Rev 8 to Procedure QI-QP-11.3-28.7, Verify Proper Lug or Connector/Connection Type,Size & Final Crimps
ML20199E006
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 08/13/1982
From: Scott B
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
Shared Package
ML20199D912 List: ... further results
References
FOIA-86-36 QI-QP-11.3-28.7, NUDOCS 8606230158
Download: ML20199E006 (4)


Text

( 2 L ,

' INc.nUCTICN ISSUE TCCAS UT!UTIES GENERATING CO. NUMBER . MEVISICN CATE PAGs- .

CPsEs I

QI-QP-11.3-28.7 8 1 f3 M 13 W

PRESARED SY
Mh. b T- A 8(ted81 i VERIFY PROPER LUG OR , .

OfiE  !

CONNECTOR / CONNECTION  !

, APPROVED 3Y: / ,de //J / s. n: - p c. -

- TYPE, SIZE AND FINAL ~,  ; " , , _ ' ~_

CRIMPS i I

APPRCVED SY: .[ "

S?

0 ATE l l 1 L

1.0 REFERENCES

b' q i

! 1-A QI-QP-11.3-28, " Class IE Cable erminat<ons l i

1-B QI-QP-11.3-41, " Verify Soldering Electrical Connections" l

2.0 GENERAL 5 * , 6D 73}

'2h d f'  !

l l

2.1 PURPOSE AND SCOPE @k}, l'b 4{g Q ch

! The purpcse of thid idttYuc ion is to supplement Reference !l 1-A and to provide inspection criteria and technique for l l; i electrical QC personnel in the accomplishment of " Verify  ;,

Proper. Lug or Connector / Connection Type, Size and Final - i Crimp" inspections. l l 3.0 INSTRUCTIONS  !

I f 3.1 VERIFY PROPER LUG OR CONNECTOR / CONNECTION, TYPE AND SIZE l The QC Inspector shall visually inspect or witness (as

, required) . Class 1E cable terminations in accordance with l

! standard work practices and any applicable tennination

. manufacturer's recommendations and the following criteria: ,

a. Terminal lugs and connectors shall be compression solderless tin plated copper type, unless supplied by equipment manufacturer.
  1. All cables / wires shall be terminated in accordance with i Engineering approved drawings and/or vendor drawings. i I

l . Multipin connectors shall be assembled and verified in NY " accordance with the manufacturer's instruction ,'(see i QI-QP-11.3-28.17). l tuoco cA --

hh62 8 860609 GARDE 86-36 PDR L - ~ _ . . . _ - .. .____--.....m .- . . c a .-

1 h

t

.. p INSTRUCTION REVISION IO3N PAG l

U#'*

4 TEXAS UTIUTIES GENERATING CO.

~

CPSES i

[I-QP-11.3-28.7 q 8 l Aus 19 van, 2 of 3 i

d. The QC Inspector shall verify solder connections as delineated in Reference 1-B. -

! l 3.1.1 600 Volt Terminations (Power and Control)  ! j i

The criteria is as follows:

a. For 600V power and control cable sizes #8AWG and smaller, terminal lugs shall be insulated. For insulated terminals two (2) crimps, one shall be on the conductor and one on the insulation, per manufac-turer's reconnendations.
b. For 600V cable sizes #6AWG and larger, terminal lugs shall be uninsulated, tongue type having either two (2) bolt hole lugs or one (1) bolt hole lugs. One bolt hole lugs may be utilized when supplied by equipment vendor or whenever equipment has provisions for lugs with only one bolt hole.
c. For 600V cables sizes #6AWG through 500 MCM, compression  ;

, type terminal lugs shall be either short barrel lugs  !

with single cable compression indent or long barrel l type having two (2) cable compression indents.

d. For 600V cable sizes 750 MCM and larger the compression type tenninal lugs shall be the long barrel type having two (2) cable compression indents.

3.1.2 Instrument Cable and Thermocouple Wire Terminations l

l l e t Compression type tenninals shall not be used on thermo-  !

l l couple wire. Connections at instrument and reference j j l Junctions shall be made in accordance with the instrument ,

I manufacturer's recommendations. Wires will be looped I under screws in a clockwise direction.

I l l 3.1.3 8kV Terminations and Motor Connections l'

The criteria is as follows-I

a. Connectors used on all 8kV terminations and motor  :

connections will be those approved for use on 600Y  !

applications (see Section 3.1.1).  !

l I

l l l . l l 1 3

TUGCC oA .

-e nw .s see - - " @ .A,o, w , e g- , , ye Mth gQs y.n 3j me--. L

r.

I l INSTRUCTION REVISION ISSUE PAGE

, TEXAS UTIUTIES GENERATING CO.

CPSES 1 i 8' l AUG 131982 l 3 of 3 QI-QP-11.3-28.?  ; , l

b. 8kV tenninations shall be installed with RAYCHEM "N-HVT" terminations kits in accordance with the i manufacturer's reconnendations and detailed instructions.

(See QI-QP-11.3-28.16) .  !

l

c. For 8kV power cable (4/0 AWG and larger), one bolt hole lugs may be utilized when supplied by equipment '

vendor or whenever equipment has provisions .for lugs with only one bolt hole.

3.2 VERIFY FINAL CRIMP The QC Inspector shall visually inspect final crimps for attributes consistent with a quality installation. Care-ful attention should be focused on the following:

a. No conductor strands outside of Connector Barrel;
b. No " Splitting" evident on the Connector Barrel; I c. Conductor should be visible from the Inspection Hole i when lug has an inspection hole provided; l
d. Actual Crimps are located correctly; i e. Amount of Conductor between the Connector Barrel and the Insulation (refer to QI-QP-11.3-28.4);

I I

f. Excess material, indicating improper lug size;
g. No evidence of Connector insulation damage.

3.3 DOCUMENTATION Inspection results shall be documented on the Inspection j Report (Figure 1 of Reference 1-A) and fonvarded to the QC l 4

Supervisor or his designee for resolution.

l l

l I

T1JGCC oA

%g,

~

\ . j l_

TEXAS UTILITIES GENERATING COMhNY O F FI,C E M E M O R A N D U M Te Historical File men Itose. Texas subject Re-numberino/ Deletion of Procedures / Instructions l

This Procedure / Instruction Av.&9- //,3 af, J has been deleted as of this date.

i JuL M /s A --- -

7 g-n '

NJO (dn.cupeut&ce &r-se-u a-ar