Finding | |
|---|---|
| Title | 4160 Vac Switchgear Preventive Maintenance Procedure Failed to Provide Adequate Resistance Values and Acceptance Criteria |
| Description | The team identified a finding of very low safety significance, and an associated NCV of Title 10, Code of Federal Regulations (CFR), Part 50, Appendix B, Criterion XI, Test Control, for the licensees failure to have an acceptance criteria for electrical contact resistance values in preventive maintenance procedures for 4160 Vac switchgear. Specifically, the licensees preventive maintenance Procedure PE 0009, 4kV Switchgear Preventive Maintenance, failed to provide adequate resistance values and acceptance criteria for electrical connections at bus bar connection points and between 4kV switchgear cubicles. The licensee entered this finding into their Corrective Action Program (CAP) with a recommended action to add acceptance criteria into Table 1 of procedure PE 0009. The performance deficiency was determined to be more than minor because it was associated with the procedural quality attribute of the Mitigating Systems cornerstone, and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as of very low safety significance because it was a design or qualification deficiency that did not represent a loss of operability or functionality. Specifically, the licensee determined the 4160 Vac switchgear cubicles were operable using guidance from Electric Power Research Institute Technical Report 1013457. The finding had a cross-cutting aspect associated with resources in the area of human performance. Specifically, the licensee management failed to ensure procedures are available to support successful work performance. |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2015007 Section 1R21 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | C Jackel C Lipa G O'Dwyer I Hafeez J Chiloyan J Neurauter J Zudans R Walton |
| Violation of: | 10 CFR 50 Appendix B Criterion XI |
| CCA | H.1, Resources |
| INPO aspect | LA.1 |
| ' | |