ML20199E216

From kanterella
Revision as of 08:01, 10 December 2024 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Engineering Evaluation Rept EER-136, AMP Pidg PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence. Related Documentation Encl
ML20199E216
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 04/01/1985
From: Fleming D, Renshaw F
AMP, INC.
To:
Shared Package
ML20199D912 List: ... further results
References
FOIA-86-36 EER-136, NUDOCS 8606230226
Download: ML20199E216 (160)


Text

..

.g C:3 ENGINEERING EVALUATION REPORP 4/01/85 g

i

.........i,....iJCEKiPEDDhCS IQ iUJ.2!.!D liliikbi WAlII!X PM DF AMP INCGRFORAIG.

EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence Table of Contents Introduction.

......... Page 1 Test Specimen Description.

Page 1 Test Schedule.

Pago 1 Test Methods Page 1 I

Test Data Summary.

e2 W' ORMAI,01N1Pa

.r Appendix A (Engineering Conclusions) 2e e2

.f

},D y

a

.^.

eb b

?NV a

Prepared by w

Approved b

]4

,'p p

David Fleming Q

FloydReFphaw Test Engineering Product Engineering Supv.

General Products Group General Products Division 8606230226 860609 PDR FOIA

  • Trademark of AMP Incorporated eenenAL miooucts enoup Aasp N000ApeAATES. MAHRIBSume. PA. 1F188 U.S.A.

Q l

o INTRODUCTION This report c6ntains results of tests conducted on PIDG PVT 2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 60o and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 U0lVATON' TEST SPECIMEN DESCRIPTION The following Terminals and quantities were tested.

b Quantities ner Test Grou1 13Oll Terminal Part No.

Wire Size GrouD 1 Grous

'd-A ki 1 53425-1 10 AWG L @ 600 Bends 4 @ 900 Bends 4 @ h50 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Groue and Secuence Test Groun 1 Groue 2 Groun 1 Voltage Droe 1-1 1-4 1-4 Vibration 2

2 2

TEST METHODS Voltage Dron.

Each terminal was measured for voltage drop by energizing with 55 Emperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all l

slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes i

mutually perpendicular to each other and to the axis of the wire.

1-

TEST DATA

SUMMARY

r Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Soecimen # 1 2

1 k

1 2

1 4

1 2

1 h

Initial 19.1 14.8 19.h 19.1 1k.9 19.2 19.2 19.0 19.7 1k.7 19.8 19.1 After Vib.

16.4 16.1 19.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 19.7 MIL-T-7928G Max 19.9 19.9 19.9

  • Sample broke after 9.0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 9n0 The same can be said of the twisted tongue to h50 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

WORNAT10%

COPY PPRV L

l... - _. _ _ - - - -. - _ -.

i COMANCHE PEAK STEAM ELECTRIC STATION TExsS uTiuTIES NCR Na GENERATING CO.

NONCONFORMANCE REPORT (NCR)

E-84-01073 R.1 Page 1 of g

UNIT STRUCTUREr SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

l Cubicle #9 1

S. G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION or twisteF ARMS

'T Lugs listed below are bent over 60 Terminal block Terminal points INDEXED hz P.B.

3 3, 4

,8 PLT. RECORD p

rittuc 4 /

a.

p,p.

2 om y

c P.F.

4

,3 g

A.A.

1, 2, 14 c:

Hold tag applied, all unrelated work may Continue.

ES-100 2

2.7.1 AEFEAENCE CCCUVENT.

ogy p,,,

REPORTED GY:

CATE:

Steve Bufkin 4

9 84 :

f f

CE REVIEW /ADPACVA /

)

DATE:

G L1A O/!O$iES u

3 ACTION ACORESSEE DEPARTMENT I. Vogelsang Eng.

i CISPOSITICN:

6 REWCRK REPAIR USE AS fS XX SCRAP See attached disposition.

s

- NORMAT.10h3 COPY o

5 P?RV 4

L

)

I ENG REVIEW / APPROVAL DATE:

L Ikil y

? rg

'~ % 7^Uyh{

j

/iYes-)

U

~SSPOSiflON WRIFICATION I CLOSURE $:h/a>& I idAT'27; O

C V;

  1. H D

CoWENTS: Rev. 1:

Reopened to C1arify di sition.

fjdoU DISPOSITION: NCR #E-84-01073 R.1 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering.

The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PB 3

PC 3&4 PA 3

PP 2

PF 4

PJ 8

LA 1&3 AA 1,2,14 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

$>4 pin /d IICN

>,l E0RM1A70K COPY

?PN a

i

.~,OMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES CENERATING CO.

NONCOf 4FORMANCE REPORT (NCR)

E-7 4 - OI DV

$9 I ITEWCOMFCNENT TAGilQ Nut.tSER LOCATION CR ELEVATICN RIR NO.

UNIT STRUCTU A Ei SYSTEM J703/GC2'M cu%che 9 l

6. G.* l Vonk. Lus.s coiens uen-. x R,v,tos n.7x1

>v/At NONCONFCPMING CCNOITION Y

40-) M CUAA & C N

N.crm Als8 A l%Ic e l<,

Tvtf,thf/4 90 47,

f

9. b.

G h

h. b '

b9 99.

3 a p%m%,,Q Pp*

A

o. s.

a P J-1 6 % d a_. (

L.. A.

1A T

As A.

ljk)

A l

REV PARA e

REFEAENCE COCUMENT*

REPCRTEC SY:

-N CATE:

g l./ / h /

d LW D

,3

/

A

,E REVIEW / APPROVAL:

CATE:

A - f ~_c.__-

V / 9 / [2.

kg lCEPARTMENT O

ACTION ACC AESSEE /

4

  • T*/%1ES / dom & A T1~7 "T F dr-S Cs-I CLSPOSITICN:

AEWCAK AEPAIR USE AS IS Y

SCRAP W G CUfLGMT* M4QdSACTV2G2'S POSIDCM i9 T%r TEttMI AJ ALS Mni 8C 6CA3T-CMG nME. TD

  • 90' PM p OP Tb s20* AnTu sM GMc,oOGGRI AK, GVA t GArrod. EA)G s MG.G et A)G HAb RGs/tGsd_E2. 774G Feus-ca UG TE%IAJALS IAJ '?CES TIOLi' TEEMIAJAG occo<'

TE2M/AIAt-PctUrs r-ikn:0RM m 10h\\

m

  1. . e.

3 u

ac ss y

p, A,

3 e

a P. P.

2.

f"*q

/

Q{'

Q R F.

4 F.J. ' ~~ '

8 L

z c, A.l i, S C

A. A.

i, z,14 h

If is oce cxtes.Manou TaAr mese weminAus I:o per Mss Ato Ghd m-

% Raic.EABtLtTY fW]Bwcm AsuQ M AY BE. OSED A5 15.

1 00T'G ; Ar4P TECMtMAL5 HAJG Oeed iMSTpiu GD BY T4G i/C-MDDE.

l 6F-E A f r A ci4 E D

(_ PPA.BS,24 l.

I

('."b, l}m//

ENG. AEVIEW/ APPROVAL CATE:

}

41/9is c

j r

CE f.EVIEW APPROVAL:

A OATE:

dfm g %ne= _

+' i/ si FY U r3iSPCSITICN VERIFICATICN & CLCSURE:

CATE:

/

/

CCMMENTS:

u r.s 6.

4-TEL1EFliENE CONVIRSATION RECORD oo,, 4-17-84

Time, 3:30 P.M.

Call by: W. I. Vogelsang of TUGC0'- Enoineerino Div.

W1 WI Answer by:

Floyd Renshaw of AMP Prod'uctr ternoration. Product Engineer INomel E -

,l Contract No:

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOLISTRAND*

' terminals

. ~..

INFORMAilVN e"'e t

k

(

r, Tradomark nf AMD intnennentpd riOD\\1 L s

,tt SUMMAltY OF DISCUSSION, DECl$lONS AND COMMITMENT 5.

W. I. Vogelsang discussed the AMP memo dated September 2, 1981*in which Mr.

B. Eister.had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (nonnally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45* tend.

However, this does not pr.eclude bending the terminals up to 120*. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these tenninals, they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90* to 120* would not retain its full mechanical strength it would mainatin its electrical characteristics.

~

Wy:a, z _ l ~.

cc: ARMS s r,J.LT L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

s "OMANCHE PEAK STEAM ELECTRIC STATION i MAS ununts l NCR No, CENERATING CO.

NONCONFORMANCE REPORT (NCR) lE-7 9 - OI DV uNir STauCTuaE,5YSTEu irEv/C vPCsENT rAccipNuEsEm toCArios em ELEvAr:CN' air No.

$703/GC29'A coschs 9 l

G.G? l p nk Lues ' tout.suco ex R miol EL. 9n Ju/A I

NONCONFCAMING CCNOITION gg 0.lg h a 9. +oy44,(,o* g

%me.

i GI 71rminos A S to e l<.

%,n5 4 98..TJ

=

e.cs.

2 a

e. c..

q%

u N U tV A. 0 \\.

5

e. a.

s fuoE%gg s

-.g Q

l P.p.

j

p. F %e.

\\

g g

P. J.

T h*2 ji f

ke$*

j3 I

c M-

!, 2., n.l Q\\f

  • b>

b A

PARA O, ).

EEFERENCE CCCUMENT-AEV I

F.EPORTED BY:

A DATE:

I g

LJ / 9 i CE REVIEW / APPROVAL:

CATE:

._ d -

~3 V I 9 / 5 2.

w 1 CEPARTMENT O

ACTION ACORESSEE TW8C #DME Aff7

*T*f::dr-S Gs-I CISPOSITICN:

REWCAK REPAIR USE AS IS XYI SCRAP

_ Twa.euttastr' AAAwuPAcrottR2.9stfDo*8 n *t Hair.TM TEtnaas&ts A44# Da *D44sT' #NE TIMf'TU 'J AND M ltot wfrWsMdedsstWd. RVALWATIOK, t.NMNgttauty-MAS psytswg#j ysMserm.

1stweegg tv j

ywy JOSafl00t' ung 'TupesteA4.'3uzJt Tehneet L Peter 7V TE EaAme4L8ust '1984m64L 9MNT1; T1htania:AA.,11wt.K 'Insmusa4L De m ;

.S

'RR L

4.A.

._.$3

'P. (

i) */_. _ __ _ _._"P.F.. _ _ _ __ __ 'I

. A A. _.

St in/

f E

'P. A.

S It's.

8

. If IE 08E EDE1ERAtu64T10tf DedW" TNS84 75AAemas.3 De Nit" M M g.7;c="" f5AF#4M4#Y Pf888 84A.__ l QA RECORD Asan mAnw tw"ukan n a"

$&r saarrir ses musain.

ENG. REVIEW / APPROVAL

/

7tTN.

QA REV QATE:

I

._.O

[.> @ 8/ _

Y/2,3/ S'4 f w > v- ~

CE REVIEW APPROVAL:

C

. OLSPOSIT:CN VERIPICATICN & CLdsuhE:

]

j %

DA COMMENTS:50CffE8 AmeP TS" -^^

.S HAVE 3B55Af -r K

P XP i,.ii psma0cd

$st AWAl>90 6.AA4 349.Y/

$ /A $ b _" e" c A Y

?

'Yk kf

'/ '

f

COMANCHE PEAK STEAM ELECTRIC STATION

= TEXAS OTibTIES NCR No' NONCONFORMANCE REPORT (NCR)

CENICA. TING CO.

E-84 01073 R.2 Page 1 of b tJNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /ID NUMBER LOCATION OR ELEVATION RIR NO.

I Cubicle #9 1

S.G. #1 Vendor Luas CP1-EPSWEA-02 Rm. 103 El. 852' N/A YONCONFORMING CON 0lTION 0

Lugs listed below are bent over 60 or twisted.

.h Terminal block Terminal points z

P.B.

3 j

i P4 FORVAE0h i it

'COPY g

L.A.

1, 3 A.A.

1, 2, 14 33 g

l c:

Hold tag applied, all unrelated work may Continue.

l 2

2.7.1 ES-100 ngy p,,,

AEFERENCE CCCUMENT:

DATE:

1 REPORTED GY:

4 9,84 l Steve Bufkin f

DATE:

OE REVIEW / APPAOVAL:

1 tM S ll$ W

/

1 w

! DEPARTMENT I

O ACTION ACORESSEE I. Vogelsang Eng.

i XX SCRAP REWORK REPAIR USE AS IS See attached disposition.

I w

0i ARWS I

PERM. PLT. RECORD l

,e!

INDEXED

@j g l t ec.

IL' am 2

JUN 041985 o u,,moc.

Q,:

Urf 4

g DATE:

ENG R EVIEW/ APPROVAL f

/h k OE REVIEW APPROVAL:

U CATE:

w YMM :

[ ll *f / W

^1 C

OISPOSiTION VERIFICATION & CLOSUR DATE:

Wtt)Whl2f 7m"~! '- =0 5~il7i W 00MMENTS: Rev. 1:

Reopened to Clartfy disposition.

Rev. 2:

Reopened to attach AMP Engineering evaluation report & to address twisting.

$$ 551R' f

&a,/g. i DISPOSITION: flCR #E-84-01073 RgA 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering.

The inspection indicated that these terminals were bent less than 90* and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TER!11NAL POINT PB 3

PC 3&4 PA 3

PP 2

PF 4

PJ 8

LA 1&3 AA 1,2,14 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problen, ff IIck<

>,l 2.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

M r/n/er M Y A~

S~// 7 /W 1

I Gh0 vQ?If l

r*

l

??N l

[

L

, TE[A4 JTiu'WES COMAl*CHE PEAK STEAM ELECTRIC STATION NCR N2.

GENERATING CO.

NONCONFORMANCE REPORT (NCR) s f84~06972, y

UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RlR NO.

?

S'&

O2 cm-Ena"mt64 'E $f 7to 44 i

NONCONFORMING CONDITION QA RECORD I ARMS QA REVIEW

.J DEXED re gsg.ui z

Z FILE NO.

DATE:

SUBFil E NO.

l gg[ /)7QeA &b I

en

~

REFERENCE DOCUMENT-REV PARA -

2 REPORTED BY:f 0

OE REVIEW / APPROVAL:

DATE:

ff$ctft/g b ibO D 2

=

/

ACTION ADDRESSEE

/

\\)cqe h q DEPARTMENT E,3u-e rc,,9 q

OISPOSITION:

V d

REWORK REPAIR USE AS IS SCRAP Thg AMP current pgsition (CPPA 38241) is that their tenninals may be bent one time to 90 and up to 120 with an Engineering evaluation.

In this case, General Electric Company's application is for short jumpers in the MCC draw-out units.

These short jumpers are such that they are not susceptible to vibra-tions.

As such the terminals full mechanical strength is not required.

Additionally, this installation configuration is the same as that qualified by General Electric Company in their IEEE 323 qualification program.

Engineering has determined that the terminals bent to 120 do not pose an equipment serviceability problem and may be used as is.

,nn O$

ENG. REVIEW / APPROVAL h, l YK)

QS M' ~ ~

]

4 i14 i YY DATE:

j CE REVIEW APPROVAL:

Wmus/ix[s/M s>n 4 ED 4rW OlSPOSITION VERIFICATION & C'LO5ub:

g nAT3:

R/G M,,is, a b i/61N-(/

~

COMMENTS: g(3 g f5 35, ffog g 7,g

,q,,,o s,pp, f

p st M FMA gM

h

~?

\\
;4...

Page 2 of 2 1

NCR E-84-00972 While working Traveler #EE84-0692-02CI, (Replacement of thermal' overload relay),itwasnotedthattoinstallthethgemaloverloadrelaytgat amp lugs have to be bent anywhere from a 90 to approximately 120 bend, this is in violation of amp letter VBR 16624 dated September 2, 1981. Compartment being inspected was 7C of CP2-EPMCEB-03. After dis-covering this situation compartments 7F and 6F also disp. lay same con-figuration, and in some cases barrel of lug has been bent over retaining screw head, indicating the fact that it is very doubtful that reannealing process as required by amp has ever occurred at General Electric when equipment was manufactured.

This is also in violation of amp procedures and appears to be a generic problem in all motor control centers with starter, thermal overload relay combination arrangements.

I hold tag appl.ied to Comp. 7C All other unrelated work may continue.

l l

pr W

p W*

O l

i t

L 4

!a

COMANCHE PEAK STEAM ELECTRIC STATION

' Ey.*.S OTit: TIES 0.':200 TING CO.

NONCONFORMANCE REPORT (NCR)

E-84-01069 R.1 Page 1 of 1

UNIT STRUCTURE / SYSTEM ITEM /COM PONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

Cubicle #4 1

S.G. #1 Vendor Luos CP1-EPSWEA-02 Jim 103 El. R52' NLA IY' n '-

A"RMS m

NONCONFORMING CONDITION jNDgg-T Lugs listed below are bent in excess of 60 degrees.

y h

Terminal block Terminal points g

AA 1, 2

~

to 5

Hold tags applied, all unrelated work may continue.

PpRM. PLT. RECORD amg rv.c i.oc O

suer:La Loc.

j Q

/V6AJ/-

t S-100 2

  • l AEFEh iNCE CCCU'. TENT:

ngy PARA REPOITr0 BY; OATE:

1 Steve Bufkin 4 / 9 i84 !

///* h DATE:

OE REVIEW /APPAOV.

(Al$11L oI ioC8C u

J ACTION ACCAESSEE DEPARTMENT l

I. Vogel <;ang Fng.

l CISPOSITION:

XX(2)

XX (1)

REPAIR USE AS IS SCRAP j

AEWCAK See attached disposition.

N U1V A",0b j

OOPY l

m 3

I l

i i

! ERG AEVIEW/ APPROVAL L

lA)Ilbuh v

/i 5~f: r 'i DATE n.

r-n U

OATE:

i CE REVIEW L-

~ Al Y rris A

I l$

u n

O 5SPOSITI6N VERYlCATION & CLOSURE:6 WoYaw s##

/ i6%

CATE*

COWENTS: Rev. 1:

Reopened to clarify dis ition.

l

Q,j{ dl%

DISPOSITION:

NCR #E-84-01069 R.1 1.

The following termonal point and associated tenninal was inspected by Electrical Egnineering. The inspection indicated that the tenninal was bent less than 90 and that no flaking,. cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characterisitics are manitained as evidenced by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT AA 1

Based on the above evaluation, the terminal may be used as is as it does not pose a serviceability problem.

2.

The following terminal point and associated terminal was inspected by Electrical Engineering and was found to be bent less than 90 but it does show signs of fatigue. This terminal is to be replaced - Rework.

TERMINAL BLOCK TERMINAL POINT AA 2

,Q' yi/

ikk<

goW3?

COPY PP@

l

TEIAS UTILITIES COMANCHE PEAK STEAM ELECTRIC STATION NCR Nw CENERATING CO.

NONCONFORMANCE REPORT (NCR)

E-99 01O(o9 unit STauCTuaE, Sv5TEu t iTEu/CCurcsENT TAccio NussEa i.CCATiCN Ca ELEvAv:CN miR No 6903/GC2 d f

cus CCJe 4 l

S G.'/

lvemeb-19u colspsuen.o3 R m /o3 EA 9D

/1)/A NCNCCNFORMING CCNCITION DAll

&?Ph j

$$6' W ags %

Irpt. OlotA

"'fo r m. Po N 5 1.N-g NS lj sk

^r

?f'MW,@

e J LAra=_0N

' 'M 5m

,m 4

f

=

a_

m%h.

L 7 - ff 4 - o g qA AEFERENCE CCCUMENT-b' b

AEV

[

REPCRTED Sv:

CATE:

i Y / *1 / h

' CE AEVIEW/ AP840 VAL-I

/

CATE:

I u / 9 /8f l

A r wC ACTICN ACCAESSEE f

l CEPARTMENT, e

'IbMt.s /doueer/

r:::e ate s l

CISPOSITICN:

REWCRK IN REPAIR USE AS IS IY SCRAP "DE *I'ERMlHAA LAMOED eM TSEMINAL,,h AA Pet >ff't.11"IO*fh 5 RER.AC&b. Rs.WCILC.

~

t I

.T*45 ovetaWT' A44uoMA.TUR6th hfftu iS THAT TERMINALE AAAvind 'StWcNK Tim 8 TO90j Amo op_....]

ww l

$ 'To sto* wiry Ag aus,sMa&Riutr EVALva(TtDN.El4&tMESEINF Ha!, REVIEW 50 FAK MM40MMir 15&M/Af4&f I

w

_.1 g JN $04Alf10W l

O.

"TE.RM488AL % Lout T3AAAggAL MgNT AA f

5 __%t.th out stretMinnTion 7%st tws Tammiunt. ' boss Her ha6 Bu SWIPnAsdr saavecgC/W "P9d1RSM AND MAv 'hE 9840 43 13,

W SE.E #cTE tu <*~--surs ENG. REVIEW /APPRCVAL CATE:

'i //V /8Y l Q3 REVIEW APPROVAL:

CATE:

w

$L W?Y

/l $/ YY Q

CISPOSITICN VERIFICATICN & CLCS E:

CATE:

of dill 4CUI.1

[/O / M COMMENTS:tt0(Et AMP TateienAL3 paavs 948N /NJPMf4dD Br 745 pgAscoA, saa ATT4tWED @P9A S$f4l j

FtnAL' M E-l-coVO M 9

u en-a,.,e TELEPHONE CONVERSATION RECORD g,,

4 17_g4 Time 3:30 P.M.

Call by: W. I. Vogelsana of TUGC0'- Enoineerino Div.

Mmel Answer by:

Floyd Renshaw of AMP Prod'uctr Cerocration. Product Fngineer Wmen Jc====rt Contract No:

)

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRTo*. er snLitTonun*

lV03MNiOT

' terminals P O D "I:I vv2

  • Tradema rk nf AMP inenennratpd 1

sUMMAltY OF DISCUSSION, DECISIONS AND CDMAUTMENts.

W. I. Vogelsang discussed the AMP memo dated September 2,1981'in which Mr.

B. Eister. had indicated a 60* bend without reannealing was acceptable. It was discussed that with some. suppliers at CPSES (GE Co in particular) that it was necessary to bend tenninals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (nonnally under 18 inches), and as such, the full mechanical strength of the connector was not required.

l Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90 bend or two times to a 45* bend.

l-However, this does not pr.eclude. bending the terminals up to 120*. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire to be supported by the terminal the susceptibility to vibrations b) c)

once installed if it is contemplated rebending these terminals,

~

they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised thati while a terminal bent more that 90* to 120* would not retain its full mechanical strength it would mainatin its

.. - electrical characteristi.c. s.

V:dw' cc: ARMS r#

L.M. Popplewell AMP Products Corporation F. Harned/D. A. Wilkinson/F. Renshaw Valley Forge, Pa. 19482 i

I

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTIUTIES NCP No.

GENERATING Co.

NONCONFORMANCE REPORT (NCR)

E-9 4 O l O G cl UNIT STRUCTUAE,5YSTEM ITEM /CCvFCNENT TAG /ID NUP SER LOCATiCN OR ELEVAT:CN RIA NO.

1703/66.2oA cus s'c3s 4 I

S, G. '/

verwb-loes cmasoea-os 9 m /03 B. 9El

/WM NCNCONFORMING CCNCITICN M.nA~ x.h s.;- m y

d 6 o' c%p.

y Z

~. O I(/4. Olo Od

~fo i m. @ cide 5 da IUORMA-~0iY O

i COPY b-WhY W

LM b

)

b-b O. 7. [ 'i AEFEPENCE COCUMENT-REV PAAA REPORTED BY:

CATE:

4 Y/h/

.;E AEVIEW/ APP:CVAL:

I

/'

CATE:

  • YA LJ / f /hV A

0 ACTICN ACCRESSEE f

lCEPARTMENT l

'Ioun.s /soAterrr/

o Ts=e te, s i

REWCRK REPAIR USE AS IS SCRAP 7~HG TG2M1AJAL. t.AAJCG9 CD TE~ 2MIA!AL Scock AA Poidr 2 15.Tb 66 2ER.ACCO. REAtated.

W 77W c.0Ls*6er MAUJfALYt)AE2h Fbse ncA) as runt 7ECM1AJAus May'eE BEAJrCAA DM6 TD W P
UD JP Tb ICo*.J.TH A*J ciV6 CGatiAJ4 EVAcuADOA). 6'UGlCEG2JAJ4 rfAS REViEsdGP 77se y

Foe t.cvJi AJ c: TECMcAJAt.s tr) 90 cst 10A1.*

Q TEAM /AIAG BeocK KLMIA]bc Post T

'O AA 1

'Z Dr 96 00C 1% TERM 1AjaDOAJ.AIAT~ TNIS TERMIAJAL TMfS NOT F%SG A4) E'QOtPMEA!Y O

gEggc,g,A6 LITY pac 6c6M %D MW 6C OsED As is.

MOR,' AT TtcMrAJAL5 HAVE 6eGd OsTAtt.rD Sy W C s/Co h R.

$6E p;rrAC4ED (PPA 38,2A (

i ENG. REVIEW /APPACVA1.

OATE:

gf/%@ !

CE REVIEW APPROVAL:

DATE:

/f Y/

y

' O ' CISPOSITICN VERIFICATICM & CLCSURE:

CATE:

/

/

COMMENTS:

7l*M AN CHE FGK STEAM L.ZCUIC 37a73CN w I

-, f 9703/6620 A INSPECTTCN REPCRT lnsy _,_ y,,gy39,l g.ca.,r.rc.sr.ca,c. w4 istsra e s awcr.= ca.s. cur.c=

i o. asscairr.ca czjpss 1E SQukmf vcos-Epsa)CA-oz

~ 02 BS2 ' SGI em-so3 J

p,4.ccir ac

.lw u ccc. a av. a cm a,o.

vu..s

m..

sa

.u.

G27-c20-/Ay-se B6 VO ES-/00,l 1

/

C \\">a18M'n C F" M Wen"*" Q W !"

&*,.%s C %'%n

,l en

w. nr.ma.:s (msm: an ew r e. u.:. meam.irzas sarmerce

,M f g_,g4 C iasm cie aw.z n. u=== merce iro= us c ar :w

  • ^7"
  • ct 1,carg j,*79,g INSPECT!CN AT7MIEU43

/

I &,ew2/xdwa resirsh h % x m n s l- -t l I

I I rasw-hs/ Nn rAe reeksihd niiskmb l l l l

l Is,rcr-co-// 3-2e R-20 I Ii i

i rii i

i I TPrm&AL &6cr A A & mw)wL W &*2.

I& I i

l l

l l l l

\\

l i I I I

I I

I i l i

l I

I i i i

l i

l I i l

I i

___L_ i '

i

(

1 I

i ntdoMall LMii i

i e i y T

._1

-i 1 I

l#'*36'%.EiW W i I

iM 1%t 13 11 11, t I i

\\ %.n I.

\\\\

l 1

I IODgy 11 I

\\ W' l

I I I I l

l I

I I I I

l I

I l l l

l I

i l I l

I I i l l

l "c"*"s t-m.m t=> Leysam ines/sr es ece E-sv-c/oc 7 Sa'A / 924-9

,q-v i-co 34 9/ 9 &# est

/Ha'o' WP fexasc/

tcy sw 7:e.n, nis's we v.ehr4 w*'ar Disp * "Y' rB ris t/o n h & 1 R.

nr e c,ca se

art up-

[- 8 ElI-- C / 6 6 9 N

.g e

cc agsw,g ;g 2tv i(-.e J. b3-t gy,,,g

.d_

h.:.c c -- 9-.g y w

A A

A A ON c'

7,xAS UT?uTIES CENbATING CO.

NONCONFORMANCE REPORT (NCR)

E 451075R.2 Page 1 of k

IJNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /10 NUMBER LOCATION OR ELEVATION RIA NO.

I Cubicle #11 1

! S.G. #1 Vendor lues CP1-EPSWEA-02 Rm. 103 El. 852' N/A IONCONFORMING CONDtTION i

l 0

Lugs listed below are bent in excess of 60 or twisted.

ay Terminal block Tenninal points l

z P.E.

G g

p [.

, 8

,\\,,0hVATOlY D;

"*f' y j(Oq a-P.B.

4 0

P.P.

1, 2 h

P.R.

1 f

e O

S Hold tag applied, all unrelated work may Continue.

}g cl d

I I

AEFERENCE CGCUVENT:

REV PARA AEPORTED GY:

DATE:

Steve Bufkin 4 / 9 /84 DATE:

l OE 1EVIEW/ APPROVAL:

u,g l M

h

$ //$ / f>'

I. Vogelsang lEng.

CEPARTMENT C

ACT:ON ACDAESSEE

ISF CSITION:

(1&3)XX SCRAP (2)XX AEPAIR USE AS IS REWCAK mL See attached disposition.

u-

!U ARMS PERM. PLT. RECORD g,

INDEXED a

_l.. =, '

c:

g l.

JUN 041985 e u er,<uoc.

l 8i Wf I

l g

l I

I DATE ENG AEVIEW/ APPROVAL Y.

[i }~1 I

' CE REVIEW APPROVAL; DATE:

b we O f~/17iFJ'!

w O

ISPOSITION VERIFICATION & CLOSURE:

DATE:

i Y$ EN05 T d ^^^

$~ t l? I f 5 0 CC M'iNTS; Rev.1:

Reopened to Clarify disposition.

Rev. 2:

Reopened to attach AMP Engineering evaluation report & to address twisting.

t,,lV.g$

hE b P DISPOSITION:

NCR #E-84-01075 R.7 2 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PE G

~

PJ 7&8 PB 4

PP 1&2 PR 1

Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal point and associated terminal was inspected by Electrical Engineering and was found to be bent less than 90 but it does show signs of fatigue.

This terminal is to be replace -

Rework.

TERMINAL BLOCK TERMINAL POINT PS 3

Mft yy ilcW 3.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

M dW WORgG0h

-+wo-COPY mv l

C 3) h A_ a ::

ENGINEERING EUALUATION REPORT 4/01/85

^

.....,..... L....

3 CE EEPE000CG C iid.!D Giii.ai WiliTS PDESIN GF AMP IEGAPORAIG.

EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence N.

Table of Contents Introduction.

'"ge 1 Test Specimen Description.

Pi tge 1 Test Schedule.

Lge 1 L...D...a...a.* P.

Test Methods tge 1 Test Data Summary.

.P tge 2 q

Appendix A (Engineering Conclusions)

.......... Page 2 Prepared by h

Approved by j f

x 4

David Fleming Q

Floyd Rephaw Test Engineering Product Engineering Supv.

General Products Group General Products Division

  • Trademark of AMP Incorporated essesnat pocoucre enour asse secomponatus, naneussuna. pa.. ittes v.s.A.

t l

INTRODUCTION This report cbntains results of tests conducted on PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products 0 and 900 and a performance when subjected to bending of terminal tongues of 60 twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 M 0 M E 0'v 1

0 TEST SPECIMEN DESCRIPTION The following Terminals and quantities were tested.

Quantities ner Test GrMOf f I

Terminal Part No.

Wire Size Group 1 Grdu; 2 IdEduo 1

/!

53425-1 10 AWG 4 @ 600 Bends 4 @ 90o Bends 4 @ h50 Twists

. Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Groue and Seauence Test Groun 1 Group 2 G roun 1 Voltare Droe 1-3 1-4 1-9 Vibration 2

2 2

TEST METHODS Voltare Droo.

Each' terminal was measured for voltage drop by energizing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the Junction of the other end of the test sample was secured to a stable rapport 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

1-

~

TEST DATA 'SUt98ARY f

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Soecimen # 1 2

1 h

1 2

1 4

1 2

1 h,

Initial 15.1 14.8 15.4 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib.

16.h 16.1 15.9 16.1 19.1 17.1 16.1 16.h 17.1 16.2 15.7 MIL-T-7928G Max 19.5 14.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tengue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects, i

1MFORgGOM PP l

1

COMANCHE PEAK STEAM ELECTRIC STATION

~

Tcxid UTILITIES "U

GENE ~ATING CO.

NONCONFORMANCE REPORT (NCR)

E-84-01075 R.1 Page 1 of f

UNIT STRUCTUAE/ SYSTEM '

ITEM /CCMPONENT TAG /lO rkiMBER LOCATION OR ELEVATION RIR NO.

Cubicle #11 1

S.G. #1 Vendor Lugs CP1-EPSWEA-02 g Rm. 103 El. 852' N/A NONCONFORMING CONDITION M _

9 Lugs listed below are bent in excess of 600 or twisted.

INDEXED' Tc al block Tenninal points RN'hi_T. RECORD J

,8 rira nt: to j

P'.B M/1N M 4

suanceLoc.

a.

P P.

1, 2 O

P.R.

1 8g Hold tag applied, all unrelated work may continue.

c:

AEFERENCE CCCUMENT:

REV PARA AEPORTED BY:

DATE:

Steve Bufkin 4 / 9 / 84 i OE REVIEW / APPROVAL:

C DATE:

u

/U

/O /

3 ACTION ACDAESSEE DEPARTMENT l

I. Vogelsang Eng.

i OlSPOSITICN:

(2)XX (1)XX AEPAIR USE AS IS SCAAP

{

AEWCAK

'N F0Ph AT OK See attached disposition.

h g

vua C:

"W 8;

N n

f ]

DATE:

I ENG R EVIEW/ APPROVAL bL

./ / C/

  • 13 A

/

1S_S,T 1,,c_> CeSeRE; p

,,gg

=

Reopenedtociarifydisytion.

0 - E~TS: aev. 1:

ff,Bo(A DISPOSITION:

NCR #E-84-01075 R.1 1.

The following terminal points and associated terminals have been in-spected.by Electrical Engineering. The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PE G

PJ 7&8 PB 4

PP 1&2 PR 1

Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal point and associated terminal was inspected by Electrical Engineering and was found to be bent less than 90 but it does show signs of fatigue. This terminal is to be replace -

Rework.

TERMINAL BLOCK TERMINAL P0. INT PS 3

Y pjQ l))(V Ilhl 1

E0RMA7 ION I

COPY PPW s

TEES UTIUTIES COMANCHE PEAK STEAM ELECTRIC STATION CENERATING CO.

NONCONFORMANCE REPORT (NCR)

E-T y - D I DM UNIT STRUCTUREi SYSTEM ITEM /COMFONENT TAGUD Nu SER LOCATiCN OR ELEVAT:CN RI A NO.

H&5/d2CA

c. u s ic] r )s S.C.7 Vader Lue 3 cpl EPswe4 o &

R m lo3 EL7.0 1>/4 i

NONCONFORMING CONDITION i

Q Sa a. A % h a woAeof6e*et. W,I 66i o ek.

%, b o i,,a r.

I 0K c

[W0n%,.Wiib i

u c.

I.'$.'

"'l

9 k

L u.u e

QA RECORD coRil l

P. n..

i L

' QA pEVIEW II l

O p

r 30 r-aw w

C Q

FILE No,

15. /

l SU.8 FILE No,

.S.

/O O 5'M Gl o 76._

,AR, 1 AI REFERENCE CCCUMENT.

REPORTED BY:

s OATE:

1M h, / 9 / ((

OE REVIEW / APPROVAL:

7 f

CATE:

b.C h/

/hY w

-~

j CEPARTMENT O

ACTION ACCRESpEE i

2DMEt /6."WaJrr/

i t s: & C c' i l

DISPOSITICN:

i REWORK AYY REPAIR USE AS IS YYY SCRAP l

._T)4s istualNAL. LMett ow7symeent hW. P.S 1%ngT 3151b 1%e tatus.En 'RE.woet.

_sva eseenwr me,Ac,Tvests Testmmt nTHErTammentsMAver aaurews near n sof.4Ao up vo _j y. 2c? wnWamuwnaw:r-svam aMementsue- **t Rensseo ne AwwAs-neewinun su samW i E. TuesamAt ti.oc.u. ; T).e..- 1?"I.- P. B.

"P.P. tR.

._ 1 o

Q. TseraiwAt posur; e - JS gt. - l

__ q z9 G _TT ts eet misawmmow nwr rwau. Tasumts no war ame, aw agoipwaar seawesAstury m A%b MAY f55 USED AS 15Y

%aL nar$TE we 8_^= "" MM.

ENG. REVIEW / APPROVAL DATE:

n'11 L. (

Y /$/N l n

x

>v OE REVIEW APPROVAL:

O clSPOSITION VERIFICATION & CLC RE:

OATE:

_!=-

[ t// i FY COuuENTS:N01K: Au915*Amnu JMur

/nV7MedD DY W UONOat.

2 6 s M T K y s 0 c A M. 9 4 t,s//

FINAL.T.A E t co*40957

4-IEliiROAE COhvi.7.5Ai!ON RECORD 3.e 4-17-M

'~

Time, 3:30 P.M.

Call by: W.1. Vogel sang of TUGC0'- Enoineerina Div.

gn=e=rl

(%m.l Answer by:

Floyd Renshaw of AMP Producte Ccrocration. Product Engineer

~

c===M (mmel Contract No:

Sub[ect discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOL 1 STRAND *

.d

' terminals t%#%Q\\

\\MW' yO y

  • Tradema rk nf AMP ine nrnnratori

\\

(V

SUMMARY

CF DISCUSSION, DECISIONS AND CCMMITM_ %

W. I. Vogelsang discussed the AMP memo dated September 2,1981'in which Mr.

B. Eister. had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (nonnally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45 bend.

However, this does.not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'd be supported by the terminal b) the susceptibility to vibrations l

c) once installed if it is contemplated rebending these terminals, l,

they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to l

120* would not retain its full mechanical strength it would mainatin its electrical characteristics..

y;gh ' '}. 5l*,

cc: ARMS

-XJ L.M. Popplewell F. Harned/0. A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

4

^

^

^

TE7AS UTILITIES NCR No' CENERATING CO.

NONCONFORMANCE REPORT (NCR)

. 0 9 y ~ D ) D Y _.-

UNIT STRUCTURE / SYSTEM ITEM /COMFCNENT TAG /lO NUMBER LOCATION OR ELEVATION RtR NO.

~

d,U%ic][j) b.b.

WMdor_kuc3 OPIEPSWM 03 EMlD3 E@l 11/ 4 NONCCNFORMING CONDITION 4

MM bD 04,

% i e d.

hai,or.

a R s.

G juo FC #E o

P. J.

t'ed, P.6..pnm/6r9

}feAS CL E6 k

h%

p MU 0

P. 9 -

1 1 Y

\\r\\

3 17 fL GhA z

\\)

Y g

P. n..

1 W., - '"

, m s'"% 0,.~5s 1

?

e

%/'

S.

/O O

,Ev 4,

2_M l

EEFEAENCE 00CUMENT.-

M L a 13 v.

t OATE:

REPORTED &Y:

e/ i 9 i P(

OE r:EVIEW/ APPROVAL:

CATE:

us hf V/ f /W W2..

'O ACTION ACCRESSEE IDEPARTMENT I

DISPOSITION:

y REWORK REPAIR USE AS IS SCRAP

  1. e rmea (Just r 1erm 'Al b bel PS PL13 & 4 le Pfalad. Akad-fa ca rted Ms.s*4dwr's Psita t.' t'Ad fe&k "1 h M onf@ f*

go*g u w eH&f wdA c4m9 6maj A f /%p to Izo'wirA-te.r&c i s q m M.'

l&

$a l

fer.J 8/ocA f M Po d, 8

ge G

A pf 21 l>q lz ps 1-fP N [t is ne hierN4 Hsf dese te.r Jr af pse. w of4O ser.?rM4iT9 M*b/w o~A % be. xM/ @ n A, /4 &r. 6dd/CPAf.se2 Mre, Antr % kJ /s Lu mAAW 4/.

I ENG. REVIEW / APPROVAL

'fid CATE.

//f/

Y

^

f3

  1. 2 gM U

DATE:

QE REVIEW APPROVAL:

47 e : : ^*,. _

A-14 N bW V f Y / l0 / YY

us OLSPOSITION VERIFICATION & CLOSURE

DATE:

l l

/

/

COMMENTS:

COM AN CNE PEAM STEAM E&.C *R1C

$TaToCN snw-

/ -, /

epos/sczc p sumcmcu men

m g,.c;o,,e,,,

,g

. a m a,n.a.

,.se c.,u r.a s cu.,, ema amer n _..

Q'4SS 14 f9MDMWf scc /V-C Ri14 EAf-cz-

~o2 252'sSG t V- / O 3 al w

. m m.,/

,lpr.c. =..

v..o.ast. 3-se n<

u Csycc d u.

..m.,

e 2.

c1" Rim c % Mle = c w rg cmh-.,,

ces'g.,,

,j Jasp. u sus.73

[/ erT.l,"Os 33sp.E"E3, AL:. MMUC.aat.E ITMS SAT:EP&CTCM eMj ggq.gtys.

3 c. e:

==, r a,.

=c c. irc= win se :.

e INSPETICN AT7RISUTE3

=

gArg

,7, i

irk ewake ranks /en an sea L-1 l l

\\rurmekd %" rAn re/whsL l l l l

f f M-wkm/s e,rcr-enin ze sr-zo I i ;

l l

l lI i l

I 2'-

I rer/&wt sta>- pd re Not M M 3 I4 I I

I l

l l l l

l i

I I I I

i l

I I II i

I I II I

I I

1 4 1\\

l I

I f inAl\\

l i

X d\\M _ l4\\ l l

f aY&' 1-4 W N I

I

\\ \\W%d.A I S l\\

l I

\\'aM 9 m.! I i \\

l I

\\4 L>I 'ai V

i i

\\9-#

noWV I I

I

\\

Wi i

i I

l

\\

fl i l l

l 1

V l l l l

l I

I II I

I i

i l l l

l l i l l

l

  • o**a t:+ see:1. t=.n icy.r we irp cc-/u AW #cs ess-oso 76-w M /4'Z9'9' pcu-./- cost 7/ 9 Irkm 206~

Mch/ rst #Wme'd

'r144 is-ddo-rik Z.4.

hg,g.)/h7f-,l L K. C: ".4C g,4 "*

Y Ng- ; sissar.A=

., l

)

g m t-d 6

)d 4-L u c.) -d Ave 3 # Y 1

4 i

l I

COMANCHE PEAK STEAM ELECTRIC STATION TEYA3 UTILITIES NONCONFORMANCE REPORT (NCR)

GErdRATING CO.

E-84-01076 R.2 Page 1 of b

IJNIT STRUCTURE / SYSTEM ITEMiCOMPONENT TAGilDNh8ER LOCATION OR ELEVATION AIR NO.

t

~

Cubicle #12 1

. S.G. #1 Vendor Lugs CP1-EPSUEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION Lh.26 0 or twisted.

M w ' ""

Lugs listed below are bent in excess of 60 l

p.k on W

,w Terminal block Terminal points WFORMATiON 3,

?*

c P.G.

3, 4 k

E P.B.

G 5s,'

/

o P.P.

2, 4 3 c #

k d

j A.A.

1, 2, 17, 1.8 e

c" O E ?

[

Hold tag applied, all unrelated work may continue.

ffhi c:

2*7 1 ES-100 AEV 2 PARA REFEAENCE CGCUVENT:

DATE:

AEPORTED GY:

Steve Bufkin 4

9 84 f

f OATE:

[ OE REVIEW /APPAOVAL:

wl

/w f i / t i C.s' C ~ ACTICN ACC AESSEE I DEPARTMENT i

I. Vogelsang

! Eng.

i CISPOSITION.

USE AS IS(183)XX ScAAP (2)XX AEPAIR AEWCAK t

See attached disen W ~.

5:

ARN Mi

%Q{KEO PERM. PLT. RECORD i

m:

!{

yjn04M

~ L I ~

' '" / s /

=1 svants toe.

Ill'C #

gi E<

ENG AEVIEW/ APPROVAL DATE.

I il]IK i v

i J CE REVIEW AAPROVAL:

V DATE:

Ym_e 0 f i t ? i P.S

~

w C

ctSPCsiTICN SERIFICATION & CLOSURE:

DATE:

l wodu/d O 7 &'~

C it71 er s 0"NN*S: ReV. 1: Reopen 6d to Clarify disposition.

F.ev. 2: Reopened to attach AMP Engineering evaluation report & to address twisting.

~

w w

p fgwi ' '^

gfgIV DISPOSITION: NCR #E-84-01076 R.F A 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering.

The inspection indicated that these terminals, were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PA 3

PT 3&4 PG 3&4 PB G

AA 1,2,17,18 Based on the above evaluation,'the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal points and associated terminals have been in-spgeted by Electrical Engineering and were found to be bent more than 90, the vendor maximum allowed without an engineering evaluation.

These tenninals are to be replaced - Rework.

TERMINAL BLOCK TERMINAL POINT 2&$

  • jldkhg PP

/

/k/3h 3.

The twisted terminals are to be used as is.

See the attached AfiP Engineering evaluation report.

4p, d u r[

7/ 7 nw 9c8 c#

~

AA. a =3 )

C ENGINEERING EVALUATION REPORT 4/01/85

^

......... L....-.. !] BE KEPE000CU la TUJ.:d.iD iiiiieLi WidiTEX PERISSEE OF AMP IEckPORAIG.

EER - 136 i

3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence

\\y\\foEWOh Table of contents ege 1 Introduction.

Test Specimen Description.

...... Page 1 Test Schedule.

Page 1 Test Methods.

Page 1 Paga 2 Test Data Sum::'.ary.

Appendix A (Engineering Conclusions)

Page 2 l

f p

424 Prepared by h

Approved b David Fleming Q

Floyd Rei haw l

Test Engineering Product ngineering Supv.

General Products Group General P.roducts Division l

l

  • Trademark of AMP Incorporated l

OENEnAL Pn000 CTS en0UP 1

mesecomponarao.namneeune,ca mesv.s.a.

. ~.

INTRODUCTION This report cbntains results of tests conducted en PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the mo of March, 1985 SMFORgn0M TEST SPECIMEN DESCRIPTION sh The following Terminals and quantities were tested.

1snB\\ I Cuantities ner Teht h "f hl Terminal Part No.

Wire Site Groue 1 Group uroup i 53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testing was per MIL-W-5086 with tin plated copper-strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Group and Sequence Test Group 1 Group 2 Groun 1 Voltage Droo 1-1 1-4 1-3 Vibration 2

2 2

TEST METHODS Voltare Droo.

Each terminal was measured for voltage crop by energi:ing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

l TEST DATA

SUMMARY

i Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2

3 4

1 2

1 4

1 2

1 4

Initial 15.1 14.8 15.4 15.1 14.5 y.2 15.2 35.0 18 7 14.7 15.8 15.1 After Vib.

16.4 16.1 15.0 16.1 19.1_ 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5

'19.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9.0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other tvo groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by neavy equipment running, we feel that tne testing proves that the terminations vill withstand such a l

condition without any detrimental affects.

l C{

O m

i i

__.__...____,___,._,,,__._,mm._.m

~

TEXAS UTILITIES NCR Na CENEIATING C3.

NONCONFORMANCE REPORT (NCR)

E-84-01076 R.1 Paga 1 of el UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

l Cubicle #12 1

S.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION Lugs listed below are bent in excess of 60 or twisted.

I h

Tenninal block Terminal points PERM. PLT. RECORD z

P.A.

3 J'

3, 4

""[

"'" /d, /

8 P.T.

P.G.

3, 4 suer u ioc. /(/(1/M c.

P.B.

G c

P.P.

2, 4 A.A.

1, 2, 17, 18 8

ARMSN'M Hold tag applied, all unrelated work may continue.

c.

e INDEXEU. N DATES P~$ERENCE CCCUMENT:

AEV PARA AEPORTED DY:

OATE:

Steve Bufkin 4, 9,84 l OE REVIEW /APPACVAL:

jfj C,g[

f DATE-

/// /A (H 0/10fl85 uJ ACTION ACCRESSEE

~

DEPARTMENT I. Vogelsang Eng.

{

CISPOSITION:

(1)XX l

)XX REPAIR USE AS IS SCRAP AEWORK See attached disposition.

i

'f

\\'hg l

r0y?

8 i

v g

InlW i,c c:

DATE ENG REVIEW / APPROVAL n,

/f l

og a

0 WSPOSiflON VERIFICATION & CLOSURE:

DA COMMENTS: Rev. 1:

Reopened to Clarify di p )sition.

l I

fgANA DISPOSITION: NCR #E-84-01076 R.1 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PA 3

PT 3&4 PG 3&4 PB G

AA 1,2,17,18 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal points and associated terminals have been in-spgeted by Electrical Engineering and were found to be bent more than 90, the vendo'r maximum allowed without an engineering evaluation.

These terminals are to be replaced - Rework.

TERMINAL BLOCK TERMINAL POINT 2&$' 54Y lg PP ik

/k/3 gy iker c-e#

g 1-

mes.

e.

i

.yp gg y

i

.gm.

COMANCHE PEAK STEAM ELECTRIC STATION

)

TexIs UTiuTIES

]

NCR Na e.ENERATING CO.

NONCONFORMANCE REPORT (NCR)

E-7 y - nI n v I UNIT STRUCTURE / SYSTEM ITEM /COMPCNENT TAG /Q NU SER LOCATION 09 ELEVATION RIR NO 8903/' u=U uscae":x f C #l deJne Lne.$ 29) FM rJEA-c.1 Nm/n3 RE}

2)/A l

NONCONFORMING CONDITION N

wm 6 0 ',a C % Q.

a T*

  • i S oc k.

%7,o,i. / R[or.

z 2

P. A-3 o

( Mi hDPl ed 5,.FtyintECURD 3

E. O.

OA REVIEW q

C 5

g h.

, P P-3rt[N.

ib15# 8v' 4,, Q.,4 A

A. A.

FILE N.

,g

),

c SUSFILE NO.

E* WU-0lD N, H

s i

k 2

  • 7.

l REV PARA AEFERENCE UMENT*

DATE:

I REPORTED BY:

9/f/IY

/

OATE:

OE REVIEW / APPROVAL:

w

/L/W' V/9/,fV c

O ICEPARTMENT f

ACTION ACORESSEp

  • 3rnamit leCWMAry?
  • I54sr SWi OtSPOSITICN:

REWORK XXI REPAIR '

USE AS IS YM SCRAP IHe cut 3ENT Aneters4cTt#EtrN,'fDsfiloW stTHAT"fERAMidAL1, AAR$f MW oNE"rtM6'rt 90,*thub UP_'10.110" W A9V' A nf E N 6/N SE D N 6' JVI9dengfl0 W e _&Nb484 WAR & M4f MMw6n90 rhlC.~r^ ^,: 13REwAself M qsdSTIN//

I w

JET.mW AL 'BlatX 7E$ssist4LK T3tJAINA1.,1KcCJC 11AMittAL POINT; TE.E AAtuAL f5Let.8C 7t' DaattaAL.T%iefry E

P. A.

~P.ar.

44 A.A.

I, r.,13 is

__ j c

$ -. E*T 3, af

- p, gg,

2*L11_evittsTEsemustnon nurr THtus TsanAnnu.s em wer Pase Aw sqviemswt Marwes44n.sy a

5, ~PRootaA4 Aun uny os 'Esto u V'

<, _1%44 *ttR44404ALS LA% deb att TBSAAINAL.StalCJL Y.P. b#8TJ % N M S 1 0 R 8' M M M A O N ssE NWTE W toaAMewd

~

ENG. REVIEW / APPROVAL

/

OATE:

k /25/84 l u

i r, r s OE REVIEW APPROVAL:

/j OAT -

aAJOA M / P 4--

w0 OlSPOSITION VERIFICATION & CL SORE-DATE:

/

filli 8V CouuENTS: wors Amp rasaiuusas m mass rescae es,' rses' reassen l

ses mitAcuan eAPA. - Sof28//

ElemL TD E. l.OO*409.1llf' P

l

.:...c,,s-Dat e-4-17~84

~.T5EFNONE CONVtr,SATION REC'ORD Time:

3:30 P.M.

Call by: W. I. Vogelsang of TUGC0'- Enoineerina Div.

Caeer)

(Nomel Answer by:

Floyd Renshaw of AMP Products Cerocration. Product Fngineer hM (Namel Contract No:

PIDG, PLASTI-GRIP *, or SOLL%'9fM*

Subject discussed: Bending of PIDG*, Nuclear mCGQN

' terminals

\\g g \\s a 5 -

4.-

M tg 3

  • Tradamark nf At1P inenrnnrated

\\_ f SUfA7AARY CF DISCUSSION. DECISIONS AND COMA 4 TW_~%*IS.

W. I. Vogelsang discussed the AMP memo dated September 2,1981'in which Mr.

B. Eister. had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90 bend or two times to a 45 bend.

However, this does not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'6 be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these terminals,

~

they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to 120 would not retain its full mechanical strength it would mainatin its electrical characteristics.,

Vidw-' [ -

~2..

cc: ARMS

-X L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

^"

^

^

^

TEXAS UTILITIES NCR No'

' GENERATING CO.

NONCONFORMANCE REPORT (NCR) b7 f - O l O '78

't.?

UNIT STRUCTUREiSYSTE M ITEM /COMFCNENT TAG /j,0 NUMBER LOCATION OR ELEVATION RIR NO.

Sfos/ct*1A tu s.cle "t x SCf/

e d r e h 4 M P) F R$fJi M - 0,1 Il@/n3 FL 951 2][/l *

~

l NCNCONFOPMING CCNCITION Q W %b N AC-m q 60 "e M

J E

% ~ a i BAc.k.

hh/ R-[or.

A.A.

y - SPd*

A

.L N)

S pp@

k 2

  • 7.

I AEV PARA AEFERENCE CCCUMENT-REPCRTED BY DATE:

9/f/Y o

CE REVIEW /APPRCVAL:

CATE:

w'

. s6

' '? 4 V/fthV O

ACTION ACCRESSEC l CEPARTMENT

'TONM WEA777 7 @ <:r C C-y-I CISPCSITICN:

DY AEPAIR USE AS IS XM SCAAP AEWCAK j

  • cum & 47 tar J5 I

' h 9 0 ', a d.4/

h /2D" ddh' w

l "" " A W T_r Wad l

Hk!

5 AA.

S a

RE 3, 4

. R B.

3,G tZ

'R4.

4 A. A.

I, 2, /7, /8 Y

ff WDW hn ogg) es& y'j&A 14 nn: u s a u k a m A L os.$0 M b

& rtu Nf h

. msu em-saw ENG. AEVIEW/IPPACVAL

/

CATE:

s-vL, k ll$1 N CE REVIEW APPACVAL:

DATE:

lm Y /[i/ I CISPOSITICN VERIFICATION & CLCSURE:

CATE:

/

/

CCMMENTS:

j

~

~~.M AN CHE PGX STDM L.IO"'MIC 37a71CN e.e.-

I, r

2903/6627A IN9ECT1cN REPcni lmy_pg,,,;

. n. auc.wr.cn i.serre.ar a 5 at,,u is n r- <s m cr n cas.s w.cn

& pss'1E"E % uA sk W &

eCP/-EAS/d64 -O z-

~ 08 8'FZ ' SCr/

8/77-/C3 4

p.d.se r.ac www au a.s ccc. a grv. a camisa e

.u.

ES-/C0.hw.

gws a z-e CZ-GA-/AATR H-6~

m NC r

1= asps::ns Cpn =r-it.unen C tus c:ren E1hau.

Cpn n-l m

en vore.ar.ca

asn: cm asn:: en wsn:cen JmEP. MEZW,.is Emspe m :=w r n, u meam.: ims mananc c=

,, M, mf.g4 C ins,ce en c:w.z n, unam.meren ime e ar_:w

'd***

3^73

.e INSPECTICN ATTRIBUTE 3

, gayg ei

/

I &,**nfLl3(t // /C W J n; y E AFY d5 x_f AV4X9 M lb I l

izwsm+ed' kg rA

-scAx/2se saiwszy l 1l 1

l l

l /A c:z:cs //.1-2s s-zo l Ii l

I I

rii l

l I cN rewdx M&er PR sadf) rewlnt 4kB l l l

l 1244 id i I

I I

I II i

i l

l lI i

l 1

1 I I M\\

l l

IM o\\l \\

l 1

f ) 6 \\l\\W l.<\\

l i

X, dWSOf ' l.,,: 41~.7 \\

l

\\ \\\\* ' h-f93 l %. \\

l I

\\ A 41 M FL i

\\

l I

\\ fi

.%# 1 ai

>I 1

\\V l.kOWif I

i

\\

l ! \\VI i

\\Ei i

l I

'l l l l

l i

I l l I

l I

I ll l

l 1

i i i I

I I i l l

l w"x t:wm x c s tcyu asse sw ww sce c=c4-oso m em 17z+ 9 G C V- /- C034-9 /*7 bJ 86 &

l

/WW 74y H&sreveg/

rdk is 6 -r7AM z; 8.

4 0 743

.lLM. CCgg[

gg_; staaw M

,l cc gp,;,;a J

%.a. y M-. +

~

n u s. m l

COMANCHE PEAK STEAM ELECTRIC STATION TixAS UT10T:ES NCR No.

NONCONFORMANCE REPORT (NCR)

GENTRATING CO.

E-84-01077 R.2 Page 1 of k UNIT STRUCTURE / SYSTEM ITEM /COM PONENT TAG /lO NUMBER LOCATION OR ELEVATION RIA NO.

l Cubicle #13 1

S. G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 E1. 852' N/A I

NONCONFORMING CONDITION 0 or twisted.

Lugs listed below are bent in excess of 60 aw Terminal block Terminal points

,Ip;p o g g y 10 G 5

P.D.

G:D L ur' 1t 8

P.P.

2, 3 6,. e c

P.R.

2<

3.

5,9,TT4,3_,2.,,1

('

a a e, w,

6 y

y.3, Hold tag applied, all unrelated work may continue.

s PPR\\r e

c t

I 2

2.7.1 ES-100 pgv p3,4 REFERENCE CCCUVENT:

CATE:

REPORTED BY:

Steve Bufkin 4

9f 84 f

CATE-l OE REVIEW / APPROVAL:

C ACT!CN ACCRESSEE 0EPARTMENT

! Eno.

I. Voaelsana CISPCSITION:

REWCAK REPAIR USE AS IS SCRAP j

j See attached disposition.

Q PERM. PLT. RECORD o

as m

Tuar:Leloc, Bi weg l

M bfu. L-~

sindI DATE l

ENG REVIEW / APPROVAL CE REVIEW APPROVAL:

V OATE:

I fW.' f ^-

$ / $1 / E5"

.?

.y C

CISPOSITION VERIFICATION & CLOS 'RE:

oATE:

hYhl*fd{

f

' fn m'!= h

$ /l9/T$

COMMENTS: Rev. 1:

Reopened to clarify disposition.

Rev. 2:

Reopened to attach AMP Engineering evaluation report & to address twisting.

I

0e.) s1.2 i

.s Ci,y DISPOSITION: NCR #E-84-01077 R XA 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 90* and that no flat.ing, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PD g

2Ef R

PS gg3 LB 1,2,3,4,7,9,10 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem, f

wd Md 2.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

0 e L A A rs e,c

\\bc+

l

C"3 ENGINEERING EVALUATION REPORT 4/01/85 g

... L....

70 CE EEPK000CG N~.1 iUJ :!.!D iiiiidui YlElII(X PI M ES E OF AntP IE0liPORAIG.

EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence 4 m Table of Contents a

'i ^'

u y

Introduction.

e1 Test Specimen Description.

Page 1 Test Schedule.

Page 1 Test 4 thods Page 1 Page 2 Test Data Summary.

Page 2 Appendix A (Engineering Conclusions) p F

Prepared by h

Approved b David Fleming Q

FloydRephaw l

Test Engineering Product Engineering Supv.

General Products Group General Products Division

  • Trademark of AMP Incorporated GENERAL PRODUCTS GROUP AasP ueC0mPORATIO. MAnnSSURG. PdL.1F185 UJ.A.

i l

INTRODUCTION This report c6ntains results of tests conducted on PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the me of March, 1985 N0? SAT 10N

[

TEST SPECIMEN DESCRIPTION The following Terminals and quantities were tested.

m1TW

}

Quantities eer T est GroutI i AY Terminal Part No.

Wire Si:e Grouc 1 Group roun 1 0 Bends k @ 450 Twists Bend Q @ 90 53425-1 10 AWG 4 @ 600 Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Groue and Seouence Test Group 1 Greue 2 Groun 1 Voltage Droe 1-9 l-4 1-3 l

Vibration 2

2 2

TEST METHODS Voltage Dron.

Each terminal was measured for voltage drop by energizing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the teeminal probe point.

Vibratien.

Terminals were rigidly mounted to and not more than 1 inch _above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2

1 4

1 2

1 h

1 2

1 h,

Initial 15.1 14.8 15.4 19.1 14.5 19.2 19.2 19.0 19.7 14.7 19.8 19.1 After Vib.

16.h 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 14.5 19.9

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 45 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand sue condition without any detrimental affects, vos vp

AM

+ExA'S uT.LITIES GENERATING CO.

NONCONFORMANCE REPORT (NCR)

E-84-01077 R.1 Page 1 of 4

f UNIT STRUCTUREi SYSTEM ITEM /COMPONEN T TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

Cubicle #13 i

i 1

S. G. #1 Vendor Lugs.CP1-EPSWEA-02 Rm. 103 El 852' N/A NONCONFORMING CONDITION 0

Lugs listed below are bent in excess of 60 or twisted.

h Terminal block Terminal points z

P.D.

G PfRM. PLT. RECORD 8

P.P 2, 3 Fu P.R.

2 I. -

78,/

Ah/g

.B.

b,9,7,4,3,2,1 J

Hold tag applied, all unrelated work may continue.

. ARMS. -,im l

a.

N w

e INDEXED 4'

AEFERENCE CCCUVENT: ES-100 DATES REV 2

PARA 2.7.1 AEPORTED DY:

DATE:

Steve Bufkin 4

9 84 l

/

/

ll1 N' Y!Ob0S DATE-CE REVIEW /APPAOVAL:

u 3

ACTICN ADDRESSEE

' DEPARTMENT l

I. Vogelsano

!Eng.

l DISPOSITICN:

XX REWCAK AEDA'R USE AS IS SCRAP t

See attached disposition.

f 3

?

b A

ENG AEVIEW/ APPROVAL

[

[il DATE.

I

!/

/

/

'CE AEV _

m-s x P

L: <

V' DATE:

Y

/

I

  • n a

O

_DISPdSITIC'N 'V5AIFICATION & CLOSUAE:

O COMMENTS: Rev.1:

Reopened to clarify disp i ion.

ff AdlA DISPOSITION: NCR #E-84-01077 R.1 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that 8

these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PD G

PP 2&3 PR 2

PS 2&3 LB 1,2,3,4,7,9,10 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

f l}N IkB M) iIdd

  1. '*'cO>$

v4

--w

~

_,,_f eq

+dmM&'"A3.

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES NONCONFORMANCE REPORT (NCR)

&'t 4 -D l n') )

GENERATING CO.

umT STRUCTURE, SYSTEu iTEveCeurCNENT TAoiia NuusER i.OCATiON OR ELEVAT;CN RIR NO.

99a/C62 M tussc\\e*l,3 CS #/

andor Loes kpl 591L)EA-01 flin /03 FL.75 L oh9 W

NONCONFORMING CONDITION W W &Lw ~ SAL w q 6o w % q.

W we ma h.h.or k3 M' O Ri/ 4 b

.d wm A

=

p.a.

P.6 1s J d

A s.

10, %., m.t, %

1 a,

g S

ARMS

,)P W a

1NDEXED m

A 2-),

/

[

.b nATE:

AgV p4RA REFERENCE COCUMENT.

REPORTED BY:

CATE:

b

/h/YY a

' OE REVIEWi APPROVAL:

A CATE:

tL,

- A bt I

I O

ACTION ACCRESSEE ICEPARTMENT snuns./muntn

, rr<,.

v_i OtSPOSITICN:

REWORK R ED AIR USE AS IS XIY SCRAP i

'vG_evetswr_mkuuse: ruts's postrfoH.11 THMTTeemuM.1 #Ay ans 1herrONE T1wn TD 90*AHo eP

'D \\to*wmt Art sNMnEstw avnLunnod. sN616santmee N41pavissMD TAE AmoeVrhe TEtwNALK I>I

)

h @ vest 10al: Tununaht Stoc.x, Tat e:44.14merj TusMNAL*4Me&M. TEGAMMAL 'TDIWT E

TD,

_ T*.L.

'43 a

C e

?.f.

1,3 _

c.1b, i,2,% % 9,80 g

P. R.

2.

5.xr is ava osuminunow wxTrasas Tatww.s n. Hornas a seos,mewr saewcpan.iry

  • T=enna noy,,9s."

ns,is a

i saan.,

in - - w e AL RECORO ENG. REVIEW / APPROVAL OAT r;,

RLV

,s s,

m OE REVIEW APPROVAL: /

h FILE t O O

cisPOSmON VERIFICATION & C[OSURE:

J#%"*Ib7) k $OT:24-Edb

. N f.j f M./

24 x~

COMMENTS;Merst Adup yngewWg,g Afeg Sggv Sy M #d4 Set l

ssa AffAussa o.AAA sgtW Yadh bbr:ACWM5$

'V

/

7

u....,..-

TaEPHONE CONVEF.5A110N RECORD m 4-17-84 Time:

3:30 P.M.

Call by:

W. I. Vogelsang of TUGC0'- Enoineerina Div.

3Cmganyj (Name)

Answer by:

Flo'vd Renshaw of AMP Producte Ccrocration. Product Engineer hari (Namel Contract No:

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-G16SOUI AfftMW y[Unm \\ t W '

.mune A *dYkk,

' terminals t ar wm e # u,py 4

as P?RY

  • Tradema rk of AMP inenrnnrated

SUMMARY

CF DISCUSSION, DECISIONS AND CCMMITASINIS.

W. I. Vogelsang discussed the AMP memo dated September 2,1981 in which Mr.

B. Eister had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90" bend or two times to a 45* bend.

~

s However, this does not pr.eclude bending the terminals up to 120*.' In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'd be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these tenninals, they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to 120* would not retain its full mechanical strength it would mainatin its electrical characteristics.

b..~

~~

l V:dw' cc: ARMS

,I.M l

1..M. Popplewell i

F. Harned/D. A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES NONCONFORMANCE REPORT (NCR)

E 'it 4 -O I n1 )

CENERATING CO.

.)

UNIT STRUCTURE / SYSTEM ITEu/CCMFCNENT T AG /lQ, NUM B E R LOCATiCN CR ELEVATION RIR NO.

996.r/C& 2 7A c.u sicl e=I3 G.G "l a w d o ? L a r s e p1 Cl?L La cn ~o x nin}OX kl.9$1 D}A NOMCCNFORMING CONDITION h9a TU p 6o w%%.e r

"T'a rm e n b lb l 6c.k.

$r in Do. sO I' r

~

.2.

9.S L> ]

p'at y s

Ove he l0

%) & A h

J J J j

N p

PP@.

[

REFERENCE COCUMENT-REV PARA

=

REPORTED BY:

OATE:

LA

/h/$Y CE REVIEW /APPRCVAL:

5 CATE:

W/

/W

//,

./

1 <

ACTICN AOCRESSEE IDEPARTMENT "JhMEL /&Md.ATTI i *T R,. sA DISPOSITICN:

REWORK REPAIR USE AS IS WW SCRAP

.YMUStdb' * '/kW/-

<' <f Mr.4 3 I/td>

c' f$,

$2i Cuo/Jrh 47'2**t Ylk l'elthdf) j '

2 QttJ.? f' $O' /20 ' Uk c2?r.1 Jr l Lt/cl!A$Esuo 0ytfis=l4US N/d.L' Ns Yt4 Y Y. JJ jdMsy %klv.abya&yh*%Yk'T.,y I Lk

_%qL IWL y

m:

e ei:

2,3

/i 4.

O

]O A S.

29 3 p

l<

hJhew *bhrus'U <st

.hMw'sts/J h p g arja _,

2 d

fr an$-s/tAy h, Jr:1.t'.tk J.,b.$'hu:t.rb 42e<

Jin Jsublb Auf Y'fA.A%/dH: 4Y a'h'.5kt::l a,

l-t/c}c.' /Iy /A 38 ?4/.

ff l

ENG. REVIEW /APPjiOVAL

/

OATE-CE REVIEW APPROVAL:

DATE:.

MMM Y//T/IY m

l OISPOSITION VERIFICATICN & CLCSURE:

CATE:

/

/

G*

CIMMENTS:

l

~. '. -

CCMANCHE PEAK STEAM ELECTRIC STATION

/* TEXIS UTILITIES

" C" "#'

NONCONFORMANCE REPORT (NCR)

CENE7ATING CO.

E-84-01078 R.3 Page 1 of 1 UNIT STRUCTUREiSYSTEM ITEM / COMPONENT TAGilD NUMBER LOCATION OR ELEVATION RIR NO.

Cubicle #14 1

! S.G. #1 Vendor Luos CPI-EPSWEA-02 Rm. 103 El. 852' N/A I

NONCONFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted.

h Tarminal block Terminal points z

P.S.

2, 4 8

P.B.

3, 4 m

A.A.

1, 25, 26 3iI03/LATON e

g Hold tag applied, all unrelated work may continue, i

i COPY,,,,j

??RV i

2 2.7.1

~

ES-100 REv p4AA AEFERENCE CCCUMENT:

DATE:

REPORTED BY.

84 l Steve Bufkin 4,13 f DATE:

OE REVIEW /APPACVAL: hYE&wb S* i / 61 ^7s '

I w

O ACTICN ACDRESSEE l DEPARTMENT I. Vocelsana

>Eng.

I CISPOSITION:

XX SCRAP REWCRK REPAIR USE AS IS See attached disposition.

W PERM. PLT.RECnRO l

RTN F L ' ( 9 0.

bf suSFILE LOC.

i e

=

9' E<

MW Ki niK' DATE:

ENG. REVIEW / APPROVAL OE f.EviEW APPROVAL:

U DATE:

b - foe.r>=P b b~ i 11 l W M

w O

CISPOSITION VERIFICATION & CLOSURE:

DATE:

,Wu[/u/jr Lk = A*' L W 0 C ij7 iW COMMENTS:Rev. 1:

For correction of terminal point numbers.

Rev. 2:

Reopened to clarify disposition.

Rev. 3:

Reopened to attach Af1P Engineering evaluation report & to address twisting.

(.t.)d"I A sh gs ch,I4 v

  • DISPOSITION: NCR #E-84-01078 R.f S 1.

Th.e following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PS 2&4 PB 3&4 AA 1,25,26 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability p'roblem.

I

}

hll tlCW 2.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

M C/n d eLs 7Al/7/?J

~

f d*5

  • 2Qk.

g eve

C:3)

ENGINEERING EVALUATION REPORT 4/01/85

^

_ \\ A-r

......... i,....... ?] GE KIPRODUCG C iiiJ.u!.!D GiTUui WRiiiEX PGIGIIM OF AMP INCGRPORAIG.

EER - 136 3029-50013 7

AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequenc
  • c7 Y 4 kJ

[

j d'

Qi

< g, s.

ooglt

-(

l l

Table of Contentu L_

Introduction.

Page 1 Test Specimen Description.

...... Page 1 Test Schedule.

..... Page 1 Test Methods Page 1 Test Data Summary.

Page 2

. Page 2 l

Appendix A (Engineering Conclusions) l l

t Prepared by w

Approved b

]

p 4'

David Fleming Q

FloydRephaw Test Engineering Product Engineering Supv.

General Products Group General Products Division

  • Trademark of AMP Incorporated a==== mas pnoouenenoup Aaseesconroname.=a-= PA.17tesU.S.A.

INTRODUCTION This report c6ntains results of tests conducted on PIDG PVT 2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 1IFORMATi0h TEST SPECIMEN DESCRIPTION The following Terminals and quantities were tested.

1 Quantities ner M GM LES d'

Terminal Part No.

Wire size Groue 1 Groue\\2 "

~Groue 3 53h25-1 10 AWG 4 @ 600 Bends 4 @ 900 g Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TES*/ SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Groue and Sequence Test Groun 1 Groun 2 Groun 1 Voltare Droo 1-1 1-4 1-9 Vibration 2

2 2

TEST METHODS Voltare Droe, Each terminal was measured for voltage drop by energizing with SS amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

l -

. g

' TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2

1 4

1 2

1 4

1 2

1 4,

Initini 15.1 14.8 15.4 15.1 14.9 15.2 19.2 19.0 19.7 14.7 19.8 19.1 After Vib.

16.4 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 i

MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plar.e of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

"-All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke o'ff after 9 0 hout-in the first plane of vibration apparently was mounted improperly as all c. the remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without j

displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

(

t6xA's UTittrlES COMANCHE PEAK STEAM ELECTRIC STATION

~

NCR No.

CENERATING C3.

NONCONFORMANCE REPORT (NCR)

E-84-01078 R.2 Page 1 of j UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

l Cubicle #14 1

S.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION 0 or twisted, Lugs listed below are bent in excess of 60 d

Terminal block Terminal points E

P.S.

2, 4 PfRM. PLT. RECORD 0

P.B 3, 4 h

A.Al 1, 25, 26

"" /

"'* '/g, /

$UBFILE LOC.

g Hold tag applied, all unrelated work may Continue.

g(1g i

ARMS

's

?

INDEXED' c;

DATES

{

ES-100 2

2.7.1 AEFERENCE CCCUMENT.

,,y AErORTED DY:

DATC:

i Steve Bufkin 4 / 13/ 84 !

OE REVIEW /APPAOVAL:

6 DATE:

fll(L Of /0N ES u

J ACTION ACCAESSEE OEPARTMENT l

V I. Vocelsana Eno.

DISPOSITION:

AEWORK AEPAIR USE AS IS XX SCRAP See attached disposition.

M s

\\MFORM e

es%?M O

h k1 b

l a

2 8

PPR\\l l

0 l

l a

ENG AEVIEW/ APPROVAL 0

u YL' g//(1,*g U

DATE:

CE REVIEW AP llSti$

I

~

O

/

0 DISPOSITION VE' RIM TION & CLOSURE:

/ "

DATE:

i n,dwAA>

/ iEid m

m OMMENTS: Rev. 1:

For Correction of term'n 11 point numbers, j

Rev. 2:

Reopened to Clarify d s osition.

i--

g,,( s n e '

DISPOSITION: NCR #E-84-01078 R.2 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would 1.adicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion cf system testing.

TERMINAL BLOCK TERMINAL POINT PS 2&4 PB 3G4 AA 1>25,26 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

d< c iW s.1 hMI 1

\\}\\iO+M W '

C O M,;. y PP@

e COMANCHE PEAK STEAM ELECTRIC STATION m,g gy,gg CENERATING CO NONCONFORMANCE REPORT (NCR) l E-s u -nlo 7 9 ru

' TEM CCvFCNEI47 TAGin JU\\ISER LOCATiCN CA ELEVAT:CN AIA NO l

STEM unif sinuCm mE,S}442%f W

& ((-

l

{, C..

h US L.m s D14%)ent-o1 % ID3 SS 'L MlA NONCCNFCAMING CCNCITION EAA A %%h h of 6v i a

g.

I m

m

\\

A t3.

Yh-T8eh a

e o s s__

L COPY 7; yn I

KEFERENCE COCUMENT'

  • b LOO AEV

_1 PARA 1*)*I LEFCRTED BY:

CATE.

i S

0-L/ / (5 Y e/ b x

CE 5 EVIEW/ AppaCVAL:

CATE:

I wl 4 //f /7/

l m

O ACTICN ACC AESSE'

~ CEPARTMENT l

"TbNf3 do/eth4M D&

f fLr l

C15POSITICN; REWCAK

, PEPMM USE AS IS III SCAAP

  • 048 CDt2BMT* AAANVFALTURO& W 11*INIDJAL) AAA'(155 W ONE TIME TD90,*AMD

.upve rv wmv A imm.v.em sunucmv.amasemme tw esm.wso Tu mx4 m unwea.t.

mw ARMS rg.iu e m a:

reuAim m-2.

T=-w. we s __..

u-2,4 INDEXED l

k 7.D.

44 h

A+ A.

I Z$ 1(*

gg s

E rT is,Dyt. DSTER.AWMTicW *TMNT *THe4G 'TARm:4W bo NOr1086 AH SQulPRAS6fr SEAvr.AADH.tT't

,T9".TH.EM $.44tlb % y'ESE WSSO 96% 11b r as -a w,----- ts QA RECORD ENG. REVIEW / A#PRCVAL 7

g QA REVIEW CATE-I y L.it Js#

NA4/

Y /.M8/N Ca :.EviEw AreaCvAt; j

/

~

4g e

_ CE,T,CN E. _ CN.CLCEe.m jgfgy 4 gg O

coautum %. I p5 = rs wr,u.h

~ a p w.

l Ws

= =T=.: aur Ta m.

14K ATT/KMean C.P.P.A. 34 g,q(

/

.r m.m m

. m. sgk

,e-

- h e imom em=* e m *we hwm-- m -- moe*m eye g e a.a-*wa

- = 7 -= w =e,m,

.....e,_e.-

TEl.EFHCNE CONVEi;5ATION F.ECORD m 4-17.34 Tim,,

3:30 P.M.

C-Il by: W.1. Vogelsang of TUGC0'- Enoineerino Div.

3Cepany)

'Nomel Answer by:

Floyd Renshaw of AMP Prod'ucts Corocration. Product Engineer c=== v1 (Namel Contract No.

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or S0llSTRAt40*

{ Num"{

r

_ _ m.. n -ri tu terminal s

.,* M T "T m

\\C% W 5

  • TradFN Pk Of' 4M9 InedennrAtAr$

EUMMAltY CF DiscutSCN. CEct$10 NS AND CoMMITRINT3.

W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr.

B. Eister had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one timc to a 90" bend or two times to a 45 bend.

However, this does not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

length of wire t'o be supported by the terminal a

b the susceptibility to vibrations once installed if it is contemplated rebending these tenninals, c

they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terininal bent more that 90 to 120 would not retain its full mechanical strength it would mainatin its electrical characteristics..

  • Y.

~

~

4:dg -

i cc: ARMS X4 L.M. Popplewell F. Harned/0. A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES GENERAUNG CO.

NONCONFORMANCtE REPORT (NCR)

E-? 4 -01o19 UNIT STRUCTUREi SYSTEM ITEM /CCMPCNENT TAGalO NUMBER LOCATION OR ELEVATION RIA NO.

1903/6629A Cvsecl< 14

_l 8 G.# /

vg d e Loes celF9stwn c1 Dih los EL PQ n)//J U

NONCONFORMING CONDITION MCAob (o D n ka%s.

a M ' N 4 l-k lot,lr.**-

g, gy O

9 be gq P' D-L4 NR g

N) Y g

Sc:

b O <- ) -

f4EFERENCE COCUVENT-REV PARA KEPORTED BY:

CATE:

H / &/ h s

I CC REVIEW / APPROVAL:

CATE:

. ; c im" 4'/ 9 /P Y w

O ACTION ACORE SEE

' CEPARTMENT

~1DHES enMAA Tfl I T141,- t dlr 1 OtSPOSITION:

REWOPK REPAIR USE AS IS SCRAP k

\\n i i gg y

w s

A 3

0 O

y 8

??@

s<

l ENG. REV:EW/ APPROVAL DATE:

/

/

CE REVIEW APPROVAL:

DATE:

w

/

/

I O OtCPCSITION VERIFICATICN & CLCSURE:

DATE:

/

/

j COMMENTS:

/

  • ,..a

^

TEXAS UTILITIES NCR No~

GENERATING CO, NONCONFORMANCE REPORT (NCR) c-su -nlo 7 9 ru y!

TAG /l BER LOCATiCN CR ELEVAT'CN RIR NO.

UNIT STRUCTUREi SYSTEM ITEWCOMFCNENT ch$U W l

G. C,..? ~

aa n%t. Le tR) tips u+a-o x k.,1ch

%h n)/A NONCCNFORMING CONDITION i

Exk A %L* _.Je q g Ct ca. ~.

-r_. a

9. s.

D N0gA30M

9. * -

n.+.

') MM

D f q&

J s

~

%e Oxs n.u., n

%rJ

?PRV 1*).I 5

OO R E'I PARA AEFERENCE CCCUMENT-F.EPONTED BY:

CATE-4/{

y/

s

/

CE REVIEW / APPROVAt.:

CATE:

k 4 t/f /W y- _ m __

, CEIPARTMENT 91 ACTICN ACCRESSEE CISPOSITICN:

REWCRK REPAIR USE AS IS M'Y N SCRAP

$/: curar) -mt..w/a42a' d cd<2b >.; 4..Zizl f/

, $ m a :a f,i

.} m,7l64, sv.E acj/.+. no 'un.d az. xy2w,a,;.,.<n d.i%sa &w'../t.,8

' ~

, tr yo o a

gh,4 >,&,.a.,.e m d. is. p a c k v

.TermJ Bid Fey ( Rd r

i: s.

z'4

~

R6

= 4

~-

~

A.

i % c-16 f Y ^8 4,ggyygpl gjgQ{ h

f. d a,.,. w.<-

.n. n a.,, g;g.,& rg;r & ly,q/. M,g g ;

A' W

'I s

x.

tbb: 8'i p k n. Idv.bws,$VC.J b.,l.Y44%!bt.

2.aYM'bC/'X-SM4).

/

l

['

[

OATE:

(Y', b kW ENG. REVIEWIAPPROVAL

-11/91 Bf t

~

l CE REVIEW APPROVAL:

g CISPOSITICN VERIFICATICN & CLCSURE:d)h % d4 its;ry OATE-QATE:

%.i p a n 4 I a.s p w.

l c== === 1

A ON

{

TE.:/.s UTILITIES NCR No.

NONCONFORMANCE REPORT (NCR)

CENERATING CO.

E-84-01079 R.2 Page 1 of Y

IJNIT STRUCTURE / SYSTEM ITEMICOMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

Cubicle #15 1

iS.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted.

I i

d Terminal block Terminal points E

A.A.

3 8

NP.A.

al l - r.., ' ' --^T i -

1 KF0gE0M

}

nductors 14AA1, 13AA1, 13AA2, 14AA2 h

Hold tags applied, all unrelated work may continue.

)

i i

2 2.7.1 ES-100 pgy pani

  • ~FCAENCE CGCUVENT:

DATE:

I HEPORTED GY:

Steve Bufkin l

4,9,84l DATE:

i l OE REVIEW / APPAOVAL:

M/7

[ // d i T[

4 wl O

ACTiCN ACCAESSEE l DEPARTMENT i

I. Vogelsang Eng.

l

SPOSITION-AEWCAK AEPAIR USE AS IS XX SCAAP See attached disposition.

.de l

(

khNb PERM. PLT. RECORD h

L l~

RTN jr'l 2'

y m 0 4 'S M

=uen't 'oc.

l2' A/c f d 9i DATE:

i ENG AEVIEvv/ APPROVAL f

4 b

lNI CE REVIEW APPROVAL:

U DATE:

&^

YW!W (tl? / W W

O CISTOSITION VERIFICATION & CLOSUR -

DATE-Y Ebf8V 2 Y T m 2'= h

[ t));ff OW ENTS: Rev. 1:

Reopened to clarify disposition.

Rev. 2:

Recpened to attach AMP Engineering evaluation report & to address twisting.

/p M N 4

WYl/f /

DISPOSITION:

NCR #E-84-0107/ R4 A

,gi j

1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering.

The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT AA 3

PA ALL PR ALL PF ALL PT ALL AA CONDUCTORS 14AA1, 13AA14, 13AA2, 14AA2 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

'f

) h jp/l/

'l W 2.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

Wo r/n/g eLs ra sw Wr.c-

\\

4 e [ s..

Ch.,.(

c:=2 ENGINEERING EVALUATION REPORT 4/01/85

.g

........ i,..... 3 CE GG00C0 N".1 iU.:d.!D liill' sui WTdiTEN Pim 0F AnlP IEGRPollATG.

EER - 136 3029-50013 A:4P* PIDG* PVF2 Terminals Tested to 14IL-T-7928G Vibration Sequen e 11%y k

A.mSe 9

s O

Table of Contents Introduction.

... Page 1 s

Test Specimen Description.

Page 1 Test Schedule.

Page 1 Test Methods Page 1 Page 2 Test Data Summary.

Appendix A (Engineering Conclusions)

Page 2 Prepared by Approved b

]

p 4'

David Fleming Q

Floyd Re@ haw Test Engineering Product Engineering Supv.

General Products Group General Products Division

  • Trademark of A14P Incorporated oceanAs.Pacoucts enoup Aase esopaponATED. "*==""" PA.,17148 U.S.A.

INTRODUCTION This report c6ntains results of tests conducted on PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 3FORMhTLON TEST SPECIMEN DESCRIPTION c.

The following Terminals and Quantities were tested.

Quantities eer, Test Gro add f

h.Clw

^

Terminal Past No.

Wire Size Groun 1 G rei n '

53425-1 10 AWG 4 @ 600 Bends k @ 900 Bends k @ h50 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Group and Secuence Test Groue 1 Groun 2 Groun 1 l

Voltage Droe 1-4 1-4 1-i Vibration 2

2 2

TEST METHODS Voltage Droo.

Each terminal was measured for voltage drop by energi:ing with 55 amperes with DC current and probing at the intersection of the tongue and l

wire barrel and a point on the wire 6" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes i

mutually perpendicular to each other and to the axis of the wire. l l

TEST DATA

SUMMARY

i Voltage Drop in Millivolts at 55 Amperes DC gy,pM Groun 2 Groun 1 Snecimen # 1 2

1 h

1 2

1 h

1 2

1 h.

Initial 19.1 14.8 19.k 19.1 14.5 19.2 19.2 19.0 19.7 14.7 19.8 19.1 After Vib.

16.h 16.1 19.9 16.1 19.1 17.1 16.1 16.h 17.1 16.2 19.7 MIL-T-792SG Max 19.9 19.9 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the t Q and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say th'at any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 45 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

  1. ? %.

e.?

COT#

COMANCHE PEAK STEAM ELECTRIC STATION C..AS UTILITIES CENEZATING CO.

NONCONFORMANCE REPORT (NCR)

)

E-84-01079 R.1 Page 1 of 4

l UNIT ST AUCTU AEs SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION AIR NO.

Cubicle #15 1

S.G. #1 Ver. dor Lugs CP1-EPSWEA-02 Rm. 103 El.852' N/A ToNCONFORMING CCNDITION Lugs listed below are bent in excess of 600 or twisted.

l Terminal block Terminal points PpRM. PLT. RECORD z

A.A.

3 8

P.A.

all

"* 4

"" 7g /

P.R.

all

^

,,,,u we o.

P.F.

all ggy e

P.T.

all A.A.

3 f

g A.A.

conductors 14AA1, 13AA14, 13Af2, 14AA2 ARMS

%.3 a

INDEXED 3

i c:

Hold tags applied, all unrelated work may continue. _

l DATEg I

ES-100 2

2.7.1 AEFERENCE CCCUVENT.

pay

p3n, AEPORTED BY:

DATE:

l Steve Bufkin 4 i 9 /84 i

Cd DATE:

$ll(L 0/ iOfi Pf' CE REVIEW / APPROVAL:

J ACTICN ACCAESSEE DEPARTMENT I. Vocelsana Eno.

I DISPOSITICN:

REWCAK AEPAIR USE AS IS XX SCRAP See attached disposition.

-o?

bJ %

8 b=

i n

A I

ENG AEVIEW/ APPROVAL DATE-Y'

. l ""M"$$8LM N-

/iEefl

^

O CISPOSITION VEAqFICAT:ON & CLOSURE:We T/hyrD

/ idAT :iB51

/W D

COYMENTS: Rev. 1:

Reopened to clarify Iosition.

j i

pp. A d2 Mf/cy 4

DISPOSITION: NCR#E-84-0107/R.1 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering.

The inspection indicated that i

these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT AA 3

PA ALL PR ALL PF ALL PT ALL AA CONDUCTORS 14AA1, 13AA14, 13AA2, 14AA2 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem, f

f

)

jylll

!lflW p ff21 c-

^

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTIUTIES I" -W - olo 7 9 GENERATING CO.

NONCONFORMANCE REPORT (NCR)

E UNIT STRUCTURE / SYSTEM i ITEM /CCMPCNENT TAG /lO NU SER LOCATICN OR ELEVATION RIA NO 8903/46foA c&cJo I6

/

A 4?/

o,,eh.- Loc _s cvisescoe a - o.1-R rn 103 h, F6.1.

tin NONCONFORMING CCNCITION

--A OA.,R.,

p of s.o

  • o c%..'34L -

T r M 90s TM IWO A l Slod.lg G

b@I 4

G-4.aJ DOfL

9. k
  • p g_

a t

g gC.

u.

L g

9. T.

pAA 3

A. 4, 3

, E.-YM i

5 QM h

e

\\WDEXED. (

A4-6"*{oL l

~^

!OO REV PARA D

/.

REF CE CCC;.; MENT-REPCRTED BY:

i CATE:

. kM e m Jb

  1. f / T. / M 4/

l CE REVIEW / APPROVAL:

CATE:

___-U j /kr U / 9' / Wu O

ACTICN ACORES3EE lCEPARTMENTj i

TDMat /ccAfa.6f]7

. TFCo-ccm-I DISPOSITICN:

REWORK REPAIR USE AS IS XU SCRAP

  • Tus_evataur Mhuur.Mn21RA "2carflow asTHMr3ME TEthuN AL 1 MA4lDE.DfMDME.31kE.1u 90}Auh_,,

.U~5'1D 11.O*NWM ANEN6tMEEDN6 AVM.tArf>tW. ANdrINiit/New His R&V/6WED TM6 MOW & WAMfM4L $ __.

y.1M _ Q u tST1o We

_..... _ _.TE.tA4:nM.DLot.% WRPAipm. sq'3ERusuu Dtot.w., rsiugipac pegerl-E. ILEMiwM 1Loat Witutek.pett4Tj P. R.

MA.PoistT1 A. A.

S

.i O

Q AA.

S

. P. F.

A LL PottrT5 A.A coMoosDRI.14AAll3A41(

j P. A.

Au.feie413 P.T.

_ ALL PoiWT5

_.lW2,NAAL g

.T.TJg cog OcragMINAT104 THAT '1WESC 'TEtwatS Do Nor9osE kw Equt9aAabfr se.Rvic.amnis 7Y 9tO%WAA J h x_M J gg_M J%

s a.s wort aw con w n.nr1 ENG. REVIEW /APPROV/L k/b/N l CATE:

G f

a CE REVIEW APPROVAL:

/'

j //

OT-in M

t

/

1 O

Ol0 POSITION VERIFICATICN & CLOSURE:

/ //

DA* :

,_M./=h

/

/

COMMENTS:Mwit.s AMP 75AA4swddl A84W 884M /&prAedQF TAE FAM8 cit 36K JDffcMrO cfRg sq,gW

{f b /A / & & VEd 5 Yh Y r

'ta:

a.

HLEPHONE CONVCr.SATION RECORD w 4-17-84 Tirn.,

3:30 P.M.

Call by: W. I. Vogelsang of TUGC0'- Enoineerino Div.

%)

(Namel Answer by:

Floyd Renshaw of AMP Products Corocration. Product Engineer Enrm7)

(Namel Controct No:

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOLISTPM terminal s gni v

., ~

t 4s w

/u a

4 y

pew

  • Tradnmark nf AMP int nrnnrated

SUMMARY

oF DISCUS $10N, OEctSIONS At4D COMMrT#1N15.

W. I. Vogelsang discussed the AMP memo dated September 2,1981'in which Mr.

B. Eister. had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45* bend.

However, this does.not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'6 be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these terminals,

~

they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to 120* would not retain its full mechanical strength it would mainatin its electrical characteristics.,,

l1).

2-

.:'~

WIV:dw"... ' :'..

cc: ARMS

% -X L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

u.

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTsuTIES NCR No.

cENERATIN'G CO.

NONCONFORMANCE REPORT (NCR)

P -SN - olv i 9

-}

UNIT STPUCTURE/ SYSTEM ITEM /COMFCNENT TAG /lO NUMBER LOCATICN OR ELEVATION RIR NO.

89C3//;&fo,4 cx % clo I6 l

A G.* I a eh.- h s tvineswo ct-oa_

R m l OA EL. M on 9

c NCNCONFORMING CCNCITICN.

%g etam~wa-of c.o

  • 4..LM.

d Tec t v06 ) Blec,lg Torm 9eIoT -

M' O N A.,0ik; r

a s

a wagsma.

7' m

Q.

W OO(L 9 k*

g_

h E' Y*

4') 1. L.

&V 6

9. T.

Ad f

A. A a O

fh-1 y

ll A.

00!L'CNSNU d 0 ^ ?, A b esti)sfy I 3 f)JQ, lynA A b

REV.

PARA D

/

8tEFE:ENCE COCUMENT-RETCRTED BY:

DATE:

.Y

-. _~ D

'/ / 9 / h *(

e

.. J CE REVIEW / APPROVAL:

2 CATE:

y V / 9/W C

~~

I.CTICN ACCRES3EE CEPARTMENTj

%Nt25 /ccA/P,4-177 T P C,- R&I DISPOSITICN:

USE AS IS YYXX SCpAp REWORK REPAIR hl Eut+47f s7XJ r:M Y!Lish fCb 'k b',,YlAbYkr'..bM*t011l.4,<fl?<k bls dis *rh* +1: o kAus

+'

, W di

.Af' Y*' ' /2W (A.*bY;,. GhtU a* *1 ib'rWks'.? Atksftd,(,,

a t4

,,,/ks,,,,.,,,qp yyhss,af,'

p N

) ',' ly g' Ni!T

/S t. :

<g

.Nyrnind $locN

'Q,.,,o,,,, f ho i r, {

h A.A.

3 O

?s A-s4l.4. j'O/s/rs 8.

Alt.

f'On/7.6 Q

r

'A A f*

At /,. f'o/My B.N.

/?!. t-I'c/Nr.s Z

je A.s$

4tW/4:'7T45 / 4 AA/> t.14Alf, i.34A2 14M2 3

o

}'

Q

'A

  1. ~ ~* Nf #Sff'NAk'an*klo ly fn nx6 4 W./

4tjy.,g sa,th h.,, y,,lg.y ; }_,fl,.} ff/','9 -]gg llW Y#

ENG. REVIEW / APPROVAL

'I CATE:

' ~ ~

%. t/M

  • h// / &\\

CE REVIEW APPPOVAL:.

DATE-ul b Lf'>*A h %

Y /{

$I{

OISPCSITION VERIFICATICN & CLOSURE:

DATE:

/

/

CCMMENTS:

COMANCHE PEAK STEAM ELECTRIC STATION

~

Tc :.s uTiutics NONCONFORMANCE REPORT (NCR) 4-b1080R.3 CEAEATING CO.

Page 1 of L-

'JNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIA NO.

Cubicle #16 1

l S.G. #1 Vendor Luas CPI-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION I

I Lugs listed below are bent in excess of 600 or twisted.

d Terminal block Terminal points l;

E A.A.

1, 33, 34 o

<n g

Hold tag applied, all unrelated work may continue.

j

!~

N0MIAT OK e

COPY Vi iN L.

2 2.7.1 ES-100 AgV PARA AEFEAENCE CCCUVENT:

REPORTED GY:

DATE:

84 -

Steve Bufkin 4, 13 1 CE REVIEW /APPAOVAL:

CATE: W

// /

U.!

O ACTICN ACDRESSEE lCEPARTMENT I. Vogelsang Eng.

CISPCSITION:

REWCAK AEPAIR USE AS IS XX SCRAP See attached disposition.

du Si PERM. PLT. RECORD Wt i

_I-...,

}5/

em, El

~

l sueriLE Loc.

Si NOSY 1 co l

l ENG REVIEW / APPROVAL y DATE:

D / /7/

i 0

E' 7~ m~m&

( ij 7i PS'l DATE:

CE REVIEW APPROVAL:

(

.a O

CISPOSITICN VERIFICATION & CLOSURE:

DATE-1 2M[

[ATMc

[ //7 1~ t COMMENTS: Rev. 1:

For correction of terminal point numbers.

Rev. 2:

Reopened to clarify disposition.

Rev. 3:

Reopened to attach AMP Engineering evaluation report & to address i

twisting.

f9.A 012 As, DISPOSITION: NCR#E-84-01080/R./.3 1.

The following terminal points and associated terminals have been in-

~

spected by Electrical Engineering.

The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechar.ical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT AA 1,33,34 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

l

)$

4

&W 2.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

Ahl/ rk.r/7/ft s

5/n/s.r

\\h COS we

e o

Q)

ENGINEERING EVALEIATICN REPORT 4/01/85

^

KA a

.. i...... ;] H KEPE000CG r

N'2 idJ.::!.!D GiTLLI YlilII[X P M OF AMP IE0liFORATS.

EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals i

I Tested to MIL-T-7928G Vibration Sequence

.. vs

\\,

y Qt

1 a

Table of Contents tw j

Introduction.

Page 1 Test Specimen Description.

..... Page 1 Test Schedule.

...................... Page 1 Test Methods Page 1 Test Data Summary.

Page 2 Appendix A (Engineering Conclusions)

Page 2

\\

Approved b

]

h p

42 7 Prepared by David Fleming Q

FloydReii/shaw Test Engineering Product Engineering Supv.

General Products Group General Products Division l

  • Trademark of AMP Incorporated cemenALpeooucvs enoup AaseneocaronATso.Hannsevne.PA mesu.s.A.

l

INTRODUCTION This report c6ntains results of tests conducted on PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 NORNATh0M TEST SPECIMEN DESCRIPTION pe, N J'

The following Terminals and quantities were tested.

__et Quantities ner ~ est"GrouY'#E(M r

Terminal Part No, Wire Size Group 1 Grout [_2

'Iivuo 3 53425-1 10 AWG k @ 600 Bends 4 @ 900 Bends 4 @ h50 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Groue and Secuence Test Groun 1 Groue 2 Groun 1 Voltage Droe 1-9 l-9 l-;

Vibration 2

2 2

TEST METHODS Voltage Droo.

Each terminal was measured for voltage crop by energizing with 95 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire e" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals vere so mounted that the Junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

t I

1-

TEST DATA

SUMMARY

Voltage Drop in Mil 11 volts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2

1 h

1 2

1 h

1 2

1 h,

Initial 15.1 14.8 15.h 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib.

16.4 16.1 15.9 16.1 19.1 17.1 16.1 16.h 17.1 16.2 15.7 MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of v,ibration apparently was mounted improperly as all of thg remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental I

results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to l

face moderate vibration such as that set up by heavy equipment running, we I

feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

\\

l

COMANCHE PEAK S?@AM @L@@9610@ @?oW@C6 TEWA3 UTJLITIES GENERATING C3.

NONCONFORMANCE REPORT (NCR)

E-84-01080 R.2 Page 1 of 4

UNIT STRUCTUREiSYSTEM ITEM / COMPONENT TAG /lO NU ER LOCATION OR ELEVATION RIA NO.

Cubicle #16 1

S.G. #1 Vendor Lugs CPI-EPSWEA-02 Rm. 103 El. 852' N/A i

NONCONFORMING CONDITION

~

ANMS\\

0 or twisted.

Lugs listed below are bent in excess of 60 INDEXED' nw Terminal block Terminal points f

A.A.

1, 33, 34 DArea Hold tag applied, all unrelated work may continue.

yRM. PLT. RECORD ATA nLL 60 O

sueFILt I oc.Ykk i

2

  • *1 ES-100 ngy PARA REFERENCE CCCUMENT.

REPORTED BY:

DATE:

Steve Bufkin 4

13,84!

f DATE:

OE REVIEW / APPROV

/O /

u

/

J ACTION ACORESSEE CEPARTMENT I. Vooelsano Eno.

CISPOSITION:

AEWORK REPAIR USE AS IS XX SCRAP g]hh See attached disposition.

e i

/

k k*

l g

n, c

3 k

PPRu

=

9 5

7

  • C A

L

.Wllbv, S4~J_'

/ iridT, REVIEW / APPROVAL DATE:

lENG O

//

u O

ciSPOS'IT1WVERIFICATIOY& CLOSURE:

O

/ /[ ATE-COMMENTS: Rev. 1:

For correction of ter i al point numbers.

l Rev. 2:

Reopened to clarify i osition.

vs

ffc$oU DISPOSITION: NCR #E-84-010808 R.2 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that t

these terminals were bent less than 90* and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK 7ERMINAL POINT

^

1,33,34 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

lW)$

ty@

lkW enpV vv1 PPW 1

l l

t

COMANCHE PEAK STEAM ELECTRIC STATION

-TEXAS ununt$

,NCR No.

CENERAMNG CO.

NONCONFORMANCE REPORT (NCR)

!F 01070 su l

i TEV/CCMFCNENT l TA il NUMBER LCCATiCN CA ELEVAT:CN AIA NO UNir STAUCTU AEr pSTEM l

8903/44d/

l 4G

\\

6.G. *l Urdoc Lues t 9s E%eos -ot Rmio3

?S.Ll N/A NCNCCNFCAMING CCNCITION l

g M

JW

&D e

AM%&.

Z Y*

lh-h[, Qptv m C

. w.

lj h

\\

I a

! "%W "F3%;, 7 h

4 7C DEXED o $tco

(

A iVn 1

O NATL 9

1* ! !

AEFERENCE CCCUMENT.

REv PAAA l

CATE:

i F.EPORTED BY:

w b

b N /O/

w CATE:

CE REVIEW / APPROVAL:

tzs M s ML 10/N O

ACDCN ACCAESSEE

! OEPAATMENT I

b Re-s4.N i

ages./emmerr 7 T

CISPOSITICN:

AEWCRK REPAIR USE AS IS NX SCAAP

-_'us.soetseur namwarven't.2comop tr mar varoraut.r pay-ns neurows rau suso,' Ano en ro 4

.120' wirx Au sNwestrus EWiewnoot. ANetuunsw was asytese.o na susevw+r=

w e.sw..

g g.Qu_esnout rtuninas.Dieur. _ newpau "bigr A. A. ___' _. _

1 33,3 *f 2

@ _2TJs ova.setumusumrunwarwe.ss tsemwws no war' Pose. Ausgomspr ssawcsasacry f '?9*h AmQ MM W.WJdD AS IS E

wtt Amt rsawwei.a HAve tGEN iM/MIP4&ED D*f "D4E V8N004 ser nyiptase eppA seg tyr q

,4 i

ENG. REVIEW /APPACVAL f

CATE:

t f

C.

+ i.nis+ l

/

P I Ca Review APpRCvAu p C

CISPCSIDCN VERIFICAUCN & CLC5UREI

/

O co""5"75: f 6.i b W a(

p.# 4 m.

l y d,X b A s//r

  1. 5/A rAreas

.e,_v.-

11;LEFHCNE CONVERSAi!CN P.ECORD

)=t e 4-17-84 Tima 3:30 P.M.

Call by: W. I. Vogelsang of TUGC0'- Enoineerino Div.

(Namel

%)

Answer by:

Floyd Renshaw of AMP Prod'ucts Corocration. Product Fngineer

==M pmel Contract No:

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOLISTRAND*

{

. terminals E03MAUUN M

.m

[D f M.) $f k

V d

%t i.

=

N y ~ V==

  • Tradema rk nf AMP inenrnnrated nnrMf rrny

}

sU.WAARY CF DISCUS $1CN, DECISIONS AND CoMMITENs W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr.

B. Eister had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90 'uend or two times to a 45 bend.

However, this does.not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'd be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these terminals, they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to 120 would not retain its full mechanical strength it would mainatin its electrical characteristics.

^

i y{gy lb.

~

cc: ARMS W

L.M. Popplewell F. Harned/D. A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

A A

AM ELECTRIC STADON TUAS UTIUTIES GENERATING CO.

NONCONFORMANCE REPORT (NCR)

.t Ol o ?D UNIT STRUCTURE / SYSTEM ITEM /CCMPCNENT TAG /lO NUMBER LOCATICN OR ELEVATION AIA NO 7963/ 46/SA 609 ;c]* f(o I

S.G d hebe A vu Cp1Emwn-ci f2mloA EL E 1 A)M NONCONFORMING CONDITION

~

W %WA %

f6

, M h

O'O' IL%M s

z 8

"Tacmsos l bloc g 7o r mi,un 3 90. J}

e I

E h

HM~

Qb-I L>.> &

M.

,R

/ OO nEV a_

n. 7_ /

EEFQAENCE COCUMENT.

REPCRTED BY:

DATE:

0 Y/9/hl A

l CE REVIEW /APAROVAL:

//

7 CATE:

h

'b?,. __

Y / 9 / W, C

ACTICN ACCRESSJE

CEPARTMENT MWI /dDNFJWT/

l *TT-dr 1 CISPOSITICN:

REWORK AEPAIR USE AS IS SCPAP

{

Y k

8 e% 84 11 h

e U'

8 PPR\\'

c<

ENG REVIEW / APPROVAL CATE:

/

/

CE REVIEW APPROVAL:

DATE:

w

/

/

O OtSPOSITION VERIFICATICN & CLOSURE:

DATE:

/

/

COMMENTS:

.=

e COMANCHE PEAK STEAM ELECTRIC STATION j

TEXAS UTIUTIES

'." '7 4 - o 1 0 7 0 n.)

GENET.ATING CO.

NONCONFOR MNCE REPORT (NCR) e-j UNIT STAUCTUREiSYSTEM ITEM /CCMFCNENT M cR LOCATION OR ELEVAT:CN AIR NO.

I

6. $. "l U+ doe Lt.es e 91e95 tae4 -on Rm to 3 E6A 74 >/4 NONCONFORMING CONCITION g

<b4 J[vD2AD bD whu.

=

i m %.

w.G 5r,FORMM. ON -

,' q ag

n. a,

L uAw&

(QV nL pph i "" # "A c

9 1*

O A f.V PAAA KEFERENCE COCUMENT-REPORTED BY:

CATE; M

b N / /3 /M w

h 1

CE REVIEW /APPcCVAL:

CATE:

  • c s 1A' lf//$/E(Y ACTICN ACCRESSEE CEPARTMENT CISPOS6TICN:

AEWCAK AEPAIR USE AS IS M' < ?

SCAAP 4/ -f

/ df'.et g

-g

.i j g.,,,,ug',,,z).,, b A s:/ m.dac.

2 l

g & _i-Di

,h,,a,a x<,m, m a xam -

.h c}[* gip f a 2 s, lE0

(- A '. S-Y

,c.&i..di jdaun, h% n'sul'f' !4a.

'"?y Ts,dd /.!Icl-3/ t:-l/%,.l

~./Y. ? e,'.~ 8L.w;idh f%J si..%. A se b,$,cDl$,o eau,o...<}

N M W "dE NE% &shi-niit k AL'at' cL". ),%

ich g g' % 4 la n.a m&t.sy A n n' s.A dl q

b n - 3 8 C 4 /.

//

]

ENG. REVIEW /APPRCVAL CATE-A 1. - f

~/l 4 l /'/p(f, CE REVIEW APP 90 VAL:

DATE:

WA % =

Y //9/ SY

- DISPOSITICN VERIFICATICN & C.CSURE:

CATE:

I l

c:MMeats; fw,.. i w e.( h p w.

l

COMANCHE PEAK STEAM ELECTRIC STATION

.TE$A UT:t.lTIE5 "C" "

  • NONCONFORMANCE REPORT (NCR)

CENERATING CO.

E-84-01081 R.2 Page 1 of k

UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RI A NO.

l Cubicle #17 1

S.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A

~ NONCONFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted.

Tcrminal block Terminal points aw A.K.

all 5

P.A.

3, 4 c o l

l:E

M En ggi y cogE' uON c.

P.D.

3, 4 Hold tags applied, all unrelatet wa i n o

P.E.

3, 4 '

t e

i P.G.

LB 4 conductors <_ b -

J A

c P.L.

all 2

P.K.

all

(([

j P.M.

all P.W.

all l

i P.U.

all AEFERENCE CCCUYENT:

REV PARA DATE:

REPORTED GY:

Steve Bufkin 4 /9 S4 l

DATE:

I OE REVIEW / APPAOVAL:

e W rn.t ** *

.6

/// / W w

O ACTICN ACORESSEE

!CEPARTMENT I

I. Vogelsana Eng.

AEWCRK AEPAIR USE AS IS SCRAP See attached disposition.

wl i

g '.

PERM. PLT.RFCnRD d ',

n;.

5' L

,q,j l

ll; O

suertog tee, M l' C 4 l

oi l C l k DATE:

ENG REVIEW / APPROVAL hj q J

(A/

Vf/11 ill & g

~OE REVIEW APPROVAL:

DATE:

Y %m 0 f 117 i Ts'

.n O

CISPOSITICN VERIFICATION & CLOSURE DATE:

h 8$

VM " -

A

/E9/ W COWENTS: Rev. 1: Reopened to Clarify disposition.

Rev. 2: Reopened to attach AMP Engineering evaluation report & to address

twisting, i

ypww -

3,/G*

DISPOSITION: NCR # E-84-01081 RI 1 1.

The following terminal points and associated terminals have been inspected by Electrical Engineering.The inspection indicated that these terminals were bent less than 90* and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidenced by satisfactory

  • completion of system testing.

TERMINAL BLOCK TERMINAL POINT WOgg0ft j AK ALL PA 3&4 PB 3&4 4g y

$$ s[tSgW' 3&4 PC

\\

A PK ALL T..

PM ALL PW ALL PU ALL Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem,

]n Pll5l9f W

gy th<

2.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

a rbr/nkt M

f*//7/rf l

1 I

l

h.JL a=3)

C ENGINEERING EVALUATION REPORT 4/01/85

  • ^

6...... D "E KEPEDO E S r

IQ isu ".iB Gilidui WRiil[X PIM OF AMP IEGUDRAIEL EER - 136 3029-50013 AMP

  • PIDG* PVF2 Turminals

~ ORMA ]i h1

-,l Tested to MIL-T-7928G Vibration Sequence 4D i.

y, e

s w(

\\n O

Table of Contents Introduction,.

.... Page 1 Test Specimen Description.

..... Page 1 Test Schedule.

Page 1 Test. Methods Page 1 Test Data Summary.

Page 2 l

I Appendix A (Engineering Conclusions)

Page 2 Prepared by h

Approved b

_p 42 7 David Fleming Q

Floyd Rephaw Test Engineering Product Engineering Supv.

j General Products Group General Products Division

  • Trademark of AMP Incorporated l

l a== mas encoucTsenoue anse secompomTuo. Manneouns. PA., met u.S.A.

INTRODUCTION This report cbntains,results of tests conducted on PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products perfornance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 Tl.IOWlA..,0ya TEST SPECIMEN DESCRIPTION t

DTIb P;gs 7

The following Terminals and quantitie. were tested.

i.

9 Q

k Quantities ner Te st Grounes1%rMi Terminal Part No.

Wire Size Groun 1 Groun{2 fridh h 3

53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Groue and Secuence Test Groun 1 Groun 2 Croun 1 Voltage Dron 1-1 1-3 1-3 Vibration 2

2 2

TEST METHODS Voltare Dron.

Each *,erminal was measured for voltage drop by energizing with 95 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

Vibratien.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was l

secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes l

mutually perpendicular to each other and to the axis of the wire.

i

\\

TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2

3 4

1 2

1 h

1 2

1 4,

Initial 15.1 14.8 15.4 15,1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib.

16.4 16.1 15.9' 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broNe off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other tuc groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 45 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

e 5 _

'.TE)AS UTILITIES A

A A

C STAN

'CENEr$ TING CO.

NONCONFORMANCE REPORT (NCR)

E-84-01081 R.1 Page 1 of A-UNIT STRUCTURES SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

Cubicle #17 1

S.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A i

NONCONFORMING CONDITION 0

Lugs listed below are bent in excess of 60 or twisted.

PyRM. PLT. RECORD h

Terminal block Terminal points

"* f "tzg' j g

A.K.

All suo mei.oe, s

"i i:

su

  • 4 o-P.C.

3, 4 y

P.D.

3, 4 Hold tags applied, all unrelated work may h

Continue.

q B

Conductors a.

P.L.

All m

5 P.K.

All INDEXED P.M.

All P.W.

All OATEs AEFERENCE CCCUVENT:

REV PARA REPORTED GY:

CATE:

i Steve Bufkin _

4 / 9 / 84 I CE REVIEW / APPROVAL:

G CATE:

J u

Al W /8 I

J ACTION ACCRESSEE

' DEPARTMENT I

i I. Vogelsang Eng.

DISPOSITICN:

REWCAK REPAIR USE AS IS XX SCRAP See attached disposition.

9sp1o@S]h 4 I

e i

.,n..,

8

(

a e

A fG ENG REVIEW / APPROVAL DATE:

llE VOl)

) / T/ $

A.

1' 4"

/N

'y

/

O OlSPOSIT(ON VERidiCATION & CLOSURE:

/ //

DATE-

.A

//

COYMENTS: Rev. 1:

Reopened to Clarify dispos on.

o fy.80[k.

DISPOSITION: NCR # E-84-01081 R1 1.

The following tenninal points and associated terminals have been inspected by Electrical Engineering.The inspection indicated that these terminals were bent less than 90* and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidenced by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT AK ALL PA 3&4 PB 3&4 PC 3&4 PD 3&4 PE 3&4 PG LB4 Conductors PL ALL PK ALL PM ALL PW ALL PU ALL Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

M41[

h I

,g wh<

l

' COMANCHE PEAK STEAM ELECTRIC STATION 7txAS UTILiTIF.S NCA N3.

GENERATING Co.

NONCOWFORMANCE REPORT (NCR)

E'VV nl09I mu e i n.

UNIT STR CTUREi SYSTEM ITEM /COMPCNENT TAGilD NUMBER LOCATION OR ELEVAT:CN AIR NO.

Mc3/fmA 6 17 i

&nhoe l0PL f 9f W t t't_> D ~ (11 RW)Oh 0.Yb Mllb i

N'ONCONFOPMiNG CONOtTION s

M M

d 6 0

  • d 3 :_-_ &,

T* w sc 4 I oloc k.

'7se m. po,eT.

i e dQ %Q;ngd

[j-Et

'[5 f\\j h

b M

M e

N* D '

) Lf g g'-

9 st e

.n wg 8

3; u

~, J o-y p

p.,_

u<sa cv.va s.-s

~ny a

P.i A A o.

I P. <. '

m-O Ji 13 w-AEFEAENCE COCUMENT-AEV PARA F.EPORTED BY:

OATE:

I

%b

<M-N /N /

Y CE AEVIEW/ APPROVAL:

DATE:

. /h '

4._

U / '/ / ff' w

O ACTION A00AESSEy 1CEPAATMENT4

[

sbums /doA/.2m/

i T F e.,

'L e I t

OISPOSITICN:

i AEWCAK AEPAIR USE AS IS IN SCAAP

. IME cuntsWF. MhuuPACTVnst's PostnoA/ // TAWT'K5EnWWL1 AAAv 13613sMT ONs7/md. TP 30.12.O..wtTW 4W KNGIN&tt/An' JVALMTfDAf. EMWWaERAy6. NM ANY/KWED Th4'.couewty&-

_TRAnduN ALC gy gogyrloff.'

E IssumuAlgiacc inesem sinwr,TsanstwALSura TsamumLlmwr,, reanumat.cux# fzamWI. Awet-OO 4.K.

ALL.

P.0.

$, */

"l% K.

4 04.

f P. A.

R4 P. L.. _.

3s Y 9.M.

ALL.

9.S.

J./

P.G.

L$9/AI4MrlW5 R W.

ALL.

O= C hY "P. L.

hLL

i. U.

8 L t,*

_ 8 8 C E Riaffr&l!E lffY M (18 5 ' - L IT II est ---

t"1MATTW6tf ra4MINM t bo NWr" his AW W:_^

ENG. AEVIEW/ APPROVAL DATE:

W l.A.5/W

~f.

I m,

,s m

w

/?

845 n

O OtSPOSITICN VERtFvl.T1CN & CLCSUAE:

M O

CCMMENTS: NOTE.' AAAP "ft.EmpAW HAadd~ 888N /Nfr$ De r 7As v6Aeco/Z.

l Sers MTacwso e P. P. A,'3P,2.'//. L/

l Ad/b '72,<rb&owA Y,?

'V/.7//h4'

ETTAC W Maut * *TO MLl2 E-844-OID81 he,E af opt nim n iow : coh.

may w uirn u is.

sam commeur-escwtou woe mars.

d ennN \\

\\ \\punen,i~; g

\\ m r%TC3 %i \\

  • \\.

\\?L,A D S

\\

\\

-mu

\\

WM l

l l

l_

1

Oct e-4-17-84

'7dEPHONE CONVERSAilCN RECORD Tima 3:30 P.M.

Call by:

W. 1. Vogelsang of TUGC0'- Enoineerino Div.

W)

(Name!

An$wer by:

Floyd Renshaw of AMP Producte Corocration. Product Engineer

%M gem.

Contract No:

Subject discussed: Bending of PIDG*, Nuclear PIDG PLASTI-GRIP

  • or SOLISTPAtJD*

- LN70?NATLOK

' terminals 0;

A d

1 PPRV l

  • Tradema rk nf AfiP inenennrated

SUMMARY

CF OlSCUSSION, DECISIONS AND CCMMIT9Sts.

I. Vogelsang discussed the AMP memo dated September 2,1981 in which Mr.

W.B. Eister.had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was p(ointed out that for these cases, the application was for short jumper the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90 bend or two times to a 45 bend.

However, this does not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'd be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these terminals, they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to would not retain its full mechanical strength it would mainatin its 120 electrical characteristics.

~

V[dw -

cc: ARMS

-M L.M. Popplewell F. Harned/D. A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

COMANCHE PEAK STEAM ELECTRIC STATION TEAAS UTILITIES CENERATING CO.

NONCONFORMANCE REPORT (NCR)

E'VV nl 0 9 I s

UNIT ST AUCTUR E,5Y STEM ITEM /CCMFCNENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

nc3/l W% ri C.G.fua l

a,k,. L ees' (R EW er> n m RM 0%

CL ?S1 n_I M tIONCONFOAMING CCNCITION d 6o* d Q,

% *'"I'un I olce t.

~~Grm.po,,oT.

~

y Mb& af{hd OK pu.

E' d2 % ua

$i' 5n -

T i' ?

M0 n/E. 0h, m

i 7 C.

9. c.

t s!

[i.'

8J b ifhp%

$3, L. Q Q C* O U1)b VC.5c f 0

=

A P. l<.

na s

DDQ\\l

\\

Pim-i' T3 e c* 8 -

nt l(

'u'

b. /b0 '

[.

AEFERENCE COCUMENT-REV FAAA REPORTED SY:

OATE:

mNo J-N /9 /

Y

,s JE REVIEW / APPROVAL:

CATE:

f*#

r

+. m A-- -

V / 9 / Sf C

ACTICN ACC AE!SEc.

CEPARTMENT j

4

  • r P f-r-S Cs. I
  • 1bMG% / dDAl.3 417) s DISPOSITICN:

S REWORK REPAIR USE AS IS SCRAP T56 cuC2Gdr-MAAJLifACTV2GE'S (bbt TrCU tb TRAr TG2MIMALS MAY 66 6 GUT CMG YtMG TO 90' AUT) 09 Tb Izo AiTA Au G-M4 80ECC *D4 CVAuG47*0M. EUGoDCCBIA%g NAS ENGulGQ 77/E Fot Godsac, TGoCMrMAcS sd 4'd&S nCA).'

TE~ ens odAu PctMT* \\*iGCMtOku P)tcCK TER.tAldau Posd7 TE2mo uAu A. R. 6eccK Act P. G.

c.64 <oupotrocs m'y F' A.

3,4 P. L.

Acu c-P. 6.

3,4 P. K.

Auv

'O P. G.

3,4 P. M s Acc j

P. D.

34 P. W,

Au P. G.

3;#4-P. tJ.,

A cc, z

p TT 15 ovat IX-1ERMIM PatcA T' RAT TuGSC. TERM 10ALS D3 Oc i-Pose Ad EcetPMGHT-

~

o SEEviccA6 utTr FCo0LfcM Ad9 MAY C)E 05E9 /26 is.

00TE: AMP T6R.m\\ pass PrAVG 6GGd #0STALLEp P;Y TMC VEMDOR.

SEE. efY-ATTAc. hep CFPA 38;241.

s -ne,-e4 _

ENG. REVIEW /APPR VAL,

f.

g j/

gp.

OE REVIEW APPROVAL:

DATE:

us M

/$ / D OtSPOSITION VERIFICATION & CLOSURE:

DATE:

COMMENTS:

I

COMANCHE PEAK STEAM ELECTRIC STATION td4 'JTILITIEs NCR No.

NONCONFORMANCE REPORT (NCR)

CENENATING CO.

E-84-01074 R.2

)

Page 1 of 2.

IJNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

I Cubicle #10 1

iS.G. #1 Vendor Lugs CPI-EPSWEA-02 Rm. 103 El. 852' N/A

~ NONCONFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted.

Gj Terminal block Tenninal points h

E P.D.

G t:o P.B.

3, 4 i[,i....\\

'I(lgipM,.1 p, o l

lU 1 c

P.C.

3, 4 E

P.F.

G

,q

?

D J D11 i'

g Hold tag applied, all unrelated work may Continue.

1 i ay i

i e

ES-100 2

2.7.1 AE:EAENCE CT,CUVENT:

, gy p,,,

DAid!:

l REPCRTED GY:

Steve Bufkin 4 /9 i 84 l DATE:

i l OE REVIEW / APPAOVAL:

b //I / 8Y u.! I

  1. 4'M DEPARTMENT C j ACTICN ACCRESSEE I

I. Vogelsang Eng.

USE AS IS(1&OXX SCRAP AEWORKI2_bbXX AEPAIR See attached disposition.

I hf PERM. PLT. RECORD i

"*g}

c.

SUSFILE LOC.

(

Cq A/ c f a J@ D u sB5 yi 5'

l DATE:

ENG REVIEW / APPROVAL j,

[

V

//7/ t" r

iT I CE REVIEW APPROVAL:

U OATE:

{/

/Y{

bb?'N ?

t LLIC CISPOSITICN VERIFICATION & CLOSURE:

DATE:

W$ftsfh(

?^

fenss:;=

$ /}? /W COMMENTS: Rev. 1-Reopened to Clarify disposition.

Rev. 2:

Reopened to attach AMP Engineering evaluation report & to address twisting.

q$

.J.S W p.IV E

DISPOSITION:

NCR #E-84-01074 R.f -

1.

The following terminal points and associated terminals have been in" spected by Electrical Engineering.

The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PD G

~

PC 3&4 PF G

PS 1

AA 1&2 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal points and associated terminals have been in-spgeted by Electrical Engineering and were found to be bent less than 90 but they do show signs of fatigue.

TW s terminalj Q to be re-gv placed - Rework.

TidA.t g

I X TERMINAL BLOCK TERMINAL POIfiT PB 3&4 3.

The following terminal point and associated terminal was inspected by Electrical Engineering and was found to be bent more than 90 the vendor maximum allowed without an engineering evaluation. This terminal is to be replaced - Rework.

TERMINAL g orv TERMINAL POINT F (K70S!AT'0K COPY g M

P?RV yt)

!l$W 4.

The twisted terminals are to be used as is.

See attached AMP Engineering evaluation report.

E s/n/r d.A rA r//Wn-

C"3 ENGINEERING EVALUATION REPORT 4/01/85 g

....... i,....... -] OE KEPE00EG C iR.=.iG GiLi,I MiTEX PGiuSIE OF AMP IEMPORATEL EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-792SG Vibration Sequence

\\

i I {<

i.

~

\\

Table of Contents C...O...PY. ge Introduction.

1

)') )

Test Specimen Description.

.\\

. Page 1

Test Schedule.

.... Page 1 Test Methods Page 1 Test Data Summary.

Page 2 Appendix A (Engineering Conclusions)

Page 2 Prepared by w

Approved b x

v David Fleming Q

.FloydRephaw Test Engineering Product Engineering Supv.

General Products Group General Products Division

  • Trademark of AMP Incorporated amassaa' P9000CT5 0ROUp assp os00npOnatus. naa--- pa..triesu.s.A.

\\

INTRODUCTION This report c6ntains results of tests conducted on PIDG PVF2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286. Testing was conducted in AMP Laboratories during the month of March, 1985 TEST SPECIMEN DESCRIPTION l

The following Terminals and quantities were tested.

Quantities ne - Test G raue ns.

Terminal Part No.

Wire Si e Group 1 Group 2 F f d-9ue 1 53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands.

t TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Group and Sequence Test Groun 1 Groun 2 Groun 1 Voltage Dron 1-3 1-9 l-:

Vibration 2

2 2

TEST METHODS Voltage Droo.

Each terminal was measured for voltage drop by energizing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

l Vibration.

Terminals were rigidly mounted to and not more than 1 inch above l

the vibrating platform by their normal mounting means.

The test terminals were so mounted that the Junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

1-

TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2

1 4

1 2

1 4

1 2

1 4,

Initial 15.1 14.8 15.4 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib.

16.4 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 14.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 nours of both planes without' displaying any signs of physical damage.

Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminstions will withstand such a condition without any detrimental affects.

1 3170RMAT0N COPY PP1RS' -

-.-...c

COMANCH3 {;UQK btu 1EL1 L:LL:KcM;JOLci b$vnW9R)

I Texas' UTILITIES NONCONFORMANCE REPORT (NCR)

CENER,ATING CO.

E-84-01074 R.1 Page 1 of c2 UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

l Cubicle #10 1

S.G. #1 Vendor Luas CP1-EPSWEA-02 Rm. 201_El. 852' N/A

'~

7 NONCONFORMING CONDITION

.~.,

lND{g{g 0 or twisted.

Lugs listed below are bent in excess of 60 h

Terminal block Terminal points z

P.D.

G 8

P.B.

  • 3, 4 P)ERM. PLT. RECORD "u

P.C.

3, 4

' am P.F.

G I

, n:.c toc /, 8, /

l e

k PRl

""" ' c Md. [ M l

1 i

P.S 1

A.A.

1, 2 g

i c

Hold tag applied, all unrelated work may continue.

AEFERENCE CCCUMENT-REV PARA AEPORTED GY:

DATE:

Steve Bufkin 4

,9,84 CE REVIEW /APPACVAL:

DATE:

u Ol 10$1 J

ACTION ACORESSEE

' OEPARTMENT I. Vogelsang

!Eng.

CISPOSITICN:

(2.3)XX REPAIR USE AS IS fl)XX SCRAA REWORK See attached disposition.

diw s

FOM AT 0h C

i COPY

')"

PPN ENG REVIEW / APPROVAL DA

FNWHM O

i,Ehr!

^

n O

DISPC[SI'ffCN 'VERIFICATlON & CLOSURE:

N DATE-I COMMENTS: Rev. 1:

Reopened to clarify dis ition.

i t

-u.._

-m ~.

w ~ w--,

wm e

Q. cf en~

DISPOSITION: NCR #E-84-01074 R.1 1.

The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characteristics are maintained as evidence by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PD G

PC 3&4 PF G

PS 1

AA 1&2 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal points and associated terminals have been in-spected by Electrical Engineering and were found to be _ bent less than

@isterminal;Qtobere-gv 90 but they do show signs of fatigue.

Th g

(

placed - Rework.

TERMINAL BLOCK TERMINAL POINT PB 3&4 3.

The following terminal point and associated terminal was inspec}ed by Electrical Engineering and was found to be bent more than 90 the vendor maximum allowed without an engineering evaluation.

ThD terminal is to be replaced - Rework.

TERMINAL BLOCK TERMINAL POINT PR 1

\\%f08%00 plMk C O P Y p)[l

</dr s

PPRV y

~. -

_ %-v.. r

_e,=*evee-- w-+-~~=*-w M ~ v o yew *F:T*-

MAS UT1uTiES COMANCHE PEAK STEAM ELECTRIC STATION 1

, "C# "

  • CENERATING CO.

NONCONFORMANCE REPORT (NCR) lE-74-ol el d UNIT STAUCTU AE. SYSTEM t ITEu/CCMFONENT TAG /Q NU EA LOCATION C A ELEVAFCN '

AI A NO.

1 i

$703/GGpsA I

d49 ec)e."(0 l

f 5,N ou% 1.uth 'C91-Eps txA - c 3 R mlo3 ELS$aL k)lA NONCONFQAMING CCNDITION Y

h AM bO l

e n M.

i i

%. = siocx.

%,;t p;,s.

. b.

g o

  • b.

14 I

i}h yld]

0f R

i g

9. c..

r4 9:"C

?

' 't h

ab.

)

tj, j

S AA.

34

.)

sh c_-

J de).[

AEFEAENCE CCCUMENT-AEV PAAA REPCATED BY:

7 CATE.

i M

W k/h/

' CE REVIEW / APPACVAL:

CATE:

I

/ ' ' hk__

/ ? /,$

l w

C ACTICN ACCRESSyE lCEPARTMENT #

l rnwasI#mMAATTI

'TFar-K e, I l

CISPOSITICN:

AEWCAK AEPAIA USE AS IS YXY SCAAP

_TWE 1stMsNM3 LAMoab *N rassr/MW. StoCJC 'P.D.hnst5 Si L4, AMD eN TasmanAL tout T.R_PtsNr i

_a m m m.wEo....woa.

J mw I

y._*tVG cm21.Wr AAAWoppc vesas ?esmoM 15 t%AT TERM 1MM.S MAY OF1sNT rxt TIMET0 90*<*/vo r#ro

,I 7

=

i g _120' W/rF <W AN61#5641NW #6HuAsT1oW. K#6f#CEI2 intr HA% Asyssvw0TvE Sct.a.owsik raHMt/NW.,r j O _tN.quE3110NtTEtmlwhL Sodt TEGMidALPOIA/C raAsr/trA1 tout issuisAL ltzier Zo P. D.

dr P.F.

r,

_Tanamun thout A.A..

E M

3,$4

'F. 5 I

vna m mu. N wr 1,1._.

.TT._%.Oset DCTEMA7Mf TNAT' ThEN' T tANAsks OO %dV M M GQushnetMr SGlhetE@W _WOPLth Aun MAT S#hsh M ti" fan Note m (caumsurt ENG. AEVIEW/APPACVAL QA Nt:.UUKU cATE:

i mw aA stEVIEW M /M/84 Mo b/M' ri'c,"a "FY 4 4QA,84 CE F.EVIEW APPACVAL:

l-MJ S-9 m

.C CISPOSITICN VERIFICATICN &'CL A E':

/V/

OATE:

T-t dThM 7//

/7 /FP cou.ENrS m,. m asa.uu,A-~ a.v,,,- =

==,.

Anm o em wcw ARMS I

n,, / rr E-/-oo wo n.

INDEYED

~-

DATE:

W __=;,

~~

r - ::

~~ ~~ -

_n - - --

- m-m---n

' fELET'.'ON CO tRSA110N RECORD Dde 4-l7-'84 d

Tim:,

3:30 P.M. _

Call by: W. I. Vooelsang of TUGC0'- Enoineerina Div.

3Co,:p:my)

(Namel Answer by:

Floyd Renshaw of AMP Producte Corocration. Product Engineer s:= = =,r1 (Nom.:

Contract No:

PIDG. PLASTI-GRIP *. or SOLISTRAND*

Sub[ect discussed: Bending of PIDG*, Nuclear

. terminals N 0RN AT OK r's%DT7 wv1 1

  • Tradema rk nf AMP inenrnnrated DDD1!

SUfA1AARY CF DISCUSSION, DEclSICNS AND COMMITM A

A W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr.

B. Eister had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90 bend or two times to a 45 bend.

However, this does not pr.eclude bending the terminals up to 120. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows:

a) length of wire t'd be supported by the terminal the susceptibility to vibrations b)c) once installed if it is contemplated rebending these terminals, they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90 to would not retain its full mechanical strength it would mainatin its 120 electrical characteristics....

~

~

~

Ny;s,.

. ~

cc: ARMS

-Af L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

COMANCHE PEAK STEAM ELECTRIC STATION TEYAS UTILITIES NCa no.

GENERATING CO.

NONCONFORMANCE REPORT (NCR)

E-74-Dl el d C :.1 UNIT STAUCTUAEf SYSTEM ITEM /CCMFCNENT TIG/lQ NUMBER LOCATION CR ELEVA T:CN AIR NO.

27A5/66ps#

tuosole */0 i

SG."I n w1.w 'em-muca.a omios n.?u vu E

i NCNCCNFCPMING CCNCITION

$9 Db (LAAM A -CMEG k 6 0

N TrEW4 Gloc/(.

%,dt p' g7,

9. O.

g

9. b.

1 4{

P. c..

59-F

_s n

P.

l

!O AEFE:ENCE CCCUMENT-AEV P4AA REPCRTEC aY:

a i

CATE:

W N/9/Y[

OE AEvirn/APPACVAL:

CATE:

- > > WL

/ f I,W lCEPAATMENT j ACTION ACCAESS E

'XbMGL PDM?-AYT1 i T FCs-t (, l CISPOSITICN:

XbX AEPAIR USE AS IS NO SCAAP AEWCRK g

h && & / en~.1s&&.bbtabo PO, fo'8 5 ' As "*A #

t g

. PR, & / m fo-

f. AduN.

W

.q??do Nh M

h /25

~0W A f

- ms.up:

ugas 7--gaid P. C,

3, G-4

=

P F.

R S.

I 5*

YA h&fMA r/

?"!d

U WOg%s %)uarthly.& a4 Ja.atah6 m as.w.

ENG. REVIEW /APPACVAL CATE CI f.EVIEW APPROVAL:'.

CATE:

Y llS/ Py CISPOSITICN VERIFICATICN & CLCSURE:

CATE:

( - COMMENTS:

_ _ _. _. _ m _ __

..e

..m-m._

".HAN CME PEAX STEAad Ei ZO~RIC

$7aTICN n ew- /

w /

8903/6625'A PE-/-fbc//B G,5.I a*'Ds 4&3C3#P.CM GC8 M G=A M %

c! LASS A F Eft 4NA$

b*cpt-EMuffkdg,M/g g&T3 N /3TMuCTwAE ;E.3.G#ea7;Ce e

cz

~C2 A8 952' SEI 91-/03 J

pd iscs..as.

gnu.

gaur car. scc. e uv. a shamsa m gasMunt a ar-ass.

.u.

E" ~/W tt 2-- et Md262/4.I--5$ SS 6

m AfD i

mia mens C Par'as-ig m en C terca CW Cparw l

"* AsPU"*.CM vN CA..CM

mSPC""CM

.sesptC="cM hapc= cM asp.

rs C mePe-:ee==mm.czn. au. meanu irons sar:sneten aM, f f _pg.

O inspe am c:w r: n, wisemme ce ims uran ast:w "7"

e INSPECTICN ATTRIBUTE 3 ga;g

n. -

en

/

I rAe m1~4o nmkehhe mw treen IA l l

1 r w <- M des rA ads /cn. aweis-Asr I ii i

i av cz-6Av.,.r-ze x-zo ili i

I i

rii I

i 2

I n w e az i w eA pts

-ew;xa n-7xb 3se

! --+ l l

\\

3 l

n s,

p8 n

/

I. -I I I

I I

I II I

I I

I II I

i i

l l I I

i i

l i i i

i l

l i I I

i 1

I ll l

l I

I i i i

l I

i i i i l

l I

I I

l!'Ji-lllt'lul4iH11 11 I

i l

.. J.J. L I

i 1

/

SY 4 91 J % #

I l

i

%.2 % 21 l LL) l l

I i i Il l

l 1

M if \\1 I i i l

i I

i ii i

l I

i l l l

l l

l i l l

l m t-msne:x, c:.s t.o9s aw mr~.o's Aw New c-e4 - cic 7+

W/449 /9M9 KV- /- 003f 9/9 8cf.3 92f

/sVW W 7Wf S M k

-77)& 4 che enwe.ne, ar a c sca sc.

f*84ll = 8/C74 gL*

uit lA

. #A A

g g;

A/$m cc nspe. -~ n g,

k IM '1-uv,,.s F t :.c dr/rv 4.V I 4.se e /. b E

3 l

i

~.

^

TEAAS itLitlES NCR No' NONCONFORMANCE REPORT (NCR)

C*INEIATING CO.

E-84-01071 R 2 Page 1 of D

,g, tjNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /tD NUMBER LOCATION OR ELEVATION AIR NO.

I Cubicle #7 1 l S. G. #1 Vendor Lugs

.CP1-EPSWEA-02 Rm. 103 El. 852' N/A l

NONCONFORMING CONDITION 0 or twisted.

Lugs listed below are bent in excess of 60 d

Terminal block No.

Terminal points 5

P.A.

73, 4 Edw..0 P.C.

3, 4

[,J;., 1 l y Q'.jyj' {]

cc P.D.

3, 4 ph s

!E P.E.

3, 4

,. J ;

s' 7

, $e kJ e

P.F.

3, 4 E

P.G.

4,3 C =.1..1 J'

E P.W.

1, 4

{,.!'

2 P.X.

1, 3',

2

.,t 3)gjf

?-

y P.Y.

1 Hold tags applied, all un' el afdff work ma >

L.B.

1, 3 continue.

l t

i' ES-100 nEv 2

pAnA 2.7.1 AEFEAENCE CCCUMENT.

CATE:

I REPORTED GY Steve Bufkin 4 / 9 / 84 !

OE REVIEW /APPACVAL:

DATE:

$ k r>s4A

$ ll$ /

w O

ACTION ACCAESSEE l DEPARTMENT i

i Eng.

I I. Vogelsang CISPOSITION:

(1&3)XX (2)XX SCAAP AEPAIR USE AS IS AEWCAK See attached disposition.

PERM. PLT. RECORD Sh 1

Mf ARMS L

I re te:.N '

m i

I ll WDEXED

"""" p c g

,3' ym 0 41985 8

Gy

))fff &.

S jy W:

DATE l,

ENG P EVIEW/ APPROVAL i

CE REVIEW APPROVAL:

V DATE:

f49%!A': w lll / Wb

/

^

,w O

CISPOSITION VERIFICATION & CLOSURE:

DATE:

Lkm 5 &_=-_m 0 f i)7iff 0

fSfwl2S~

l OOMMENTS: Rev. 1: Reopened to clarify disposition.

Rev. 2: Reopened to attach AftP Engineering evaluation report & to address twisting.

4 f9.b u (p y/V,

' DISPOSITION:

NCR#E-84-01071R.77-1.

The following teminal points and associated terminals have been inspected by Electrical Engineering.

The inspection indicated that these teminals were bent less than 90* and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characterisitics are maintained as evidenced by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PA 384 PF 3&4 PG 4

PX 182 PY 1

LB 1

Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following teminal points and associated teminals have been inspected by Electrical Engineering and were found to be bent less than 90 but they do show signs of fatigue.

These terminals are to replaced - Rework.

TERMINAL BLOCK TERMINAL POINT PC 3&4 PD 3&4 PE 3&4 E

iMFORMATi0h 1&4 LB 3

gg"g j

l#P ppay i

1 llCkT g

3.

The twisted terminals are to be used as is.

See attached AfP Engineering evaluation report.

l eLs em l

SY/7/rs' l

C3 ENGINEERING EVALUATION REPORT 4/01/85

.. L...... 3 CE KEPEODUCED C 7h:.10 Giii.di hKiiTUI PIERSIR Of AMP IEDU0ilATED.

EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence It NFORNA 0N ens x ;;yr.7 Table of Contents 2000 l\\ 7 Introduction.

..... Page 1 Test Specimen Description.

...... Page 1 Test Schedule.

. Page 1 Test Methods

.. Page 1 Test Data Summary.

. Page 2 Appendix A (Engineering Conclusions)

. Page 2 l

I i

/

Prepared by h

Approved b ]

p 4'

David Fleming Q

?loydRephaw Test Engineering Product Engineering Supv.

General Products Group General Products Division

  • Tre.demark of AMP Incorporated a=====as pacouemenour anse seconronatus, namnesune, pa.. trtes u.s.A.

i

INTRODUCTION This report c6ntains results of tests conducted on PIDG PVT 2 radiation resistant terminals.

Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to i

Millivolt drop followed by vibration and a final millivolt drop measurement I

per MIL-T-79286.

Testing was conducted in AMP Laboratories during the month of March, 1985 INFORMA" ION TEST SPECIMEN DESCRIPTION f

u,

, f *f k

n 4

I iJ The following Terminals and quantities were tested.

.2 Quantities ner Test Grc253QhI Terminal Part No.

Wire Size Group 1 Gro2r 2

'C9:E:

53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands.

TEST SCHEDULE Terminals were subjected to the following test in the sequence specified.

Test Group and Sequence Test Groun 1 Groun 2 Groun 1 Voltare Droo 1-1 1-4 1-3 Vibration 2

2 2

TEST METHODS Voltare Dron.

Each terminal was measured for voltage drop by energizing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point.

Vibration.

Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means.

The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire.

The specimens were vibrated in j

I accordance with method 201 of MIL-STD-202 for 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on each of two axes mutually perpendicular to each other and to the axis of the wire.

l l

1-

- --=

m

.,-- -,~z zc, -

y,

__y___

TEST DATA SUISIARY

?

Voltage Drop in Millivolts at 55 Amperes oc Groun 1 Groun 2 Groun 1 Snecimen # 1 2

1 4

1 2

1 4

1 2

1 h,

Initial 15.1 14.8 15.4 19.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8~15.1 After Vib.

16.k 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel.

All other samples displayed no signs of physical damage.

APPENDIX A j

The sample which broke off after 9 0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> of both planes without displaying any signs of physical damage.

Based on the information acquired frem this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

e

i. - mom m 0K

\\ COPY

?PRV a

L 2-

~

.J..n,,..

_ m _, w

COMANCHE PEAK STEAM ELECTRIC STATION ten 3 UTruTiES NCR Na

, GENE ATING CO.

NONCONFORMANCE REPORT (NCR)

E-84-01071 R.1 Page 1 of 4

UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO.

Cubicle #7 1

S.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A i

NONCONFORMING CONDITION r,w Lugs listed below are bent in excess of 600 or twisted'

'kkMS 3

INDEXED ~

a us Terminal block No.

~Tenninal points P.A.

3, 4 PKRM. P 3, 4 P.C.

w 5

P.D.

3, 4

[

/

a o.

P.E.

3, 4 g

P.F.

3, 4

"'"' hgg g

P.G.

4 g

P.W.

1, 4 c.

P.X.

1,3,2 l

E P.Y.

1 Hold tags applied, all unrelated work may I

L.B.

1, 3 Continue.

ES-100 2

2.7.1 AEFE AENCE CCOU?>ENT:

agy p,n, EPORTED BY:

CATE:

Steve Bufkin 4

, 9 /84 OE AEVIEW/ ADP AOVAL:

//'

DATE:

JJ//

of i0 05,,,

u l OEPARTMENT J

ACTION ADDRESSEE I. Voaelsana Fng.

OtSPOSITICN:

(2)XX USE AS IS (1)XX SCAAP AEPAIR REWCAK See attached disposition.

l x

NFORMIGON l

q ey i

3__

.g A

ENG REVIEvv/ APPROVAL DA V

OATE:

CE AEVIEW A J Y }{,

O

/

/hJ l

.y n

n c

v5 POSITION VERiflCATION & CLOSURE:

D COMMENTS: Rev. 1:

Reopened to Clarify di ition.

jp.c) o o n o

DISPOSITION: NCR #E-84-01071 R.1 1.

The following tenninal points and associated tenninals have been inspected by Electrical Engineering.

The inspection indicated that these terminals were bent less than 90* and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength.

Electrical characterisitics are maintained as evidenced by satisfactory completion of system testing.

TERMINAL BLOCK TERMINAL POINT PA 3&4 PF 3&4 PG 4

PX 1&2 PY 1

LB 1

Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem.

2.

The following terminal points and associated tenninals have been inspected by Electrical Engineering and were found to be bent less than 90 but they do show signs of fatigue.

These terminals are to replaced - Rework.

TERMINAL BLOCK TERMINAL POINT PC 3&4 PD 3&4 PE 3&4 PW 1&4 PX 3

LB 3

l

)

]

9 jyl&

llY t

50gEON COPY av s

1

....... ~. - -,... - ~..,.. _,,

.-n

COMANCHE PEAq STEAM ELECTRIC STATION

~

TEXAS UTiuTIES NCR No.

CENERATING CO.

NONCONFORMANCE REPORT (NCR) j E1 u-oIo')1 l

unit STRuCruRE, SYSTEu

'iTev/CCMFCNENT TAGilD NU BEA LOCATiCN C A ELEVAT:CN' Rf A NO C. $.

  • q M 6pBEc)s S JVM/66 I

ik d or Luet'6PI-EPLuea~ot I? min A EL. ?L ]

ru)A i

NONCONFORMING CONDITION

% WW %AE - y W nM.

e NF0HATON j

a m,,

ao

[i

{'{y n'

cm

9. A,

h,(

QA RECORD i

y E

ceg

9. c.

T- 'a^ azview 4

A e

<z P F.

  • ' "'-'M 3,

i %

"2' o

FILE No, /

9 p, G, w

~

8

/5.

=

gr p

o$

p,, v.

v.

svar:LE No, I; 4 p, g.

E.-P4.-ol#7 /

b,4 ;'-

\\;

b !O b AAAA 2. ). /

l AEFERENCE CCCUMENT-AEV T.EPORTED BY:

DATE.

s

_T. J m

N / h / haf CE REVIEW /APPACVAL:

CATE:

/f/f w

.m e

C ACT CN AccRESSEE

~

! CEPARTMENT '

l Jbums bomammri r es e d I

CISPOSITICN:

AEWCAK IN REPAIR USE AS IS M SCRAP rum vntwniaants Launa eW isamanagStoct 'Rt. hiutt g,4 7.&%)otwrs gy.t.-P.&. Pousrj '.}4; f

LBe f.W. Nu13 t,*(3T.be PJf.TolurSJ %-T.15.-L.16. Tour.3;Aas vees it5AAc40, itswetX.

, y

, w l @ -_'TM cutRetrT~ A4MWp4cfv4A2190tmoW &TW4f Teammut MAY '44 neNr does FrAe( rd go },4As ego rW /go *_

' y m'seasewwe awneumone was m arm o raw me.w-tme==wc.r veeme O 788944LWecA afgewenL1tMNrs tenwegAguiut tsmaueAL'9e#f5 TEAmiaa%.tuRM,

'TatansAL lbtWT3.

8

?.A.

_. _.%'4

'>. 6.

64

'P. Y.

8 i

$._1 F.

4V R ar.

VA 1.'&.

I

_D OUA DEhEARINAITeOW 7%MT TM&lt 15alilowsLT op A4F" JWM AM AS48AISif' EdEMes.dd4/TV ACdilfddM A4dh Amat Ba an a n As lif Sam" M tal 8an=_^=aaff3.

/

QATE:

I ENG. REVitp'v/ APPROVAL b g ]d) _

'f I.2ll0f l Ls f.*s/JM e.

k hOAiff L'

I QE REVIEW APPROVAL:

C OISPOSITICN VERIFICATICN & CLCSURE "'

QATE:

d'

,_f 9

/M / k dro COMMENTS:AIOTE,i AMS TERMcMLT g SSE.TAf#Mf.4ED 57 TAE ME4@8Cd l

ase 4TTM. mad e.P.P.A.38,24I 18luu 2.T. 4.-I-o*840939

""~~uo v

TEiEPHONE CCNVERSATION RECORD oote.4-17-84 Tw 3:30 P.M.

Call by:

W. I. Vogelsang of TUGC0'- Enoineerino Div.

mi 1

Answer by:

Floyd Renshaw of AMP Prod'ucts tcrocration. Product Engineer ph.i e

Contract No:

Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOLISTRfg@*

' terminals

'N nn u A~'f%

l'i, Vi\\nVin M i' jams # % T % V 7

> %.,M.hj

\\

b b

h mi,

==

  • Trademark nf AMP inenennrated i

sUMMAltY OF Dl5CUS$10N, OK!$10NS AND CDMMITMEN15.

W. I. Vogelsang discussed the AMP memo dated September 2, 1981*in which Mr.

B. Eister had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120*. It was l

pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechani. cal strength of the connector was not required.

Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45* bend.

However, this does not pr.eclude bending the terminals up to 120*. In this case, an Engineering evaluation for the s)ecific type of application could be done by the product user. Items that s1ould be taken into account are as follows:

a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these tenninals,

~

they should be discarded and replaced by a new terminal.

Floyd Renshaw also advised that while a terminal bent more that 90* to 120* would not retain its full mechanical strength it would mainatin its electrical characteristics.

V:dw- ', [

,-k,

cc: ARMS

% r A;*

L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482 i

i COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UT1UTIES NCR No.

" F.N EN.T:NG CO.

NONCONFORMANCE REPORT (NCR)

Ed u,-oIo')1 1.4 UNIT ST AUCTU AEe SY3TEV ITEV/COMFCNENT TAG /lO NU SER LOCATION CR ELEVAT;CN AIR NO.

Jyu/scq::vo c.oe7cha-S

$,0, f

ik' r) dor ku e$ 'd PI-EPua.ra -o1 Rmin A EL. 9A )

ItA NCNCCNFCFMING CCNCITION 1 % UJC %AC m y y a nta. ezZ b Ock it)O. 90 d h.~0 Ul A 10K-g 9.n 2, y p. a f.t. 9 my >, 4 v s. g Y. 'J b b' b }. [ AEFEPENCE CCCUMENT: AEV PARA REPCRTED BY: DATE: w Ne.A _ AG Y / $ / hl/ ~ J .E L'EVIEW/ APPo.CVAL: CATE: / k/ _ _/ /'s 9-* _L__ ACTICN ACCAESSEE ~ lCEPARTMENT' 'JDMM i 8o M *ETT1 !"TE:6-yr OtSPCSITICN: M AEWCAK REPAIR USE AS IS SCAAP Se rceswm uww te ramm saa nc. or.arp s.4 re 8 0. e..ars s,4 rs es. Po,a s s 4, rs _ P. N. Pood75 I,4,18 R X,' feir7.6, 409 7E5 t,8, Peuot-b A C/5-Tb SG Ef fLEceQ. RGs acM. L -54 cvet4A.'r MAA,'Oracrdf64's fbs\\ Tic 4 LS Tuw TERMiOALS Mc Y 6C BGer cec Test it po* 4 amp OF rb itc' WeTu A4 cAhiA)(ECIM(i svAL.vATICM. EA',6tucCfid4 HAS REVIEW 6p Tuc fccccWerk, TCRmsdaes la GCEsto0M: k TERMIAlec 6ccxil TG2MIAJ4L. fttaJis J-F A. 3,4 P. F. 3,4 ~ ~ ~ P. G. 4 r P. x., 1, 2. N. T. \\ L.B. n TT* 45 occ 'CE4EM14ATICu "TilAT B4GSE T6CMIMALS CD Rc7 RSE W 600iFMEOT SEfNicS A64.lTY 'PkBt4M is49 M AY BE U52.'D A5 '5. UCTE: AMP TEEMiMA%r. AAV6 Bc6Ai it057Actcr) e1 Tuc. VsupoR. SEE MTAcMED <_ PPIk 38 E4l. E.NG. AEVIEW/ APPROVAL A/2* M 1,niu I QATE: I ~' \\ J CE AEVIEW APPROVAL: DATE: Mf " ^ Wi(fiTV 'SPCSiriCN vEmiriCAT:CN a CLCSuaE: oATE: i q CCMMENTS:

, _.j ^~ ^ '~ ~ ~ ~ ~ ~ ~ ~ ~

mancas acu erzau ruz: aic sva,cu n.e~

4 -s 1 g?03/6923A INSFECTicN REPCRT lne.p _,_ g 49,,, ,g . o cuc.m.c. i.u.,r.sc.cr.a w,., imm,.mc. me r.c. ev ass 1 r w /'a w y d ecp/.cpsaEA-o r- ~ O2-952'scrI Wm-/03 J pal scu.p ar.s.s i ;ss. gasr es ccs. a uv. a cnaset.E e. g w^s a .u. 55-/00 si 2-e DF-C/2 /AJ-J8 W-F. /0 m C'p wOF* Car. cme =s-i a rtan c p=ng7'.*5CM l Q i=.=MSPC CM C9=MsPt'"-*cM < in==ce m surca =. e n-

  • ASP'. 0CM ee

.35P. 73 C Jesut""tlM *: asp.C"z3, AL' Af'NCaat.E ITDas SA?llEPAC"OfM p gr g, g l CinsPc:on c=nssa.r tm, unsar:sme cm imss us to me :w i es INSPcC71cN AT7Ml8UTE3 8 carg / I 1%c.- RL&w/Eyc TermNdtnNc A44V6 BBN I'--f l l 1 izmwehad 4-Sp de -rzeAxile-44 swsumes<hl l l l ln.e c'?r-O-i% 3-2 9 l'T-20 I l i l l I riJ i 2. I Te>miest. Els-h-c pc-mentAwk3&Tl I l l l 1r 14 4 ld I I I n er xD ir I i, r, pr or s d-4 l. A ' i 1 l l ir so pw or tr 14 4 l.4 l 1 l I se et px or to G l& l 1 l l LS rr .s .o or 3 VI I 1 l 1 I I I I l 1 I Ii _I l l ..i3,i. 3 -ri n M i i r-l i

! i rU f\\lklh 4 P ' '

l l l , l..M PbM ? l 1 l u' ' M ! 14 t}=*f 'd i i ~' 1 4. plWA' A I ll I I I I imismi ll l 1 l li'i t\\ 3 "l "i ~ l l 1 l l l l Il l l l i i I l I l 1 l l l

    • % % E'*J MS m tRge4ce/gs Mn A/cn d~s?4.. opc 7/

rd'.sns'w,.r:sf, 47g :, ,' e63,89+y $E.( U!OW9 / 92+ 9 pC V-/~ M4 9) 9 / At%/ 7'#f AI&' not4V/ rds n,4,n h a r K. fg.hf7/ ., I I.M. C.;3C MA C A/4 i *' **'* ,l ae ,,,,2-a M i4.= s.). b3-L u g,\\ D- %e S-C -W / .. ~ _ _ _. I

V 7gy,'s uT UT$Ed. COMANCHE PEAK STEAM ELECTRIC STATION NCR No. GENER AT'ING CO. NONCONFORMANCE REPORT (NCR) E-84-01072 R.2 Page 1 of b IJNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lO NUMBER LOCATION ~ OR ELEVATION RIR NO. l Cubicle #8 1 i S.G. #1 Vendor Luas CP1-EPSWEA-02 Rm. 103 El. 852' N/A l -NONCCNFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted. l ay Terminal block No. Terminal points z P.A. 43, 4~i 8 P.J. 8 T' \\ ]'] Q ~ g8 5 P.T. 1, 2 c-P.S. 1,' 3, 2-g P.T. 3,' 4< gM g = l P.B. 41 ) te g L.A. 1,2,3 m', iQ '~ c. L.B. 2,3,4 P.G. Groundg )) { Hold tag applied, all unrelated work may continue. ~ AEFERENCE CCCUVENT-AEV PARA AEPORTED GY: DATE: i i Steve Bufkin 4/9 /84 l CE REVIEW / APPACVAL: DATE: i wl 0 Yn ?/ lS/ W C ACTION ACORESSEE IDEPARTMENT I Eng. i

1. Vooelsana CISPCSITICN:

AEWCAK AEPAIR USE AS IS SCRAP See attached disposition. u3 PERM. PLT. RECORD 05 l ARMS ~ gi INDEXED c l~ g / SU? FILE LOC. gj JUN 0 41985 u c c.g E ENG REVIEW / APPROVAL q t7 / CATE: I l /N/ CE AEVIEW APPROVAL; DATE: // 7 / 8jr-w

  • t

[d>fvW ^

  1. 1:

0 OISPOSITICN VERIFICATION & CLOSURE-DATE: a h$Ybf 8 YYTw!^= b / O / T.1~ COMMENTS: Rev. 1: Reopened to clarify disposition. Rev. 2: Reopened to attach AMP Engineering evaluation report & to address twisting.

fc$A# ~ i W yk,jG DISPOSITI0ft: fiCR #E-84-01072 R./ A 1. The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidance by satisfactory completion of system testing. TERMIl4AL BLOCK TERMINAL POINT PA 3&4 ~ PJ 8 PT 1,2,3,4 PS 1,3,2 PB 4 LA 1,2,3 LB 2,3,4 PG GROUND Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem. wn! &c 2. The twisted terminals are to be used as is. See attached AMP Engineering evaluation report. NLlnpf sInW eks ra/n' CO7 iMFORMAT10% i DOPY mv

cl3) ENGINEERING EVALUATION REPORT 4/01/85 l ........ L..... 73 BE KEPE0 DEED N~.1 TUJ.:,d.!D tiiLiJ WRiiTDI PHESIE OF A61P IEDRPORAIG. EER - 136 3029-50013 AMP

  • PIDG* PVF2 Teminals Tested to MIL-T-7928G Vibration Sequence Table of Contents Introduction.

Page 1 Test Specimen Description. ..... Page 1 Test Schedule. ....................... Page 1 Test Methods Page 1

l..ly" ~0Rh,Ral dh Test Data Su==ary.

? P Appendix A (Engineering Conclusions) [ k. l 9 ?PW I Prepared by h Approved b p F David Fle aing Q Floyd Re haw Test Engineering Product ngineering Supv. General Products Group General Products Division l

  • Trademark of AMP Incor wrated esmanatencoucts enove amp escomponavso, nasuuseone. pa mes v.s.a.

INTRODUCTION This report cbntains results of tests conducted on PIDG PVF2 radiation resistant terminals. Testing was conducted to evaluate the products 0 and 900 and a performance when subjected to bending of terminal tongues of 60 twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop====~----t per MIL-T-79286. Testing was conducted in AMP Laborator r<o i th TEST P I EN ESCRIPTION -The following Terminals and quantities were tested. 3 ) RV Quantities ner Test Grout Terminal Part No. Wire size Group 1 Group 2 Group 1 53425-1 10 AWG 4 d 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands. TEST SCHEDULE Terminals were subjected to the following test in the sequence specified. Test Groue and Sequence Test Groue 1 Grouc 2 Grout 1 2 tare Droo 1-1 1-4 1-1 1 V Vibration 2 2 2 TEST METHODS Voltare Droo. Each terminal was measured for voltage crop by energi::ing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point. Vibration. Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means. The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire. The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours on each of two axes mutually perpendicular to each other and to the axis of the wire. 1-

TEST DATA SUletARY Voltage Drop in Mil 11 volts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Specimen # 1 2 1 4 1 2 1 4 1 2 1 4, Initial 15.1 14.8 15.4 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib. 16.h 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel. All other samples displayed no signs of physical damage. APPENDIX A The sample which broke off after 9 0 hours in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours of both planes without displaying any signs of physical damage. Based on the information acquired from this test, we can say that any static appl.Leation, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same csn be said of the twisted tongue to 450 Even if the terminals were to l face moderate vibration such as that set up by heavy equipment running, we i feel that the testing proves that the terminations will withstand such a condition without any detrimental affects. \\g0%\\ Y COOT e M M

COMANCHE PEAK STEAM ELECTRIC STATION TExi.s oT10 TIES CENERATING CO. NONCONFORMANCE REPORT (NCR) E-84-01072 R.1 Pag 21 of 2 UNIT ST AUCTURE/ SYSTEM ITEM [ COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIA NO. Cubicle #8 1 S.G. #1 Vendpr Luas CP1-EPSWEA-02 Rn. 103 El. 852' N/A i NONCONFORMING CONDITION 0 or twisted. F $RM3 Lugs listed below are bent in excess of 60 INDEXED' a Terminal block No. Terminal points P.. 4 PpRM.PL( p G.C g P.T. 1, 2 { n't 'ocyg/ j g P.S. 1,3,2 s

t mia L.A.

1,2,3 o L.B. 2,3,4 S P.G. Ground Hold tag applied, all unrelated work may continue. C I, 2 2.7.1 ES-100 pEv PAAA AEFEAENCE CCCU'. TENT: AEPCRTED GY: DATE: I Steve Bufkin 4 / 9 i84 l //j " 3 OATEjf CE REVIEW /APPACVAL: (UAUL O/105 i86 u /" ' CEPARTMENT J ACTION ACDAESSEE I. Vogelsang !Eng. CISPOSITION: AEWOAK AEPAIR UsE AS iS XX ScmAP See attached disposition, j l t a \\h5* Y k e \\- b hd g r,r ??@. i l I ENG AEVIEW/APPAOVAL L Wllltru0s,~u i c/an' DATE: i ^ V L : ', ~T Q OAT : CE AEVtE ./ ^ l ii u _cisPOSiTicNMAiFTCATiian a cLosunE: O WnY)aw?b /i$AW L / // o

  • 0VMENTS: Rev. 1:

Reopened to clarify disp i tion.

W# DISPOSITION: liCR #E-84-01072 R.1 1. The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidence by satisfactory completion of system testing. TERMINAL BLOCK TERMINAL POINT PA 3&4 PJ 8 PT 1,2,3,4 PS 1,3,2 PB 4 LA 1,2,3 LB 2,3,4 PG GROUND Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem. wn/ kW COP ??'W

COMANCHE PEAK STEAM ELECTRIC STATION TDAs UTtuTIES ,, NCs Na CENERATING CO. NONCONFORMANCE REPORT (NCR) lI-9 9 - A I 07 2 UNIT STRUCTUREi SYSTEM ' ITEM / COMPCNENT TAG /lO NUMBER LOCAT.ON C A ELEVAT.CN AIA NC j S90.s/ C& 23At I l W e^<. " 8 M.#/ cnArv Loe5 h9sE9 m en o s Rmloa EL.95.1 A)/4 NONCONFC AMING CCNCITION

  • ND Q g

d60*a h, s 0 Os l- % E 0 t.ok 100. $rm; gj. yo', gT,), a 94 = 3

9. s.

ARMS 3p ggg g-g-s g

9. r.

INDEXED '; 2. C 9= &

  • l, 'b, eh DATE:

m a. o xa i A. 6 .t.; 3 4 0 3 MI i

e. G.

amoub i \\V i E8 b /O B 7* AEV ) KEFEAENCE CCCUMENT-PARA EEPCRTED BY: CATE. j g /-/ /9 / h ! l y CE REVIEW /APPACVAL: CATE; W/N/M w LA W C ACTICN ACCAESSEE j

OtPARTMENT
  • It24E1 / CCAJ "AATD W Car-

_t G 1 i CISPOSITICN: REWCRK AEPAIR USE AS IS NY SC3AP l TReMEdWMAkuMefMRid2 J%st!FaW /t..fAWrfnO*Ag/41 A4 Mal nantf_*oMg 7wG rc.90,*Antn .up To sto* wiry Au guenventhtw AVAwcrN>d AN64VD&RMb HM 46HwksO 'rWd PtudseROMe TR&NOVAU w I wy.m nannoW: A f

  • ftIrMn6AL%uxX,T8tM'. 6AL f% elf. 'TEBAmeAL TWootJTEtmosALPD94G TERAAeM.TMout.,TERNMAL *Doldt.

j P. A. 1V '?.S. 8,47. L. A. AS . ) 94- [ ... 'P.4. S RT. _.1. 4 L. %. p '8,3,4 E P.T. f,1 P.4 4 'P. W GED*46h. ._) l _zt is o.m smemnTion ww wss* masawAu. to marpass Agpmaenrr unm.sassury 4 m umm m - w b u a" na.su - 'd?.. RECORD SE4 ENG. REVIEW / APPROVAL / RTN. i QA R g gArg; t A41 mAI N V/ K W /.2.$/ N l 1 2 ~ KEE E La = w [ j C CE r.EVIEW APPROVAL: Q CtsPOSITICN VERIFICATICN & CLCSUPt // CCMMENTS:niWil'. 4A4P 'F41A4sW448 WAtW Sde# MA4 V Shf D'saue( 48s ATTAtasec a.4AA gg ggf b, A'hvfd& V.Ans' 9' .a _ _ _ =_. ~

u..s.d.. w kELEPHONE CONVERSATION RECORD Date 4-17-84 Tim., 3:30 P.M. ~ Call by: W. I. Vogelsang of TUGC0 - Enoineerino Div. (Nm) stage,y) Answer by: Floyd Renshaw of AMP Prod'ucte Cerooration. Product Engineer .N=1 w Contract No: Subject discussed: Bending of PIDG*, Nuclear PIDG. PLASTI-GRIP *. or SOLISTRAND* terminals I ur-n,,in-+ndi 1rUfy H LU -m. n - m.,, , '_:^ e N bl

  • Tradema rk nf AMP inenrnnratnet

SUMMARY

oF Di$CUS$10N, DEctSIONS AND CDAWITMENts. W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr. B. Eister. had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120*. It was pointed out that for these cases, the application was for short jumpers (nonnally under 18 inches), and as such, the full mechanical strength of the connector was not required. Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45* bend. However, this does not preclude bending the terminals up to 120*. In this case, an Engineering evaluation fcr the specific type of application could be donc by the product user. Items that should be taken into account are as follows: a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) on:e installed if it is contemplated rebending these tenninals, they should be discarded and replaced by a new terminal. ~ Floyd Renshaw also advised that while a terminal bent more that 90* to 120* would not retain its full mechanical strength it would mainatir, its electrical characteristics. ~ V:dw' cc: ARMS <M L.M. Popplewell F. Harned/D. A. Wilkinson/F. Renshaw AMP Products Corporation Vallev Forge, Pa. 19482

i COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES CENERATING CO. NONCONFORMANCE REPORT (NCR) 1:~9 4 - n in D 2 .y UNIT STAUCTU AEi SYSTEM ITEM / CC(tFCNENT TAG /lO NUMSEA ' LOCATiCN OR ELEVAFCN AIR NO, 3905/t&23A c a c> e 8 ~ / SA.'/ Vedrv Logs ceiepmcti.o,> RmloA S. 95 1 A)/4 NCNCONFCRMING CONDITION A h a LEw of 6o a m, ez Z h I" M i l OIC6h MO.. ~$m,hg. p[,J,

k. OM.A,Oh.-

L e u i U. bpAl t P. 6 l> 3>.;L, Z b e o 9sT. ~5, lj A Q 9'b d ) )d]/ I C A. a.' b 1,3 J k 6* 4 3, H (Os 0

  • Ol'cwb Ei& /0 0

? .2, ). / AEv ..AA REFERENCE CCCUMENT. LEPCRTED BY: g CATE: _M. bu. 4 - k* / 9 / . UE EEVIEW/APPAOVAL: CATE: ' M2_ V / f /,V f C ACTICN ACCAESSEE j lOtPAATMENT 7DtJE3 / COME4TD

"T"T: C r-fd 1 CISPOSITICN:

g, AEWCPK REPAIR USE AS IS ^ SCAAP T'/J6 6044.6 A.)T" M ddd FAc.TO R6 R'S AoS i ri C d t $ TH AT

  • TEEM t O A LS @Y BC 66 *JT 006 TIM 6 TD c)o* Aup 0F To ite WiTA A4 6 4s toe 6R. tog svAvo ATiou. CM4i04co Oc3 4AS R.EJtEMP d

TM FCL'ou 04 TEEMi4 ALS tO C 045T104*. n TECMI O AL Bloc 4 "TE R mi d Ai., Po i mJT' W P. A. 3.4

9. G.

9 o F. T. l. f-C

9. S,

i.3.2. P. T(* 3,4 Z R $. 4 9 L. A. [9 3 G c.6. z!,"3'.4

9. 6.

Ca#.00OD t *, c4E DETGt1Mt4ATicu VA'T Tussr TecminAi.$ Oc utt EbsE AO EQ0iFMGOT SERVirJ A6it.iTY th.GM A49 MA'T 14 Ost.D 45 ti. Mor6' OMP TUcMium.5 4AVC MEO IM5TMLE D BY TMC VGODrf. MC ATTAf M D c. PPA M24 i / i (g g' 4 J $// Y/ bh ENG. AEVIEW/APPACVAL CATE: ( s CE LEVIEW APPAOVAL:. CATE. - WA?U" Y llit SW y I 'ISPOSITICN VEALFICATICN & CLCSUAE: CATE: / / CCMMENTS: J

[. C MAN 7343.dfluTIES NCR No. NONCONFORMANCE REPORT (NCR) GENE *' ATING CO. E-84-01070 R.3 Page 1 of M ljNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lo NUMBER LOCATION OR ELEVATION RIR NO. l Cubicle #6 1 ! S.G. #1 Vendor Luas CPI-EPSWEA-02 Rm. 103 El. 852' N/A t NONCONFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted. d Terminal block No. Terminal points 5 P.A. 3, 4 8 P.C. 3, 4 s U: \\~0RVK 0N c ~ Hold tag applied, all unrelated work may continue. a-u 33 3 2.7.1 ES-100 ngy _2

pan, AEFERENCE CGCUVENT:

CATE: AETORTE3 GY. Steve Bufkin 4 /13i 84 ! DATE: l CE KEVIEW/ AppAOVAL: wl ha Ne 8 / / / / FJ' l C ACTICN ACCRESSEE l CEPARTMENT I. Vogelsana ! Eng/ \\ CISPCSITION (183)XX SCRAR mEwonw(2)XX __ _ A F A A 1 A USE AS IS See attached disposition. le. 05 ARMS m lHDEXED esam.etr.necono i i gj ypt 041985 ""c l~ w,q,, suonLE Loc. C k ? I ( f +!- ENG AEviEW/ APPROVAL DATE: $ 1{}/ W h hl CE REVIEW APPROVAL; M OATE; &_^ ^ $ / l ? / YO ~ .y C CISPOSITICN VERIFICATION & CLOSURE. oATE: W.%/WZe/af h = l A v! 0 5 i 191 ts

OwtNTS; Rev.1:

For correction of tenninal point numbers. Rev. 2: Reopened to clarify disposition. Rev. 3: Reopened to attach AMP Engineering evaluation report & to address twisting.

g.g -S'S ?S# DISPOSITION: NCR#E-84-01070R/3 1. The following tenninal points and associated teminals have been inspected by Electrical Engineering. The inspection indicated these terminals were bent less than 90' and that no flaking, cracks or other physical discon-tinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidenced by satisfactory completior, of system testing. TERMINAL BLOCK TERMINAL POINT PA 3&4 PC 3&4 PG 4 Based on the above evaluation, the teminals may be used as is as they do not pose a serviceability problem. 2. The following tenninal point and associated teminal was inspected by Electrical Engineering and was found to be bent less than 90 but it does show signs of fatigue. This tenninal is to be replaced - Rework. TERMINAL BLOCK TERMINAL POINT / f V rk/g 3. The twisted terminals are to be used as is. See attached AMP Engineering evaluaticn report. u n/ ll ilii s/n lg{ M ~,a S// 7/ P.s' it4FORMMU' \\ COPY PP W

7 CD) ENGINEERING EVALUATION REPORT 4/01/83 g ........ L..... 3 O! KEPE000CD C TU.a!.!D Giii.aisi WidiTDI PGIDEIE Of AMP INCGAPORAIS. EER - 136 3029-50013 AMP

  • PIDG* PVF2 Terminhls Tested to MIL-T-7928G Vibration Sequence Table of Contents Introduction.

... Page 1 Test Specimen Description. ..... Page 1 Test Schedule. Page 1 Test Methods. Page 1 Test Data Summary. ? ; -h- .FORBIA"ON2 Appendix A (Engineering Conclusions) h ,1 v i ~ ')')RV-l Prepared by kh Approved b ] y 41 David Fleming Q FloydFmFfhaw Test Engineering Product engineering Supv. General Products Group General Products Division

  • Trademark of AMP Incorporated esssenat recoucTs ensur aaseescompomates.Manasseuse,pa triesU.s.a.

INTRODUCTION This report cbntains results of tests conducted on PIDG PVF2 radiation resistant terminals. Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286. Testing was conducted in AMP Laboratories during the month of March, 1985 WORidClok TEST SPECIMEN DESCRIPTION gmq g The following Terminals and Quantities were tested. Ph 4 m a a Quantities ner Test GroEIN Terminal Part No. Wire size Groue 1 Groun e uccuu 53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands. TEST SCHEDt'LE Terminals were subjected to the following test in the sequence specified. Test Groue and Sequence Test Groun 1 Greue 2 Groun 1 Voltage Droo 1-4 1-4 1-4 Vibration 2 2 2 TEST METHODS Voltage Dron. Each terminal was measured for voltare crop by energiaing with 95 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wtre 6" back from the terminal probe point. Vibration. Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means. The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire. The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours on each of two axes rutually perpendicular to each other and to the axis of the wire..

TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2 1 4 1 2 1 h 1 2 1 h, Initial 15.1 14.8 15.4 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib. 16.4 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Mar 19.5 19.5 19.5

  • Sample broke after 9 0 hours in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel. All other samples displayed no signs of physical damage. APPENDIX A The sample which broke off after 9 0 hours in the first.pihne of vibration apparently was mounted improperly as al'1 of the remaining samples of group 1 and the other two gioups went the full 18 hours of both planes'without displaying any signs of physical damage. Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to o00 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we reel that the testing proves that the terminations will withstand such a condition without any detrimental affects. ... m _ _ _ y _ a _,. ~ .,,,,,7,, .g pr_ mm.y a

)ExAssuTitlTies CZMANCHE PEAK STEAM ELECTRIC STATION . GENERATING CO. NONCONFORMANCE REPORT (NCR) E-84-01070 R.2 Page 1 of 2 l UNIT STRUCTURE / SYSTEM ITEM /COMPCNENT TAG /10 NUMBER LOCATION OR ELEVATION RtR NO. Cubicle #6 1 S.G. #1 Vendor Lugs CP1-EPSilEA-02 Rm. 103 El. 852' N/A NosCoNroRMING CONDITION

  • f

' ' t.*y Lugs listed below are bent in excess of 600 or twisted. g d Terminal block No. Teminal points E P.A. 3, 4 DATES h

  • 4 PpRM. PLT. RECORD p,

P.T. 2 [ nu 'jegj Hold tag applied, all unrelated work may continu [." " '** g g b i e I ES-100 2 2.7.1 CEFERENCE CCOU'. TENT. ,gy CEPORTED DY: CATE: Steve Bufkin 4,13, 84 I GE REVIEW / APPAOVAL: / / 6,// OATE: if/MUb O/ iofiEf uJ ACTION ACORESSEE lCEPARTMENT i I. Vogelsang ,Eng. l CISPOSITICN: AEWCA4(2)XX AEPAin uSE AS IS(I) XX SCAAP See attached disposition. i y l \\MoRMM\\0?.,\\ \\ s qJ. v. n. Q. % g ~a cr I 3 9 p?R\\' _..t. l ENG AEviEW/APPAoVAL DATE: /( 1 1 x /AL V OATE: GE RE ' f / / Adhf 0 /$/$ u 0 ois/oSiticriveRiriCArion a cLoSumE.Ws&ugs/ l / EAT 25 W c 00VMENis. Rev. 1: For correction of termi 1 point numbers l Rev. 2: Reopened to clarify di ition.

QD 0 7 A. DISPOSITION: NCR #E-84-01070 R.2 1. The following teminal points and associated teminals have been inspected ' by Electrical Engineering. The inspection indicated these terminals were bent less than 90 and tha+ no flaking, cracks or other physical discon-tinuties exist which would indicate a loss of mechanical strength, Electrical characteristics are maintained as evidenced by satisfactory completion of system tet, ting. TERMINAL BLOCK TERMINAL POINT PA 3&4 PC 3&4 PG 4 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem. 2. The following tenninal point and associated terminal was inspected by Electrical Engineering and was found to be bent less than 90 but it does show signs of fatigue. This tenninal is to be replaced - Rework. TERMINAL BLOCK TERMINAL POINT rbM P, &g gik WORM $0N COP'Y( wu

COMANCHE PEAK STEAM ELECTRIC STATION TEXA UtuTIES , NCn NL CENECATING CO. NONCONFORMANCE REPORT (NCR) l$-90 ~DIO lO R 1 I UNIT STAUCT' A, SYSTEM ' tTEu/CCMFCNENT TAGliO NUMSEA LOCATiCN CA ELEVAf CN: AIR NC. hD4 DO S(C)f, (se /

5. Gi.

l W,odo,. Lots'c.9)Eh>F#M 9m lo3 ELP.o L d/4 NONCCNFCPMING CONCITION U l N bO s m .W l 5 lt $1 (2'CfMY b ua pMS 2"g9RF 8 da m%96A.ay& monED m ~ 'm = I 5./oo

gys,

,Ey 2 a,7. I j KEFEnENCE CCCUMENT: ..R, CATE I RETCRTEC SY: $ / El h I CE AEVIEW/AP8ACVAL: CATE. w A'u / M k d3 / @ C ACTICN ACCjESSCE l TptrCEPAATMEN4 l ha s / thsAsrr s&i l CISPCSIT!CN: N 8EWCAM PEP 41R USE AS IS SCAAP . "D46 TERJNN4L.LANus0.oN_T9ltAAINAL 1ht,3yt.?.T.' Tesarrt is101bs esetacan mwo staTtAiieno, tower.c. _ THE 4944ep(T MAWUSAgrV348'8 9t$lT10td l% TMilf 'ftthWNhb$ MW 'M lb4WT ON4 'f/A46 fD 90*, A40 WF TO ywy.._110' WffH 44are&ltests#e SVALW47 pew. EW6tMie4F NAS asyl4WSO *nti MLLa@ Weetti IN W f TSRAALM64. *bL6LIC 74RAApeAL lionNT" .l e v. u l 5 PA. 49 i I O f.&. H l 3.T 11 494. OSTBaMIMaffWWTMAT 'TM464 'fttamath(4 90 NOT' M A*4 @fManff' 8%AVff.EhDlblT/ P249L4M l hun mAM 'ha iaaan h la. maar nasur w --- 42 ENG. REVIEW / APPROVAL. CATE: I i i y I/ /f/OI l CE REVIEW APPAOVAL: CATE: ' ' fM: f f.^^ Y //1/ WY ^* 7 w l O CISPOSITICN VEMIFICATICN & CLC RE. CATE: l^ m'^=^ f/N/YV c=""*" %. i. mm s u p aa. I mers:.we v==== i sasu w a s s b r m. Ses asses,Mab 471% 93,1.48 g,,AL Lg g,,,,t)q,,g, = - -,. ... _ =

~ u r a .0,., s. TELEPHONE CGNVERSATION RECORD Date. 4-17-84 Tim., 3:30 P.M. Call by: W. I. Vogelsang of TUGC0'- Enoineerino Div. (Nomei M Answer by: Floyd Renshaw of AMP Prod'ucte Ccrocration. Product Engineer E p4.m.: Contract No: Subject discussed: Bending of PIDG*, Nuclear PIDG. PLASTI-GRIP *. or SOLISTRAND* t-rt nM ' terminals \\ goxwo*'.. _ --g I.y w

  • Tradnma rk nf AMP inenrnnratori su m Any oF DiscusslON, DECISIONS AND CDMITMENIS.

W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr. B. Eister had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120*. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full me,chanical strength of the connector was not required. Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45* bend. Howmer, this does not pr.eclude bending the terminals up to 120*. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows: a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these tenninals, they should be discarded and replaced by a new terminal. Floyd Renshaw also advised that while a terminal bent more that 90* to 120' would not retain its full mechanical strength it would mainatin its electrical characteristics., Ny.a,. cc: ARMS % rS* 1..M. Popplewell F. Harned/0. A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

OMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES CENERATING CO. NONCONFCRMANCE REPORT (NCR) $~9tJ ~DlO 10 g i i UNIT STAUC hGiE. SYSTEM

T E V/ CC'.1F C N EN T TAG /lO NUP.tBER LCCAT.CN CR ELEVAT CN AI A NO.

Cu C')ide 6 0 S. Cml?

  • a% Lues e%LQS63en oL Rm 103 EL.'?.D M,9 U

NCNCCNFCFMING CCNOlTlON M [O* ^ aLA' x m m! L. he oO. m m. v:.or % 0 R M Mr 0 n'.i a

e. a.

3m j 5 T (COPY %ac% J O AEFEFENCE CCCUMENT- ' /Oo .1 4,7. l nEv ,,nA AEFC?.TEC BY: CATE: $ / 0/ . s_ {. OE r.EVIEW/ APPACVAu I CATE: V (3 / SY l A j?w i w C ACTION ACCPESSEE CEPARTMENT CISPC:lT!CN: X AEWCAK AEPAIR USE AS IS SCAAP IM TE8tMsMAL LA4% p c0 TC Ctm O As %cc=(. 9.T. 9cidT 2 is te st (t4PsAcEp AC CLTCA6MQ. EcWCcn. TR: c 0CG MT t@ USA:T C1C-C'S Rhmou iS TAAT itCMnOALS MAY'66 644T Gr4C: TtMG To c)o Au p W W 7 b OP Td Itc* wiTu M mc,idesc.iOG GVAc0 ATio4. CocuMecAi% RAS REVGc-D i m sac-r o vsc u i d C, TE RMIM Ai S g4 0005T c4: m TECMi e A esoc< TCEMi4Ac b4T g P. A. 3.4 o F.C.

5. 4 P. (a.,,

O 4 IT is ces. VeTecMtMATic4 MT WCSE TecmiNM.5 Cb r40T~ ME AG CCdiPMEOT 9 SCl V g CC ABgLgTY % SsC M Pit @ MM B& USAO AC 4 5 Q A30TE ; Am? Tec.miaAus 3Avc ecco.ounusco ey rac WetoR. $CC ATTAmeo

c. epa Ez4 i

/f / CATE: I E.NG. f,EVIEW/ APP ACVAL ff4d ( x Y 4 inil4' l ~ CE r.EVIEW APPAOVAu C4ffE. Y Y Y !$N N m P '31SPC58TICN VERIFICATICN & CLCSUAE CATE: / / Av. l @ Mw q WQ Q Mu. C""'" l

~ COMANCHE PEAK STEAM ELECTRIC STATION tex 43 UriuTits ' e"U CENERATING CC. NONCONFORMANCE REPORT (NCR) l 49- 0107 o uNif sTAuCTuaE. SYSTEM ITEM /CCMFCNENT TAG /IO NM SEA LOCATiCN CR ELEVATCN' AIR No. S9c3/GC2M cssicle U S. C. # l Mn - Luol p1EPswn -o t _ am lo3 EJ.fs1 U//9 I wm% g i NCNCCNFCAMING CCNCiflCN w nm. .m e rs% 8 b b ) OC,l{ $ O. Q 7 u mea i 1 COPY w no ~ et a m. OO Q ,,,, A, 7, / Agy REFERENCE CCCUMENT. s& a f 6. AO 4,,, H f.EPORTED 8Y: CATE. i 2E KEVIEN/ AP8ACVAL: 7 CATE: I w /, 4, L / 0 /$V l C ACTION ACCAESSEE 'CEPAATMENT l -fahams dweern ' Tpc - e 8 i CtSPCSITICN: A E'WC AK AEPAiR USE AS IS SCAAP l W 1 m 8 ! C< l Z i o l G l 0< ENG. REVIEW / APPACVAL DATE: / / CE LEVIEW AP**CVAL: CATE: . m / / O CISPCSITION VERIFICATICN & CLCSUAE: CATE: l / / I cautNTS: L

1 CCAs AM CME PEAM STEAas L.ZC"MIC $7ATICN w / / M963/662/A IN " CYCN

  1. U I"' E-/-ix)</ofr/.l I

rus 0,s.sca:M".cn g.su nrranea M g.m g, gavaTas / suwcr.as a.6.sman GANLE L'&E0mswf. s t:3 0/* f A ~d.d e d - c t-w 02-93~2

  • 4Gt
  1. M-/63 sl arr.:; m e asy.

elw as, sss, a uv. a saamais a asaams en.. Sa d. sci.. a CS~-/00 t Z-07-04. N.J -39

  1. - 3 ~~ m NO C I"as Tst C Tc N N " " O I N EcT W"#ne-en UTMen n

-asp. RE2iA.1'S Impa on c=wu en, a.:. mcass.: itens sar:wac;cnr , M m.g c e ,o,u, im. -.e. a = 'a=<c=

== .e IMSPECT1CN AT7ll8UTE3 0 OAft !i a m= e / I &/~//swsAw YPr# Af b *) d $' ev A b W N W. fN d i s. a f I c InoMsk vehbe%4 n d>=. m h's,c'cr m l l 1 l l I //, J-2B #-po l Ii i l I 1 l~ l i l t.- I um%e nee ><- 4 7~ zarrkd Abivt z.- Is-4 I I l I I il i l i I I lI i l I l l l 1 I I I i# I i i X11.c m t) \\ l l I \\ tMCfWJHL Nt ' 3 l \\ uu - ; _,pg.[. y g 1 l \\rs?fl W l'n \\ l l \\d M 14 I" \\ l l \\W h.la ' I \\ l l 1 \\ l WilO i ) I i ii l i i l 1 1 I i i l I l i l l l I I I I I I i i i lI l I i l i I I I l l l 1 wanus (:, spen, r :a leys m tTM/ x An avce n1g4. csoro iT-/ MA /92YT pcy-/. cc34 9/9.ZW 902" i Mcvs' zwf Kwcw/ 1%> h th.,rr$'M ran. ac.4n:.ca.c an \\

  • 4

[Ll$.* D/DN Sg Ns9 ' d Y.,,w,. Ci 1 a t CC NSFtC**A g QV l 4,n& & gg j' ~ f-Sf vt t _ [ y g} )) 1 l.-

y CCMANCHE PEAK STEAM ELECTRIC STATION TEXI.S UTIOTIES "C" "" NONCONFORMANCE REPORT (NCR) C ENER A'.*iNG C3. E-84-01068 R.2 Page 1 of 2 ~ f (JNIT STRUCTURES SYSTEM ITEM / COMPONENT TAG /10 NUMBER LOCATION OR ELEVATION AIR NO. Cubicle #3 1 S.G. #1 Vendor i.ugs . CP1-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION Lugs listed below are bent in excess of 600 or twisted. ay Tenninal black No. Terminal points z P.G. 7, 8 k,_0R VK101\\ 8 P.H. 7, 8 m P.D.

3. 4 L.A.

1 O O P.S. 2 P.A. all lugs V g P.B. all lugs a. P.K. all lugs 33JU i t iiV E P.J. all lugs Hold tag applied, all unrelated work may continue. i 2*7*1 ES-100 pay 2 PARA REFE AENCE CGCUVENT. f,ETORTED BY. DATE: Steve Bufkin 4,9 , 84 l CE REVIEW / APPAQVAL: DATE: 4 l $ /l$/ W wC ACTION ACORESSEE CEPARTMENT I

1. Vogelsana Eng.

i I C'SrCS TION: (2) XX USE AS IS (1&3)XX AEPAIR SCAAA i AEWoAK See attached disposition. t m, I w s ': ARMS l i 9 INDEXED PERM. PLT. RECORD ,,,, L p. mMI g}i JUN 0 41985 tuenLE Loc. U Alc f 4L ENG AEVIEW/ APPROVAL l l t DATE: /b/ l w, C DATE: QE REVIEW APPROVAL: TwnS S* i 17 i PC~ .aC CISPOSITION VERIFICATION & CLOSUAE. DATE: 24!$I 7ed t [ //7 / PI*

OMEENTS; Rev. 1:

Reopened to clarify disposition. Rev. 2: Reopened to attach AMP Engineering evaluation report & to address twisting.

f. M ^'

sY lV y DISPOSITION: NCR #E-84-01068 R./ 2-o 1. The following tenninal points and associated terminals have been inspected by Electr ' Engineering. The inspection indicated that these terminals than 90' and that no flaking, cracks or other physical fBhwerebent discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidenced by satisfactory completion of system testing. TERMINAL BLOCK TERMINAL POINT PG 7&8 PH 7&B PK ALL PD 3&4 PS 2 PJ ALL PA ALL PB ALL Based on the above evaluation, the teminals may be used as is as they do not pose a serviceability orobelm. 2. The following teminal point and associated teminal was inspect by Electrical Engineering and was found to be bent less than 90 but it does show signs of fatigue. This terminal is to be replace - Rework. TERMINAL BLOCK TERMINAL POINT LA 1 /$ p Ilck 3. The twisted terminals are to be used as is. See attached AMP Engineering evaluation report. j eM A- \\gyo%g\\o% man rO v ??N

) C=3 ) ENGINEERING EVALUATION REPORT 4/01/85 O y L...... !] M KEPK000CG C TG d.!D GliiW WiliTH PUMIIM OF AMP IEGAPORAIG. EER - 136 3029-50013 AMP

  • PIDG* PVF2 Teminals Tested to MIL-T-7928G Vibration Sequence VORYADON ri.

ywy Table of Contents l 5Y Introduction. ...... Page 1 Test Specimen Description. Page 1 Test Schedule. ....................... Page 1 Test Methods Page 1 Test Data Summary. Page 2 Appendix A (Engineering Conclusions) Page 2 Prepared by h Approved b ] E v David Fleming Q FloydRaphaw Test Engineering Product Engineerina Supv. General Products Group General Products Division

  • Trademark of AMP Incorporated eensnatenoeversenour asse esconeonatso. pa-une. Pa., mes v.s.A.

{. INTRODUCTION This report cbntains results of tests conducted on PIDG PVT 2 radiation resistant terminals. Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286. Testing was conducted in AMP Laboratcri-- during the month of March, 1985 N'rORYATON TEST SPECIMEN DESCRIPTION The following Terminals and Quantities were tested. 3 }:311 i%I Quantities Der 7 2 T _ g Terminal Part No. Wire Sire Groue 1 Group 2 Groun 1 'M 53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 45 Twists Wire used for testing was per MIL-W-5086 with tin plated copper strands. TEST SCHEDULE Terminals were subjected to the following test in the sequence specified. Test Groue and Sequence Test Groun 1 Groue 2 Groun 1 E21tage Droe 1-4 1-4 1-3 Vibration 2 2 2 I TEST METHODS j Voltage Droo. Each terminal was measured for voltage orop by anergt:ing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wtre 6" back from the terminal probe point. Vibration. Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means. The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire. The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours on each of two axes mutually perpendicular to each other and to the axis of the wire. l -

TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Suecimen #1 2 1 4 1 2 1 4 1 2 1 4, Initial 15.1 14.8 19.4 15.1 14.5 19.2 15.2 15.0 19.7 %.7 15.8 19.1 l l After Vib. 16.4 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel. All other samples displayed no signs of physical damage. APPENDIX A The sample which broke off after 9 0 hours in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours of both planes without displaying any signs of physical damage. Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Ev,en if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects. 5 0R p 0% COPT nax

rnAs uTsuTIES COMANCHE PEAK STEAM ELECTRIC STATION NCR No. GENERATING C3. NONCONFORMANCE REPORT (NCR) ~ E-84-01068 R.1 Page 1 of 2 l UNIT STRUCTUREi SYSTEM l'IM/ COMPONENT TAG /lO NUMBER LOCATION OR ELEVATION RIR NO. Cubicle #3 1 S.G. #1 Vendor Lugs CP1-EPSUEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION Y or twisted. r ARMS ~N 0 Lugs listed below are bent in excess of 60 INDEXED' ,w Teminal bolCk No. Terminal points P.G. 7, 8 DArea QRM.PL*r. RECORD 8 P.H. 7, 8 I ] ~ P.A. all lugs J g P.B. all lugs c. P.K. all lugs l E P.J. all lugs Hold tag applied, all unrelated work may Continue I ES-100 2 2.7.1 Asv PARA AEFERENCE CCCUVENT. AEPORTED QY: DATE: Steve Bufkin 4 9 84 ! f f i / CE REVIEW / APPROVAL: 4 / DATE: l0 U // J J ACTION ADDRESSEE ~ l DEPARTMENT 4 Fno. I I. Vocelsano DISPOSITICN: EX (1) (2)XX AEPAIR USE AS IS SCAAP REWORK 6 See attached disposition. i s WiFORM20yn i i COPY t 8 PPRV DATE: j ) ENG AEviEW/ APPROVAL l I lUN \\, / / ! n. 1 ^ 07A : Q DATE: l OE REVIE' /AJ $ _D n I I l u _DISPOSITICNTERIFICATION ICLOSURE:

  1. M DAT -

O O h / COYMENTS: Rev. 1: Reopened to Clarify dis ion. j

Q.Ab A DISPOSITION: NCR #E-84-01068 R.1 l 1. The following terminal points and associated terminals have been~ inspected l by Electr a Engineering. The inspection indicated that these terminals than 90* and that no flaking, cracks or other physical Bhwerebentdiscontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidenced by satisfactory completion of system testing. TERMINAL BLOCK TERMINAL POINT PG 788 PH 7&8 PK ALL PD 3&4 PS 2 PJ ALL PA ALL PB ALL Based on the above evaluation, the tenninals may be used as is as they do not pose a serviceability probelm. 2. The following terminal point and associated terminal was inspect by Electrical Engineering and was found to be bent less.than 90 but it does show signs of fatigue. This terminal is to be replace - Rework. TERMINAL BLOCK TERMINAL P0 INT LA 1 p IkW $0RgG0% voff w ??@ l l l

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTIUTIES I "C" " G'ENERATING CO. NONCONFORMANCE REPORT (NCR) l E-S 9 - 010 (W 1 1903/'ssN4 l f 7EV/CCvFCNENT TAGliD NytSER LOCATiCN CR ELEVAT:CN' RtR NO. l UNIT STRUCTURE: SYSTEM cMeie *3 ,I.,..f G."I tveabr-Luc.s r91 LPs924 DL R rn 1D3 EL 7KJ )01A l U tidl%t;@MAMING CONDITION 6 \\ NDEXED MWmQzof LTg eO W i z o,, TermidnL bloc R voo-haval bd5 Q RECORD 4 pl( w& p 7y'I QA REVIEW

9. D.

A 'I E l w ~% +"-~ g: ga,3 84 i < -@0M/Ki i ~' Sus ,[ [ NO, l a' iE-kofc(og p: y anu v s s l g gg ALL M d* ggi d )- f l REFERENCE CCCUMENT-REV _; s KEPORTED BY I il3LI nA-r E A I N / h / E)/ \\ q DATE: I CE REVIEW / APPROVAL: WI?If? l w b {CEPARTMENT 4 i ACTICN ACCRESSEE

  • IDL1K1 & 2A/ 4 4 TT/

'T F4r. St: 1 I DISPOSITICN: i REWORK IN REPAIR USE AS IS IN SCRAP l l ms.1 sew =A6. unnoso ow namnu moc.m.L.A.'bNr* out(8) WWbE SEtur.EO. Etwoes TwE f.atser MauvFAcruits$l TtAmou TWAT M.tamMA MY1W. %EWF CM. TIME E9G(4NO &#A T l m l w ' g w/rnweeau.+ syAwrwn AWerissasine, unt stEwswsb THE wmunuWW rsd=/ wit /#9683f/aw; y neunut1poca nommeL9mgr rsmawt.tAact Tseman.1tzuS1ansseptukumsutter l @ 'P k._... ta P.o $$6 m A. as4.a.ue.s l l RH _ 7,6 P.5 A. 74 aLL uws o._ P. A atsue.s M. 46i.6ues , ETCon3E DSTRAMNumped M ME M De 4WT W AN M KSit4/KAMILW MW l kuh seAv 'ha e At ti a SEE umrt lN * ^^^ ^^ M l ENG. REVIEW / APPROVAt. DATE: I . m, W /$ /0h CE REVIEW APPROVAL: g DATE: y O W W Y //$/ $ i Q o:SPCSITICN VERIFICATICN & CLCS E: OATE: dg;,7?'* ! & - f /// / f QMMENTS: WER$3 AMP' TERA 4N4Lf ##5'9MW M M WED 1W McMast, l ses atter. Nab e#PA M,zett muAt_ La s.-t-mo+e958

u r.s-ce., e 'TELETFONE CONVERSATION RECORD pa, 4-17-84 Tim., 3:30 P.M. Call by: W. I. Vogelsang of TUGC0'- Enoineerina Div. (Nomej h) Answer by: Floyd Renshaw of AMP Productr Cerocration. Product Fngineer (Nome l JCanown) Contract No: Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOLISTRAND* ' terminals N:0FAAT Oi! RnYn7 U%93, .1

  • Tradema rk nf AMP inenennrated OD _ A' D

I I I\\ #

SUMMARY

OF DISCUSSION. DECISIONS AND CDMMnMINTL W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr. B. Eister had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend tenninals for internal wiring up to 120. It was pointed out that for these cases, the application was for short jumpers (normally under 18 inches), and as such, the full mechanical strength of the connector was not required. Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45 bend. However, this does not pr.eclude bending the terminals up to 120*. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows: a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these tenninals, they should be discarded and replaced by a new tenninal. Floyd Renshaw also advised that while a terminal bent more that 90 to 120 would not retain its full mechanical strength it would mainatin its electrical characteristics. y.dw - I cc: ARMS s M L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482

~ COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTILITIES c.NE.AT:NG CO. NONCONFOFMANCE REPORT (NCR) R tM 9 - 010 62 D UNIT ST AUCTUREe SYSTEM IT E M/ CC'.1FC N EN T TAG.*;O NUf.1SER LCCATiCN C A Et.EVATCN' AIR NO. 2903/LS414 cas.c)s #3 I .Q G.*'l tienbr Lues C91.EPstMA-OL R rn lo A EL TEL )Oj A U NONCCNFORMING CCNCITION l pdj.h"M A"$ a f TcTmin$9L bloc 14 v00* % 'Enl b oTS EL (D G' % 7-P. s. 'M AM..uMM we&_ h P. D. M .Lc ~%, s g H: saTg mM i F.% T.."(N?0RNATl0M i as k *

p. y AE.:EPENCE CCCUMENT*

A j

7. f A

TEPCATED BY: f M ~- CCE: bb Y/ , / E )l e A \\ \\ i r 9i ?

E AEVIEW/APPciOVAL

// \\ "^_. . ~.. 71.x_ W/fI$f ACTION ACCRESSEE /

CEPARTMENT 4

ICu:s NoA/e477/

t r-c se l OtSPC3lTICN:

N-REWCAM REPAIR USE AS IS SCRAP Jh6 T6CMtdhu LAdQ69 CM TLLMrLAG 6AK L. A. PCIUT 1 IS TD et GEfcACCO, REsJced. THE cs:2Lcs)? MAAhlfALTUALC'S T3s T cal it, TIMr TERMIA;k.S MAY BC BGUT C.UG TIMG Ti> 9C' h/JO UP Tt 120' ~ Jam Ad E%dEGCgL]q G4AGU4rocM. EM6tMC-GesMA 45 REVoEA Q 36 FCLucu)nMG TECMIAJC.6 ea GUESToCAl,' TTfMs O4c 6tock TU4Ms4).ic Pc;or "P G. 'l, 6 P. A. ~7. 6 P. D.

3. 4 P

O P. S. .A. Au-Luca P.6 A L L LOM P. K.. ' Acc LL)45 P J. ALL Lt45 "IT se cec WTGCMidATicu iMAT The. TECMIMALS Do Mc7 AcsC $d 6Q0iPM6AY SERVE (.GA6stery No6uM AND M M OG USED As is. MOTT, *. AMF TERMt AJAL6 i4 AVE /3660 foSTT.LL6 D BY THC V&AJDo f. l S EG-ATTAd.AG.D 6994 36.241 ENG. AEVIEW/APPACVAL CATE: gjgjy CE KEVIEW APPROVAL: -- CATE: M f $ ^^ - Y/ $/ h mSPcSitiCN VERIFICATICN & CLCSURE: DATE: f / / - CCMMENT3:

..-m. OOM AN CNE PLW STEJM L.KCMIC STATCN w I I w ^ EnM3/GSC 9A INSPECTICN REPCRT lna g,j. g g g g g f> j . = suc.w.ca i.ser.rcar.a w,y ins.ai smcr n u.wr.a i C&' ASS 12 c~0' smreAf ECD / ERSWFA-et-02 Bd*2 W/ /f W - / C.,3 as U w p d.acer. g ar.s.s w. gasr a.r sec. a av. a c. names a g ws. a a. ES-/00 v z-e, cr-po- // J-38 H-S~ NO C lN m*0!!3 [pM 'NfNU.mCm ] {W:asn:mem Qf,MM. [pn TT" l ECM wt= ca vcercar.ca asn:- en upt:nen asp. RELLTs 7me:- an c=w r n. u.:. means iTzus sar:pacte ,,j. M s y.dt;f C insm :cm c=w.r sn. unsar.smcrce iras wrc ac.:w

    • 'hsmm
an

.c INSP"::7ICN ATTRISUTZ3

,lgarg e

e i I rAn,cusvasie rem;w&as xsvee_ex rs<streks' I& I l I es & whdst s-wi%enfs e>%7-CE/t.J-JB I l l l l lg_po I li i l i r!l l z-Ir-wnsva es-rt.n & awwn/ nwt' i id'I I I i l l l 1 l I I I I I I I l lI I l l l l I I I l l II l l l l l l l 1 I IIM I I A i-nnN \\ \\ l \\ t M E O K m thi M ' 3 I l \\ LIw 6%% f t I I \\ in nTr A Y l t's \\ l \\% 4L JS I" \\ i \\" l j _im t I \\ l 1 \\ l WIN V l i t i! i I I I II I I I i l I I l I i l l l ma t +m t=.n der 9s arm &,ameda ex ec-esr-e+-caners TsWe /9249 s yd /?rf #&wsW pc y-Z/est? BB V Ma cMee4 s ge, rem /- 0o34 9/ 9asse-a.sedes /S, AS R3R 4crf 'b'SP"' f' ** 7 77% /k& f/5AL. Z~ A7 sa N_'l$f$gg.,i 1.8. c = 2 caC e : 8"'" "[,m, ,I fuse.~.d.by-L w e.\\ E-hs 5^ VN

COMANCHE PEAK STEAM ELECTRIC STATION

  • TEEAS UTIOTIES NONCONFORMANCE REPORT (NCR)

GENEf:4 TING CO. E-84-01067 R.3 Page 1 of L f UNIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /lo NUMBER LOCATION OR ELEVATION Rf A NO. Cubicle #2 1 S.G. #1 Vendor Lugs CP1-EPSWEA-02 Rm. 103 El. 852' N/A NONCONFORMING CONDITION Lugs listed below are twisted. d Terminal block No. Tenninal point E P.U. 2 " ^- 4 i UORMARO\\ Hold tag applied, all unrelated work may continue. o. COPY 3. e RV 2*7 1 2 PARA ES-100 pEV AEFERENCE COCUMENT: REPORTED BY: DATE: i Steve Bufkin 4 /13 / 84 l OATE: CE REVIEW / APPROVAL: p 5' // 4 /6e E.! l/t 'uO ACTICN ACDRESSEE DEPARTMENT I. Vogelsang Eng. ciSPOSmON: l XX REWORK AEPAIR USE AS IS SCRAP l l t l See attached disposition. j

f-ARMS I

$[ @Q[)([Q PERM. PLT. RECORD i RTH'

r.,,. L ^ C.

C /5. I ? Jijy 0 41985 sunnLE L'oC. 5 MC( 4! 1 L A ENG AEVIEW/ APPROVAL DATE: /bI WVI i f\\ CE REVIEW APPROVAL: V DATE: f Ye%W L ^ f llY / W uJ O CISPOSITION VERIFICATION & CLOSURE: DATE- @J CITellS ek& Y& 5 / l'y / W l COMMENTS: Rev. 1: For correction of terminal point numbers. Rev. 2: Reopened to clarify disposition. Rev. 3: Reopened to attach AMP Engineering evaluation report & address twisting.

S g -S DISPOSITION: NCR #E-84-01067 R. 4.3 l 1. The following terminal points and associated terminals have been in-spected by Electrical Engineering. Thginspectionindicatedthat these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidence by satisfactory completion of system testing. TERfflNAL BLOCK TERMINAL POINT PU 2 PA 4 Based on the above evaluation, the terminals tray be used as is as they do not pose a serviceability problera, f hl' lYR ik g lc lyl 2. The twisted terminals are to be used as is. See attached AllP Engineering evaluation report. Il Q '7 J-spr/er \\NTO COY,. ???D

C::3 ENGINEERING EUALtiATION REPORT 4/01/85 b 3 .......L...... 73 ~! IEPE000CED C Idu ::.iU dilia'ui hidIIdi EM OF AMP INColiFORATED. EER - 136 3029-50013 A:4P' PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence Table of Contents Introduction. T ove Test Specimen Description. a1 Test Schedule. ..[ P 1 x~a 3. Test :%thods .... Page 1 )M/ Te s t Data S umm ry. .t\\1. Page 2 l nppendix A (Engineering Conclusions) .. Page 2 l Prepared by kh Approved b ] p c?t David Fleming Q FloydPaFphaw Test Engineering Product Engineering Supv. General Products Group General Products Division

  • Trademark of AMP Incorporated eGNEnaL pn000 CTS op0UP Aasesecomponavuo.Maswusevne.Pa mesu.s.a.

I

INTRODUCTION This report cbntains results of tests conducted on PIDG PVF2 radiation resistant terminals. Testing was conducted to evaluate the products 0 and 900 and a performance when subjected to bending of terminal tongues of 60 twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286. Testing was conducted in AMP Laborat"-irr tarin: "r renth of March, 1985 h TEST SPECIMEN DESCRIPTION I.QN d' The following Terminals and quantities were tested. )P]\\/ Quantities ner u vuu Terminal Part No. Wire size Groue 1 Group 2 Groue 3 53425-1 10 AWG 4 @ 600 Bends 4 @ 900 Bends 4 @ 450 Twists Wire used for testi,ng was per MIL-W-5086 with tin plated copper strands. TEST SCHEDULE Terminals were subjected to the following test in the sequence specified. Test Group and Sequence Test Groun 1 Groue 2 Groun 1 Voltaae Droe 1-3 1-3 1-; Vibration 2 2 2 TEST METHODS Voltare Dron. Each terminal was measured for voltage crop by energizing with 55 amperes with DC current s.nd probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point. Vibration. Terminals were rigidly mounted to and not more *.han 1 inch above the vibrating platform by their normal mounting means. The test terminals were so mounted *. hat the Junction of the other end of the test sample was secured to a stable support 12 inches external to the vibrating table with all slack or tension removed from the wire. The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours on each of two axes mutually perpendicular to each other and to the axis of the wire. TEST DATA

SUMMARY

Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2 1 4 1 2 1 h 1 2 1 h Initial 15.1 1k.8 15.4 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib. 16.h 16.1 15.4 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G hax 19.5 19.5 19.5

  • Sample broke after 9 0 hours in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel. All other samples displayed no signs of physical damage. APPEN, DIX A The sample which broke off after 9 0 hours in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours of both planes without displaying any signs of physical damage. Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects.

COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTipTIES NCM No CENpAT JG CO. NONCONFORMANCE REPORT (NCR) g_gg 01067 R.2 Page 1 of J2 UNIT STRUCTUREiSYSTEM ITEM /COM PONENT TAG /ID NUMBER LOCATION OR ELEVATION AlH NO. Cubicle #2 i 1 S.G. #1 Vendor Luas CPI-EPSWEA-02 Rm. 103 El. 852' N/A I NONCONFORMING CONDITION Lugs listed below are twisted. PfRM. PLT.RE Tem n 1 block No. Terminal point Nap j Hold tag applied, all unrelated work may continue Z sf"5 i Y ARMS M INDEXED ~ l c: DATES 1 ES-100 2 2.7.1 AEFERENCE CCCUMENT: agy p,n, REPORTED GY: DATE: I Steve Bufkin 4 / 13/ 84 ! OE REVIEW / APPROVAL: DAT ~' DEPARTMENT j U ACTION ADDRESSEE I. Vogelsang Eng. DISPOSITICN: REWORK REPAIR USE AS IS XX SCRAP 4 i See attached disposition. _I j r gog m 0% l ~ l LCOPY ?PRV__ ENG REVIEW / APPROVAL DATE: I O I V t / / A r e vfl V DATE: QI REVIEW u / //{1 [ I f/h O 5SPOSITICh'VIRIFICATION & CLOSURE: M D F e w/ // /,$ATER51 D COMMENTS: Rev. 1: For Correction of terminal p int numbers. Rev. 2: Reopened to Clarify dispo ion.

i ff.}?odA DISPOSITION: NCR #E-84-01067 R. 2 1. The following terminal points and associated terminals have been in-spected by Electrical Engineering. Thg inspection indicated that these terminals were bent less than 90 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidence by satisfactory completion of systet testing. TERf11NAL BLOCK TERMINAL POINT PU 2 PA 4 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem. $1 Mef lyl gk/c \\%o%\\00 COPT ???d

v. COMANCHE PEAK STEAM ELECTRIC STATION TnX 3 UTILITIES CENERATING CO. NONCONFORMANCE REPORT (NCR) -Ifho/067 R t - i i 88kl8 !ML8LA UNif STRUCTUREi SYSTEM 'lTEV/CCMFCNENT TAGliO NUMBER ' LCCATiCN C A ELEVA?:CN' RIR NO b B eye. ".k I I S.# / vodneL e 'CPIEP3 wa-oi R m /oA TA' J x)//q NCNCONFCAMING CCNCITION 'f N e i i /~.6kh e 2 $h. 8

9. O -

A R A. 4 aq' yKIL0% V i sa p v s j et ma S nm Tem ppw L \\ ~ AEFEAENCE CCCUMENT-Ob ) e) [ AEV PARA F.EPORTED BY: CATE: I N / lh! $ q ~f CE REVIEW /APPACVAL: d CATE: Y' LL W / l3 / N w O ACTICN ACCAESSEE ICEPARTMENT CISPOSITICN: 6 REWCRK REPAIR USE AS IS YN SCRAP .rAeVclanenwr MAuvrmssO humaw t.1Tmr1EONW44.5 MMY tur asAtrmrrims rv90* ; no a ao'waeiaumwas amaw: mmaawna amm na ~<a.- 4 g $ 14ttNLIMM.1_Itt_CR9ET1 Dell._ f TERMsNAL *DLCt.K 'TEEWuMAL IDtfE1 .i _._ _, j "P. U. 2. Q_ _.7. 8 e. N o E11 cmJG.1*TEttatWmTote 'TMNT TME14.WtoMLS h NdT" %E M EQutPMac snw43w, l %M huc MAY ~6E 05ED ha s.1, Il M SEC hf0TE fW doo4MsnK" sGCItonL _ ") A ( rir na-g // ' "- W FT L./ CATE: I ENG. REVIEW /APPRCVAL c. 2@f-nru, I 4 nay,,, i .,;r,j9,gg l ~, CF. REVIEW APPROVAL: ~ Y W%nS ' g" "N. } PZ Yi/9:?f CATE-1 wc j CisPosmCN VERIFICATICN & C1.CSURE: g GAT $k ng = '"bl fng) k C=-T%.w % you m. Nota: AMP Teamralks Mee asaw ear o rur sere:ue. MM NbW # 7

N TELEPHONE CONVERSATION RECORD oom 4-17-84 t Time: 3:30 P.M. Call by: W.1. Vogelsang of TUGC0'- Enoineerino Div. tN.=.1 st Answer by: Floyd Renshaw of AMP Prod'ucte tcrocration. Product Engineer (Nomel W Contract No: Subject discussed: Bending of PIDG*, Nuclear PIDG, PLAm-GRIP *, or SOLISTRAND* I r __..__m,eim terminals i WUKM e \\ - - n.~a 7 { ~

  • Tradema rk nf AMP ine-nrnnrated j

$UAUAARY OF Dl5CU$510N, DECISIONS AND COMWiMEN15. W. I. Vogelsang discussed the AMP memo dated September 2,1981'in which Mr. B. Eister. had indicated a 60 bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend teminals for internal wiring up to 120*. It was pointed out that for these cases, the application was for short jumpers (nomally under 18 inches), and as such, the full mechanical strength of the connector was not required. Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent nne time to a 90* bend or two times to a 45* bend. However, this does not pr.eclude bending,the terminals up to 120*. In thi, case, an Engineering evaluation for the specific type of application c.

  • d be done by the product user. Items that should be taken into account

.v as follows: a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these terminals, ~ they should be discarded and, replaced by a new terminal. Floyd Renshaw also advised that while a terminal bent more that 90* to 120* would not retain its full mechanical strength it would mainatin its electrical characteristics. V:dw' .[ cc: ARMS % eX L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge,' Pa.19482

g E ununES COMANCHE PEAK STEAM ELECTRIC STATION NCR No. ' GENERATING CO. NONCONFORMANCE REPORT (NCR) E O I O % UNIT STRUCTURE / SYSTEM ITEM /COMFCNENT TAG /lO NU SER LOCATION OR ELEVATION RIR NO. noycsw c a rcs e ='A. 1 . C C,." I th dw La em-cvsun-o.t R m io3 EL9.O tvlA NONCONFORMING CONDITION W _n ez Yml1V4LOlod OO. Termt A>dk 908 #* g 5 j~ E0RMATON o a:v O M (, . if 7 N, h fif 4

  • W'8 W

W N ppRy REV / REFERENCE COCUMENT* PARA EEPORTED BY: DATE; LD J Y / $ / ?Y OE REVIEW / APPROVAL: o CATE: O /-.. ( I/ k/W m O ACTION ACCRESSEE / ~ ~ jCEPARTMENg l 2nNE1 / DON EMT/ i T Fer-5( t i OlSPOSITICN: REWORK REPAIR USE AS IS SCRAP i W l 0 8 e Z9 E< ENG. REVIEW / APPROVAL DATE: / / CE REVIEW APPROVAL: DATE: W / / ^ O DISPOSITION VERIFICATION & CLOSURE: DATE: / / COMMENTS:

G }... COMANCHE PEAK STEAM ELECTRIC STATION TEXAS UTillTIES cENERATING CO. NONCONFORMANCE REPORT (NCR) t_,e i-O lO 6 7 R t - s UNIT STAUCTUREi SYSTEM ITEM /COMFCNENT TAG /lO NUP SER LOCATiCN OR ELEVAT:CN AIR NO. G n wJe. *>. l ( b.# [ Uoxhne Lop C911*PJ fJe 4 o.t_R m /OA N) )C//9 NCNCCNFOPMING CONCITION b h Lb ca Mbh, /~. 65La. w.

w. pJ
9. o.

P A-d NF0UlATON L pg DV nA 4%g v rL fu t* ** c% OO 3 1,7 / nEv P.nA CEFEFENCE CCCUMENT. REPCRTED BY: DATE: u _f _ L N/Ib/7Y e ..! CEVIEW/ A.. 4CVAL: I / CATE: l 7,t_. W /I,3/ W m. ACTICN ACCAESSEE CEPARTMENT CLSPCSITICN: y AEWCAK AEPAIR USE AS IS ^ SCRAP - fn6 Q)22GA)r MANdfac7yttES Pos:TioAl IS TMT~ TEEMINALS MAY EG BEAJrei>e 71MG TO 90' NJO 0P Tb I20' WITM kJ GUGo/UGe^21 A3G Gs/AU)ATICAl. GAI4INGE21AIG F/AS 9 GJtER-p TM6 FottoWiUA TEd'Mt4At_5 i O o t4 sito u; TEMiOAL Btoc< TERMIMAL Poi 49

  • R G.

2 P'. A. 4 It is ooz peTeemiOAnou nwr TAesE. Tegsuents to uoT P os s A O @ vtPM 643r GG Edic6 A66 lit ~T We e L GrA AMO M AY eE OsED As LS. OCTE'. AMP TEEMi@ts HAVE E660 LOSTAU 6D thy THE. V64Dod. SEE ATTACHED GPPA 36 24i 3 CE REVIEW APPROVAL:. DATE: OLT)* ! ! : ^ Y // $/ SY

  • 'VCSITICN VERIFICATICN & CLCSURE:

DATE: / / h M f

f A C STATION 5 tex *lS tJTauTIEG" l NONCONFORMANCE REPORT (NCR) ,4sENE;ATING CO. E-84-01066 R.2 i Page 1 of 2. 61 NIT STRUCTURE / SYSTEM ITEM / COMPONENT TAG /10 NUMBER LOCATION OR ELEVATION RIA NO. l Cubicle #1 1 l S.G. #1 Vendor Lugs CPI-EPSWEA-02 Rm. 103 El. 852' N/A ~ NONCONFORMING CC.';OITION Lugs listed below are bent in excess of 60 or twisted. l Gi Terminal block No. Terminal point P.P. 2, 4 i "i 1, 4 N:0H A 0N i B! I' OOPY 2 Hold tag applied, all unrelated work may continue. g:RV w l ES-100 2 2.7.1 REFERENCE CCCUMENT. pay p,n, REPORTED GY: CATE: Steve Bufkin 4,9,84 i CE REVIEW / APPROVAL: DATE: I {l, f 5 //b/ w O ACTICN AOCRESSEE DEPARTMENT t I. Vocelsana Eno. I CISPCSITION: XX f REWORK REPAIR USE AS IS SCRAP _ See attached disposition. u PERM. PLT. RECORD

[

j; INDEXED r T T "'is. [ li JUN 041985 3/cc d I l 91 l w)a I I DATE: ENG. REVIEW / APPROVAL f W K/t l Y / U /W r CE REVIEW APPROVAL. DATE* h $ / /1/ W 'w I O CISPOSITIQN VERIFICATION & LOSURE: DATE: MS/trl8f ' rw m_Q fiyyiV COMMENTS:Rev. 1: Reopened to clarify disposition, j Rev. 2: Reopened to attach AMP Engineering evaluation report & to address twisting.

fy a a i n V cfg (W DISPOSITI0ft: NCR #E-84-01066 R. G 1. The following terminal points and associated terminals have been in-1 spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks ) or other physical discontinuties exist which would indicate a loss of I mechanical strength. Electrical characteristics are maintained as evidence by satisfactory completion of system testing. TERMINAL BLOCK TERMINAL POINT PP 2&4 PT 1 LA 1 PR 2&4 PS 1&3 PJ 7 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem. l l gg ikW 2. The twisted terminals are to be used as is. See attached AftP Engineering evaluation report. NW sln/Y eL.D rA F//7/fi~ FORVA30N i COPV YN 1 l

M ,Cll3 ) ENGINEERING EVALUATION REPORT 4/01/85 a ......... L..... 73 M EPGDUCG N:2 isJ.a:.!D Glii.at WJiTG PDESEN OF AMP IEGRPORAIG. ESR - 136 3029-50013 AMP

  • PIDG* PVF2 Terminals Tested to MIL-T-7928G Vibration Sequence Table of Contents Intr'oduction.

......... Page 1 Test Spccimen Description. ............. Page 1 Test Schedule. ........ Page 1 Test. Methods Page 1 Test Data Summary. ..... Page 2 Paga 2 Appendix A (Engineering Conclusions) lh201 VAR 0h COPY w Approved bM & , hy. d4 Prepared by w David Fleming Q FloydPe@ haw Test Engineering Product Engineering Supv. General Products Group General Products Division

  • Trademark of AMP Incorporated amassaan Pacoucreenour asse escomponAtus. Mansueevne. A iries u.s.A.

r. 1 INTRODUCTION i This report cbntains results of tests conducted on PIDG PVF2 radiation resistant terminals. Testing was conducted to evaluate the products performance when subjected to bending of terminal tongues of 600 and 900 and a twist of the tongue approximately 45 These variations were subjected to Millivolt drop followed by vibration and a final millivolt drop measurement per MIL-T-79286. Testing was conducted in AMP Laboratories during the month of March, 1985 TEST SPECIMEN DESCRIPTION A The following Terminals and quantities were tested. Quantities ner Test Groun Terminal Part No. Wire Sire Group 1 Groue 2 Groun 1 53425-1 10 AWG 4 9 600 Bends 4 @ 900 Bends 4 @ 45 Twists F l h Wire used for testing was per MIL-W-5086 with tin plat TEST SCHEDULE Terminals were subjected to the following test in t 1e sequence specifi PPRV Test Groue and Sequence Test Group 1 Grouc 2 Group 1 Voltage Droe 1-3 1-4 1-3 Vibration 2 2 2 TEST METHODS Voltage Droo. Each terminal was measured for voltage drop by energizing with 55 amperes with DC current and probing at the intersection of the tongue and wire barrel and a point on the wire 6" back from the terminal probe point. Vibration. Terminals were rigidly mounted to and not more than 1 inch above the vibrating platform by their normal mounting means. The test terminals were so mounted that the junction of the other end of the test sample was secured to a stable support 12 inches external to the vibratin6 table with all slack or tension removed from the wire. The specimens were vibrated in accordance with method 201 of MIL-STD-202 for 18 hours on each of two axes mutually perpendicular to each other and to the axis of the wire. 1-

{ TEST DATA SUtetARY Voltage Drop in Millivolts at 55 Amperes DC Groun 1 Groun 2 Groun 1 Snecimen # 1 2 1 4 1 2 1 h 1 2 1 h, Initial 15.1 14.8 15.4 15.1 14.5 15.2 15.2 15.0 15.7 14.7 15.8 15.1 After Vib. 16.4 16.1 15.9 16.1 19.1 17.1 16.1 16.4 17.1 16.2 15.7 MIL-T-7928G Max 19.5 19.5 19.5

  • Sample broke after 9 0 hours in the first plane of Vibration.

The sample was bent 600 and broke in the transition area between the tongue and wire barrel. All other samples displayed no signs of physical da 7ma '- APPENDIX A The sample which broke off after 9 0 hours in the first plane of vibration apparently was mounted improperly as all of the remaining samples of group 1 and the other two groups went the full 18 hours of both planes without displaying any signs of physical damage. Based on the information acquired from this test, we can say that any static application, with little or no vibration present, should see no detrimental results through bending of the togue on a one time basis to 600 or 900 The same can be said of the twisted tongue to 450 Even if the terminals were to face moderate vibration such as that set up by heavy equipment running, we feel that the testing proves that the terminations will withstand such a condition without any detrimental affects. N0?gATh0M F COPY PPW 2- \\

COMANCHE PEAK STEAM ELECTRIC STATION i 'TF.xas UTtuT:ES CR N4 CENEI.ATING CO. NONCONFORMANCE REPORT (NCR) g-84-01066 R.1 Page 1 of 4 UNIT STRUCTU AE/ SYSTEM ITEMfCOMPONENT TAGilO NUMBER LOCATION OR ELEVAT.ON RIR NO. Cubicle #1 1 S.G. #1 Vendor Luos CP1-EPSWEA-02 Rm. 103 El. 852' N/A ' " ~ " NONCONFORMING CONDITION ARMSN :..M Lugs listed below are bent in excess of 600 or twisted. INDEXED' E Terminal block No. Terminal point Z P.P. 2, 4 g P.T. 1 PfRM. PLT. RECORD w P.R. 2, 4 P.S. 1, 3 "*L " g j z .J. 7 susnu wegg L.A. 1 g g g Hold tag applied, all unrelated work may Continue ES-100 2 2.7.1 AEFERENCE CCCU'. TENT. pay

pan, AEPORTED BY:

DATE: Steve Bufkin 4 i 9 i84 OE REVIEW /APPAOVA DAT l' OEPARTMENT U ACTION ADDRESSEE Eng. I. Vogelsang OtSPOSITION: l XX SCAAP AEWCAK AEPAIR USE AS IS g NOM; A9m0h1 See attached disposition. u .r l 'f I \\ o C a v 2 2 P?W 4 y ENG REVIEW / APPROVAL 0 TE ~OE REVtEW APPA. llUM/W D ) // j/ Q DATE- /iM .u C 5SPOSITION VdRIFid'A'TidN &'CLO'SiiRET N // DAT - A W lt MENTS: Rev. 1: Reopened to clarify disp ion.

hc$cNS ? DISPOSITION: NCR #E-84-01066 R. 1 1. The following terminal points and associated terminals have been in-spected by Electrical Engineering. The inspection indicated that these terminals were bent less than 900 and that no flaking, cracks or other physical discontinuties exist which would indicate a loss of mechanical strength. Electrical characteristics are maintained as evidence by satisfactory completion of system testing. TERMINAL BLOCK TERMINAL POINT PP 2&4 PT 1 LA 1 PR 2&4 PS 1&3 PJ 7 Based on the above evaluation, the terminals may be used as is as they do not pose a serviceability problem. l l /yjg INW x MORMEON COPY m h I

? ' texas ur$bnEs COMANCHE PEAK STEAM ELECTRIC STATION i NCR Na GENERAnNG CO. NONCONFORMANCE REPORT (NCR) I F-9 4 - O lolo (o ITEM /CCVFCNENT TAG /lO NU SER LOCATiCN CR ELEVA7:CN AIA NC. STRUCT)RE SYSTEM ca ssc.sesI UNIT 19u ssop l $.0,0 thchev-Loss E91.2%2nnR FL962 Rmlu'A h)) A NONCCNFORMING CONDITION I imA Ch.AJL (o 0 ' AY - dzz 8 TrmooAL 6100,k (DD-b mWat b cT a,. 5 fS* t'" \\ =0%WQN b da. k I3 f( i

  • TT 3PV/

KEFZRENCE CCCUMENT. OO 3 .,,, A,7. l .Ev LEPCRTED 8Y: O E CE REVIEW / APP'40 VAL: OATE: w d A.. '%L O/?/VV O ACnCN ACORESSEEj lOEPAATMENT rwan /eantenn ,-n. u DISPCSITICN: IU AEWCRK REPAIR USE AS IS SCRAP ._ ms c 4aavrauuop4e.rs48Ms himou is rgau rsammats my sc seur aus rai6 to sofsvo, 29To sw* wmv suammseeses.amanrams sannaann hws annEwso rAE nuossene stimun.t g _m.quamow: E rsament. hocx rammi,mt. Poiwr rammWAWoct. TEammu.1beelr 8< T.P. s,al 9.R. z'l l ?.T. RS. f,3 G u. I P.7. 7 It is, out marssniseaw ner se.is vsamauct w Mctr B$E AW squePMaps ss.fNitKARIL11Y P M mat ANth AA AV TY. esesO As th 11E 9kNE IN 8 N ^^fatri ENG. asviEw/AppmCvAi. g g _QA]ECORD y,ff gf l v-ca LEviEw APenov4L: L., gg oATE. D'lEn n g , 7WAV g '/ i/9119 8 cispoSmCN vtRIF.CAUCN & C1.CSURE;M. - j 18, E.- e*u n/ 4 AQA:24 a. MMmQ: /I M M o, MerrE: Aanp mnempts #4Hg asa# /Nird SP Aser w ~ k b Y g. )f;pypypA fYY-- fg f /

emwws m . iELEPHOr4E CONVERSATION RECORD Date. 4-17-84 Time: 3:30 P.M. Call by: W. I. Vogelsang of TUGC0'- Enoineerino Div. (Nom l M Answer by: Floyd Renshaw of AMP Producte Ccrocration. Product Fngineer (Nomel Kmwevi Contract No: Subject discussed: Bending of PIDG*, Nuclear PIDG, PLASTI-GRIP *. or SOLISTRAND* . terminals n'rnm4 m -- n m ' MUM M , Uli m m mm s %D

  • Tradema rk nf AMP ine nrnnratad suMMAltY OF. DISCUSSION, DECl$lONS AND COMMITMENTS.

W. I. Vogelsang discussed the AMP memo dated September 2,1981*in which Mr. B. Eister. had indicated a 60* bend without reannealing was acceptable. It was discussed that with some suppliers at CPSES (GE Co in particular) that it was necessary to bend terminals for internal wiring up to 120. It was 'd., pointed out th'at for these cases, the application was for short jumpers 'd (normally under 18 inches), and as such, the full mechanical strength of the connector was not required. Floyd Renshaw responded that the current AMP position was that the subject teiminals could be bent one time to a 90* bend or two times to a 45* bend. However, this does not preclude. bending the terminals up to 120*. In this case, an Engineering evaluation for the specific type of application could be done by the product user. Items that should be taken into account are as follows: a) length of wire to be supported by the terminal b) the susceptibility to vibrations c) once installed if it is contemplated rebending these tenninals, they should be discarded and replaced by a new terminal. Floyd Renshaw also advised that while a terminal bent more that 90* to 120* would not retain its full' mechanical strength it would mainatin its electrical characteristics., V:dw' cc: ARMS % W L.M. Popplewell F. Harned/D.A. Wilkinson/F. Renshaw AMP Products Corporation Valley Forge, Pa. 19482 i _ __ _ _. _J

he I lhAK STEAM ELECTRIC STATION COMANCHE AS UT LITsES CENERATING CO. NONCONFORMANCE REPORT (NCR) E-9 4 - O lo lo (o '*) UNar STRUCTy A Er SYSTEM ITEM /CCMFCNENT TAG /iG NUMSER LOCATION OR ELEVAT:CN RI A NO. 59(3/ GSC '1A CM s ICle.' I f t/en, dor hr 5 IPl.FfMfcFAMR FLT51 Grn/Q3 h))O NCNCCNFOPMING CCNCITION 3 C5 A % O.DA,%R. e 60 % A. ZZ b fantrCAL 610Cl{ $0 $ f,yjirgr4 9 0i,g T e 2 PR J,4 )Y bd b3 u 8

p. s.

dL S P[.' NN - ] i OO Pev .3 _ AEFERENCE CCCUMENT. CAAA REPCRTED SY: CATE: Y M LL / / // JE REVIEW / APP 90 VAL: /2 CATE: Q. ~

CEPARTMENT

/ .>t u i 7 i Fc/ O ACTION AOCAESSEEj ToHEt /fDAf 2-A777 Y F&- S 6, I CISPOSITICN: AEWCAK REPAIR \\ USE AS IS SCAAP '}l/G c.t)fAEA1T* MANOFAff0262's Pc5t Th^J 15 THAT Te2+1 stALS MAY BE t$E V E. To $6" AAJO UP Tc 62d'.0 TT4 ova G A.k okitcei^% E '/ALLIADDAl & tr 26 1E dG D I .TNG FDLLosJIAJ6) TffhfiUAG IA) 00657:04J : ,nDU s .y TERM /04L &cc( 'G4M/4.14L PetAX [g nVil us BR 2,4 -? h W. 5.. D D (! El4 4 ~ <1 E

e. s.

i3 3 a $k ? o _1T I?> oVE VGTERMi AJAT)DAl WAT W6SE TERMitVALS- "Do uor esr2 A4 Q c SEC.Vic.GABit.i TT 1F'Cc 6 LC M PMD M M BC V5SD AS is. M' AMP TE9MtOAL,5 MAV6 SGGG LOSTALLED BY TM6 VEMDoQ., , SEE. ATTACWp c. PPA 38,7.4l, [ ) [ 4 ll fib $ ENG. REVIEW / APPROVAL o CATE: .,k &s .( OATE: CE REVIEW APPROVAL;. Y //1/ VY T MJ% u,y C CISPOSITICN VERIFICATICN & CLCSURE: CATE: / / CCMMENT3; )

CCMANC2I ?IAK STE.L". ELE G IC STATION NC2 :lo. GENERI.TDIC C3. NONCCNFORMANCI AEPORT (UC2) f:-$$-/OJ % l$ ?1ge. l oi / L* NIT [ STKUGI/S*lSTD1 ~TD'./ CCMPON DT TAC / D :,JMEER LCCATICN CE ILITAT:CN .U R NO. I farse 8waia4 a&st l$ Dapc3-% a. s,'f/ d & pf4 Wi r u ay y.g 30NCCNTCRitDC CONDI!!CN (y Qgf hY f kl$ N {0 SIS ~~ YYIS" WOSY l$ f04Qf $ s/Spd'& iM & I'9'- n

w L.

._.= 5= 0 .d. W & ':) * //*.5'" A l* PARA ).h.] b IETE3rDC OCCOtENT: IE7 RE?ORTI3 3Y: DATE: Y $&A/h /O t/O /( CE ?r/Irw*/A2?RCVAL: CA 5: u / / C" (C~lCN ACORESSEI OE2AgntE3T RE2CRT.utI InfDE?. tCC7EO.35(e): t-TIS NO RE7 Tir: 3Y:

a IF YES. RI?"fC': IDAR/ORR f 0 ISPOSCION:

?E4CFX RE?All '!CE M :S SCIA 2 u W v,s ud== E 5 ?o< DC. Kr/IEJ/AP?ROVAL DATE: / / qE Ar/IEb' APPROVAL: OATE: e / / { 7 Gt5PCSITION VERII!CATIOM L CLOSURE: CATI: i I / / \\ CO.T.DTS : I .}}