3harles R. Ogle -Re: SATAUS OF HATCH SDP ITEM1S ON YOUR LIST -- Pg__

From: Charles R. Ogle /-7' To: Merzke, Daniel Date: 1/27/04 2:08PM

Subject:

Re: SATAUS OF HATCH SDP ITEMS ON YOUR LIST Yes -01 and -02 need tp be on your list. Also the corresponding NA items need to be included also.

>>> Daniel Merz e 01/27/04 01:17PM >>>

Thanks Chuck. My last update indicated URI-03-06-06 was being closed out. I don't have URI-03-06-01 listed on my matrix because when I read the inspection report, it indicated that it was still pending additional review, and not awaiting SDP, which is the criterion for making the list. If you'd like me to put it on, I will do so. Let me know.

Dan

>>> Charles R. Ogfe01/22/04 09:11AM >>>

Dan, I wanted to follow up on my previous e-mail regarding the hatch open items pending SDP.

Currently there are two URIs in the Fire Protection area which are open that will require SDP analysis.

They are:

50-366/03-06-01 URI Concerns Associated with Potential Opening of SRVs (Section 1R05.03.b) 50-366/03-06-02 URI Untimely and Unapproved Manual Operator Action for Post-Fire SSD (Section 1R.04/05.b.1)

Both of these issues deal with a vulnerability that exists in the routing of cabling associated with the SRVs at Hatch. As a result of this cable routing in certain scenarios SRVs can lift and endanger the licensee's safe shutdown. The first URI deals with the cable routing; the second deals with the licensee's manual actions taken in response to the potential vulnerability. Currently we are trying to determine if there is a credible fire scenario that could endanger the cables. The geometry of the equipment space is more involved than the models the inspectors have been provided. As a result the FP folks in HQ are running the proposed fire scenario through their more sophisticated model.

Please note that URI 03-06-06 is closed in the current report which is in routing for concurrence.

If there are any questions please let me know.

C:\TEMP\GW)0001.TMPI -- Paae1l

.r Mi E Mail Envelope Properties (4016B71D.739: 20: 51263)

Subject:

Re: SATAUS OF HATCH SDP ITEMS ON YOUR LIST Creation Date: 1/27/b4 2:08PM From: Charles R. Ogle Created By: CRO@nrc.gov Recipients Action Date & Time nrc.gov owf2_po.OWFNDO Delivered 01/27/04 02:08PM DXM2 (Daniel Merzke) Opened 01/28/04 07:38AM Post Office Delivered Route owf2_po.OWFNDO 01/27/04 02:08PM nrc.gov Files Size Date & Time MESSAGE 3104 01/27/04 02:08PM Options Auto Delete: No Expiration Date: None Notify Recipients: Yes

  • Priority: Standard Reply Requested: No Return Notification: None Concealed

Subject:

No Security: Standard To Be Delivered: Immediate Status Tracking: Delivered & Opened