{{#Wiki_filter:ENCLOSURE 5 SHEARON HARRIS NUCLEAR POWER PLANT NRC DOCKET NO. 50-400/LICENSE NO. NPF-63 REQUEST FOR LICENSE AMENDMENT MOTOR OPERATED VALVES THERMAL OVERLOAD BYPASS FUNCTION TE HNI AL PE IFI ATI N PA
{{#Wiki_filter:ENCLOSURE 5 SHEARON HARRIS NUCLEAR POWER PLANT NRC DOCKET NO. 50-400/LICENSE NO. NPF-63 REQUEST FOR LICENSE AMENDMENT MOTOR OPERATED VALVES THERMAL OVERLOAD BYPASS FUNCTION TE HNI AL PE IFI ATI N PA P'...
,
P'...
9404050268 940325
9404050268 940325
-PDR  ADOCK 05000400
-PDR  ADOCK 05000400

Latest revision as of 19:58, 3 February 2020

Proposed Tech Specs Eliminating Term 'Motor Starter' & Replacing W/More Accurate Description of MOV Bypass Configuration at Shnpp
ML18011A402
Person / Time
Site: Harris Duke Energy icon.png
Issue date: 03/25/1994
From:
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML18011A401 List:
References
NUDOCS 9404050268
Download: ML18011A402 (4)


Text

ENCLOSURE 5 SHEARON HARRIS NUCLEAR POWER PLANT NRC DOCKET NO. 50-400/LICENSE NO. NPF-63 REQUEST FOR LICENSE AMENDMENT MOTOR OPERATED VALVES THERMAL OVERLOAD BYPASS FUNCTION TE HNI AL PE IFI ATI N PA P'...

9404050268 940325

-PDR ADOCK 05000400

'DR Page E5-1

h I 4

' p I

t

1

~

~

ELECTRICAL POWER SYSTEMS ELECTRICAL E UIPMENT PROTECTIVE DEVICES

'MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION LIMITING CONDITION FOR OPERATION 3.8.4. 2 The thermal overload protection of each valve, specified in the Technical Specification Equipment List Program, plant procedure PLP-106, requiring bypass protection, shall be bypassed only under accident conditions by an OPERABLE bypass device.

APPLICABILITY: Whenever the motor-operated valve is required to be OPERABLE.

ACTION:

With the thermal overload protection for one or more of the above required valves not capable of being bypassed under conditions for which it is designed to be bypassed, restore the inoperable device or provide a means to bypass the thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, or declare the affecred valve(s) inoperable and apply the appropriate ACTION Statement(s) of the affected system(s).

SURVEILLANCE RE UIREMENTS 4.8.4.2 The thermal overload protection for the above required valves shall be verified to be bypassed only under accident conditions by an OPERABLE integral bypass device by the performance of a TRIP ACTUATION DEVICE OPERATIONAL TEST of the bypass circuitry.'

~ At least once per 18 months for those rhermal overloads which are normally in force during plant operation and are bypassed only under accident conditions', and

b. Following maintenance on the Hl srmal 'OVorloV bypass 08.14iiS gag C irc.'v liras, SHEARON HARRIS - UNIT 1 3/4 8"39 Amendment No.

ELECTRICAL POWER SYSTEMS ELECTRICAL E UIPMENT PROTECTIVE DEVICES MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION LIMITING CONDITION FOR OPERATION 3.8.4.2 The thermal overload protection of each valve, specified in the Technical Specification Equipment List Program, plant procedure PLP-106, requiring bypass protection, shall be bypassed only under accident conditions by an OPERABLE bypass device.

APPLICABILITY: Whenever the motor-operated valve is required to be OPERABLE.

ACTION:

With the thermal overload protection for one or more of the above required valves not capable of being bypassed under conditions for which it is designed to be bypassed, restore the inoperable device or provide a means to bypass the thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, or declare the affected valve(s) inoperable and apply the appropriate ACTION Statement(s) of the affected system(s).

SURVEILLANCE RE(UIREHENTS 4.8.4.2 The thermal overload protection for the above required valves shall be verified to be bypassed only under accident conditions by an OPERABLE integral bypass device by the performance of a TRIP ACTUATION DEVICE OPERATIONAL TEST of the bypass circuitry:

'a ~ At least once per 18 months for those thermal overloads which are normally in force during plant operation and are bypassed only under accident conditions; and

b. Following maintenance on the thermal overload bypass relays and circuitry.

SHEARON HARRIS - UNIT 1 3/4 8-39 Amendment No.