{{#Wiki_filter: | {{#Wiki_filter:CONTROLSYSTEMPOKERSUPPLYANDSENSORMALFUNCTION STUDYPreparedfor:Pennsylvania PowerandLightCompanySusquehanna SteamElectricStationPreparedby:EDSNuclearInesMarch,1982ReportNo.02-0160-1102 Revision1831018048i 831014PDRADOCK05000387P,PDR Il' ReportNo.02-0160-1102 Revision1hCONTROLSYSTEMPOWERSUPPLYANDSENSORMALFUNCTION STUDYTABLEOFCONTENTSSact1onPacae1.0Introduction 2'0Executive Summary3.0Methodology | ||
ReportNo.02-0160- | ==4.0 SummaryofResults50References== | ||
15Appendices AppendixATechnical Procedure forthePerformance oftheAnalysisAppendixBControlSystems/Safety Functions AppendixCControlSystemIdentification DiagramsAppendixDCommonality DiagramsAppendixEFailureModesandEffectsAnalysisAppendixFMalfunction AnalysisTables ReportNo.0201601102Revision0CONTROLSYSTEMPOWERSUPPLYANDSENSORMALFUNCTION STUDY1~0INTRODUCTION OnJune15,1981,Pennsylvania PowerandLightCompany(PPEL)requested thatEDSNuclearInc~(EDS)assisttheminresponding totheSafetyEvaluation Report(SER)itemconcerning thefailureofnon-safety gradecontrolsystemsduetofailure/malfunction ofpowersuppliesorsensordthatarecommontothesecontrolsytemsfortheSusquehanna SteamElectricStation(SSES)~Verification wasrequested toensurethatthesubjectcontrolsystemfailureswouldnotimpactonplantsafety.Theobjective oftheanalysiscontained hereinistwofold-1.Toidentifypowersuppliesandsensorstotwoormorenon-safety gradecontrolsystems.2.Toanalyzetheeffectsofthefailureormalfunction ofthesepowersuppliesandsensorsoncontrolsystemstodetermine iftheresulting plantconditions arecontained withintheboundaryofChapter15analysisandarewithinthecapabilities ofoperators andsafetysystems.Inordertoachievetheseobjectives, EDSemployedatwo-phase approachconsisting oftheIdentification PhaseandtheAnalysisPhase.IntheIdentification Phase,diagramsweregenerated toidentifythenon-safety gradecontrolsystemsandtheirpowersuppliesandsensors.Thesediagramswerefurtneranalyzedinordertodetermine thosecommonpowersuppliesandsensors.IntheAnalysisPhase,Failure"Modes andEffectAnalyses(FMEA)wasutilizedtodetermine theeffectsofthesepowersupplyandsensorfailuresontheirrespective controlsystemsand,ultimately, onplantperformances TheFMEAswerethenanalyzedtodetermine thesafetyimplications (ifany)forthefailureofthesecontrolsystems.Thisreportdocuments theresultofthisanalysis. | |||
Themethodology employedisdescribed generally inSection3'andingreaterdetailinAppendixA.Asummaryofresultsispresented ingeneraltermsinSection4.0andindetailinAppendices 3throughF.References areprovidedinSection5.0.AnExecutive SummaryisprovidedinSection2.0whichhighlights thesalientresultsofthisproject.C c2.0EXECUTIVE SUMMARYReportNo.02-0160-1102 Revision0Thepurposeofthisreportistodetermine ifthefailureofcommonpowersuppliesandsensorsfoznon-safety gradecontrolsystemswillimpactonplantsafety.Thiswasaccomplished byfirstidentifying thosecommonpowersuppliesandsensors,thenanalyzing theeffectsthosecontrolsystemfailuresonplantsafety.Inaddition, forthosecontrolsystemfailuresthatimpactedonplantsafetybutwerenotaddressed byChapter15analysisandwerenotwithinoperatorandsafetysystem'apabilities, recommendations forplantmodification orChapter15reanalysis weremade.Theprojectwasdividedintotwophases-theIdentification PhaseandtheAnalysisPhase~Intheidentification Phase,keyplantsafetyfunctions wereidentified usingChapter15.Thecontrolsystemsthatcouldaffectthesesafetyfunctions werethenidentified fromthoselistedinChapter7'7,"ControlSystemsNotRequiredforSafety."Thepowersuppliesandsensorsthatprovidepowerorsignalstothesecontrolsystemswereidentified'or thesekeyitems-safetyfunctions, controlsystems,powersupplies, andsensors-ControlSystemIdentification Diagrams(CSID)weregenerated todocumentthisinformation andtoassistinfurtheranalysis'ower supplyandsensorcommonality wasdetermined usingtheCSIDs.Aseconddiagram--Commonali tyDiagram(CD)--wasgenerated toshowthecontrolsystemsandtheirassociated components thatwereaffectedbyeachcommonpowersupplyorsensor.IntheAnalysisPhase,FailureModesandEffectsAnalysis(FMEA)wasperformed oneachcommonpowersupplyandsensortodetermine theeffectofthefailureonthecontrolsytemandonplantperformances Analysiswasthenperformed usingtheFMEAresultstodetermine thefollowing: | |||
l.Impactonplantsafetyincluding plantresponseasperChapter15.2.Iftheplantconditions werewithinoperatorandsafetysystemcapabilities asperChapter15~Forthoseconditions thatdidnotmeetthecriteriaofitems{l)and{2),recommendations forplantmodifications orChapter15reanalysis wereprovided. | |||
ReportNo~02-0160-1102 Revision12.2ResultsAtotaloftenpowersupplyandsensorcommonalities wereidentified andanalyzed. | |||
Ofthesetencommonalities< | |||
n-'ne(9)'wereofthepowersupplytypeandone(1)wasoftnesensortype.1.Thefailureofpowersupply1D635125VDCthatiscommontotheReactorFeedwater ControlSystemand.Pxessure Regulator andT/GControlSystemresultedinplantconditions thatmaynotbeboundedbyChapter15analysis. | |||
Thecondition isgenerated byamaximumdemandsignalfromtheFeedwater SystemduetoazeroflowsignalfromtheBtrainflowsensorinstrumentation beingprocessed bytheFeedwater Systemonlossofthepowersupply.ThispowersupplyalsopowerstheReactorFeedPumpTurbineCtripcixcuit.Ifthereactorvesselhighleveltripsetpointisreachedinthismaximumfeeddemandsituation, RFPTsAandBwilltrip;RFPTCwillcontinuetooperateduetothetripcircuitfailure.Itshouldbenotedthatdataisnotcurrently available toverifythattheLevel8txippointwillbereached.EDS,therefore, recommends thattheappropriate instrument perfoxmance bereviewedandtransient analysisbeperformed toverifythecondition exists.IftheLevel8tripisnotreached<theconditions generated bythefailureof1D635areboundedbyChapter15analysis. | |||
Ifitisdetexmined thattheLevel8trippointisreached,EDSrecommends thataplantmodification bemadetoprovidedifferent powersuppliesfortheBtrainfeedflowinstrumentation andtheReactorFeedPumpTurbineCtripcircuit.Asanalternate | |||
: solution, EDSrecommends thatthemaximumfeeddemandcondition inChapter15bereanalyzed tovexifythatthefailureofthefeedpumptotripis,infact,boundedbycurrentChapter15analysis. | |||
2~Allothercommonpowexsupplyandsensorfailuresweredetexmined tobeeitherboundedbyChapter15analysisandwithinoperatorandsafetysystemcapabilities ortonotimpactplantsafety.Detailedanalysisdocumenting theresultsiscontained inSection4.0andAppendices BthroughF. | |||
El ReportNo.02-0160-1102 Revision03~0METHODOLOGY Asindicated intheintroduction, themethodology thatwasutilizedbyEDSforthisprojectwasdesignedtomeetthefollowing objectives: | |||
1.Toidentifypowersuppliesandsensorstotwoormorenon-safety gradecontrolsystems.2.Toanalyzetheeffectsofthefailureormalfunction ofthesepowersuppliesandsensorsoncontrolsystemstodetermine iftheresulting plantconditions arecontained withintheboundaryofChapter15analysisandarewithinthecapabilities ofoper'ators andsafetysystems'he methodology employedtoachievetheseobjectives issummarized inthissection.Adetaileddescription ofthismethodology iscontained inAppendixA,"Technical Procedures forthePerformance oftheAnalysis. | |||
"Atwo-phase approachwasusedaspartofthismethodology. | |||
Phase1,the"Identification Phase,"consisted ofidentifying thefollowing items:Plantsafetyfunctions ControlsystemsPowersuppliesandsensorstothecontrolsystemsPowersuppliesandsensorscommontocontrolsystemsPhase2,the"Analysis Phase,"consisted oftheanalysisofthefailureofthesecommonpowersuppliesandsensorswithrespecttotheirassociated controlsystems.Thecontrolsystemfailureswereanalyzedwithrespecttothefollowing criteria: | |||
PlantresponseasperChapter15Plantconditions withinoperatorandsafetysystemcapabilities Reanalysis ormodifications requiredtocorrectanyproblemsnotcoveredbythefirsttwocriteria3.1Identification PhaseThefirstpartoftheidentification phaseconsisted ofidentifying thenon-safety gradecontrolsystemsthatcouldimpactplantsafety.Inordertoaccomplish this,itwasfirstnecessary toidentifythoseplantsafetyfunctions thatarerequiredtobemetduringthevariousmodesofplantoperation. | |||
Thesafetyfunctions weregenerated usingChapter15,Appendix15AoftheCESAR.Theplantoperating modesandsafetyfunctions wereaddedtotheControlSystem ReportNo.02-0160-1102 Revision0Identification Diagrams(CSIDs).Thesediagramscontainalltheidentification information requiredtodetermine commonality withrespecttopowersuppliesandsensors-Subsequent tosafetyfunctionidentification, thecontrolsystemswhichcouldaffect.thesesafetyfunctions wereidentified. | |||
Thesecontrolsystemswereselectedfromthelistofnon-safety gradecontrolsystemsprovidedinChapter7'oftheFSAR.ThecontrolsystemswerethenaddedtotheCSIDs.Thepowersuppliesandsensorsrequiredtosupportthesecontrolsystemswereidentified andaddedtotheCSIDs-Thepowersupplyidentification alsoincludedtheCascading PowerSupplyEffect,thatis,thepotential forfailureofhigherlevelpowersuppliesduetofailureofacorresponding lowerlevelpowersupply'he boundaryofthecascading effectwaslimitedtothe120VACand125VDCinstrument andcontrolbuses.Thisboundarywasbasedoninformation providedbythePPSLElectrical Groupconcerning crediblehigherlevelpowersupplybusfailures. | |||
CSIDsareshowninAppendixC.Thefinal.partoftheidentification phasewastodetermine whichpowersuppliesandsensorswerecommontomorethanonecontrolsystem.Thiscommonality wasaccomplished usingtheCSIDs.Eachcommonpowersupplyandsensornotedwasthenusedasthefocalpointofaseconddiagram-Commonality Diagram(CD)~Thisdiagrampresented thecommonpowersupplyorsensor,thecontrolsystemsaffected, andthekeycomponents andcircuitsthatarepartofthesecontrolsystems~CDsareshowninAppendixD.'.2AnalsisPhaseThemethodology employedintheanalysisphaseconsisted oftwoparts:FailureModesandEffectsAnalysis(FMEA)andMalfunction Analysis. | |||
TheFMEAtechnique wasusedtogeneratefailureeffectsinformation oneachcontrolsystemasitpertainstoitscommonmode.powersupplyorsensorfailure.Usingtheinformation fromtheCDs,theoveralleffectofthepowersupplyorsensorfailurewasdetermined withrespecttocontrolsystemandplantperformance. | |||
Theresultsofthispartoftheanalysisweredocumented onFMEAformsascontained inAppe'ndix E.Malfunction analysiswasthenperformed usingtheFNEAstodetermine iftheplantconditions generated impactedonplantsafetyandwerewithinthecapabilities ofoperators andsafetysystems.Theconditions generated asperthe ReportNo.02-0160-1102 Revision0PMEAswerecomparedwithChapter15analysisforverificationofplantresponse, operatorresponse, andsafetysystemresponseForthoseplantconditions inwhichplantsafetywasimpactedwithoutappropriate Chapter15analysisandoperatorandsafetysystemcapability verifications, systemmodifications orChapter15analysisrecommendations wereprovided. | |||
ThetablesinAppendixFwereusedasatooltodocumentthemalfunction analysis. | |||
Thisinformation wasthensummarized intheresultssectionofthisreport. | |||
ReportNo.02-0160-1102 Revision0.4.0SUMMARYOFRESULTSThepurposeofthiseffortwastodetermine ifthefailureofcommonpowersuppliesandsensorsfornon-safety gradecontrolsystemscouldimpactonSSESplantsafety.Theresultsofthiseffortaredividedintotwomajorareas:Identification ofkeyelementsControlsystemsthatcouldimpactplantsafetyPowersuppliesandsensorstothesecontrolsystemsCommonpowersuppliesandsensorsforthesecontrolsystems2.AnalysisofcontrolsystemfailureReferenced totheFSAR-Chapter15Withincapabilities ofoperatorandsafetysystemsRecommendations forreanalysis ormodification ifrequiredThissectionprovidesasummaryoftheresultsdetermined byEDSwithrespecttoeachofthetwomajorareas'moredetaileditem-by-item listingoftheresultsiscontained inAppendices BthroughF.4.1Identification Priortoperforming theanalysisonthesubjectcontrolsystemfailure,itwasnecessary tofirstdetermine whichofthoseSSESnon-safety gradecontrolsystemcouldimpactplantsafety.Basedontheplantsafetyfunctions foreachplantoperating modeasdescribed inChapter15andthecontrolsystemsdescribed inChapter7',"ControlSystemNotRequiredforSafety,"thecontrolsystemsthatcouldimpactplantsafetyweredetermined anddocumented asfollows:1~2.3.4,~5.6.~7~8.9~ReactorManualControlSystemRecirculation FlowControlSystemReactorFeedwater ControlSystemPressureRegulator andTurbineGenerator ControlSystemTraversing In-CoreProbeControlSystemReactorWaterCleanupControlSystemRefueling Interlock ControlSystemRodBlockMonitorSystemNuclearPressureReliefControlSystemItshouldbeemphasized thatthislistincludesthosecontrolsystemsthatcouldimpactplantsafety.Actualdetermination ofthosecontrolsystemsthat,infact,doimpactplantsafetywouldbeaccomplished duringthe ReportNo.02-0160-1102 Revision1analysisphaseoftheproject-Documentation ofthesafetyfunctions andcontrolsystemsiscontained intheControlSystemIdentification Diagrams(CSIDs)inAppendixC.BasedonthecontrolsystemscopeasdefinedinChapter7.7,thepowersuppliesandsensorsthatsupporteachofthesecontrolsystemswereidentified. | |||
Thepowersuppliesidentified werethosespecific120VACand125VDCinstrument andcontrolpowersupplies. | |||
Thesensorsidentified werethosesensorsthatprovideinputsintothecontrolsystem.Detaileddocumentation ofthesepowersuppliesandsensorsisalsocontained intheCSIDs.Intheprocessofidentifying controlsystempowersupplies, theCascading PowerSupplyEffectwasalsoadd"essed. | |||
Basedonastudyperformed bythePPGLElectrical Group,itwasdetermined thattheonlycrediblecascading powersupplyfailurepossibleatSSESwasthatcombination of1Y218and1Y219120VACbuses.Thesearetheonlytwoinstrument andcontrolpowersuppliesthatwouldbesubjecttothecascading effectbasedonthedesignoftheSSESelectrical distribution system.Allotherpowersuppliesatahigherlevelarebackedupbyeitheranalternate ACsourceorabattery.Uponcompletion ofthepowersupplyandsensoridentification, powersupplyandsensorcommonality wasdetermined. | |||
Commonality Diagrams(CDs)weregenerated toshowcommonality betweenthosecontrolsystemsidentified. | |||
Atotaloften(10)commonalities weredetermined. | |||
Thesecommonalities formthebasisfortheanalysisphaseoftheproject.TheCDsarecontained inAppendixD.4.2AnalysisTheanalysisofthecontrolsystemsthatcontained commonpowersuppliesandsensorswasaccomplished usingFailureModesandEffectsAnalysis(BREA),thenanalyzing theoverallimpactofeachsystemFMEAontheplant.TheFMEAsweregenerated foreachcontrolsystemasitpertainstothecommonpowersupply.orsensor.ThedetailedresultsofeachFMEAarecontained inAppendixE.BasedontheBKAs,thedetailedanalysisofthesecontrolsystemswasperformed. | |||
Theresultsarepresented hereintwocategories: | |||
(1)Failuresthatcouldimpactplant'afetyrequiring furtheranalysis, and(2)failuresthatcouldimpactplantsafetyaddressed byChapter15/failures thatdonotimpactplantsafety. | |||
ReportNo.02-0160-1102 Revision11.FailuresThatCouldImactPlantSafetReirinFurtherAnalysisEDSanalysisdetermined thatfailureofthepowersupply1D635125VDCcouldimpactplantsafetyandtherefore requiresfurtheranalysis. | |||
ThecontrolsystemsaffectedbythispowersupplyfailurearetheReactorFeedwater andthePressureRegulator andT/GControlSystems.Theconditions thatmaynotbeboundedbyChapter15analysisare,however,isolatedtotheFeedwater Systemonly-specifically theFeedwater FlowControlandReactorFeedwater PumpTurbine(RFPT)TripContxolsub-systems. | |||
Thelossofthispowersupplydoesnotgenerateconditions outsideoftheboundaryofChapter15analysisforthePressureRegulator andT/GControlSystem.Basedondatacurrently available, thesequenceofeventsthatresultfromthelossofthispowersupplyfortheFeedwater Systemisasfollows:a.HM.leoperating at100%reactorpower,theplantexperiences alossof1D635.Thefeedwater flowsignalfromtheBtraininstrumentation poweredby1D635(FlowTransmitter FTlN002BandSRU6)changestozeroduetothelossof1D635-Sincethefeedwater flowsignalsfromtrainsA,BandCazesummed,thetotalfeedflowsignalchangesfrom100%feedflowto67%feedflowsubsequent toreceiving theerroneous zerosignalfromtheB,train.Thisintroduces amismatchbetweensteamflow,whichisstillat100%,andfeedflowwhichisat67%.b.Inresponsetothissteamflow,feedflowmismatch, theFeedwater FlowContxolSystemsendsasignaltothethreeRFPT'stoinczeasefeedflowtomakeupfortheerroneous 33%decxeaseinflow.Actualfeedflowatthispointwouldbeapproximately 135%.cdSinceactualfeedflowissignificantly greaterthanthatrequired, theincreaseinreactorvessellevel~marea'chtheLevel8(highlevel)'tripsetpoint~d-IftheLevel8tripsetpointisreached,atripsignalwillbesenttoRFPTsA,B,andCandtheT/G.RFPTsAandBandtheT/Gtrip.RFPTCfailstotripbecauseitstripcircuitwasdisableduponlossof1D635. | |||
ReportNo~02-0160-1102 Revision1Basedontheassumption thattheLevel8setpointisreachedduetoexcessive feedwater demand,theresulting conditions arenotexplicitly addressed byChapter15-Chapter15statesthattheplantresponsetoaLevel8condition, initiated byexcessfeedflow,shouldincludethetripofallRPPTsandtheT/G.Sincetheconditions generated subsequent tothefailureofRPPTCtotriparenotknown<itcannotbedetexmined iftheplantsystemcapabilities areadequateusingpresentChapter15analysis. | |||
TheoperatordoesretaintheabilitytotakemanualcontroloftheRPPTCtomitigatetheeffectsofitscontinued operation. | |||
TheoperatorwouldbealertedtotherisingreactorvessellevelbytheLevel7alarm.Thiscondition, therefore, appearstobewithinthecapabilities oftheoperator. | |||
Xnordertoresolvethisproblem,EDSrecommends that,first,ananalysis(thermalhydraulic andinstrument) beconducted toverifythattheLevel8setpointwillbereached,basedonthesequenceofeventspreviously postulated. | |||
ZftheresultsofthisanalysisverifythattheLevel8setpointisnotreached,thentheconditions generated bythelossofpowersupply1D635125VDCareinfactboundedbyChapter15analysis'f theLevel8setpointisreached,thentheresulting conditions requirefurtheranalysis. | |||
Porthoseconditions notexplicitly addressed byChapter15analysis, EDSrecommends resolution ofthisproblembeaccomplished inoneoftwoways.Aplantmodification couldbemadetoremovethecommonality betweenthefeedwater flowBprocessinstrumentation (PlowTransmitter andSRU)andtheRPPTCtripcircuit.BasedonEDSfailuremodesandeffectsanalysis, changingtheseinstruments toanalternate powersupplywouldresolvethisproblem.1D615andXD625shouldbeeliminated asalternatives sincetheyprovidepowertotheRPPTAandBtripcircuits, respectively. | |||
EDSrecommends thattheBtraininstruments bemovedtotheACpowersupplythatiscurrently providing powertothePeedwater PlowControlSyst:em-1Y218Breaker13.Theappropriate conversion deviceswouldalsohavetobeaddedinordertoaccountforthechangeover oftheseinstruments fromDCtoAC.Movingtheseinstruments tolY218wouldnotchangetheoveralleffectontheFeedwater PlowControlSystemsubsequent tothelossoflY218-Thesystemeffectsandplantresponseasnotedinthe1Y218PMEAwouldremainthesame~-10 ReportNo-02-0160-1102 Revision1Ztshouldbenotedthatifanypowersupplyotherthan1Y218isselected, theappropriate FailureModesandEffectsAnalysisshouldbeperformed toensurethatanewproblemisnotcreated.Thesecondmethodofproblemresolution wouldbetoanalyzetheconditions generated bythecontinued operation ofRFPTCtoverifythattheplantsystemswill<infact,mitigatetheprobleminspiteofthisnewcondition. | |||
2.FailuresThatZmctPlantSafetyAddressed byChater15/Failures ThatDoNotImpactPlantSafetyTheremaining nine(9)controlsystemcommonalities havebeendetexmined byEDStobeeith'eraddressed byChapter15ortonotimpactplantsafety.Norecommendations foxmodification oranalysisarerequired. | |||
Eachoneissummarized asfollows:a.1D615125VDCThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Control,PressureRegulator | |||
-T/GControl,andRecirculation FlowContxol.Theonlyplantsafety-related condition generated bythisfailureisalossofrecirculation flowinLoopAandarecirculation runbackinLoopB.Thiscondition andtheplantresponseiscoveredbyChapter15analysis. | |||
Thiscondition isalsowithinthecapabilities oftheoperator. | |||
Znaddition< | |||
safetysystemresponseisnotrequixed. | |||
b1D625125VDCThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Control,PressureRegulator | |||
-T/GControl,Recirculation FlowControl,andtheTraversing Zn-CoxeProbe.Theonlyplantsafety-related condition generated bythisfailureisalossofrecirculation flowLoopB.Thiscondition andtheplantresponseforsingleloopflowarecoveredbyChaptez15analysis. | |||
Thiscondition isalsowithinthecapabilities oftheoperator. | |||
Inaddition, safetysystemresponseisnotrequired-ReportNo.02-0160-1102 Revision0C~1D645125VDCThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Controland'ressure Regulator | |||
-T/6Control.Theonlyplantsafety-related condition generated bythisfailureisapotential highreactorvessellevelduetothefailureoftheFeedwater Blevelsensor..Thisfailurecombinedwithmaximumfeedwater flowdemand(worstcase)isaddressed inChapter15.Thisvesselhighlevelcondition iswithinoperatorcapabilities sincemanualcontroloftheReactorFeedwater ControlSystemisstillavailable. | |||
ThesafetysystemsthatrespondperChapter15forthiscondition possessthenecessary capabilities tomitigatetheproblem.'d~lY218120VACThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Contol,ReactorManualControlRecirculation FlowControl,PressureRegulation | |||
-T/6Control,ReactorWaterCleanup,NuclearPressureRelief,andTraversing'n-Core ProbeTheplantsafetycondition generated bythisfailureisapotential highorlowreactorvessellevelresulting fromtheFeedwater ControlSystemfailingatmaximumorminimumdemand.Thefailureofthispowersupplyinvolvesa"speedfreeze"ofthereactorfeedwater pumpturbines(RFPT)~A"speedfreeze"meansthattheRFPTspeedislockedinattheratethatwaspresentpriortothelossofpower.Thisspeedfreezeatmaximumorminimumdemanddirectlyleadstoahighorlowwaterlevel,respectively. | |||
Theplantresponsetothemaximumorminimumfeedflowdemandisaddressed inChapter15.Inthemaximumdemandcondition, aLevel8tripwillresult,eventually leadingtoRFPTtrip,T/6trip,reactorscram,recirculation pumptrip,andHPC1'/RCIC actuation. | |||
Theminimumdemandcondition condition, asperChapter15,willresultinaplantresponseofaLevel3tripfollowedbyaLevel2trip~Thisresultsinareactorscram,recirculation pumptrip,MSIVclosure,T/6trip,andHPCI/RCIC actuation. | |||
12 | |||
ReportNo.02-0160-1102 Revision0Themaximumandminimumdemandconditions arewithinoperatorcapabiliti'es. | |||
ThesafetysystemsthatrespondperChapter15fortheseconditions possessthenecessary capabilities tomitigatethisproblem.Itshouldbenotedthatalthoughthecondition generated inbetweenmaximumandminimumfeedflowdemandisnotsafetyrelated,itpreventschangesfrombeingmadeontheReactorManualControl,ReactorFeedwater Control,andtheRecirculation PlowControlsystems'pon lossofpower,eachofthesesystemsremainsintheconfiguration itwasinpriortothelossofpower.Specifically, rodscannotbemovedandfeedwater andrecirculation flowcannotbealtered.Thiscondition isnotbeyondoperatorcapabilities, butshouldbeconsidered whenPPSLisgenerating planttrainingoroperating procedures. | |||
e.1Y219.120VACThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorManualControlSystemandtheReactorWaterCleanupSystem.Therearenoplantsafety-related conditions associated withthelossofthispowersupply;therefore, noChapter15analysisisrequired'perator orsafetysystemresponseisnotrequired. | |||
1Y226120VACgoThecontrolsystemsinvolvedwiththispowersupplyfailurearetheNuclearPressureReliefSystemandtheReactorWaterCleanupSystem.Therearenoplantsafety-related conditions associated withthelossofthispowersupply;therefore, noChapter15analysisisrequired. | |||
Operatororsafetysystemresponseisnotrequired. | |||
1Y629120VAC1ThecontrolsystemsinvolvedwiththispowersupplyfailurearethePressureRegulator | |||
-T/6Control,TheanalysisforlY629failureisbasedonT/6solenoidvalvesfailing"asis."Thisassumption hastobemadeduetoalackofspecificreference information. | |||
13 ReportNo.02-0160-1102 Revision0theReactorManualControlSystem,'andthe~Recirculation FlowControlSystem.Theconditions associated withthispowersupplyfailureareaT/6tripatlessthan30%poweroraT/6tripandreactorscramatgreaterthan30%power..Theplantresponseforeithercondition iscoveredbyChapter15analysis'oth theT/6tripandthereactorscramarewithinoperatorcapabilities. | |||
These.conditions arealsowithinthecapabilities ofthesafetysystems,including Scram,,HPCI, | |||
'andRCIC,asperChapter15.Feedwater FlowElements-FElNOOlA,B,CThecontrolsystemsinvolvedwiththissensorfailurearetheReactorFeedwater ControlandtheRecirculation Control~Theplantsafetycondition generated bythisfailureisapotential highorlowreactorvessellevelresulting fromtheFeedwater ControlSystemfailingatmaximumorminimumdemand.Thisfailureiscausedbyonefeedwater flowelementfailingsuchthateitherahighfloworlowflowsignalisgenerated. | |||
Theplantresponsetothemaximumorminimumfeedflowdemandisaddressed inChapter15.Inthemaximumdemandcondition, aLevel8tripwillresult,eventually leadingtoRFPTtrip,T/6trip,reactorscram,recirculation pumptrip,andHPCI/RCIC actuation. | |||
Theminimumdemandcondition condition, asperChapter15,willresultinaplantresponseofaLevel3tripfollowedbyaLevel2trip~Thisresultinareactorscram,recirculation pumptrip,MSIVclosure,T/6trip,andHPCI/RCIC actuation. | |||
Themaximumandminimumdemandconditions arewithinoperatorcapabilities | |||
~Thesafetysystems-thatrespondperChapter15fortheseconditions possessthenecessary capabilities tomitigatethisproblem.Itshouldbenotedthataflowelementfailurecausedbyamechanical problem(i.e.,cloggingatthesensinginletoroutlet)wouldtakeplaceoverarelatively longperiodoftimeFlowdegradation shouldbenotedthroughroutineflowindication monitoring'4 ReportNo.02-0160-1102 Revision0i.CascadinPowerSu1Effect-lY218and1Y219120VACInanalyzing theSSESelectrical distribution system,itispossiblethatafailureinpowersupply1X219couldcausepowersupply1Y218tofail,aswell,sinceitsuppliespowertolY219.Thefailureofahigherlevelpowersupplyduetoafailureofacorresponding lowerlevelpowersupplyisdefinedastheCascading PowerSupplyEffect.ThecombinedfailureoflY218and1Y219doesnotinvokeconditions notalreadycoveredintheanalysisofeachofthesepowersuppliesinsub-paragraphs (d)and(e)respectively. | |||
Thiscombinedfailureis,therefore, boundedbyChapter15analysisandwithinthecapabilities oftheoperatorandsafetysystems.Nootheranalysisisrequired. | |||
15 | |||
. | . | ||
==5.0REFERENCES== | ==5.0REFERENCES== | ||
ReportNo.02-,0160- | ReportNo.02-0160-1102 Revision0Thefollowing isthelistofreferences usedduringthisproject:5.1GeneralInformation Susquehanna SteamElectricStation,Units1and2,FinalSafetyAnalysisReport,Pennsylvania PowerandLightCompany,Volumes1-17,Revision23,6/81.5'SstemDescritiveReferences ReactorFeedwater ControlSstemInstruction Manuals4110and4125,Alphaline PressureTransmitters AbsoluteandGage,Models1151APand1151GP,Rosemount. | ||
2~3.5.6.7~8.Indicating | |||
: Switches, LiquidLevel-Differential Pressure-Plow Rate,Product/Bullet, in288A/289A, ITTBarton.BaileyServiceManual,Type771NarrowRollStrip-Chart Recorder(4577Kll-300A) | |||
BaileyPartsManual,Type771,772,and773Strip-Chart Recorders, (4577Kll-350) | |||
~Operating andInstruction Manual,StaticInverterModelN250-MRS-125-60-115, TopazElectronics, October1974.Information aboutthe(OrificePlate)BoreCalculation, Vikery-Simms, Inc.,VSIJobNo~-N-1053andN-1175.OrificeBoreCalculation LiquidFlow,Vike~-Simms, Inc.,2/23/76.PressureSwitchesPartsPriceList,Code1BourdonTube,Barksdale (Bulletin No.671221-B), | |||
January1,1973.9.BaileyServiceManual,Type745SingleandDualAlarm,.(4574K15-300F | |||
)~.10~BaileyServiceManual,Type754FunctionGenerator, (4575K14-300A). | |||
llewBaileyInstallation Manual,Type754FunctionGenerator, (4575K14-001). | |||
ReportNo'.02-0160-1102 Revision012~BaileyInstructions, Type760001VoltageSignalSources,(4576K10-001). | |||
13'aileyServiceManual,755DynamicCompensator, (4575K15-300B). | |||
14..Bailey Difference Data,Type755DynamicCompensator Cat~No~50-755010AAAA1NAB (4575K15-003). | |||
15~16.BaileyInstallation Manual,Type701BasicController, | |||
(.4570K11-001A). | |||
Susquehanna 1,Operations andMaintenance Instructions, Feedwater ControlSystem,GeneralElectric(GEK-73592A), | |||
April,1981.Recirculation FlowControlSstem2.3.4~5.7~8.9~10.Susquehanna 1,Operations andMaintenance Instructions, | |||
.Recirculation FlowControlSystem,GeneralElectric(GEK-73590), | |||
: February, 1979.BaileyServiceManual,Type724LogicUnit,(4572K14-300B). | |||
BaileyInstallation Manual,Type745SingleandDualAlarm,(4574K15-001A). | |||
BaileyServiceManual,Type745SingleandDualAlarm,(4574K15-300F). | |||
BaileyInstallation Manual,Type752TwoInputandFourInputSummers,(4575K12-001B) | |||
.Installation andOperating Instructions, Regulated DCPowerSupplies, GeneralElectric(GEI-54440). | |||
BaileyInstallation Manual,Type744Difference Alarm,(4574K14-001). | |||
BaileyInstallation Manual,Type720UtilityStations, (4572K10-001)- | |||
BaileyServiceManual,Type720UtilityStations, (4574K10-300). | |||
BaileyInstructions, Type766SignalResistorUnitsCat~No.766--*,(4576K16-007A). | |||
17 ReportNo.02-0160-1102 Revision012.13'4.15~BaileyInstallation Manual,Type724LogicUnit,(4572K14-001). | |||
BaileyInstallation Manual,Type740Millivolt Converters, (4574K10-001A). | |||
BaileyServiceManual,Type723Proportional andDelayUnit,(4572K13-300). | |||
BaileyInstallation Manual,Type723,Proportional andDelayUnit,(4572K13-001) | |||
.BaileyInstallation Manual,,Type746SignalLimiter,(4574K16-001A)- | |||
16'BaileyInstallation Manual,Type722ManualUnit,(4572K12-001). | |||
17'8.19~20.21.22.23.24.BaileyServiceManual,Type722ManualUnit,(4572K12-300A). | |||
BaileyInstallation Manual,Type721ControlUnit,(4572K11-001). | |||
BaileyServiceManual,Type721ControlUnit,(4572K11-300). | |||
ACRPanels120/125Vand24VFeederTabulation, Susquehanna Project,BechtelPowerCorporation, Electrical SchemeGroup,June22,1981.Instructions forOperation, Installation, Maintenance, andCalibration, Electronic FlowTransmitter 73G-0049M, Ametek/Schutte sKoerting(74S-0269M-001), | |||
July,1974.I'nstruction Manual,(4104/4126) | |||
Model1151DPAlphaline, Differential andHighDifferential PressureTransmitters, Rosemount (8856-J03-A-25-1). | |||
BaileyServiceManual,Type751Sealer,(4575K11-300F). | |||
IEEEGuideforGeneralPrinciples ofReliability AnalysisofNuclearPowerGenerating StationProtection Systems,IEEEStandard352-1975. | |||
ReactorWaterCleanuSstemSusquehanna 1,Operation andMaintenance Instructions, ReactorWaterCleanupSystem,GeneralElectric(GEK-73608), | |||
February1979.18 Repox'tNo.02.-0160-1102 Revision0PressureReulatorandT/GControlSstemGenerator Protection, GeneralElectxic(GEK-75512A), | |||
: November, 1980.2~3~4~5.7~8.9-10.BasicFunctions ofElectrohydraulic Control(EHC)System,Nuclear(BoilingWaterReactor)Units,GeneralElectric(GEK-17911) | |||
~Protection System-Electrohydraulic Control,BasicFunctions, GeneralElectric, (GEK-11366). | |||
SpeedControlUnit,(Fossil-Baseload, BWR,PWR),GeneralElectric(GEK-11381E). | |||
tInstructions, EHCLineSpeedMatcher,GeneralElectric(GEK-17910A) | |||
~Instructions, Description ofLoadControlUnit(BWR),GeneralElectric, (GEK-37946). | |||
LoadControlUnit,LoadReference | |||
: Circuits, NuclearUnits,GeneralElectric(GEK-17864A). | |||
Instructions, LoadLimitCircuitsandLogic,(BWR),GeneralElectric,'(GEK-17863B) | |||
~Instructions, Chest/Shell WarmingCircuitsandLogic,3or5LightConfiguration, Nuclear-BWR, GeneralElectric, (GEK-46351B) | |||
.Rosemount PressureTransducer Model1104A,(GEK-37803). | |||
12-13~14-15~CurrenttoVoltageConverter, GeneralElectric, (GEK-25580). | |||
Instructions, RateSensitive PowerLoadUnbalance CircuitandRelays,(Nuclear), | |||
.GeneralElectric, (GEK-37959A). | |||
FlowControlUnit,GeneralElectric, (GEK-25588). | |||
ValveTestLogic,(BWR),GeneralElectric, (GEK-37941) | |||
.Pressux'e ControlUnit,(BWR),GeneralElectric, (GEK-17885A) | |||
~16.TurbineInitialPressureRegulator andControlSystem,BypassControlUnit,GeneralElectric,; | |||
(GEK-17880). | |||
19 | |||
ReportNo.02-,0160-1102 Revision017.18.19.20.21'urbineInitialPressureRegulator andControlSystem,Automatic LoadFollowing Signal,GeneralElectric, (GEK17881)~Automatic PressureSet-Point Adjust,GeneralElectric, (GEK-17882A). | |||
Instructions, ElectricAlarmandTripSystem,GeneralElectric, (GEK-11367C) | |||
.FirstHitCircuitry, GeneralElectric, (GEK-25557) | |||
.ProtectiveSystem-Electrohydraulic Control,BasicFunctions, GeneralElectric, M-392,1971.22.ElectricAlarmandTripSystem,GeneralElectric, M-3931971.23.Electrical PowerSupplies, GeneralElectric, M-399,1971.24.25.26.27.Instructions, TestingoZtheOverspeed TripSystem,GeneralElectric, (GEK-11383C). | |||
BackupOverspeed Trip,Electrohydraulic ControlSystem,GeneralElectric, (GEK-17978A). | |||
Instructions, Electrical PowerSupplies, EHCSystem,GeneralElectric, (GEK-25540A). | |||
Instruction ManualandPartsListModel730and751SeriesLiquidLevelControls, Bulletin: | |||
46-612,Magnetrol International, April1976.Traversin In-CoreProbeSstem2.3.Preliminary, Susquehanna 1and2,Operation andMaintenance Instructions, Traversing In-CoreProbeCa'libration System,GeneralElectric(GEK-73601A), | |||
February1981.Operation andMaintenance Instructions, IndexingMechanism 791E241G4 (GEK-73601A), | |||
February1981.Operation andMaintenance Instructions, DriveMechanism 706E263G13, G14,G15,andG16,GeneralElectric(GEK-39600D), | |||
March1980.20 ReportNo.02-0160-1102 Revision04..Operation andMaintenance Instructions, ValveControlMonitor112C3706G8, G10,andG12,GeneralElectric(GEK-34668D), | |||
February1980.5.Operation andMaintenance Instructions, ValveControlMonitor112C3706G7, G9,andGll,GeneralElectric(GEK-34573E), | |||
October1979.ReactorManual'ControlSstem1.Susquehanna 1and2,Operation andMaintenance Instructions, ReactorManualControlSystem,GeneralElectric(GEK-73596A), | |||
April1981.2.Susquehanna 1,Operation andMaintenance Instructions, ControlRodDriveHydraulics, GeneralElectric(GEK-73595A), | |||
March1981.NuclearPressureReliefSstem1.Susquehanna 1,Operation andMaintenance Instructions, Automatic Depressurization System,GeneralElectric(GEK-73602), | |||
February1979.5.3SstemDrawingsGeneralReferences GeneralElectricBechtel8856-Ml-H12-877 SH1-10E-10SH1-3E-42SH14-19,SH21-22E-64SH17gSHll28ReactorFeedwater ControlSstemGeneralElectricBechtel8856-Ml-C32-17 SH1-68856-M6-3 SH11E-126SH1-2J-127SH7,9j-427SH3M-106M-127SH1-2E-114SH1-2E-127SH6Recirculation FlowControlSstemGeneralElectricFF116510SH1101-1103 | |||
*8856-Ml-B31-178 SH1-218856-Ml-B31-189 SH1-58856-Ml-B31-275 SH1-2121 ReportNo.02-0160-1102 Revision00Recirculation PlowControlSstem(cont'd)BechtelM-103M-105M-106M-115M-140M-143E-129SH17J-105SH1-10J-106SH1-11J-115SH1-11J-406"SH2J-410SH4ReactorWaterCleanuSstemGeneralElectricBechtel8856-Mj-G33-140 SH1-5M-144PressureReulatorandT/GControlGeneralElectricBechtelTraversin In-CoreProbeGeneralElectricBechtel8856-M2J-6 SH1-398856-M2J-10 SH18856-M2J-34 SH1-38856-M2J-39 SH1-78856-M2J-40 SH1-108856-M2J-112 SH1-7E>>101SH4E-illSH1-4E-120SH1-8E-121SH1-4E-122SH1-4M-101791E413SH1-5*E-177SH4,8ReactorManualControlSstemGeneralElectricBechtel8856-Ml-C12-108 SH1,28856-Ml-C12-110 SH1-9,SH11-12,SH14-32'H35-36E-158SH1-3E-169SH2-4M-146M-147 ReportNo.02-0160-1102 Revision0NuclearPressureReliefSystemGeneralElectricBechtelRefuelinInterlock PGeneralElectricRodBlockMonitoring Bechtel8856-B21-'129 SH1-8E-180SH1-8M-141M-1428856MlC12110SH19gSHll12'H14-32,SH35-368856-Ml-F21-52 SH1-19E-157SH1-6E177SH1I3ISH48'Note:Bechteldrawingnumberswereusedexceptwherenotedbyanasterisk. | |||
AnasteriskwillindicateaGeneralElectricnumber.23}} |
Revision as of 19:18, 29 June 2018
ML17139B885 | |
Person / Time | |
---|---|
Site: | Susquehanna |
Issue date: | 03/31/1982 |
From: | EDS NUCLEAR, INC. |
To: | |
Shared Package | |
ML17139B884 | List: |
References | |
02-0160-1102, 02-0160-1102-R01, 2-160-1102, 2-160-1102-R1, NUDOCS 8310180481 | |
Download: ML17139B885 (29) | |
Text
CONTROLSYSTEMPOKERSUPPLYANDSENSORMALFUNCTION STUDYPreparedfor:Pennsylvania PowerandLightCompanySusquehanna SteamElectricStationPreparedby:EDSNuclearInesMarch,1982ReportNo.02-0160-1102 Revision1831018048i 831014PDRADOCK05000387P,PDR Il' ReportNo.02-0160-1102 Revision1hCONTROLSYSTEMPOWERSUPPLYANDSENSORMALFUNCTION STUDYTABLEOFCONTENTSSact1onPacae1.0Introduction 2'0Executive Summary3.0Methodology
4.0 SummaryofResults50References
15Appendices AppendixATechnical Procedure forthePerformance oftheAnalysisAppendixBControlSystems/Safety Functions AppendixCControlSystemIdentification DiagramsAppendixDCommonality DiagramsAppendixEFailureModesandEffectsAnalysisAppendixFMalfunction AnalysisTables ReportNo.0201601102Revision0CONTROLSYSTEMPOWERSUPPLYANDSENSORMALFUNCTION STUDY1~0INTRODUCTION OnJune15,1981,Pennsylvania PowerandLightCompany(PPEL)requested thatEDSNuclearInc~(EDS)assisttheminresponding totheSafetyEvaluation Report(SER)itemconcerning thefailureofnon-safety gradecontrolsystemsduetofailure/malfunction ofpowersuppliesorsensordthatarecommontothesecontrolsytemsfortheSusquehanna SteamElectricStation(SSES)~Verification wasrequested toensurethatthesubjectcontrolsystemfailureswouldnotimpactonplantsafety.Theobjective oftheanalysiscontained hereinistwofold-1.Toidentifypowersuppliesandsensorstotwoormorenon-safety gradecontrolsystems.2.Toanalyzetheeffectsofthefailureormalfunction ofthesepowersuppliesandsensorsoncontrolsystemstodetermine iftheresulting plantconditions arecontained withintheboundaryofChapter15analysisandarewithinthecapabilities ofoperators andsafetysystems.Inordertoachievetheseobjectives, EDSemployedatwo-phase approachconsisting oftheIdentification PhaseandtheAnalysisPhase.IntheIdentification Phase,diagramsweregenerated toidentifythenon-safety gradecontrolsystemsandtheirpowersuppliesandsensors.Thesediagramswerefurtneranalyzedinordertodetermine thosecommonpowersuppliesandsensors.IntheAnalysisPhase,Failure"Modes andEffectAnalyses(FMEA)wasutilizedtodetermine theeffectsofthesepowersupplyandsensorfailuresontheirrespective controlsystemsand,ultimately, onplantperformances TheFMEAswerethenanalyzedtodetermine thesafetyimplications (ifany)forthefailureofthesecontrolsystems.Thisreportdocuments theresultofthisanalysis.
Themethodology employedisdescribed generally inSection3'andingreaterdetailinAppendixA.Asummaryofresultsispresented ingeneraltermsinSection4.0andindetailinAppendices 3throughF.References areprovidedinSection5.0.AnExecutive SummaryisprovidedinSection2.0whichhighlights thesalientresultsofthisproject.C c2.0EXECUTIVE SUMMARYReportNo.02-0160-1102 Revision0Thepurposeofthisreportistodetermine ifthefailureofcommonpowersuppliesandsensorsfoznon-safety gradecontrolsystemswillimpactonplantsafety.Thiswasaccomplished byfirstidentifying thosecommonpowersuppliesandsensors,thenanalyzing theeffectsthosecontrolsystemfailuresonplantsafety.Inaddition, forthosecontrolsystemfailuresthatimpactedonplantsafetybutwerenotaddressed byChapter15analysisandwerenotwithinoperatorandsafetysystem'apabilities, recommendations forplantmodification orChapter15reanalysis weremade.Theprojectwasdividedintotwophases-theIdentification PhaseandtheAnalysisPhase~Intheidentification Phase,keyplantsafetyfunctions wereidentified usingChapter15.Thecontrolsystemsthatcouldaffectthesesafetyfunctions werethenidentified fromthoselistedinChapter7'7,"ControlSystemsNotRequiredforSafety."Thepowersuppliesandsensorsthatprovidepowerorsignalstothesecontrolsystemswereidentified'or thesekeyitems-safetyfunctions, controlsystems,powersupplies, andsensors-ControlSystemIdentification Diagrams(CSID)weregenerated todocumentthisinformation andtoassistinfurtheranalysis'ower supplyandsensorcommonality wasdetermined usingtheCSIDs.Aseconddiagram--Commonali tyDiagram(CD)--wasgenerated toshowthecontrolsystemsandtheirassociated components thatwereaffectedbyeachcommonpowersupplyorsensor.IntheAnalysisPhase,FailureModesandEffectsAnalysis(FMEA)wasperformed oneachcommonpowersupplyandsensortodetermine theeffectofthefailureonthecontrolsytemandonplantperformances Analysiswasthenperformed usingtheFMEAresultstodetermine thefollowing:
l.Impactonplantsafetyincluding plantresponseasperChapter15.2.Iftheplantconditions werewithinoperatorandsafetysystemcapabilities asperChapter15~Forthoseconditions thatdidnotmeetthecriteriaofitems{l)and{2),recommendations forplantmodifications orChapter15reanalysis wereprovided.
ReportNo~02-0160-1102 Revision12.2ResultsAtotaloftenpowersupplyandsensorcommonalities wereidentified andanalyzed.
Ofthesetencommonalities<
n-'ne(9)'wereofthepowersupplytypeandone(1)wasoftnesensortype.1.Thefailureofpowersupply1D635125VDCthatiscommontotheReactorFeedwater ControlSystemand.Pxessure Regulator andT/GControlSystemresultedinplantconditions thatmaynotbeboundedbyChapter15analysis.
Thecondition isgenerated byamaximumdemandsignalfromtheFeedwater SystemduetoazeroflowsignalfromtheBtrainflowsensorinstrumentation beingprocessed bytheFeedwater Systemonlossofthepowersupply.ThispowersupplyalsopowerstheReactorFeedPumpTurbineCtripcixcuit.Ifthereactorvesselhighleveltripsetpointisreachedinthismaximumfeeddemandsituation, RFPTsAandBwilltrip;RFPTCwillcontinuetooperateduetothetripcircuitfailure.Itshouldbenotedthatdataisnotcurrently available toverifythattheLevel8txippointwillbereached.EDS,therefore, recommends thattheappropriate instrument perfoxmance bereviewedandtransient analysisbeperformed toverifythecondition exists.IftheLevel8tripisnotreached<theconditions generated bythefailureof1D635areboundedbyChapter15analysis.
Ifitisdetexmined thattheLevel8trippointisreached,EDSrecommends thataplantmodification bemadetoprovidedifferent powersuppliesfortheBtrainfeedflowinstrumentation andtheReactorFeedPumpTurbineCtripcircuit.Asanalternate
- solution, EDSrecommends thatthemaximumfeeddemandcondition inChapter15bereanalyzed tovexifythatthefailureofthefeedpumptotripis,infact,boundedbycurrentChapter15analysis.
2~Allothercommonpowexsupplyandsensorfailuresweredetexmined tobeeitherboundedbyChapter15analysisandwithinoperatorandsafetysystemcapabilities ortonotimpactplantsafety.Detailedanalysisdocumenting theresultsiscontained inSection4.0andAppendices BthroughF.
El ReportNo.02-0160-1102 Revision03~0METHODOLOGY Asindicated intheintroduction, themethodology thatwasutilizedbyEDSforthisprojectwasdesignedtomeetthefollowing objectives:
1.Toidentifypowersuppliesandsensorstotwoormorenon-safety gradecontrolsystems.2.Toanalyzetheeffectsofthefailureormalfunction ofthesepowersuppliesandsensorsoncontrolsystemstodetermine iftheresulting plantconditions arecontained withintheboundaryofChapter15analysisandarewithinthecapabilities ofoper'ators andsafetysystems'he methodology employedtoachievetheseobjectives issummarized inthissection.Adetaileddescription ofthismethodology iscontained inAppendixA,"Technical Procedures forthePerformance oftheAnalysis.
"Atwo-phase approachwasusedaspartofthismethodology.
Phase1,the"Identification Phase,"consisted ofidentifying thefollowing items:Plantsafetyfunctions ControlsystemsPowersuppliesandsensorstothecontrolsystemsPowersuppliesandsensorscommontocontrolsystemsPhase2,the"Analysis Phase,"consisted oftheanalysisofthefailureofthesecommonpowersuppliesandsensorswithrespecttotheirassociated controlsystems.Thecontrolsystemfailureswereanalyzedwithrespecttothefollowing criteria:
PlantresponseasperChapter15Plantconditions withinoperatorandsafetysystemcapabilities Reanalysis ormodifications requiredtocorrectanyproblemsnotcoveredbythefirsttwocriteria3.1Identification PhaseThefirstpartoftheidentification phaseconsisted ofidentifying thenon-safety gradecontrolsystemsthatcouldimpactplantsafety.Inordertoaccomplish this,itwasfirstnecessary toidentifythoseplantsafetyfunctions thatarerequiredtobemetduringthevariousmodesofplantoperation.
Thesafetyfunctions weregenerated usingChapter15,Appendix15AoftheCESAR.Theplantoperating modesandsafetyfunctions wereaddedtotheControlSystem ReportNo.02-0160-1102 Revision0Identification Diagrams(CSIDs).Thesediagramscontainalltheidentification information requiredtodetermine commonality withrespecttopowersuppliesandsensors-Subsequent tosafetyfunctionidentification, thecontrolsystemswhichcouldaffect.thesesafetyfunctions wereidentified.
Thesecontrolsystemswereselectedfromthelistofnon-safety gradecontrolsystemsprovidedinChapter7'oftheFSAR.ThecontrolsystemswerethenaddedtotheCSIDs.Thepowersuppliesandsensorsrequiredtosupportthesecontrolsystemswereidentified andaddedtotheCSIDs-Thepowersupplyidentification alsoincludedtheCascading PowerSupplyEffect,thatis,thepotential forfailureofhigherlevelpowersuppliesduetofailureofacorresponding lowerlevelpowersupply'he boundaryofthecascading effectwaslimitedtothe120VACand125VDCinstrument andcontrolbuses.Thisboundarywasbasedoninformation providedbythePPSLElectrical Groupconcerning crediblehigherlevelpowersupplybusfailures.
CSIDsareshowninAppendixC.Thefinal.partoftheidentification phasewastodetermine whichpowersuppliesandsensorswerecommontomorethanonecontrolsystem.Thiscommonality wasaccomplished usingtheCSIDs.Eachcommonpowersupplyandsensornotedwasthenusedasthefocalpointofaseconddiagram-Commonality Diagram(CD)~Thisdiagrampresented thecommonpowersupplyorsensor,thecontrolsystemsaffected, andthekeycomponents andcircuitsthatarepartofthesecontrolsystems~CDsareshowninAppendixD.'.2AnalsisPhaseThemethodology employedintheanalysisphaseconsisted oftwoparts:FailureModesandEffectsAnalysis(FMEA)andMalfunction Analysis.
TheFMEAtechnique wasusedtogeneratefailureeffectsinformation oneachcontrolsystemasitpertainstoitscommonmode.powersupplyorsensorfailure.Usingtheinformation fromtheCDs,theoveralleffectofthepowersupplyorsensorfailurewasdetermined withrespecttocontrolsystemandplantperformance.
Theresultsofthispartoftheanalysisweredocumented onFMEAformsascontained inAppe'ndix E.Malfunction analysiswasthenperformed usingtheFNEAstodetermine iftheplantconditions generated impactedonplantsafetyandwerewithinthecapabilities ofoperators andsafetysystems.Theconditions generated asperthe ReportNo.02-0160-1102 Revision0PMEAswerecomparedwithChapter15analysisforverificationofplantresponse, operatorresponse, andsafetysystemresponseForthoseplantconditions inwhichplantsafetywasimpactedwithoutappropriate Chapter15analysisandoperatorandsafetysystemcapability verifications, systemmodifications orChapter15analysisrecommendations wereprovided.
ThetablesinAppendixFwereusedasatooltodocumentthemalfunction analysis.
Thisinformation wasthensummarized intheresultssectionofthisreport.
ReportNo.02-0160-1102 Revision0.4.0SUMMARYOFRESULTSThepurposeofthiseffortwastodetermine ifthefailureofcommonpowersuppliesandsensorsfornon-safety gradecontrolsystemscouldimpactonSSESplantsafety.Theresultsofthiseffortaredividedintotwomajorareas:Identification ofkeyelementsControlsystemsthatcouldimpactplantsafetyPowersuppliesandsensorstothesecontrolsystemsCommonpowersuppliesandsensorsforthesecontrolsystems2.AnalysisofcontrolsystemfailureReferenced totheFSAR-Chapter15Withincapabilities ofoperatorandsafetysystemsRecommendations forreanalysis ormodification ifrequiredThissectionprovidesasummaryoftheresultsdetermined byEDSwithrespecttoeachofthetwomajorareas'moredetaileditem-by-item listingoftheresultsiscontained inAppendices BthroughF.4.1Identification Priortoperforming theanalysisonthesubjectcontrolsystemfailure,itwasnecessary tofirstdetermine whichofthoseSSESnon-safety gradecontrolsystemcouldimpactplantsafety.Basedontheplantsafetyfunctions foreachplantoperating modeasdescribed inChapter15andthecontrolsystemsdescribed inChapter7',"ControlSystemNotRequiredforSafety,"thecontrolsystemsthatcouldimpactplantsafetyweredetermined anddocumented asfollows:1~2.3.4,~5.6.~7~8.9~ReactorManualControlSystemRecirculation FlowControlSystemReactorFeedwater ControlSystemPressureRegulator andTurbineGenerator ControlSystemTraversing In-CoreProbeControlSystemReactorWaterCleanupControlSystemRefueling Interlock ControlSystemRodBlockMonitorSystemNuclearPressureReliefControlSystemItshouldbeemphasized thatthislistincludesthosecontrolsystemsthatcouldimpactplantsafety.Actualdetermination ofthosecontrolsystemsthat,infact,doimpactplantsafetywouldbeaccomplished duringthe ReportNo.02-0160-1102 Revision1analysisphaseoftheproject-Documentation ofthesafetyfunctions andcontrolsystemsiscontained intheControlSystemIdentification Diagrams(CSIDs)inAppendixC.BasedonthecontrolsystemscopeasdefinedinChapter7.7,thepowersuppliesandsensorsthatsupporteachofthesecontrolsystemswereidentified.
Thepowersuppliesidentified werethosespecific120VACand125VDCinstrument andcontrolpowersupplies.
Thesensorsidentified werethosesensorsthatprovideinputsintothecontrolsystem.Detaileddocumentation ofthesepowersuppliesandsensorsisalsocontained intheCSIDs.Intheprocessofidentifying controlsystempowersupplies, theCascading PowerSupplyEffectwasalsoadd"essed.
Basedonastudyperformed bythePPGLElectrical Group,itwasdetermined thattheonlycrediblecascading powersupplyfailurepossibleatSSESwasthatcombination of1Y218and1Y219120VACbuses.Thesearetheonlytwoinstrument andcontrolpowersuppliesthatwouldbesubjecttothecascading effectbasedonthedesignoftheSSESelectrical distribution system.Allotherpowersuppliesatahigherlevelarebackedupbyeitheranalternate ACsourceorabattery.Uponcompletion ofthepowersupplyandsensoridentification, powersupplyandsensorcommonality wasdetermined.
Commonality Diagrams(CDs)weregenerated toshowcommonality betweenthosecontrolsystemsidentified.
Atotaloften(10)commonalities weredetermined.
Thesecommonalities formthebasisfortheanalysisphaseoftheproject.TheCDsarecontained inAppendixD.4.2AnalysisTheanalysisofthecontrolsystemsthatcontained commonpowersuppliesandsensorswasaccomplished usingFailureModesandEffectsAnalysis(BREA),thenanalyzing theoverallimpactofeachsystemFMEAontheplant.TheFMEAsweregenerated foreachcontrolsystemasitpertainstothecommonpowersupply.orsensor.ThedetailedresultsofeachFMEAarecontained inAppendixE.BasedontheBKAs,thedetailedanalysisofthesecontrolsystemswasperformed.
Theresultsarepresented hereintwocategories:
(1)Failuresthatcouldimpactplant'afetyrequiring furtheranalysis, and(2)failuresthatcouldimpactplantsafetyaddressed byChapter15/failures thatdonotimpactplantsafety.
ReportNo.02-0160-1102 Revision11.FailuresThatCouldImactPlantSafetReirinFurtherAnalysisEDSanalysisdetermined thatfailureofthepowersupply1D635125VDCcouldimpactplantsafetyandtherefore requiresfurtheranalysis.
ThecontrolsystemsaffectedbythispowersupplyfailurearetheReactorFeedwater andthePressureRegulator andT/GControlSystems.Theconditions thatmaynotbeboundedbyChapter15analysisare,however,isolatedtotheFeedwater Systemonly-specifically theFeedwater FlowControlandReactorFeedwater PumpTurbine(RFPT)TripContxolsub-systems.
Thelossofthispowersupplydoesnotgenerateconditions outsideoftheboundaryofChapter15analysisforthePressureRegulator andT/GControlSystem.Basedondatacurrently available, thesequenceofeventsthatresultfromthelossofthispowersupplyfortheFeedwater Systemisasfollows:a.HM.leoperating at100%reactorpower,theplantexperiences alossof1D635.Thefeedwater flowsignalfromtheBtraininstrumentation poweredby1D635(FlowTransmitter FTlN002BandSRU6)changestozeroduetothelossof1D635-Sincethefeedwater flowsignalsfromtrainsA,BandCazesummed,thetotalfeedflowsignalchangesfrom100%feedflowto67%feedflowsubsequent toreceiving theerroneous zerosignalfromtheB,train.Thisintroduces amismatchbetweensteamflow,whichisstillat100%,andfeedflowwhichisat67%.b.Inresponsetothissteamflow,feedflowmismatch, theFeedwater FlowContxolSystemsendsasignaltothethreeRFPT'stoinczeasefeedflowtomakeupfortheerroneous 33%decxeaseinflow.Actualfeedflowatthispointwouldbeapproximately 135%.cdSinceactualfeedflowissignificantly greaterthanthatrequired, theincreaseinreactorvessellevel~marea'chtheLevel8(highlevel)'tripsetpoint~d-IftheLevel8tripsetpointisreached,atripsignalwillbesenttoRFPTsA,B,andCandtheT/G.RFPTsAandBandtheT/Gtrip.RFPTCfailstotripbecauseitstripcircuitwasdisableduponlossof1D635.
ReportNo~02-0160-1102 Revision1Basedontheassumption thattheLevel8setpointisreachedduetoexcessive feedwater demand,theresulting conditions arenotexplicitly addressed byChapter15-Chapter15statesthattheplantresponsetoaLevel8condition, initiated byexcessfeedflow,shouldincludethetripofallRPPTsandtheT/G.Sincetheconditions generated subsequent tothefailureofRPPTCtotriparenotknown<itcannotbedetexmined iftheplantsystemcapabilities areadequateusingpresentChapter15analysis.
TheoperatordoesretaintheabilitytotakemanualcontroloftheRPPTCtomitigatetheeffectsofitscontinued operation.
TheoperatorwouldbealertedtotherisingreactorvessellevelbytheLevel7alarm.Thiscondition, therefore, appearstobewithinthecapabilities oftheoperator.
Xnordertoresolvethisproblem,EDSrecommends that,first,ananalysis(thermalhydraulic andinstrument) beconducted toverifythattheLevel8setpointwillbereached,basedonthesequenceofeventspreviously postulated.
ZftheresultsofthisanalysisverifythattheLevel8setpointisnotreached,thentheconditions generated bythelossofpowersupply1D635125VDCareinfactboundedbyChapter15analysis'f theLevel8setpointisreached,thentheresulting conditions requirefurtheranalysis.
Porthoseconditions notexplicitly addressed byChapter15analysis, EDSrecommends resolution ofthisproblembeaccomplished inoneoftwoways.Aplantmodification couldbemadetoremovethecommonality betweenthefeedwater flowBprocessinstrumentation (PlowTransmitter andSRU)andtheRPPTCtripcircuit.BasedonEDSfailuremodesandeffectsanalysis, changingtheseinstruments toanalternate powersupplywouldresolvethisproblem.1D615andXD625shouldbeeliminated asalternatives sincetheyprovidepowertotheRPPTAandBtripcircuits, respectively.
EDSrecommends thattheBtraininstruments bemovedtotheACpowersupplythatiscurrently providing powertothePeedwater PlowControlSyst:em-1Y218Breaker13.Theappropriate conversion deviceswouldalsohavetobeaddedinordertoaccountforthechangeover oftheseinstruments fromDCtoAC.Movingtheseinstruments tolY218wouldnotchangetheoveralleffectontheFeedwater PlowControlSystemsubsequent tothelossoflY218-Thesystemeffectsandplantresponseasnotedinthe1Y218PMEAwouldremainthesame~-10 ReportNo-02-0160-1102 Revision1Ztshouldbenotedthatifanypowersupplyotherthan1Y218isselected, theappropriate FailureModesandEffectsAnalysisshouldbeperformed toensurethatanewproblemisnotcreated.Thesecondmethodofproblemresolution wouldbetoanalyzetheconditions generated bythecontinued operation ofRFPTCtoverifythattheplantsystemswill<infact,mitigatetheprobleminspiteofthisnewcondition.
2.FailuresThatZmctPlantSafetyAddressed byChater15/Failures ThatDoNotImpactPlantSafetyTheremaining nine(9)controlsystemcommonalities havebeendetexmined byEDStobeeith'eraddressed byChapter15ortonotimpactplantsafety.Norecommendations foxmodification oranalysisarerequired.
Eachoneissummarized asfollows:a.1D615125VDCThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Control,PressureRegulator
-T/GControl,andRecirculation FlowContxol.Theonlyplantsafety-related condition generated bythisfailureisalossofrecirculation flowinLoopAandarecirculation runbackinLoopB.Thiscondition andtheplantresponseiscoveredbyChapter15analysis.
Thiscondition isalsowithinthecapabilities oftheoperator.
Znaddition<
safetysystemresponseisnotrequixed.
b1D625125VDCThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Control,PressureRegulator
-T/GControl,Recirculation FlowControl,andtheTraversing Zn-CoxeProbe.Theonlyplantsafety-related condition generated bythisfailureisalossofrecirculation flowLoopB.Thiscondition andtheplantresponseforsingleloopflowarecoveredbyChaptez15analysis.
Thiscondition isalsowithinthecapabilities oftheoperator.
Inaddition, safetysystemresponseisnotrequired-ReportNo.02-0160-1102 Revision0C~1D645125VDCThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Controland'ressure Regulator
-T/6Control.Theonlyplantsafety-related condition generated bythisfailureisapotential highreactorvessellevelduetothefailureoftheFeedwater Blevelsensor..Thisfailurecombinedwithmaximumfeedwater flowdemand(worstcase)isaddressed inChapter15.Thisvesselhighlevelcondition iswithinoperatorcapabilities sincemanualcontroloftheReactorFeedwater ControlSystemisstillavailable.
ThesafetysystemsthatrespondperChapter15forthiscondition possessthenecessary capabilities tomitigatetheproblem.'d~lY218120VACThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorFeedwater Contol,ReactorManualControlRecirculation FlowControl,PressureRegulation
-T/6Control,ReactorWaterCleanup,NuclearPressureRelief,andTraversing'n-Core ProbeTheplantsafetycondition generated bythisfailureisapotential highorlowreactorvessellevelresulting fromtheFeedwater ControlSystemfailingatmaximumorminimumdemand.Thefailureofthispowersupplyinvolvesa"speedfreeze"ofthereactorfeedwater pumpturbines(RFPT)~A"speedfreeze"meansthattheRFPTspeedislockedinattheratethatwaspresentpriortothelossofpower.Thisspeedfreezeatmaximumorminimumdemanddirectlyleadstoahighorlowwaterlevel,respectively.
Theplantresponsetothemaximumorminimumfeedflowdemandisaddressed inChapter15.Inthemaximumdemandcondition, aLevel8tripwillresult,eventually leadingtoRFPTtrip,T/6trip,reactorscram,recirculation pumptrip,andHPC1'/RCIC actuation.
Theminimumdemandcondition condition, asperChapter15,willresultinaplantresponseofaLevel3tripfollowedbyaLevel2trip~Thisresultsinareactorscram,recirculation pumptrip,MSIVclosure,T/6trip,andHPCI/RCIC actuation.
12
ReportNo.02-0160-1102 Revision0Themaximumandminimumdemandconditions arewithinoperatorcapabiliti'es.
ThesafetysystemsthatrespondperChapter15fortheseconditions possessthenecessary capabilities tomitigatethisproblem.Itshouldbenotedthatalthoughthecondition generated inbetweenmaximumandminimumfeedflowdemandisnotsafetyrelated,itpreventschangesfrombeingmadeontheReactorManualControl,ReactorFeedwater Control,andtheRecirculation PlowControlsystems'pon lossofpower,eachofthesesystemsremainsintheconfiguration itwasinpriortothelossofpower.Specifically, rodscannotbemovedandfeedwater andrecirculation flowcannotbealtered.Thiscondition isnotbeyondoperatorcapabilities, butshouldbeconsidered whenPPSLisgenerating planttrainingoroperating procedures.
e.1Y219.120VACThecontrolsystemsinvolvedwiththispowersupplyfailurearetheReactorManualControlSystemandtheReactorWaterCleanupSystem.Therearenoplantsafety-related conditions associated withthelossofthispowersupply;therefore, noChapter15analysisisrequired'perator orsafetysystemresponseisnotrequired.
1Y226120VACgoThecontrolsystemsinvolvedwiththispowersupplyfailurearetheNuclearPressureReliefSystemandtheReactorWaterCleanupSystem.Therearenoplantsafety-related conditions associated withthelossofthispowersupply;therefore, noChapter15analysisisrequired.
Operatororsafetysystemresponseisnotrequired.
1Y629120VAC1ThecontrolsystemsinvolvedwiththispowersupplyfailurearethePressureRegulator
-T/6Control,TheanalysisforlY629failureisbasedonT/6solenoidvalvesfailing"asis."Thisassumption hastobemadeduetoalackofspecificreference information.
13 ReportNo.02-0160-1102 Revision0theReactorManualControlSystem,'andthe~Recirculation FlowControlSystem.Theconditions associated withthispowersupplyfailureareaT/6tripatlessthan30%poweroraT/6tripandreactorscramatgreaterthan30%power..Theplantresponseforeithercondition iscoveredbyChapter15analysis'oth theT/6tripandthereactorscramarewithinoperatorcapabilities.
These.conditions arealsowithinthecapabilities ofthesafetysystems,including Scram,,HPCI,
'andRCIC,asperChapter15.Feedwater FlowElements-FElNOOlA,B,CThecontrolsystemsinvolvedwiththissensorfailurearetheReactorFeedwater ControlandtheRecirculation Control~Theplantsafetycondition generated bythisfailureisapotential highorlowreactorvessellevelresulting fromtheFeedwater ControlSystemfailingatmaximumorminimumdemand.Thisfailureiscausedbyonefeedwater flowelementfailingsuchthateitherahighfloworlowflowsignalisgenerated.
Theplantresponsetothemaximumorminimumfeedflowdemandisaddressed inChapter15.Inthemaximumdemandcondition, aLevel8tripwillresult,eventually leadingtoRFPTtrip,T/6trip,reactorscram,recirculation pumptrip,andHPCI/RCIC actuation.
Theminimumdemandcondition condition, asperChapter15,willresultinaplantresponseofaLevel3tripfollowedbyaLevel2trip~Thisresultinareactorscram,recirculation pumptrip,MSIVclosure,T/6trip,andHPCI/RCIC actuation.
Themaximumandminimumdemandconditions arewithinoperatorcapabilities
~Thesafetysystems-thatrespondperChapter15fortheseconditions possessthenecessary capabilities tomitigatethisproblem.Itshouldbenotedthataflowelementfailurecausedbyamechanical problem(i.e.,cloggingatthesensinginletoroutlet)wouldtakeplaceoverarelatively longperiodoftimeFlowdegradation shouldbenotedthroughroutineflowindication monitoring'4 ReportNo.02-0160-1102 Revision0i.CascadinPowerSu1Effect-lY218and1Y219120VACInanalyzing theSSESelectrical distribution system,itispossiblethatafailureinpowersupply1X219couldcausepowersupply1Y218tofail,aswell,sinceitsuppliespowertolY219.Thefailureofahigherlevelpowersupplyduetoafailureofacorresponding lowerlevelpowersupplyisdefinedastheCascading PowerSupplyEffect.ThecombinedfailureoflY218and1Y219doesnotinvokeconditions notalreadycoveredintheanalysisofeachofthesepowersuppliesinsub-paragraphs (d)and(e)respectively.
Thiscombinedfailureis,therefore, boundedbyChapter15analysisandwithinthecapabilities oftheoperatorandsafetysystems.Nootheranalysisisrequired.
15
.
5.0REFERENCES
ReportNo.02-0160-1102 Revision0Thefollowing isthelistofreferences usedduringthisproject:5.1GeneralInformation Susquehanna SteamElectricStation,Units1and2,FinalSafetyAnalysisReport,Pennsylvania PowerandLightCompany,Volumes1-17,Revision23,6/81.5'SstemDescritiveReferences ReactorFeedwater ControlSstemInstruction Manuals4110and4125,Alphaline PressureTransmitters AbsoluteandGage,Models1151APand1151GP,Rosemount.
2~3.5.6.7~8.Indicating
- Switches, LiquidLevel-Differential Pressure-Plow Rate,Product/Bullet, in288A/289A, ITTBarton.BaileyServiceManual,Type771NarrowRollStrip-Chart Recorder(4577Kll-300A)
BaileyPartsManual,Type771,772,and773Strip-Chart Recorders, (4577Kll-350)
~Operating andInstruction Manual,StaticInverterModelN250-MRS-125-60-115, TopazElectronics, October1974.Information aboutthe(OrificePlate)BoreCalculation, Vikery-Simms, Inc.,VSIJobNo~-N-1053andN-1175.OrificeBoreCalculation LiquidFlow,Vike~-Simms, Inc.,2/23/76.PressureSwitchesPartsPriceList,Code1BourdonTube,Barksdale (Bulletin No.671221-B),
January1,1973.9.BaileyServiceManual,Type745SingleandDualAlarm,.(4574K15-300F
)~.10~BaileyServiceManual,Type754FunctionGenerator, (4575K14-300A).
llewBaileyInstallation Manual,Type754FunctionGenerator, (4575K14-001).
ReportNo'.02-0160-1102 Revision012~BaileyInstructions, Type760001VoltageSignalSources,(4576K10-001).
13'aileyServiceManual,755DynamicCompensator, (4575K15-300B).
14..Bailey Difference Data,Type755DynamicCompensator Cat~No~50-755010AAAA1NAB (4575K15-003).
15~16.BaileyInstallation Manual,Type701BasicController,
(.4570K11-001A).
Susquehanna 1,Operations andMaintenance Instructions, Feedwater ControlSystem,GeneralElectric(GEK-73592A),
April,1981.Recirculation FlowControlSstem2.3.4~5.7~8.9~10.Susquehanna 1,Operations andMaintenance Instructions,
.Recirculation FlowControlSystem,GeneralElectric(GEK-73590),
- February, 1979.BaileyServiceManual,Type724LogicUnit,(4572K14-300B).
BaileyInstallation Manual,Type745SingleandDualAlarm,(4574K15-001A).
BaileyServiceManual,Type745SingleandDualAlarm,(4574K15-300F).
BaileyInstallation Manual,Type752TwoInputandFourInputSummers,(4575K12-001B)
.Installation andOperating Instructions, Regulated DCPowerSupplies, GeneralElectric(GEI-54440).
BaileyInstallation Manual,Type744Difference Alarm,(4574K14-001).
BaileyInstallation Manual,Type720UtilityStations, (4572K10-001)-
BaileyServiceManual,Type720UtilityStations, (4574K10-300).
BaileyInstructions, Type766SignalResistorUnitsCat~No.766--*,(4576K16-007A).
17 ReportNo.02-0160-1102 Revision012.13'4.15~BaileyInstallation Manual,Type724LogicUnit,(4572K14-001).
BaileyInstallation Manual,Type740Millivolt Converters, (4574K10-001A).
BaileyServiceManual,Type723Proportional andDelayUnit,(4572K13-300).
BaileyInstallation Manual,Type723,Proportional andDelayUnit,(4572K13-001)
.BaileyInstallation Manual,,Type746SignalLimiter,(4574K16-001A)-
16'BaileyInstallation Manual,Type722ManualUnit,(4572K12-001).
17'8.19~20.21.22.23.24.BaileyServiceManual,Type722ManualUnit,(4572K12-300A).
BaileyInstallation Manual,Type721ControlUnit,(4572K11-001).
BaileyServiceManual,Type721ControlUnit,(4572K11-300).
ACRPanels120/125Vand24VFeederTabulation, Susquehanna Project,BechtelPowerCorporation, Electrical SchemeGroup,June22,1981.Instructions forOperation, Installation, Maintenance, andCalibration, Electronic FlowTransmitter 73G-0049M, Ametek/Schutte sKoerting(74S-0269M-001),
July,1974.I'nstruction Manual,(4104/4126)
Model1151DPAlphaline, Differential andHighDifferential PressureTransmitters, Rosemount (8856-J03-A-25-1).
BaileyServiceManual,Type751Sealer,(4575K11-300F).
IEEEGuideforGeneralPrinciples ofReliability AnalysisofNuclearPowerGenerating StationProtection Systems,IEEEStandard352-1975.
ReactorWaterCleanuSstemSusquehanna 1,Operation andMaintenance Instructions, ReactorWaterCleanupSystem,GeneralElectric(GEK-73608),
February1979.18 Repox'tNo.02.-0160-1102 Revision0PressureReulatorandT/GControlSstemGenerator Protection, GeneralElectxic(GEK-75512A),
- November, 1980.2~3~4~5.7~8.9-10.BasicFunctions ofElectrohydraulic Control(EHC)System,Nuclear(BoilingWaterReactor)Units,GeneralElectric(GEK-17911)
~Protection System-Electrohydraulic Control,BasicFunctions, GeneralElectric, (GEK-11366).
SpeedControlUnit,(Fossil-Baseload, BWR,PWR),GeneralElectric(GEK-11381E).
tInstructions, EHCLineSpeedMatcher,GeneralElectric(GEK-17910A)
~Instructions, Description ofLoadControlUnit(BWR),GeneralElectric, (GEK-37946).
LoadControlUnit,LoadReference
- Circuits, NuclearUnits,GeneralElectric(GEK-17864A).
Instructions, LoadLimitCircuitsandLogic,(BWR),GeneralElectric,'(GEK-17863B)
~Instructions, Chest/Shell WarmingCircuitsandLogic,3or5LightConfiguration, Nuclear-BWR, GeneralElectric, (GEK-46351B)
.Rosemount PressureTransducer Model1104A,(GEK-37803).
12-13~14-15~CurrenttoVoltageConverter, GeneralElectric, (GEK-25580).
Instructions, RateSensitive PowerLoadUnbalance CircuitandRelays,(Nuclear),
.GeneralElectric, (GEK-37959A).
FlowControlUnit,GeneralElectric, (GEK-25588).
ValveTestLogic,(BWR),GeneralElectric, (GEK-37941)
.Pressux'e ControlUnit,(BWR),GeneralElectric, (GEK-17885A)
~16.TurbineInitialPressureRegulator andControlSystem,BypassControlUnit,GeneralElectric,;
(GEK-17880).
19
ReportNo.02-,0160-1102 Revision017.18.19.20.21'urbineInitialPressureRegulator andControlSystem,Automatic LoadFollowing Signal,GeneralElectric, (GEK17881)~Automatic PressureSet-Point Adjust,GeneralElectric, (GEK-17882A).
Instructions, ElectricAlarmandTripSystem,GeneralElectric, (GEK-11367C)
.FirstHitCircuitry, GeneralElectric, (GEK-25557)
.ProtectiveSystem-Electrohydraulic Control,BasicFunctions, GeneralElectric, M-392,1971.22.ElectricAlarmandTripSystem,GeneralElectric, M-3931971.23.Electrical PowerSupplies, GeneralElectric, M-399,1971.24.25.26.27.Instructions, TestingoZtheOverspeed TripSystem,GeneralElectric, (GEK-11383C).
BackupOverspeed Trip,Electrohydraulic ControlSystem,GeneralElectric, (GEK-17978A).
Instructions, Electrical PowerSupplies, EHCSystem,GeneralElectric, (GEK-25540A).
Instruction ManualandPartsListModel730and751SeriesLiquidLevelControls, Bulletin:
46-612,Magnetrol International, April1976.Traversin In-CoreProbeSstem2.3.Preliminary, Susquehanna 1and2,Operation andMaintenance Instructions, Traversing In-CoreProbeCa'libration System,GeneralElectric(GEK-73601A),
February1981.Operation andMaintenance Instructions, IndexingMechanism 791E241G4 (GEK-73601A),
February1981.Operation andMaintenance Instructions, DriveMechanism 706E263G13, G14,G15,andG16,GeneralElectric(GEK-39600D),
March1980.20 ReportNo.02-0160-1102 Revision04..Operation andMaintenance Instructions, ValveControlMonitor112C3706G8, G10,andG12,GeneralElectric(GEK-34668D),
February1980.5.Operation andMaintenance Instructions, ValveControlMonitor112C3706G7, G9,andGll,GeneralElectric(GEK-34573E),
October1979.ReactorManual'ControlSstem1.Susquehanna 1and2,Operation andMaintenance Instructions, ReactorManualControlSystem,GeneralElectric(GEK-73596A),
April1981.2.Susquehanna 1,Operation andMaintenance Instructions, ControlRodDriveHydraulics, GeneralElectric(GEK-73595A),
March1981.NuclearPressureReliefSstem1.Susquehanna 1,Operation andMaintenance Instructions, Automatic Depressurization System,GeneralElectric(GEK-73602),
February1979.5.3SstemDrawingsGeneralReferences GeneralElectricBechtel8856-Ml-H12-877 SH1-10E-10SH1-3E-42SH14-19,SH21-22E-64SH17gSHll28ReactorFeedwater ControlSstemGeneralElectricBechtel8856-Ml-C32-17 SH1-68856-M6-3 SH11E-126SH1-2J-127SH7,9j-427SH3M-106M-127SH1-2E-114SH1-2E-127SH6Recirculation FlowControlSstemGeneralElectricFF116510SH1101-1103
- 8856-Ml-B31-178 SH1-218856-Ml-B31-189 SH1-58856-Ml-B31-275 SH1-2121 ReportNo.02-0160-1102 Revision00Recirculation PlowControlSstem(cont'd)BechtelM-103M-105M-106M-115M-140M-143E-129SH17J-105SH1-10J-106SH1-11J-115SH1-11J-406"SH2J-410SH4ReactorWaterCleanuSstemGeneralElectricBechtel8856-Mj-G33-140 SH1-5M-144PressureReulatorandT/GControlGeneralElectricBechtelTraversin In-CoreProbeGeneralElectricBechtel8856-M2J-6 SH1-398856-M2J-10 SH18856-M2J-34 SH1-38856-M2J-39 SH1-78856-M2J-40 SH1-108856-M2J-112 SH1-7E>>101SH4E-illSH1-4E-120SH1-8E-121SH1-4E-122SH1-4M-101791E413SH1-5*E-177SH4,8ReactorManualControlSstemGeneralElectricBechtel8856-Ml-C12-108 SH1,28856-Ml-C12-110 SH1-9,SH11-12,SH14-32'H35-36E-158SH1-3E-169SH2-4M-146M-147 ReportNo.02-0160-1102 Revision0NuclearPressureReliefSystemGeneralElectricBechtelRefuelinInterlock PGeneralElectricRodBlockMonitoring Bechtel8856-B21-'129 SH1-8E-180SH1-8M-141M-1428856MlC12110SH19gSHll12'H14-32,SH35-368856-Ml-F21-52 SH1-19E-157SH1-6E177SH1I3ISH48'Note:Bechteldrawingnumberswereusedexceptwherenotedbyanasterisk.
AnasteriskwillindicateaGeneralElectricnumber.23