05000272/LER-1981-036, Forwards LER 81-036/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 81-036/03L-0.Detailed Event Analysis Encl
ML18086A454
Person / Time
Site: Salem PSEG icon.png
Issue date: 05/01/1981
From: Uderitz R
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18086A455 List:
References
NUDOCS 8105080314
Download: ML18086A454 (3)


LER-1981-036, Forwards LER 81-036/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
2721981036R00 - NRC Website

text

c:*3 PS~G Public Service Electric and Gas Company 80 Park Plaza Newark, N.J. 07101 Phone 201/430-7000 Mr. Boyce H. Grier Director of USNRC May 1, 1981 Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 81-36/03L Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 81-36/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, C'

~@~~/J

. r:,5 R. A. Uder11..z General Manager -

N~clear Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control

( 3 copies)

  • CJ.PS~G Public Service Electric and Gas Company 80 Park Plaza Newark, N.J. 07101 Phone 201/430-7000 Mr. Boyce H. Grier Director of USNRC May 1, 1981 Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 81-36/03L Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 81-36/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours,

~~

~,4'~/_;,;

R. A. Uderi6 General Manager -

N~clear Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies)

Ths Energy People

Report Number:

81-36/03L Report Date:

May 1, 1981 Occurrence Date:

4/05/81 Facility:

Salem Generating Station, Unit 1 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Inoperable Fire Hose CONDITIONS PRIOR TO OCCURRENCE:

Mode 5 -

Rx Power 0% - Unit Load 0 MW DESCRIPTION OF OCCURRENCE:

At 1400 hours0.0162 days <br />0.389 hours <br />0.00231 weeks <br />5.327e-4 months <br /> on April 5, 1981, Fire Hose No. lFP-75 located on Elevation 100' (100-Al-NN14) was discovered to be inoperable because of a 6" slash along its longitudinal axis.

Action State-ment 3.7.10.4 was entered at this time.

This occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Apparently, the slashed hose was the result of malicious mischief or vandalism by person or persons unknown.

ANALYSIS OF OCCURRENCE:

Technical Specification 3.7.10.4 requires that with this hose inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an operable hose station within one hour.

Operations personnel duplicated the cut in the hose using a 4" bladed heavy duty pocket knife which suggests a deliberate intent to damage the hose.

CORRECTIVE ACTION

The fire hose was replaced in kind.

The Action Statement was terminated at 1445 hours0.0167 days <br />0.401 hours <br />0.00239 weeks <br />5.498225e-4 months <br /> on April 5, 1981.

FAILURE DATA:

Not Applicable Prepared By W. J. Steele Manager -

Silem Generating Station SORC Meeting No.

81-30