05000293/LER-2014-001, Regarding Condition Prohibited by Technical Specifications

From kanterella
(Redirected from 05000293/LER-2014-001)
Jump to navigation Jump to search
Regarding Condition Prohibited by Technical Specifications
ML14196A042
Person / Time
Site: Pilgrim
Issue date: 07/07/2014
From: Noyes D
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
2.14.054 LER 14-001-00
Download: ML14196A042 (6)


LER-2014-001, Regarding Condition Prohibited by Technical Specifications
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function
2932014001R00 - NRC Website

text

"En terg Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360 David E. Noyes, Director Regulatory & Performance Improvement Letter No. 2.14.054 July 7, 2014 United States Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001

Subject:

LER: 2014-001-00, "Condition Prohibited By Technical Specifications" Entergy Nuclear Operation, Inc.

Pilgrim Nuclear Power Station Docket No. 50-293 License No. DPR-35

Dear Sir or Madam:

The enclosed Licensee Event Report (LER) 2014-001-00, "Condition Prohibited By Technical Specifications" is submitted in accordance with 10 CFR 50.73(a)(2)(i)(B) - "Any operation or condition which was prohibited by Technical Specifications".

This letter contains no commitments.

Please do not hesitate to contact me at (508) 830-7800, if there are any questions regarding this submittal.

Sincerely, David E.

oyes Director, Regulatory and Performance Improvement DEN/mew

Enclosure:

Pilgrim Nuclear Power Station LER 2014-001-00, "Condition Prohibited By Technical Specifications" cc:

Mr. William M. Dean Regional Administrator, Region 1

.U.S. Nuclear Regulatory Commission 2100 Renaissance Blvd., Suite 100 King of Prussia, PA 19406-2713 USNRC Senior Resident Inspector Pilgrim Nuclear Power Station Ms. Nadiyah S. Morgan, Project Manger Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop O-8-F2 11555 Rockville Pike Rockville, MD. 20852 INPO Records 700 Galleria Parkway Atlanta, GA 30399-5957

Enclosure to PNP Letter 2.14.054 Licensee Event Report 2014-001-00 "Condition Prohibited By Technical Specifications" (4 Pages)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 01/31/2017 (01-2014)

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE Pilgrim Nuclear Power Station 05000293 1 OF 4
4. TITLE Condition Prohibited By Technical Specifications
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL REV MYCLIY NOCK NUMBER NUMBER NO.

MONTH DAY YEAR N/A N/A FACILITY NAME DOCKET NUMBER 05 06 2014 2014-001 00 07 07 2014 N/A N/A

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR 6: (Check all that apply)

R NE 20.2201(b)

[

20.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii)

RU 20.2201 (d)

  • l20.2203(a)(3)(ii)

D50.73(a)(2)(ii)(A)

  • 150.73(a)(2)(viii)(A)

E 20.2203(a)(1)

E] 20.2203(a)(4) 50.73(a)(2)(ii)(B)

[

50.73(a)(2)(viii)(B)

__l 20.2203(a)(2)(i) 50.36(c)(1)(i)(A) 50.73(a)(2)(iii)

- 50.73(a)(2)(ix)(A)
10. POWER LEVEL E

20.2203(a)(2)(ii) 50.36(c)(1)(ii)(A)

I 50.73(a)(2)(iv)(A)

D 50.73(a)(2)(x)

E 20.2203(a)(2)(iii)

D 50.36(c)(2)

E 50.73(a)(2)(v)(A)

[

73.71(a)(4) 100 20.2203(a)(2)(iv)

E] 50.46(a)(3)(ii) 50.73(a)(2)(v)(B)

E 73.71(a)(5)

E] 20.2203(a)(2)(v)

El 50.73(a)(2)(i)(A)

[] 50.73(a)(2)(v)(C)

OTHER 20.2203(a)(2)(vi) 50.73(a)(2)(i)(B)

D 50.73(a)(2)(v)(D)

Specify inoAbstract3below or in NRC Form 366A

12. LICENSEE CONTACT FOR THIS LER LICENSEE CONTACT ITELEPHONE NUMBER (Include Area Code)

Mr. David E. Noyes, Regulatory and Performance Improvement Director I

14. SUPPLEMENTAL REPORT EXPECTED D-YES (If yes, complete 15. EXPECTED SUBMISSION DATE)

ABSTRACT (Limit to 1400 spaces, i.e., approximately 15 single-spaced typewritten lines)

On May 6, 2014, with Pilgrim Nuclear Power Station (PNPS) in the RUN Mode operating at 100 percent power, the NRC Resident Inspector raised a concern about the PNPS method of complying with PNPS Technical Specification (TS) Limiting Condition for Operation (LCO) 3.7.A.2.b when a Primary Containment Isolation Valve is inoperable. TS LCO 3.7.A.2.b.requires that at least one containment isolation valve in each line having an inoperable valve shall be deactivated in the isolated condition. Deactivation means to electrically or pneumatically disarm, or otherwise secure the valve. PNPS interpretation and practice had been that a "Danger" tag on the control switch meets this requirement for a fail-closed valve with no automatic valve opening signal. At the time, Primary Containment Isolation Valves AO-5042A and AO-5044A were inoperable in the isolated position but were not deactivated.

The apparent cause of this event is failure to properly revise procedures and practices when LCO TS 3.7.A.2.b was revised in 1988 to permit periodic opening of the deactivated valve in the line under administrative controls.

This event was not risk significant and had no adverse impact on the health and safety of the public.

NRC FORM 366 (01-2014)(01-2014)

1. FACILITY NAME U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

ý Pilgrim Nuclear Power Station BACKGROUND The basic function of all primary containment isolation valves is to provide necessary isolation of the containment in the event of accidents or similar critical conditions when the free release of containment atmosphere cannot be permitted.

The containment isolation valves are listed on Updated Final Safety Analysis Report Table 5.2-4. This table also defines the valve status (normally open or normally closed) during normal reactor operation and shows the signals required to initiate their desired operation. The primary containment isolation valves are grouped into three basic classes.

Class A valves are on process lines that communicate directly with the reactor vessel and penetrate the primary containment. These lines require two valves in series, one inside the primary containment and one outside the primary containment. They are located as close to the primary containment boundary as practical. Except in the case of check valves, both valves shall close automatically on isolation signal. Both valves shall receive the isolation (closure) signal even if normally closed during reactor operation. Since check valves close on reverse process flow, they are used to isolate some incoming lines. All Class A valves except check valves are capable of remote manual control from the control room.

Class B valves are on process lines that do not directly communicate with the reactor vessel, but penetrate the primary containment and communicate with the primary containment free space. These lines require two valves, in series, both of them located outside the primary containment, and as close to the primary containment boundary as practical. For process lines that have a water seal (such as Core Standby Cooling System pump suction lines), one isolation valve without an automatic isolation signal closure, in addition to the water seal is adequate to meet isolation requirements.

Except in the case of check valves or valves in water sealed process lines, both valves close automatically on isolation signal, both valves receive the isolation closure signal even if normally closed during reactor operation. All Class B motor operated or solenoid operated valves are capable of remote manual control from the control room.

Class C valves are on process lines that penetrate the primary containment but do not communicate directly with the reactor vessel, with the primary containment free space, or with the environs. Class C lines require only one valve located outside the primary containment which closes automatically by process action (i.e., reverse flow) or by remote manual operation from the control room

EVENT DESCRIPTION

On May 6, 2014, with Pilgrim Nuclear Power Station (PNPS) in the RUN Mode operating at 100 percent power, the NRC Resident Inspector raised a concern about the PNPS method of complying with PNPS Technical Specification (TS) Limiting Condition for Operation (LCO) 3.7.A.2.b when a Primary Containment Isolation Valve is inoperable. TS LCO 3.7.A.2.b.requires that at least one containment isolation valve in each line having an inoperable valve shall be deactivated in the isolated condition. Deactivation means to electrically or pneumatically disarm, or otherwise secure the valve, PNPS interpretation and practice had been that a "Danger" tag on the control switch meets this requirement for a fail-closed valve with no automatic valve opening signal. At the time, Primary Containment Isolation Valves AO-5042A and AO-5044A were inoperable in the isolated position but were not deactivated.U.S. NUCLEAR REGULATORY COMMISSIO (01-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE YEAR SEQUENTIAL REV NUMBER NO.

Pilgrim Nuclear Power Station 05000293 j 3OF4 12014 1 001 00

CAUSE OF THE EVENT

The apparent cause of this event is failure to properly revise procedures and practices when TS LCO 3.7.A.2.b was revised by the issuance of TS Amendment 113 in 1988. Prior to this amendment, TS LCO 3.7.D.2 stated: "In the event any isolation valve specified in Table 3.7.1 becomes inoperable, at least one containment isolation valve in each line having an inoperable valve shall be placed in the isolated condition." TS Amendment 113 relocated the actions for an inoperable containment isolation valve to TS LCO 3.7.A.2.b and incorporated the requirement to deactivate (not just isolate) a valve in the line in the isolated condition. The basis for requiring deactivation was to provide positive control of an isolation barrier such that the barrier cannot be adversely affected by a spurious single active failure. The PNPS interpretation and practice of placing a "Danger" tag on the control switch for a valve with no automatic valve opening signal does not provide that additional level of protection.

EXTENT OF CONDITION Seventy-one LCO entries into TS LCO 3.7.A.2.b occurred during the previous three year review period. Deactivation of a valve in the line did not occur for the following three additional LCO TS LCO 3.7.A.2.b entries:

LCO ACT-i 0110 Post Accident Sampling System Torus Gas Sample Valves LCO ACT-i 0158 Primary Containment Atmosphere Control Valve AO-5035B LCO ACT-i 0226 Post Accident Sampling System Valve SV-5065-82 The above valves were in the closed isolated position during the LCO or the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> shutdown TS LCO 3.7.A.5 was entered, if required.

CORRECTIVE ACTIONS

The immediate corrective action was to deactivate Primary Containment Isolation Valves AO-5042A and AO-5044A by isolating the air supply root valve to each of the valve actuators. The valves have been repaired and restored to operable status.

Additional corrective actions are being tracked in the Corrective Action Program under CR-PNP-2014-02008.

SAFETY CONSEQUENCES

This event posed no actual threat to the public health and safety.

During the period that Primary Containment Isolation Valves AO-5042A and AO-5044A were isolated but not deactivated, all safety systems were operable except for short durations to perform required surveillance testing. In the isolated condition, the valves were capable of performing the required safety function. The valves had been declared inoperable due to the closing time from the open position being greater than the surveillance acceptance criteria. Since each penetration has two isolation valves and each valve was closed, the safety function was satisfied, since spurious actuation of both valves would be required to prevent the safety function from occurring.U.S. NUCLEAR REGULATORY COMMISSIOlb (01-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE YEAR SEQUENTIAL REV NUMBER NO.

Pilgrim Nuclear Power Station 05000293 4 OF 4 2014 001 00

REPORTABILITY

This report is submitted in accordance with 10CFR50.73(a)(2)(i)(B) - Operation or Condition Prohibited by Technical Specifications. The failure to deactivate a valve in a containment penetration line when one isolation valve in the line is inoperable as required by TS LCO 3.7.A.2.b is a condition prohibited by the PNPS Technical Specifications.

PREVIOUS EVENTS A review for similar events reported by Licensee Event Reports (LERs) submitted to the NRC was conducted. The review focused on LERs involving a failure to properly implement a TS amendment change resulting in "Operation or Condition Prohibited by Technical Specifications". The review did not identify the occurrence of any similar events.

ENERGY INDUSTRY IDENTIFICATION SYSTEM (EIIS) CODES Not Applicable REFERENCES Condition Report CR-PNP-2014-02008 - Primary Containment Isolation Valves Not Deactivated Resulting in a Condition Prohibited by Technical Specifications 1