05000293/LER-2015-010, Regarding Motor-Operated Valve Control Circuit Vulnerability to Information Notice 92-18 Concern

From kanterella
(Redirected from 05000293/LER-2015-010)
Jump to navigation Jump to search
Regarding Motor-Operated Valve Control Circuit Vulnerability to Information Notice 92-18 Concern
ML15335A066
Person / Time
Site: Pilgrim
(DPR-035)
Issue date: 11/19/2015
From: Noyes D
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
2.15.083 LER 15-010-00
Download: ML15335A066 (7)


LER-2015-010, Regarding Motor-Operated Valve Control Circuit Vulnerability to Information Notice 92-18 Concern
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(vi)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition
2932015010R00 - NRC Website

text

'~En tergy Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360 November 19, 2015 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555

SUBJECT:

Licensee Event Report 2015-010-00, Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station Docket No.: 50-293 License No.: DPR-35 LETTER NUMBER:

2.15.083

Dear Sir or Madam:

The enclosed Licensee Event Report (LER) 201 5-01 0-00, Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern, is submitted in accordance with 10 CFR 50.73.

This letter contains no commitments.

Please do not hesitate to contact Mr. Everett P. Perkins, Jr. at (508) 830-8323, if there are any questions regarding this submittal.

Sincerely, Director, Regulatory and Performance Improvement : Licensee Event Report 2015-01 0-00, Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern (4 pages)

PNPS Letter 2.15.083 Page 2 of 2 cc:

Mr. Daniel H. Dorman Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 2100 Renaissance Blvd., Suite 100 King of Prussia, PA 19406-2713 Ms. Booma Venkataraman, Project Manager Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop O-8C2A Washington, DC 20555 USNRC Senior Resident Inspector Pilgrim Nuclear Power Station Letter Number 2.15.083 Licensee Event Report 2015-010-00 Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern (4 Pages)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXP!RES: 0113112017 (02-201 4)

=,

Estimated burden per response to comply with this mandatory collection request: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.

Reported lessons learned are incorporated into the licensing process and fed back to industry.

Send comments regarding burden estimate to the FOIA, Prinacy and Information Collections

'~ LCENSEEREORTBranch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by EVENT(LER)

Internet e-mail to Infocollects.Resource@nrc.gov, and to the Desk Officer, Office of Inforrsation and Regulatory Affairs, NEOB-1 0202, (31 50-0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently nalid 0MB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE Pilgrim Nuclear Power Station 05000293 1 OF 4
4. TITLE Motor-Operated Valve Control Circuit Vulnerability to Information Notice 92-18 Concern 5.EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YA SEET, I HE

___..____DO*UM*

YER NUMBER NO.

MONTH DAY YEAR N/A N/A ItFACILITY NAME IDOCKET NUMBER 10 05 2015 2015 -

010 001 11 I19 12015 N/A N/A

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR *: (Check all that apply)

D 20.2201(b)

I~ 20.2203(a)(3)(i)

LI] 50.73(a)(2)(i)(C)

I* 50.73(a)(2)(vii)

N D--

20.2201(d)

D 20.2203(a)(3)(ii)

L*]50.73(a)(2)(ii)(A)

D 50.73(a)(2)(viii)(A) 10 OWRLVE I

20.2203(a)(2)1) i*

20.2236()(4)ii) 50.73(a)(2)(iv)(A)

I~ 50.73(a)(2)(vi)(a L1 20.2203(a)(2)(iii)

[--] 50.36(c)(2)

I-- 50.73(a)(2)(v)(A)

D 73.71(a)(4) 10 L 20.2203(a)(2)(iv) i*

50.46(a)(3)(ii)

[I]50.73(a)(2)(v)(B)

[]

73.71(a)(5)

I* 20.2203(a)(2)(v)

  • 1 50.73(a)(2)(i)(A)

[* 50.73(a)(2)(v)(C)

OTHER fl1**

Specify in Abstract below or in 20.2203(a)(2)(vi) 50.73(a)(2)(i)(B)

'I50.73(a)(2)(v)(D)NRFom6A

12. LICENSEE CONTACT FOR THIS LER LICENSEE CONTACT TELEPHONE NUMBER (Include A*rea Code)

Mr. Everett P. Perkins, Jr. - Regulatory Assurance Manager 508-830-8323IIMANU-IREPORTABLE I.I MANU-REPORTABLE

CAUSE

I SYSTEM ICOMPONENT IFACTURER TO EPIX

':i*;

CAUSE

SYSE CMOET FACTURER TO EPIX NA

14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED MONTH DAY YEAR I,

[~1SUBMISSION Lj YES (If yee, complete 15. EXPECTED SUBMISSION DATE)

NO DATE ABSTRACT (Limit to 1400 spaces, iLe., approximately 15 sin gle-spaced typewritten lines)

On Monday, October 5, 2015 at 1725 hours0.02 days <br />0.479 hours <br />0.00285 weeks <br />6.563625e-4 months <br /> EST, with the Reactor Mode Select Switch in the Run position and the reactor at approximately 100 percent core thermal power, Pilgrim Station identified and reported a vulnerability applicable to 10 CFR 50, Appendix R, Section lll.G, Fire Protection of Safe Shutdown Capability. The specific vulnerability involved lack of limit and torque switch protection of motor operated valves (MOVs) during an unlikely scenario of a large scale fire, forced evacuation of the Main Control Room (MCR), and spurious operation of MOVs due to fire damage. This potential vulnerability is identified in NRC Information Notice (IN) 92-18. Discovery of the vulnerability was determined to be reportable.

The cause of the event was evaluated and determined to be the result of incorrect assumptions applicable to the initial evaluation of the IN 92-18 concern and improper use of the Corrective Action Program when discovering new Appendix R open items. Corrective actions taken included the performance of hourly fire watches in the plant areas where MOV local operation is credited for the MOV control cables that could be affected. Valve control circuit modifications are under development and scheduled for implementation.

A fire event did not occur. There was no impact to public health and safety.

NRC FORM 366 (01-2014)U.S. NUCLEAR REGULATORY COMMISSION (02-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET_______

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE SEQUENTIAL REV I

YEAR NUMBER NO.

Pilgrim Nuclear Power Station 05000293 2 OF 4 [2015 010 00 BACKGROUND Pilgrim is an Appendix R plant. As such, Pilgrim is required to meet 10 CFR 50, Appendix R Sections Ill.G, J, and 0 requirements. Section Ill.G, provides for fire protection of safe shutdown capability.Section III.G.3 identifies that Alternative or Dedicated Shutdown capability should be provided if the requirements of Section III.G.2 of Appendix R are not satisfied.

Pilgrim provided Alternative Shutdown capability for fires in the Main Control Room (MCR), Cable Spreading room (CSR), and for the east and west portions of the Reactor Building. The NRC approved this Alternative Shutdown capability as part of the initial Appendix R program reviews. NRC SER dated November 2, 1983 documents approval of the proposed Alternative Shutdown strategy.

As part of industry driven actions taken to address operator manual actions (OMAs) and multiple spurious operations (MSOs) in the 2006 to 2012 time frame, Pilgrim Station initiated actions to update the site calculation (PS-32) used to evaluate circuit separation and the associated software program used to perform the circuit separation analysis. This update effort involved resolution of numerous issues, including the following regulatory and non-regulatory compliance concerns:

/

1. Operator Manual Actions in lIIl.G.2 fire areas (not allowed for Hot shutdown, but allowed if important to shutdown or used for cold shutdown)
2. Operator Manual Actions in III.G.3 fire areas (allowed if feasible for both hot shutdown and cold shutdown)
3. Multiple Spurious Operations (MSOs) in III.G.2 areas (req~uired review for reg compliance)
4. Multiple Spurious Operations (MSOs) in IlI.G.3 areas (not a required review for reg compliance)
5. Other Appendix R Open Issues as noted in update reviews (i.e., Information Notice (IN) 92-18; required for compliance)

These specific issues were identified as open items and listed as open items to the Station's Appendix R circuit separation calculation (PS-32).

As part of the update effort, the station reviewed the initial assumptions related to IN 92-18 concerns. Valve wiring reviews were performed and identified that IN 92-18 wiring modifications were not performed for numerous valves that are credited for use to demonstrate Alternative Shutdown capability. This issue was identified in the PS-32 calculation as open item E and tracked as a required corrective action under a condition report (CR-PNP-2012-669). This condition report addressed actions to update the overall Appendix R report.

EVENT DESCRIPTION

During preparation for the 2015 Fire Protection Triennial Inspection, it was noted that PS-32 unresolved open items existed in Section 6.5 of the report. A review of compensatory actions taken to address these open items indicated that compensatory fire watches were not established for areas where IN 92-18 concerns were identified to exist. Condition Report (CR-PNP-2015-7993) was issued due to the lack of a compensatory fire watch.

The reportability review of the condition report for lack of a compensatory fire watch was performed on Monday, October 5, 2015. This reportability review concluded that a vulnerability applicable to 10 CFR 50, Appendix R, Section Ill.G, Fire Protection of Safe Shutdown Capability existed and that the issue should be reported per 10 CFR 50.72 report requirements. The concern was reported as a condition that resulted in an unanalyzed condition that could degrade plant safety. The specific vulnerability involves lack of limit and NRC FORM 366 (01-2014)U.S. NUCLEAR REGULATORY COMMISSION (02-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE 1 ERISEQUENTIAL IREV N UMBER NO.

Pilgrim Nuclear Power Station 05000293 3 OF 4 120151 010 I00 torque switch protection of motor operated valves (MOVs) credited for use in the Alternative Shutdown strategy. These valves are required to be isolated from their associated power and control cables routed in the MCR and CSR, and operated locally to accomplish safe shutdown. The requirement to locally operate the MOVs involves the unlikely scenario of a large scale fire, forced evacuation of the MCR, and spurious operation of MOVs due to fire damage. This is the potential vulnerability identified in NRC IN 92-18.

CAUSE OF THE EVENT

The apparent cause of the event was evaluated and determined to be the incorrect use of the Corrective Action Program by not initiating new condition reports when discovering new issues where compliance questions could not be readily answered. This would have driven a formal evaluation for each PS-32 open item for operability/reportability determination and the implementation of fire watches.

Initial tracking for MSO lll.G.2, MSO lll.G.3 and traditional Appendix R open items obscured recognition of problems that needed fire watches with issues that did not need fire watches. This led to a loss of focus and a distraction from issue resolution instead of proper condition report characterization. The difference between the regulatory requirements for MSO categories and Appendix R compliance contributed to the error trap.

When the updated Appendix R analysis report (PS-32) from the contractor was accepted by Pilgrim acknowledging all issues, a separate CR was not written to capture and evaluate the individual open items for operability and reportability.

CORRECTIVE ACTIONS

Corrective actions taken included the posting of compensatory hourly fire watches in the plant areas where MOV local operation is credited and the MOV control cables could be affected.

Valve control circuit modifications are under development to address the IN 92-18 concern. The modifications have been scheduled for implementation.

Additional corrective actions were issued to review current Appendix R (PS-32) gap items to ensure appropriate compensatory measures are in-place.

SAFETY CONSEQUENCES

Postulated Appendix R fire events have been evaluated and Safe and Alternative Shutdown strategies and capability have been provided. Safe and alternative safe shutdown systems and procedures have been developed to address the potential for postulated plant fire events that affect all equipment and all cables located in a given plant fire area. The IN 92-18 concern was identified to have a potential affect on safe shutdown capability in the MCR, CSR, and the Reactor Building east and west fire areas.

The postulated fire is assumed to spread and challenge all safe shutdown equipment and cables located in the area regardless of whether the area has significant fire hazards, ignition sources, or large spatial separation.

The postulated fire evaluation does not credit plant actions taken to minimize potential fires by controlling transient combustibles in plant areas and providing fire retardant cables. The evaluation also does not provide credit for automatic fire detection capability which alarms in the continuously manned control room; automatic suppression capability in areas with fire hazards; or the availability of a continuously manned fire brigade staff that will respond to a fire and manually suppress and control the spread of fire.

NRC FORM 366 (01-2014)U.S. NUCLEAR REGULATORY COMMISSION (02-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET____________

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE ISEQUENTIAL REV IYEAR NUMBER NO.

Pilgrim Nuclear Power Station 05000293 4 OF 4 112015 010 00 A detailed evaluation of the risk significance of fires in the areas potentially impacted by the IN 92-18 issue was performed. This risk review involved evaluation of potential ignition sources in the area; location of credited Appendix R equipment and cables in relation to the ignition sources; available fire safe shutdown procedures; the fire resistant qualities of cables and equipment provided in the area; the automatic fire detection capability provided in the area; and the automatic and manual suppression capability provided. This risk significance determination review identified that the Pilgrim vulnerability to the IN 92-18 concern met NRC acceptance criteria for a very low fire risk concern.

Based on these reviews, there was no adverse impact on the public health or safety.

REPORTABILITY

This report is submitted in accordance with 10 CFR 50.73(a)(2)(ii)(B) - Any event or condition where resulted in: the nuclear power plant being in a unanalyzed condition that significantly degraded plant safety.

PREVIOUS EVENTS 10 CFR 50, Appendix R fire protection issues that resulted in LER reports were reviewed. The most recent Appendix R LEns were reported in the 1997 to 1999 timeframe. These LERS are summarized as follows:

LER 97-029-00, Shutdown Cooling (SDC) Suction Valves Vulnerability to Damage from Potential Failure Mode Involving Hot Shorts.

LER 98-012-00, Incomplete Installation of Fire Barrier in the Cable Spreading Room.

LER 98-013-00 thru LER 98-013-02, Inconclusive Fire Barrier Test Data.

LER 98-023-00, Incorrect Wiring Modifications Affected RBCCW Train "B" Alternate Shutdown Panel.

LER 99-01 1-00, Postulated Fire in Cable Spreading Room Potentially Affecting Safe Shutdown.

These prior LEns self-identified concerns that are related to this LER because they addressed actions necessary to ensure safe shutdown capability are installed and maintained.

ENERGY INDUSTRY IDENTIFICATION SYSTEM (EllS) CODES The EIlS codes for Components and Systems referenced in this report are as follows:

COMPONENTS CODES NA SYSTEMS CODES NA

REFERENCES:

Condition Reports CR-PNP-2015-7993 and CR-PNP-2015-8286 were issued to address fire protection compensatory measures for plant fire areas where the control circuits for MOVs are vulnerable to the IN 92-18 concern.

NRC FORM 366 (01-2014)

'~En tergy Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360 November 19, 2015 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555

SUBJECT:

Licensee Event Report 2015-010-00, Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station Docket No.: 50-293 License No.: DPR-35 LETTER NUMBER:

2.15.083

Dear Sir or Madam:

The enclosed Licensee Event Report (LER) 201 5-01 0-00, Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern, is submitted in accordance with 10 CFR 50.73.

This letter contains no commitments.

Please do not hesitate to contact Mr. Everett P. Perkins, Jr. at (508) 830-8323, if there are any questions regarding this submittal.

Sincerely, Director, Regulatory and Performance Improvement : Licensee Event Report 2015-01 0-00, Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern (4 pages)

PNPS Letter 2.15.083 Page 2 of 2 cc:

Mr. Daniel H. Dorman Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 2100 Renaissance Blvd., Suite 100 King of Prussia, PA 19406-2713 Ms. Booma Venkataraman, Project Manager Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop O-8C2A Washington, DC 20555 USNRC Senior Resident Inspector Pilgrim Nuclear Power Station Letter Number 2.15.083 Licensee Event Report 2015-010-00 Motor-Operated Valve Control Circuit Vulnerability to IN 92-18 Concern (4 Pages)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXP!RES: 0113112017 (02-201 4)

=,

Estimated burden per response to comply with this mandatory collection request: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.

Reported lessons learned are incorporated into the licensing process and fed back to industry.

Send comments regarding burden estimate to the FOIA, Prinacy and Information Collections

'~ LCENSEEREORTBranch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by EVENT(LER)

Internet e-mail to Infocollects.Resource@nrc.gov, and to the Desk Officer, Office of Inforrsation and Regulatory Affairs, NEOB-1 0202, (31 50-0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently nalid 0MB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE Pilgrim Nuclear Power Station 05000293 1 OF 4
4. TITLE Motor-Operated Valve Control Circuit Vulnerability to Information Notice 92-18 Concern 5.EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YA SEET, I HE

___..____DO*UM*

YER NUMBER NO.

MONTH DAY YEAR N/A N/A ItFACILITY NAME IDOCKET NUMBER 10 05 2015 2015 -

010 001 11 I19 12015 N/A N/A

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR *: (Check all that apply)

D 20.2201(b)

I~ 20.2203(a)(3)(i)

LI] 50.73(a)(2)(i)(C)

I* 50.73(a)(2)(vii)

N D--

20.2201(d)

D 20.2203(a)(3)(ii)

L*]50.73(a)(2)(ii)(A)

D 50.73(a)(2)(viii)(A) 10 OWRLVE I

20.2203(a)(2)1) i*

20.2236()(4)ii) 50.73(a)(2)(iv)(A)

I~ 50.73(a)(2)(vi)(a L1 20.2203(a)(2)(iii)

[--] 50.36(c)(2)

I-- 50.73(a)(2)(v)(A)

D 73.71(a)(4) 10 L 20.2203(a)(2)(iv) i*

50.46(a)(3)(ii)

[I]50.73(a)(2)(v)(B)

[]

73.71(a)(5)

I* 20.2203(a)(2)(v)

  • 1 50.73(a)(2)(i)(A)

[* 50.73(a)(2)(v)(C)

OTHER fl1**

Specify in Abstract below or in 20.2203(a)(2)(vi) 50.73(a)(2)(i)(B)

'I50.73(a)(2)(v)(D)NRFom6A

12. LICENSEE CONTACT FOR THIS LER LICENSEE CONTACT TELEPHONE NUMBER (Include A*rea Code)

Mr. Everett P. Perkins, Jr. - Regulatory Assurance Manager 508-830-8323IIMANU-IREPORTABLE I.I MANU-REPORTABLE

CAUSE

I SYSTEM ICOMPONENT IFACTURER TO EPIX

':i*;

CAUSE

SYSE CMOET FACTURER TO EPIX NA

14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED MONTH DAY YEAR I,

[~1SUBMISSION Lj YES (If yee, complete 15. EXPECTED SUBMISSION DATE)

NO DATE ABSTRACT (Limit to 1400 spaces, iLe., approximately 15 sin gle-spaced typewritten lines)

On Monday, October 5, 2015 at 1725 hours0.02 days <br />0.479 hours <br />0.00285 weeks <br />6.563625e-4 months <br /> EST, with the Reactor Mode Select Switch in the Run position and the reactor at approximately 100 percent core thermal power, Pilgrim Station identified and reported a vulnerability applicable to 10 CFR 50, Appendix R, Section lll.G, Fire Protection of Safe Shutdown Capability. The specific vulnerability involved lack of limit and torque switch protection of motor operated valves (MOVs) during an unlikely scenario of a large scale fire, forced evacuation of the Main Control Room (MCR), and spurious operation of MOVs due to fire damage. This potential vulnerability is identified in NRC Information Notice (IN) 92-18. Discovery of the vulnerability was determined to be reportable.

The cause of the event was evaluated and determined to be the result of incorrect assumptions applicable to the initial evaluation of the IN 92-18 concern and improper use of the Corrective Action Program when discovering new Appendix R open items. Corrective actions taken included the performance of hourly fire watches in the plant areas where MOV local operation is credited for the MOV control cables that could be affected. Valve control circuit modifications are under development and scheduled for implementation.

A fire event did not occur. There was no impact to public health and safety.

NRC FORM 366 (01-2014)U.S. NUCLEAR REGULATORY COMMISSION (02-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET_______

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE SEQUENTIAL REV I

YEAR NUMBER NO.

Pilgrim Nuclear Power Station 05000293 2 OF 4 [2015 010 00 BACKGROUND Pilgrim is an Appendix R plant. As such, Pilgrim is required to meet 10 CFR 50, Appendix R Sections Ill.G, J, and 0 requirements. Section Ill.G, provides for fire protection of safe shutdown capability.Section III.G.3 identifies that Alternative or Dedicated Shutdown capability should be provided if the requirements of Section III.G.2 of Appendix R are not satisfied.

Pilgrim provided Alternative Shutdown capability for fires in the Main Control Room (MCR), Cable Spreading room (CSR), and for the east and west portions of the Reactor Building. The NRC approved this Alternative Shutdown capability as part of the initial Appendix R program reviews. NRC SER dated November 2, 1983 documents approval of the proposed Alternative Shutdown strategy.

As part of industry driven actions taken to address operator manual actions (OMAs) and multiple spurious operations (MSOs) in the 2006 to 2012 time frame, Pilgrim Station initiated actions to update the site calculation (PS-32) used to evaluate circuit separation and the associated software program used to perform the circuit separation analysis. This update effort involved resolution of numerous issues, including the following regulatory and non-regulatory compliance concerns:

/

1. Operator Manual Actions in lIIl.G.2 fire areas (not allowed for Hot shutdown, but allowed if important to shutdown or used for cold shutdown)
2. Operator Manual Actions in III.G.3 fire areas (allowed if feasible for both hot shutdown and cold shutdown)
3. Multiple Spurious Operations (MSOs) in III.G.2 areas (req~uired review for reg compliance)
4. Multiple Spurious Operations (MSOs) in IlI.G.3 areas (not a required review for reg compliance)
5. Other Appendix R Open Issues as noted in update reviews (i.e., Information Notice (IN) 92-18; required for compliance)

These specific issues were identified as open items and listed as open items to the Station's Appendix R circuit separation calculation (PS-32).

As part of the update effort, the station reviewed the initial assumptions related to IN 92-18 concerns. Valve wiring reviews were performed and identified that IN 92-18 wiring modifications were not performed for numerous valves that are credited for use to demonstrate Alternative Shutdown capability. This issue was identified in the PS-32 calculation as open item E and tracked as a required corrective action under a condition report (CR-PNP-2012-669). This condition report addressed actions to update the overall Appendix R report.

EVENT DESCRIPTION

During preparation for the 2015 Fire Protection Triennial Inspection, it was noted that PS-32 unresolved open items existed in Section 6.5 of the report. A review of compensatory actions taken to address these open items indicated that compensatory fire watches were not established for areas where IN 92-18 concerns were identified to exist. Condition Report (CR-PNP-2015-7993) was issued due to the lack of a compensatory fire watch.

The reportability review of the condition report for lack of a compensatory fire watch was performed on Monday, October 5, 2015. This reportability review concluded that a vulnerability applicable to 10 CFR 50, Appendix R, Section Ill.G, Fire Protection of Safe Shutdown Capability existed and that the issue should be reported per 10 CFR 50.72 report requirements. The concern was reported as a condition that resulted in an unanalyzed condition that could degrade plant safety. The specific vulnerability involves lack of limit and NRC FORM 366 (01-2014)U.S. NUCLEAR REGULATORY COMMISSION (02-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE 1 ERISEQUENTIAL IREV N UMBER NO.

Pilgrim Nuclear Power Station 05000293 3 OF 4 120151 010 I00 torque switch protection of motor operated valves (MOVs) credited for use in the Alternative Shutdown strategy. These valves are required to be isolated from their associated power and control cables routed in the MCR and CSR, and operated locally to accomplish safe shutdown. The requirement to locally operate the MOVs involves the unlikely scenario of a large scale fire, forced evacuation of the MCR, and spurious operation of MOVs due to fire damage. This is the potential vulnerability identified in NRC IN 92-18.

CAUSE OF THE EVENT

The apparent cause of the event was evaluated and determined to be the incorrect use of the Corrective Action Program by not initiating new condition reports when discovering new issues where compliance questions could not be readily answered. This would have driven a formal evaluation for each PS-32 open item for operability/reportability determination and the implementation of fire watches.

Initial tracking for MSO lll.G.2, MSO lll.G.3 and traditional Appendix R open items obscured recognition of problems that needed fire watches with issues that did not need fire watches. This led to a loss of focus and a distraction from issue resolution instead of proper condition report characterization. The difference between the regulatory requirements for MSO categories and Appendix R compliance contributed to the error trap.

When the updated Appendix R analysis report (PS-32) from the contractor was accepted by Pilgrim acknowledging all issues, a separate CR was not written to capture and evaluate the individual open items for operability and reportability.

CORRECTIVE ACTIONS

Corrective actions taken included the posting of compensatory hourly fire watches in the plant areas where MOV local operation is credited and the MOV control cables could be affected.

Valve control circuit modifications are under development to address the IN 92-18 concern. The modifications have been scheduled for implementation.

Additional corrective actions were issued to review current Appendix R (PS-32) gap items to ensure appropriate compensatory measures are in-place.

SAFETY CONSEQUENCES

Postulated Appendix R fire events have been evaluated and Safe and Alternative Shutdown strategies and capability have been provided. Safe and alternative safe shutdown systems and procedures have been developed to address the potential for postulated plant fire events that affect all equipment and all cables located in a given plant fire area. The IN 92-18 concern was identified to have a potential affect on safe shutdown capability in the MCR, CSR, and the Reactor Building east and west fire areas.

The postulated fire is assumed to spread and challenge all safe shutdown equipment and cables located in the area regardless of whether the area has significant fire hazards, ignition sources, or large spatial separation.

The postulated fire evaluation does not credit plant actions taken to minimize potential fires by controlling transient combustibles in plant areas and providing fire retardant cables. The evaluation also does not provide credit for automatic fire detection capability which alarms in the continuously manned control room; automatic suppression capability in areas with fire hazards; or the availability of a continuously manned fire brigade staff that will respond to a fire and manually suppress and control the spread of fire.

NRC FORM 366 (01-2014)U.S. NUCLEAR REGULATORY COMMISSION (02-2014)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET____________

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE ISEQUENTIAL REV IYEAR NUMBER NO.

Pilgrim Nuclear Power Station 05000293 4 OF 4 112015 010 00 A detailed evaluation of the risk significance of fires in the areas potentially impacted by the IN 92-18 issue was performed. This risk review involved evaluation of potential ignition sources in the area; location of credited Appendix R equipment and cables in relation to the ignition sources; available fire safe shutdown procedures; the fire resistant qualities of cables and equipment provided in the area; the automatic fire detection capability provided in the area; and the automatic and manual suppression capability provided. This risk significance determination review identified that the Pilgrim vulnerability to the IN 92-18 concern met NRC acceptance criteria for a very low fire risk concern.

Based on these reviews, there was no adverse impact on the public health or safety.

REPORTABILITY

This report is submitted in accordance with 10 CFR 50.73(a)(2)(ii)(B) - Any event or condition where resulted in: the nuclear power plant being in a unanalyzed condition that significantly degraded plant safety.

PREVIOUS EVENTS 10 CFR 50, Appendix R fire protection issues that resulted in LER reports were reviewed. The most recent Appendix R LEns were reported in the 1997 to 1999 timeframe. These LERS are summarized as follows:

LER 97-029-00, Shutdown Cooling (SDC) Suction Valves Vulnerability to Damage from Potential Failure Mode Involving Hot Shorts.

LER 98-012-00, Incomplete Installation of Fire Barrier in the Cable Spreading Room.

LER 98-013-00 thru LER 98-013-02, Inconclusive Fire Barrier Test Data.

LER 98-023-00, Incorrect Wiring Modifications Affected RBCCW Train "B" Alternate Shutdown Panel.

LER 99-01 1-00, Postulated Fire in Cable Spreading Room Potentially Affecting Safe Shutdown.

These prior LEns self-identified concerns that are related to this LER because they addressed actions necessary to ensure safe shutdown capability are installed and maintained.

ENERGY INDUSTRY IDENTIFICATION SYSTEM (EllS) CODES The EIlS codes for Components and Systems referenced in this report are as follows:

COMPONENTS CODES NA SYSTEMS CODES NA

REFERENCES:

Condition Reports CR-PNP-2015-7993 and CR-PNP-2015-8286 were issued to address fire protection compensatory measures for plant fire areas where the control circuits for MOVs are vulnerable to the IN 92-18 concern.

NRC FORM 366 (01-2014)