- Entergy Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360 Kevin H. Bronson Site Vice President March 11,2010 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555

SUBJECT:

Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station Docket No.: 50-293 License No.: DPR-35 Licensee Event Report 2010-001 -00 LETTER NUMBER: 2.10.017

Dear Sir or Madam:

The enclosed Licensee Event Report (LER) 2010-001 -00, "Single Train of Reactor Building Closed Cooling Water System Inoperable for Time Period Exceeding Technical Specification Limits" is submitted in accordance with 10 CFR 50.73.

This letter contains no commitments.

Please do not hesitate to contact Mr. Joseph R. Lynch, (508) 830-8403, if there are any questions regarding this submittal.

Sincrl

<~'

Kevin H. Bronson FXM Enclosure cc:

Mr. James S. Kim, Project Manager Plant Licensing Branch I-1 Division of Operator Reactor Licensing Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission One White Flint North O-8C2 11555 Rockville Pike Rockville, MD 20852 INPO Records 700 Galleria Parkway Atlanta, GA 30399-5957 Mr. Samuel J. Collins Regional Administrator, Region 1 U.S. Nuclear Regulator Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Pilgrim Nuclear Power Station

/) /2

NRC Form 366 U.S. NUCLEAR REGULATORY COMMISSION Approved by OMB: No. 3150-0104 Expires: 08/31/2010 (9-2007)

Estimated burden per response to comply with this mandatory information collection request: 80 hrs. Reported lessons learned are incorporated into the LICENSEE EVENT REPORT (LER) licensing process and fed back to industry. Send comments regarding burden estimate to the Records and FOIA/Privacy Service Branch (T-5 F52). U.S.

Nuclear RegulatoryCommission, Washington, DC 20555-0001, or by internet e-mail to infocollects@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503.

If a means used to impose and information collection does not display a currently valid control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE PILGRIM NUCLEAR POWER STATION 05000-293 1 of 5
4. TITLE Single Train of Reactor Building Closed Cooling Water System Inoperable for Time Period Exceeding Technical Specification Limits
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED SEQUENTIAL NUMBER REVISION FACILITY NAME DOCKET MONTH DAY YEAR YEAR NUMBER MONTH DAY YEAR N/A NUMBER 05000 FACILITY NAME DOCKET 01 10 2010 2010 001 00 03 11 2010 N/A NUMBER 05000
9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR: (Check one or more) 20.2201_(b) 22.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii)

N 22.2202(d) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(A) 20.2203(a)(1) 20.2203(a)(4) 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 20.2203(a)(2)(i) 50.36(3)(1 )(i)(A) 50.73(a)(2)(iii) 50.73(a)(2)(ix)(A) 20.2203(a)(2)(ii) 50.36(3)(1 )(ii)(A) 50.73(a)(2)(iv)(A) 50.73(a)(2)(x)

10. Power Level 20.2203(a)(2)(iii) 50.36(c)(2) 50.73(a)(2)(v)(A) 73.71(a)(4) 20.2203(a)(2)(iv) 50.46(a)(3)(iil) 50.73(a)(2)(v)(B) 73.71 (a)(5) 100 20.2203(a)(2)(v) 50.73(a)(2)(i)(A) 50.73(a)(2)(v)(C)

OTHER 20.2203(a)(2)(vi)

X 50.73(a)(2)(i)(B) 50.73(a)(2)(v)(D)

Specify in Abstract below or in

EVENT DESCRIPTION

On January 10, 2010 during a backwash evolution on the RBCCW System heat exchanger, plant operators discovered a broken bolt on the clamp of the seismic support for the instrument line of the local pump suction pressure gauge attached to the RBCCW "A" Train pump suction pipe. The seismic support is provided to ensure instrument line integrity and is relied on to ensure that RBCCW leakage limits will not be exceeded. The broken bolt compromised the seismic support. The RBCCW "A" Train was declared inoperable. A work request was immediately initiated and the broken bolt was replaced and the subsystem was returned to operable status. A 10 CFR 50.72 report was not required because the subsystem was restored to operable status prior to exceeding the 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> TS LCO action statement for one RBCCW subsystem inoperable as defined in TS 3.5.B.3.B.

Subsequent engineering review of the as-found condition revealed that firm evidence existed to indicate that the bolt had been broken before discovery for a time period that exceeded the 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> allowable TS LCO action statement for one RBCCW subsystem inoperable. As a result, a Licensee Event Report (LER) per 10 CFR 50.73 is required.

CAUSE

The probable apparent cause was identified to be corrosion that caused a progressive crack which eventually failed the bolt.

CORRECTIVE ACTION

The immediate corrective action included installation of a new bolt on the instrument line seismic support clamp. Additional corrective action was taken to identify extent of condition and to walkdown the Reactor Building Auxiliary Bay areas where similar conditions could exist. No other broken bolts or seismic support damage were identified. Guidance for performing system walkdowns and inspecting supports and fasteners was reviewed with System Engineering personnel. Additional corrective actions are planned to replace the bolt on the opposite side of the affected seismic support clamp and to replace both bolts on the suction gauge instrument line seismic support clamp on the RBCCW "B" Train.

Results of the formal cause evaluation and applicable corrective actions will be tracked in 'the Corrective Action Program under CR-PNP-2010-0130.

SAFETY CONSEQUENCES

The event posed no threat to public health and safety.

The event occurred at during normal power operation while at 100% power with the mode switch in the "RUN" position. The reactor vessel pressure was approximately 1030 psig with reactor water temperature at saturation temperature for that pressure.

The Core Standby Cooling Systems (CSCS) consist of the High Pressure Coolant Injection (HPCI)

System, Automatic Depressurization System (ADS), Core Spray (CS) System, and the Residual Heat Removal (RHR) System in the Low Pressure Core Coolant Injection (LPCI) mode.. Although not part of the CSCS, the Reactor Core Isolation Cooling (RCIC) System is capable of providing water to the reactor vessel for high pressure core cooling, similar to the HPCI System. These systems were operable when the bolt failure was discovered.

The RBCCW System provides cooling to the CSCS System components and provides a heat sink for the RHR System heat exchangers. The system also provides required cooling to the equipment located in the Reactor Building during normal planned station operations, and provides a barrier between the primary system and the Salt Service Water (SSW) System.

The RBCCW System consists of two independent closed loops. Each loop has three centrifugal pumps and take suction from the RBCCW heat exchanger. A 500 gallon head tank is located at the highest point in the system and accommodates system volume changes, maintains static pressure in the loop, detects gross leaks in the system, and provides a means for adding makeup water. Head tank level is monitored and will alarm in the main control room if a level deviation exists. The system is designed with sufficient redundancy so that no single system component failure can prevent the system from performing its safety objective.

The bolt failure on seismic support clamp supporting the instrument line to the RBCCW "A" Train suction gauge has no affect on the RBCCW "B" Train.

The RBCCW "A" Train main suction line instrument piping that is supported by the seismic support was functional prior to and during the time that the bolt failure was discovered. After discovery, the RBCCW "A" Train was declared inoperable. The bolt on the seismic support was replaced and the subsystem was returned to operable status within eight (8) hours after the subsystem was declared inoperable. Subsequent engineering review of the as-found condition revealed that firm evidence existed to indicate that the bolt had been broken before discovery for a time period longer than permitted by technical specifications.

REPORTABILITY

This report is submitted in accordance with 10 CFR 50.73(a)(2)(i)(B) for any operation or condition which was prohibited by Technical Specifications.

SIMILARITY TO PREVIOUS EVENTS A review was conducted of Pilgrim Station LERs which involved either failure of an RBCCW subsystem or failure of seismic supports. No LERs were found which were directly applicable to this event. The following LERs addressed similar concerns:

LER 98-003-00 describes an event where non-conformances in the RBCCW and TBCCW System heat exchanger seismic support plates were identified to be outside the design basis and non-conforming with respect to design drawings and FSAR damping values. An operability evaluation was written and corrective actions were taken to restore full qualifications.

LER 96-008-00 describes an event where a leak was discovered on the RBCCW "B" Train heat exchanger and the condition resulted in declaring the subsystem inoperable. The condition resulted in entry into TS LCO 3.5.B.3.B and subsequent plant shutdown.

LER 79-039/01T-0 describes an event where an analytical re-analysis of the RBCCW "B" Train indicated that the as-built configuration would not remain functional during Safe Shutdown Earthquake. The event resulted from a design error. Three pipe supports were modified per PDC 79-24 A-1 to correct the condition.

ENERGY INDUSTRY IDENTIFICATION SYSTEM (EIIS) CODES The following EIIS codes are applicable to this report:

COMPONENTS CODES Support SPT SYSTEMS CODES Closed / Component Cooling Water Systems (RBCCW)

CC