05000282/FIN-2015004-03
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Licensee-Identified Violation |
| Description | Title 10 CFR 50.48(b)(2) requires, in part, that all nuclear power plants licensed to operate before January 1, 1979, must satisfy the applicable requirements of Appendix R to this part, including specifically the requirements of Sections III.G, III.J, and III.O. Appendix R,Section III.G.3 of 10 CFR Part 50, requires, in part, that alternative or dedicated shutdown capability and its associated circuits, independent of cables, systems or components in the area, room, or zone under consideration should be provided where the protection of systems whose function is required for hot shutdown does not satisfy the requirement of paragraph G.2 of this section. In addition, fire detection and a fixed fire suppression system shall be installed in the area, room, or zone under consideration. Contrary to the above, on April 19, 2015, the licensee failed to ensure that alternative or dedicated shutdown capability and its associated circuits were independent of cables in the area. Specifically, procedure F5 Appendix B, Control Room Evacuation (Fire), Revision 31, did not contain actions to isolate the RCP breaker circuits to prevent restarting due to a fire induced loss of remote trip and loss of RCP seal cooling water that could lead to an increased rate of seal degradation and a small break loss of coolant accident. These actions were required to achieve and maintain safe shutdown in the event of a fire that resulted in functional loss and/or evacuation of the control/relay and cable spreading rooms. Section 9.1 of the NRC Enforcement Policy allows the NRC to exercise enforcement discretion for certain fire protection related non compliances identified as a result of a licensees transition to the new risk informed, performance based fire protection approach included in 10 CFR 50.48(c), and for certain existing non compliances that reasonably may be resolved by compliance with 10 CFR 50.48(c) as long as certain criteria are met. This risk informed, performance based approach is referred to as NFPA 805, Performance Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants. The licensee is in transition to NFPA 805 and therefore the licensee-identified violation was evaluated in accordance with the criteria established by Section 9.1(a) of the NRCs Interim Enforcement Policy Regarding Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48) for a licensee in NFPA 805 transition. The inspectors determined that for this violation: (1) the licensee would have identified the violation during the scheduled transition to 10 CFR 50.48(c); (2) the licensee had established adequate compensatory measures within a reasonable time frame following identification and would correct the violation as a result of completing the NFPA 805 transition; (3) the violation was not likely to have been previously identified by routine licensee efforts; and (4) the violation was not willful. The finding also met additional criteria established in section 12.01.b of IMC 0305, Operating Assessment Program. In addition, in order for the NRC to consider granting enforcement discretion the violation must not be associated with a finding of high safety significance (i.e., Red). The licensee performed risk evaluation V.SPA.15.012, Revision 3, dated December 18, 2015, and determined that this issue was not associated with a finding of high safety significance. A region III senior reactor analyst (SRA) reviewed the evaluation and concluded that the result was reasonable and that the finding was less than Red and eligible for enforcement discretion. The dominant core damage sequence from the licensees evaluation involved an electrical cabinet fire in the relay room involving the cables that could cause spurious operation of the RCPs and that would lead to alternate shutdown. The licensee identified several conservative assumptions in the analysis. The SRA agreed that some were conservative, notably that any fire affecting the cables in the relay room that could cause a spurious start of an RCP would also result in a loss of all seal cooling due to fire damage. The SRA used IMC 0609, Appendix F, Fire Protection Significance Determination Process, to review the results of the licensees evaluation. The relay room is similar to a cable spreading room with electrical cabinets. The fire frequency for this room in Appendix F is 6E3/yr. The probability of non-suppression was estimated to be 2E2 and the spurious operation probability was assumed to be 0.6. The product of these values (7.2E5/yr) represents a bounding relay room fire scenario delta core damage frequency (CDF) for this finding. Since the bounding result is consistent with the licensees conclusion, the SRA determined that the delta core damage frequency for the finding was less than 1E4/yr, which is less than Red. In addition, the licensee entered this issue into their corrective action program as CAP 01475242. As a result, the inspectors concluded that the violation met all four criteria established by Section 9.1(a) and that the NRC was exercising enforcement discretion to not cite this violation in accordance with the Interim Enforcement Policy Regarding Enforcement Discretion for Certain Fire Protection Issues. |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2015004 Section 4OA7 |
| Date counted | Dec 31, 2015 (2015Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Licensee-identified |
| Inspection Procedure: | |
| Inspectors (proximate) | A Shaikh G Edwards J Cassidy K Barclay K Riemer L Haeg M Garza P Laflamme S Bell |
| Violation of: | 10 CFR 50.48 |
| INPO aspect | |
| ' | |
Finding - Prairie Island - IR 05000282/2015004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Prairie Island) @ 2015Q4
Self-Identified List (Prairie Island)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||