Finding | |
|---|---|
| Title | Fidelity of Plant-Referenced Simulator |
| Description | A review of simulator performance and event data by the team confirmed one simulation deficiency which had been identified by the licensee as part of their event review. When power to safety-related 480 volt Bus E-2 was transferred to the emergency diesel generator, FCV-626 (thermal barrier heat exchanger outlet isolation flow control valve) closed unexpectedly. As discussed in more detail in the Section 4.5, Unexpected Closure of FCV-626, the as-built plant configuration resulted in the valve closing on a loss of power. This response was not obtained in the simulator because the simulator modeling of FCV-626 was based solely on CCW flow through the valve and did not take into account power to the valve operator and associated control circuit. Consequently, in simulator scenarios which included a loss of power to Instrument Bus 4, this valve remained open. Because the plant reference simulator did not demonstrate expected plant response for a loss of Instrument Bus 4, the team identified the need for additional NRC review to determine the adequacy of fidelity of the plant reference simulator for conducting loss of component cooling system control manipulations and plant evolutions. This review will also determine if this issue represents a performance deficiency. An Unresolved Item will be opened pending completion of this review. The URI is identified as05000261/2010009-04, Fidelity of Plant-Referenced Simulator. |
| Site: | Robinson |
|---|---|
| Report | IR 05000261/2010009 Section 4OA5 |
| Date counted | Jun 30, 2010 (2010Q2) |
| Type: | URI: |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 93800 |
| Inspectors (proximate) | J Hanna J Hickey L Miller L Wert P Fillion P Pieringer R Monk S Currie F Ehrhardta Nielsenc Kontz D Bollock D Mills G Laska G Skinner J Beavers J Brady J Hickey J Worosilo M Bates P Braxton R Musserr Monkf Ehrhardt J Hanna L Miller J Hickey P Fillion L Wert P Pieringer S Currie |
| INPO aspect | |
| ' | |
Finding - Robinson - IR 05000261/2010009 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Robinson) @ 2010Q2
Self-Identified List (Robinson)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||