Finding | |
---|---|
Title | Failure to Demonstrate the Capability of the Fuel Oil Storage Tank and the Service Water Pumps to Fulfill Their Safety Functions Under All Conditions |
Description | The team a Green NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the licensees failure to have calculations supporting the design bases of safety related components, specifically for the EDG fuel oil storage tank with respect to tornado wind loadings, and the net positive suction head (NPSH) of the service water pumps. No immediate operability issues were identified and the licensee entered this issue into the corrective action program as NCR 422985 and NCR 423985. The failure to demonstrate the adequacy of the design for safety related components, specifically regarding the capability of the fuel oil storage tank to withstand tornado wind loading and the failure to demonstrate that the NPSH available to the service water pumps was greater than the required NPSH, was a performance deficiency. This finding was more than minor because it affected the mitigating systems cornerstone attribute of design control to ensure the availability, reliability, and capability of safety systems that respond to initiating events to prevent undesirable consequences. This finding was of very low safety significance because the licensee performed a simplified evaluation indicating that this condition was not a design issue resulting in loss of function, it did not represent an actual loss of a system safety function, did not result in exceeding the TS allowed outage time, and did not affect external event mitigation. The team determined that no cross cutting aspect was applicable to this performance deficiency because the failure to demonstrate the adequacy of the design was determined to not be indicative of current licensee performance. |
Site: | Robinson ![]() |
---|---|
Report | IR 05000261/2010011 Section 1R21 |
Date counted | Dec 31, 2010 (2010Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | S Walker G Skinner M Yeminy S Sandal B Desai J Eargle P Braxton |
INPO aspect | |
' | |
Finding - Robinson - IR 05000261/2010011 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Robinson) @ 2010Q4
Self-Identified List (Robinson)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||