ML063170275: Difference between revisions
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
(One intermediate revision by the same user not shown) | |||
Line 3: | Line 3: | ||
| issue date = 11/13/2006 | | issue date = 11/13/2006 | ||
| title = IR 05000409-06-003; La Crosse Boiling Water Reactor; 10/17/2006 - 11/08/2006; La Crosse Site | | title = IR 05000409-06-003; La Crosse Boiling Water Reactor; 10/17/2006 - 11/08/2006; La Crosse Site | ||
| author name = Cameron J | | author name = Cameron J | ||
| author affiliation = NRC/RGN-III/DNMS/DB | | author affiliation = NRC/RGN-III/DNMS/DB | ||
| addressee name = Berg W | | addressee name = Berg W | ||
| addressee affiliation = Dairyland Power Cooperative | | addressee affiliation = Dairyland Power Cooperative | ||
| docket = 05000409 | | docket = 05000409 | ||
Line 14: | Line 14: | ||
| page count = 11 | | page count = 11 | ||
}} | }} | ||
See also: [[ | See also: [[see also::IR 05000409/2006003]] | ||
=Text= | =Text= | ||
{{#Wiki_filter:November 13, | {{#Wiki_filter:November 13, 2006 | ||
Mr. W. L. Berg | |||
General Manager | |||
Dairyland Power Cooperative | Dairyland Power Cooperative | ||
3200 East Avenue South | 3200 East Avenue South | ||
P.O. Box 817 | P.O. Box 817 | ||
La Crosse, WI | La Crosse, WI 54602-0817 | ||
(LACBWR)Dear Mr. Berg: | SUBJECT: NRC INSPECTION REPORT 050-00409/06-03(DNMS) AND | ||
On November 8, 2006, the NRC completed an inspection in response to the Notification | NOTICE OF VIOLATION - LA CROSSE BOILING WATER REACTOR | ||
October 16, 2006. | (LACBWR) | ||
prompted the declaration of the NOUE, the implementation of the | Dear Mr. Berg: | ||
procedures, and the subsequent recovery from the event conditions. | On November 8, 2006, the NRC completed an inspection in response to the Notification of | ||
Unusual Event (NOUE) declared at the La Crosse Boiling Water Reactor (LACBWR) facility on | |||
October 16, 2006. The purpose of the inspection was to determine the sequence of events that | |||
prompted the declaration of the NOUE, the implementation of the facilitys emergency response | |||
procedures, and the subsequent recovery from the event conditions. At the conclusion of the | |||
onsite inspection on October 17, 2006, the NRC inspector discussed the preliminary findings | onsite inspection on October 17, 2006, the NRC inspector discussed the preliminary findings | ||
with members of your staff. | with members of your staff. On November 8, 2006, at the conclusion of our in-office review of | ||
the circumstances related to the NOUE declaration, the inspector and I conducted a final exit | the circumstances related to the NOUE declaration, the inspector and I conducted a final exit | ||
meeting with Mr. Roger Christians, Plant Manager.The inspection consisted of an examination of activities at the facility as they relate to | meeting with Mr. Roger Christians, Plant Manager. | ||
inspection are identified in the enclosed report. | The inspection consisted of an examination of activities at the facility as they relate to safety | ||
activities in progress, and interviews with personnel.Based on the results of this inspection, the NRC has determined that one Severity Level | and compliance with the Commissions rules and regulations. Areas examined during the | ||
NRC Enforcement Policy. | inspection are identified in the enclosed report. Within these areas, the inspection consisted of | ||
; select What We Do, Enforcement, then Enforcement Policy. | a selective examination of procedures and representative records, field observations of | ||
activities in progress, and interviews with personnel. | |||
Based on the results of this inspection, the NRC has determined that one Severity Level IV | |||
violation of NRC requirements occurred. The violation was evaluated in accordance with the | |||
NRC Enforcement Policy. The current Enforcement Policy is included on the NRCs Web site | |||
at www.nrc.gov; select What We Do, Enforcement, then Enforcement Policy. The violation is | |||
cited in the enclosed Notice of Violation (Notice). The violation involves failure to immediately | |||
respond to an emergency condition by declaring an Unusual Event in accordance with your | |||
emergency plan following the identification of airborne radioactivity on the main floor of the | emergency plan following the identification of airborne radioactivity on the main floor of the | ||
reactor building exceeding the emergency action level described in your plan.Please note that you are required to respond to this letter and should follow the | reactor building exceeding the emergency action level described in your plan. | ||
Please note that you are required to respond to this letter and should follow the instructions | |||
specified in the enclosed Notice when preparing your response. In your response to this letter, | |||
please describe why your proposed corrective actions are expected to be more successful in | please describe why your proposed corrective actions are expected to be more successful in | ||
preventing future or similar violations than the actions and commitments stated in the past. | preventing future or similar violations than the actions and commitments stated in the past. The | ||
NRC will use your response, in part, to determine whether further enforcement action is | NRC will use your response, in part, to determine whether further enforcement action is | ||
necessary to ensure compliance with regulatory requirements. | necessary to ensure compliance with regulatory requirements. | ||
W. Berg-2-In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this | |||
from the Publicly Available Records (PARS) component of NRC's document system | W. Berg -2- | ||
(ADAMS). | In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter | ||
http://www.nrc.gov/reading-rm/adams.html. | and its enclosure will be available electronically in the NRC Public Document Room or | ||
Decommissioning | from the Publicly Available Records (PARS) component of NRC's document system | ||
2. | (ADAMS). The NRCs document system is accessible from the NRC Web site at | ||
J. Mettner, Chairman, Wisconsin Public | http://www.nrc.gov/reading-rm/adams.html. | ||
We will gladly discuss any questions you have concerning this inspection. | |||
Spark Burmaster, Coulee Region Energy Coalition | Sincerely, | ||
State Liaison Officer | /RA/ | ||
Chief, Radiation Protection Section | Jamnes L. Cameron, Chief | ||
Decommissioning Branch | |||
Docket No. 050-00409 | |||
:Docket File | License No. DPR-45 | ||
Enclosures: | |||
1. Notice of Violation | |||
2. Inspection Report 050-00409/06-03(DNMS) | |||
cc w/encls: Roger Christians, Plant Manager | |||
B. D. Burks, P.E., Director, Bureau of Field Operations | |||
J. Mettner, Chairman, Wisconsin Public | |||
Service Commission | |||
Spark Burmaster, Coulee Region Energy Coalition | |||
State Liaison Officer | |||
Chief, Radiation Protection Section | |||
WI Department of Health and | |||
Social Services, Division of Health | |||
DISTRIBUTION: | |||
Docket File | |||
PUBLIC IE-01 | PUBLIC IE-01 | ||
RIII PRR | RIII PRR | ||
K. I. McConnell, NMSS | K. I. McConnell, NMSS | ||
K. L. Banovac, NMSS | K. L. Banovac, NMSS | ||
C. M. Craig, NMSS | C. M. Craig, NMSS | ||
G. E. Grant, RIII | G. E. Grant, RIII | ||
S. A. Reynolds, RIII | S. A. Reynolds, RIII | ||
RIII Enf. | RIII Enf. Coordinator | ||
G Non-Publicly Available | DOCUMENT NAME:C:\FileNet\ML063170275.wpd | ||
G | X Publicly Available G Non-Publicly Available G Sensitive X Non-Sensitive | ||
NOTICE OF | To receive a copy of this document, indicate in the concurrence box "C" = Copy without attach/encl "E" = Copy with attach/encl "N" = No copy | ||
OFFICE RIII RIII | |||
NAME PJLee:mb JLCameron | |||
DATE 11/13/06 11/13/06 | |||
OFFICIAL RECORD COPY | |||
NOTICE OF VIOLATION | |||
Dairyland Power Cooperative Docket No. 050-00409 | |||
La Crosse Boiling Water Reactor License No. DPR-45 | |||
During an NRC inspection conducted on October 17, 2006, with continuing in-office review | |||
through November 8, 2006, a violation of NRC requirements was identified. In accordance with | |||
the "General Statement of Policy and Procedure for NRC Enforcement Actions," the violation is | the "General Statement of Policy and Procedure for NRC Enforcement Actions," the violation is | ||
listed below: 10 CFR 50.54(q) requires, in part, that a licensee authorized to possess and operate | listed below: | ||
standards in 10 CFR 50.47(b) and the requirements in Appendix E to 10 CFR Part 50. | 10 CFR 50.54(q) requires, in part, that a licensee authorized to possess and operate a | ||
The licensee maintained an emergency plan, "LACBWR Emergency Plan," Revision 25, | nuclear power reactor follow and maintain in effect emergency plans which meet the | ||
dated December 2004. | standards in 10 CFR 50.47(b) and the requirements in Appendix E to 10 CFR Part 50. | ||
Organization And Responsibilities," requires, in part, that the emergency response | The licensee maintained an emergency plan, "LACBWR Emergency Plan," Revision 25, | ||
organization is intended to provide immediate response to an emergency condition at | dated December 2004. Section 1.0 of the LACBWR Emergency Plan, "DPC Emergency | ||
LACBWR. | Organization And Responsibilities," requires, in part, that the emergency response | ||
lists potential plant conditions and their emergency classifications. | organization is intended to provide immediate response to an emergency condition at | ||
condition involving unplanned airborne concentrations greater than 10 times normal | LACBWR. Section 4.0 of the Emergency Plan, "Emergency Action Levels," Table 4.1, | ||
levels, the corresponding emergency classification in Table 4.1 is a Notification of | lists potential plant conditions and their emergency classifications. For the plant | ||
Unusual Event.Contrary to the above, on October 16, 2006, the licensee declared an Unusual | condition involving unplanned airborne concentrations greater than 10 times normal | ||
(DACs) in the general areas of the reactor building. | levels, the corresponding emergency classification in Table 4.1 is a Notification of | ||
provide immediate response to the emergency condition. | Unusual Event. | ||
identified americium-241 concentrations at those levels on October 13, 2006, but did not | Contrary to the above, on October 16, 2006, the licensee declared an Unusual Event | ||
declare an Unusual Event until October 16, 2006.This is a Severity Level IV violation (Supplement VI).Pursuant to the provisions of 10 CFR 2.201, Dairyland Power Cooperative is hereby required | based on airborne americium-241 concentrations of 3 to 5 derived air concentrations | ||
(DACs) in the general areas of the reactor building. As a result, the licensee failed to | |||
provide immediate response to the emergency condition. Specifically, the licensee | |||
identified americium-241 concentrations at those levels on October 13, 2006, but did not | |||
declare an Unusual Event until October 16, 2006. | |||
This is a Severity Level IV violation (Supplement VI). | |||
Pursuant to the provisions of 10 CFR 2.201, Dairyland Power Cooperative is hereby required to | |||
submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN: | |||
Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, | Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, | ||
Region III, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). | Region III, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). | ||
This reply should be clearly marked as a "Reply to a Notice of Violation | This reply should be clearly marked as a "Reply to a Notice of Violation and should include for | ||
each violation: (1) the reason for the violation, or, if contested, the basis for disputing the | |||
violation or severity level, (2) the corrective steps that have been taken and the results | violation or severity level, (2) the corrective steps that have been taken and the results | ||
achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date | achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date | ||
when full compliance will be achieved. | when full compliance will be achieved. Your response may reference or include previous | ||
docketed correspondence, if the correspondence adequately addresses the required response. | docketed correspondence, if the correspondence adequately addresses the required response. | ||
If an adequate reply is not received within the time specified in this Notice, an order or a | If an adequate reply is not received within the time specified in this Notice, an order or a | ||
Demand for Information may be issued as to why the license should not be modified, | Demand for Information may be issued as to why the license should not be modified, | ||
suspended, or revoked, or why such other action as may be proper should not be taken. | suspended, or revoked, or why such other action as may be proper should not be taken. | ||
Where good cause is shown, consideration will be given to extending the response time. | Where good cause is shown, consideration will be given to extending the response time. | ||
Regulatory Commission, Washington, DC 20555-0001. | If you contest this enforcement action, you should also provide a copy of your response, with | ||
Notice of Violation-2-Because your response will be made available electronically for public inspection in the | the basis for your denial, to the Director, Office of Enforcement, United States Nuclear | ||
NRC Web site | Regulatory Commission, Washington, DC 20555-0001. | ||
at http://www.nrc.gov/reading-rm/adams.html, to the extent possible, it | Enclosure 1 | ||
available to the public without redaction. | |||
Notice of Violation -2- | |||
Because your response will be made available electronically for public inspection in the NRC | |||
Public Document Room or from the NRCs document system (ADAMS), accessible from the | |||
NRC Web site at http://www.nrc.gov/reading-rm/adams.html, to the extent possible, it should | |||
not include any personal privacy, proprietary, or safeguards information so that it can be made | |||
available to the public without redaction. If personal privacy or proprietary information is | |||
necessary to provide an acceptable response, then please provide a bracketed copy of your | necessary to provide an acceptable response, then please provide a bracketed copy of your | ||
response that identifies the information that should be protected and a redacted copy of your | response that identifies the information that should be protected and a redacted copy of your | ||
response that deletes such information. | response that deletes such information. If you request withholding of such material, you must | ||
specifically identify the portions of your response that you seek to have withheld and provide in | |||
detail the bases for your claim of withholding (e.g., explain why the disclosure of information will | detail the bases for your claim of withholding (e.g., explain why the disclosure of information will | ||
create an unwarranted invasion of personal privacy or provide the information required by | create an unwarranted invasion of personal privacy or provide the information required by | ||
10 CFR 2.390(b) to support a request for withholding confidential commercial or financial | 10 CFR 2.390(b) to support a request for withholding confidential commercial or financial | ||
information). | information). If safeguards information is necessary to provide an acceptable response, please | ||
provide the level of protection described in 10 CFR 73.21.In accordance with 10 CFR 19.11, you may be required to post this Notice within two | provide the level of protection described in 10 CFR 73.21. | ||
In accordance with 10 CFR 19.11, you may be required to post this Notice within two working | |||
days. | |||
License No.:DPR-45 | Dated this 13th day of November 2006 | ||
Report No.:050-00409/06-03(DNMS) | Enclosure 1 | ||
Licensee:Dairyland Power Cooperative 3200 East Avenue South | |||
La Crosse, WI | U.S. NUCLEAR REGULATORY COMMISSION | ||
Location:La Crosse | REGION III | ||
Enclosure 2 | Docket No.: 050-00409 | ||
License No.: DPR-45 | |||
Report No.: 050-00409/06-03(DNMS) | |||
Licensee: Dairyland Power Cooperative | |||
3200 East Avenue South | |||
La Crosse, WI 54602 | |||
Facility: La Crosse Boiling Water Reactor | |||
Location: La Crosse Site | |||
Genoa, Wisconsin | |||
Dates: October 17, 2006 (onsite) | |||
November 8, 2006 (in-office review) | |||
Inspector: Peter J. Lee, Ph.D., CHP, Health Physicist | |||
Approved by: Jamnes L. Cameron, Chief | |||
Decommissioning Branch | |||
Enclosure 2 | |||
EXECUTIVE SUMMARY | |||
La Crosse Boiling Water Reactor (LACBWR) | |||
NRC Inspection Report 050-00409/06-03(DNMS) | |||
This was a special, reactive inspection, performed in response to the licensees October 16, | |||
2006 Notification of Unusual Event. The licensees basis for the emergency declaration was | |||
the identification of airborne concentrations in the general areas of the reactor building that | the identification of airborne concentrations in the general areas of the reactor building that | ||
exceeded 10 times the normal level. | exceeded 10 times the normal level. On October 13, 2006, the licensee identified 3 to 5 | ||
derived air concentrations (DACs) of americium-241 in the reactor building, outside of the area | derived air concentrations (DACs) of americium-241 in the reactor building, outside of the area | ||
in the lower levels of the building where licensee staff were cutting piping associated with the | in the lower levels of the building where licensee staff were cutting piping associated with the | ||
control rod drive mechanisms. | control rod drive mechanisms. The licensee did not normally observe any detectable | ||
concentrations of americium-241 in the reactor building, however, the minimum detectable | concentrations of americium-241 in the reactor building, however, the minimum detectable | ||
concentration of americium-241 for the | concentration of americium-241 for the licensees radioanalytical counting equipment was | ||
approximately 1.0 DAC. Subsequent investigation by the licensee determined that the counting equipment | approximately 1.0 DAC. | ||
americium-241. | Subsequent investigation by the licensee determined that the counting equipment was | ||
determined that airborne concentrations were below the minimum detectable concentration.Notwithstanding the | contaminated with americium-241, which resulted in false indications of airborne | ||
americium-241. Recounting of the air samples taken between October 13 and 17, 2006, | |||
determined that airborne concentrations were below the minimum detectable concentration. | |||
Notwithstanding the licensees subsequent determination that the results of earlier air sampling | |||
in the reactor building were not valid, the licensee made a declaration of an Unusual Event on | |||
October 16, 2006, based on airborne concentrations of americium-241 that it had identified on | October 16, 2006, based on airborne concentrations of americium-241 that it had identified on | ||
every air sample taken since October 13. | every air sample taken since October 13. As a result, the licensee should have made the | ||
declaration based on those conditions on October 13, rather than waiting until October 16. | declaration based on those conditions on October 13, rather than waiting until October 16. | ||
The | The licensees failure to make a timely emergency declaration constitutes a violation of | ||
10 CFR 50.54(q).The | 10 CFR 50.54(q). | ||
in any exposures to workers or release of radioactive material to the environment. | The licensees actions following the declaration were timely and appropriate, including | ||
notification to the NRC and the subsequent recovery from the event. The event did not result | |||
in any exposures to workers or release of radioactive material to the environment. | |||
2 Enclosure 2 | |||
interviews of licensee personnel, evaluation of the results of air sampling taken | |||
between October 13 and 17, 2006, and examination of the | Report Details1 | ||
used to analyze the samples. | 1.0 Radiological Safety | ||
control rod drive mechanisms. | 1.1 Occupational Radiation Exposure (83750) | ||
building indicated the presence of airborne americium-241 at approximately 8 derived | a. Inspection Scope | ||
air concentrations (DACs). | The inspector reviewed the sequence of events associated with the licensees | ||
gamma analysis. | October 16, 2006, declaration of a Notification of Unusual Event. The review included | ||
enclosure around the work area, which included dedicated ventilation using high | interviews of licensee personnel, evaluation of the results of air sampling taken | ||
efficiency particulate air (HEPA) filters. | between October 13 and 17, 2006, and examination of the licensees counting system | ||
americium-241 outside the enclosed work and on the main floor of the reactor building. | used to analyze the samples. | ||
The licensee stopped all work on the expansion ring, however, other work in the reactor | b. Observations and Findings | ||
building continued. | On October 12, 2006, the licensee removed the reactor expansion ring, the cover for | ||
contamination, did not identify the presence of americium-241. | the failed fuel system located in the upper cavity, and the leak off tubes for the upper | ||
the main floor of the reactor building taken late October 13, 2006, continued to indicate | control rod drive mechanisms. Air samples taken from the main floor of the reactor | ||
airborne americium-241 at about the 3 DACs level. | building indicated the presence of airborne americium-241 at approximately 8 derived | ||
the reactor building an airborne radioactivity area and restricted access to only those | air concentrations (DACs). The licensee verified the results on October 13, 2006, by | ||
personnel qualified to wear respiratory protection. | gamma analysis. | ||
licensee installed HEPA filtration units to draw air from the upper cavity in an attempt to | At this time the licensee postulated that the americium-241 was caused by the work in | ||
remove the airborne radioactivity.On October 14, 2006, air sampling continued to indicate airborne americium-241 | the cavity. However, when setting up for the lower cavity work, the licensee built an | ||
expansion ring and shut off the HEPA filtration units, which were still taking a draw on | enclosure around the work area, which included dedicated ventilation using high | ||
the upper cavity, in an attempt to locate the source of the americium-241. | efficiency particulate air (HEPA) filters. The licensee could not explain the presence of | ||
maintained normal reactor building ventilation to try and clear the airborne radioactivity. | americium-241 outside the enclosed work and on the main floor of the reactor building. | ||
On October 15, 2006, the levels of airborne radioactivity remained at 3 to 5 DACs. | The licensee stopped all work on the expansion ring, however, other work in the reactor | ||
building continued. Surveys, including large area surface wipes for removable | |||
contamination, did not identify the presence of americium-241. An air sample taken on | |||
in the reactor building on hold. and declared an Unusual Event and notified NRC. | the main floor of the reactor building taken late October 13, 2006, continued to indicate | ||
licensee based its decision on an emergency action level of airborne concentrations | airborne americium-241 at about the 3 DACs level. At this time, the licensee declared | ||
greater than 10 times normal levels in the plant, as described in Table 4.1 of the | the reactor building an airborne radioactivity area and restricted access to only those | ||
personnel qualified to wear respiratory protection. As an additional measure, the | |||
ventilation. | licensee installed HEPA filtration units to draw air from the upper cavity in an attempt to | ||
indicate americium-241 concentrations at 3 to 5 DACs. | remove the airborne radioactivity. | ||
stack fan to increase the air flow through the reactor building and the building ventilated | On October 14, 2006, air sampling continued to indicate airborne americium-241 levels | ||
overnight.On October 17, 2006, early morning air samples indicated no change in | in the building in the 3 to 5 DACs range. The licensee closed all drain valves to the | ||
equipment and discovered that the sample holder was contaminated with | expansion ring and shut off the HEPA filtration units, which were still taking a draw on | ||
americium-241. | the upper cavity, in an attempt to locate the source of the americium-241. The licensee | ||
counter using an americium-241 counting standard that it had made. | maintained normal reactor building ventilation to try and clear the airborne radioactivity. | ||
piece of this source likely | On October 15, 2006, the levels of airborne radioactivity remained at 3 to 5 DACs. | ||
licensee had not noticed the contaminated sample holder previously, since the holder | 1 | ||
was not used during analyses for background radiation levels. | NOTE: A list of acronyms used in the report is included at the end of the report. | ||
the counting room and did not identify any contamination. | 3 Enclosure 2 | ||
the air samples taken from October 12 through 17. | |||
background levels.On the morning of October 17, 2006, the inspector observed the sample analyses | An air sample taken in the early morning of October 16, 2006, indicated no change in | ||
samples, no detectable airborne americium-241 actually existed in the reactor building.Title 10 CFR 50.54 (q) requires, in part, that a licensee authorized to possess | the reactor building airborne concentration of americium-241. The licensee put all work | ||
meet the standards in 10 CFR 50.47 (b) and the requirements in Appendix E to 10 CFR | in the reactor building on hold. and declared an Unusual Event and notified NRC. The | ||
Part 50. | licensee based its decision on an emergency action level of airborne concentrations | ||
Revision 25, dated December 2004. | greater than 10 times normal levels in the plant, as described in Table 4.1 of the | ||
"DPC Emergency Organization And Responsibilities," requires, in part, that the | licensees emergency plan. | ||
emergency response organization provide immediate response to an emergency | Surveys in the basement of the reactor building indicated high levels of americium-241 | ||
condition at LACBWR. | contamination. The licensee decontaminated the basement area and continued normal | ||
Levels," Table 4.1, lists potential plant conditions and their emergency classifications. | ventilation. However, air samples taken in the afternoon of October 16 continued to | ||
For the plant condition involving unplanned airborne concentrations greater than 10 | indicate americium-241 concentrations at 3 to 5 DACs. The licensee started another | ||
times normal levels, the corresponding emergency classification in Table 4.1 is a | stack fan to increase the air flow through the reactor building and the building ventilated | ||
Notification of Unusual Event. | overnight. | ||
delaying declaration of the Unusual Event until October 16, 2006, rather than on | On October 17, 2006, early morning air samples indicated no change in the | ||
October 13, 2006, constitutes a violation of 10 CFR 50.54(q). | americium-241 concentrations. The licensee examined its air sample counting | ||
Level IV violation (VIO 05000409/2006003). | equipment and discovered that the sample holder was contaminated with | ||
Enclosure | americium-241. On October 12, 2006, the licensee calibrated the gas proportional | ||
the air sample analysis results, the decision to declare was not timely. | counter using an americium-241 counting standard that it had made. Evidently, a small | ||
failure to make a timely event declaration constitutes a violation of 10 CFR 50.54(q). | piece of this source likely broke free and remained on the sample holder. The | ||
Based on subsequent re-analysis of the air samples in question, the licensee | licensee had not noticed the contaminated sample holder previously, since the holder | ||
determined that no detectable airborne contamination existed. | was not used during analyses for background radiation levels. The licensee surveyed | ||
detectable exposure to workers or releases to the environment. | the counting room and did not identify any contamination. The licensee re-analyzed | ||
corrective actions will be evaluated following receipt of the response to the Notice of | the air samples taken from October 12 through 17. The results indicated only | ||
Violation and during a future inspection. 2. | background levels. | ||
exit meeting was conducted on November 8, 2006. | On the morning of October 17, 2006, the inspector observed the sample analyses and | ||
the documents or processes reviewed by the inspector as proprietary.ATTACHMENT: | evaluated the analytical results. Based on the review of analytical results of all the air | ||
samples, no detectable airborne americium-241 actually existed in the reactor building. | |||
*J. Henkelman, Quality Assurance Specialist | Title 10 CFR 50.54 (q) requires, in part, that a licensee authorized to possess and | ||
*M. Johnsen, Tech Support Engineer | operate a nuclear power reactor follow and maintain in effect emergency plans which | ||
*L. Nelson, Health and Safety Supervisor | meet the standards in 10 CFR 50.47 (b) and the requirements in Appendix E to 10 CFR | ||
*S. Rafferty, Reactor Engineer | Part 50. The licensee maintained an emergency plan, "LACBWR Emergency Plan," | ||
* M. Moe, Captain, Burns Security | Revision 25, dated December 2004. Section 1.0 of the LACBWR Emergency Plan, | ||
*D. Egge, Quality Assurance Supervisor | "DPC Emergency Organization And Responsibilities," requires, in part, that the | ||
* R. Lewton, Electrician & Instrument Technician | emergency response organization provide immediate response to an emergency | ||
* J. McRill, Tech Support Engineer* Persons present at the exit meeting.INSPECTION PROCEDURES | condition at LACBWR. Section 4.0 of the Emergency Plan, "Emergency Action | ||
of airborne concentration in the main floor of the reactor | Levels," Table 4.1, lists potential plant conditions and their emergency classifications. | ||
building exceeding the emergency action level. | For the plant condition involving unplanned airborne concentrations greater than 10 | ||
Closed None Discussed None | times normal levels, the corresponding emergency classification in Table 4.1 is a | ||
Attachment | Notification of Unusual Event. The licensees failure to provide immediate response, by | ||
delaying declaration of the Unusual Event until October 16, 2006, rather than on | |||
October 13, 2006, constitutes a violation of 10 CFR 50.54(q). This is a Severity | |||
Level IV violation (VIO 05000409/2006003). | |||
c. Conclusions | |||
The inspector concluded that the licensees October 16, 2006, declaration of an | |||
Unusual Event was based on erroneous information, due to contamination of the | |||
4 Enclosure 2 | |||
equipment used to analyze air samples. Although the licensees classification of the | |||
event as an Unusual Event was conservative, based on plant conditions indicated by | |||
the air sample analysis results, the decision to declare was not timely. The licensees | |||
failure to make a timely event declaration constitutes a violation of 10 CFR 50.54(q). | |||
Based on subsequent re-analysis of the air samples in question, the licensee | |||
determined that no detectable airborne contamination existed. As such, there was no | |||
detectable exposure to workers or releases to the environment. The licensees | |||
corrective actions will be evaluated following receipt of the response to the Notice of | |||
Violation and during a future inspection. | |||
2.0 Exit Meeting | |||
The inspector presented the preliminary inspection results to members of the licensees | |||
staff at the conclusion of the inspection on October 17, 2006. An additional telephone | |||
exit meeting was conducted on November 8, 2006. The licensee did not identify any of | |||
the documents or processes reviewed by the inspector as proprietary. | |||
ATTACHMENT: SUPPLEMENTAL INFORMATION | |||
Enclosure 2 | |||
SUPPLEMENTAL INFORMATION | |||
PARTIAL LIST OF PERSONS CONTACTED | |||
* R. Christians, Plant Manager | |||
* R. Cota, Training/Security Supervisor | |||
* J. Henkelman, Quality Assurance Specialist | |||
* M. Johnsen, Tech Support Engineer | |||
* L. Nelson, Health and Safety Supervisor | |||
* S. Rafferty, Reactor Engineer | |||
* M. Moe, Captain, Burns Security | |||
* D. Egge, Quality Assurance Supervisor | |||
* R. Lewton, Electrician & Instrument Technician | |||
* J. McRill, Tech Support Engineer | |||
* Persons present at the exit meeting. | |||
INSPECTION PROCEDURES USED | |||
IP 83750: Occupational Radiation Exposure | |||
LIST OF DOCUMENTS REVIEWED | |||
The licensee documents reviewed and utilized during the course of this inspection are | |||
specifically identified in the Report Details above. | |||
ITEMS OPENED, CLOSED, AND DISCUSSED | |||
Opened | |||
050-00409/2006-003 VIO Failure to make a timely declaration of an Unusual Event | |||
in accordance with emergency plan following identification | |||
of airborne concentration in the main floor of the reactor | |||
building exceeding the emergency action level. | |||
Closed None | |||
Discussed None | |||
Attachment | |||
INITIALISMS AND ACRONYMS | |||
ACP Administrative Control Procedure | |||
ADAMS Agencywide Documents Access and Management System | |||
CFR Code of Federal Regulations | |||
DAC Derived Air Concentration | |||
DNMS Division of Nuclear Materials Safety | |||
HEPA High Efficiency Particulate Air | |||
LACBWR La Crosse Boiling Water Reactor | |||
NRC Nuclear Regulatory Commission | |||
PARS Publicly Available Records | |||
VIO Violation | |||
2 Attachment | |||
}} | }} |
Latest revision as of 12:06, 23 November 2019
ML063170275 | |
Person / Time | |
---|---|
Site: | La Crosse File:Dairyland Power Cooperative icon.png |
Issue date: | 11/13/2006 |
From: | Jamnes Cameron NRC/RGN-III/DNMS/DB |
To: | Berg W Dairyland Power Cooperative |
References | |
IR-06-003 | |
Download: ML063170275 (11) | |
See also: IR 05000409/2006003
Text
November 13, 2006
Mr. W. L. Berg
General Manager
Dairyland Power Cooperative
3200 East Avenue South
P.O. Box 817
La Crosse, WI 54602-0817
SUBJECT: NRC INSPECTION REPORT 050-00409/06-03(DNMS) AND
NOTICE OF VIOLATION - LA CROSSE BOILING WATER REACTOR
(LACBWR)
Dear Mr. Berg:
On November 8, 2006, the NRC completed an inspection in response to the Notification of
Unusual Event (NOUE) declared at the La Crosse Boiling Water Reactor (LACBWR) facility on
October 16, 2006. The purpose of the inspection was to determine the sequence of events that
prompted the declaration of the NOUE, the implementation of the facilitys emergency response
procedures, and the subsequent recovery from the event conditions. At the conclusion of the
onsite inspection on October 17, 2006, the NRC inspector discussed the preliminary findings
with members of your staff. On November 8, 2006, at the conclusion of our in-office review of
the circumstances related to the NOUE declaration, the inspector and I conducted a final exit
meeting with Mr. Roger Christians, Plant Manager.
The inspection consisted of an examination of activities at the facility as they relate to safety
and compliance with the Commissions rules and regulations. Areas examined during the
inspection are identified in the enclosed report. Within these areas, the inspection consisted of
a selective examination of procedures and representative records, field observations of
activities in progress, and interviews with personnel.
Based on the results of this inspection, the NRC has determined that one Severity Level IV
violation of NRC requirements occurred. The violation was evaluated in accordance with the
NRC Enforcement Policy. The current Enforcement Policy is included on the NRCs Web site
at www.nrc.gov; select What We Do, Enforcement, then Enforcement Policy. The violation is
cited in the enclosed Notice of Violation (Notice). The violation involves failure to immediately
respond to an emergency condition by declaring an Unusual Event in accordance with your
emergency plan following the identification of airborne radioactivity on the main floor of the
reactor building exceeding the emergency action level described in your plan.
Please note that you are required to respond to this letter and should follow the instructions
specified in the enclosed Notice when preparing your response. In your response to this letter,
please describe why your proposed corrective actions are expected to be more successful in
preventing future or similar violations than the actions and commitments stated in the past. The
NRC will use your response, in part, to determine whether further enforcement action is
necessary to ensure compliance with regulatory requirements.
W. Berg -2-
In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter
and its enclosure will be available electronically in the NRC Public Document Room or
from the Publicly Available Records (PARS) component of NRC's document system
(ADAMS). The NRCs document system is accessible from the NRC Web site at
http://www.nrc.gov/reading-rm/adams.html.
We will gladly discuss any questions you have concerning this inspection.
Sincerely,
/RA/
Jamnes L. Cameron, Chief
Decommissioning Branch
Docket No. 050-00409
License No. DPR-45
Enclosures:
1. Notice of Violation
2. Inspection Report 050-00409/06-03(DNMS)
cc w/encls: Roger Christians, Plant Manager
B. D. Burks, P.E., Director, Bureau of Field Operations
J. Mettner, Chairman, Wisconsin Public
Service Commission
Spark Burmaster, Coulee Region Energy Coalition
State Liaison Officer
Chief, Radiation Protection Section
WI Department of Health and
Social Services, Division of Health
DISTRIBUTION:
Docket File
PUBLIC IE-01
RIII PRR
K. I. McConnell, NMSS
K. L. Banovac, NMSS
C. M. Craig, NMSS
G. E. Grant, RIII
S. A. Reynolds, RIII
RIII Enf. Coordinator
DOCUMENT NAME:C:\FileNet\ML063170275.wpd
X Publicly Available G Non-Publicly Available G Sensitive X Non-Sensitive
To receive a copy of this document, indicate in the concurrence box "C" = Copy without attach/encl "E" = Copy with attach/encl "N" = No copy
OFFICE RIII RIII
NAME PJLee:mb JLCameron
DATE 11/13/06 11/13/06
OFFICIAL RECORD COPY
NOTICE OF VIOLATION
Dairyland Power Cooperative Docket No. 050-00409
La Crosse Boiling Water Reactor License No. DPR-45
During an NRC inspection conducted on October 17, 2006, with continuing in-office review
through November 8, 2006, a violation of NRC requirements was identified. In accordance with
the "General Statement of Policy and Procedure for NRC Enforcement Actions," the violation is
listed below:
10 CFR 50.54(q) requires, in part, that a licensee authorized to possess and operate a
nuclear power reactor follow and maintain in effect emergency plans which meet the
standards in 10 CFR 50.47(b) and the requirements in Appendix E to 10 CFR Part 50.
The licensee maintained an emergency plan, "LACBWR Emergency Plan," Revision 25,
dated December 2004. Section 1.0 of the LACBWR Emergency Plan, "DPC Emergency
Organization And Responsibilities," requires, in part, that the emergency response
organization is intended to provide immediate response to an emergency condition at
LACBWR. Section 4.0 of the Emergency Plan, "Emergency Action Levels," Table 4.1,
lists potential plant conditions and their emergency classifications. For the plant
condition involving unplanned airborne concentrations greater than 10 times normal
levels, the corresponding emergency classification in Table 4.1 is a Notification of
Unusual Event.
Contrary to the above, on October 16, 2006, the licensee declared an Unusual Event
based on airborne americium-241 concentrations of 3 to 5 derived air concentrations
(DACs) in the general areas of the reactor building. As a result, the licensee failed to
provide immediate response to the emergency condition. Specifically, the licensee
identified americium-241 concentrations at those levels on October 13, 2006, but did not
declare an Unusual Event until October 16, 2006.
This is a Severity Level IV violation (Supplement VI).
Pursuant to the provisions of 10 CFR 2.201, Dairyland Power Cooperative is hereby required to
submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN:
Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator,
Region III, within 30 days of the date of the letter transmitting this Notice of Violation (Notice).
This reply should be clearly marked as a "Reply to a Notice of Violation and should include for
each violation: (1) the reason for the violation, or, if contested, the basis for disputing the
violation or severity level, (2) the corrective steps that have been taken and the results
achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date
when full compliance will be achieved. Your response may reference or include previous
docketed correspondence, if the correspondence adequately addresses the required response.
If an adequate reply is not received within the time specified in this Notice, an order or a
Demand for Information may be issued as to why the license should not be modified,
suspended, or revoked, or why such other action as may be proper should not be taken.
Where good cause is shown, consideration will be given to extending the response time.
If you contest this enforcement action, you should also provide a copy of your response, with
the basis for your denial, to the Director, Office of Enforcement, United States Nuclear
Regulatory Commission, Washington, DC 20555-0001.
Enclosure 1
Notice of Violation -2-
Because your response will be made available electronically for public inspection in the NRC
Public Document Room or from the NRCs document system (ADAMS), accessible from the
NRC Web site at http://www.nrc.gov/reading-rm/adams.html, to the extent possible, it should
not include any personal privacy, proprietary, or safeguards information so that it can be made
available to the public without redaction. If personal privacy or proprietary information is
necessary to provide an acceptable response, then please provide a bracketed copy of your
response that identifies the information that should be protected and a redacted copy of your
response that deletes such information. If you request withholding of such material, you must
specifically identify the portions of your response that you seek to have withheld and provide in
detail the bases for your claim of withholding (e.g., explain why the disclosure of information will
create an unwarranted invasion of personal privacy or provide the information required by
10 CFR 2.390(b) to support a request for withholding confidential commercial or financial
information). If safeguards information is necessary to provide an acceptable response, please
provide the level of protection described in 10 CFR 73.21.
In accordance with 10 CFR 19.11, you may be required to post this Notice within two working
days.
Dated this 13th day of November 2006
Enclosure 1
U.S. NUCLEAR REGULATORY COMMISSION
REGION III
Docket No.: 050-00409
License No.: DPR-45
Report No.: 050-00409/06-03(DNMS)
Licensee: Dairyland Power Cooperative
3200 East Avenue South
La Crosse, WI 54602
Facility: La Crosse Boiling Water Reactor
Location: La Crosse Site
Genoa, Wisconsin
Dates: October 17, 2006 (onsite)
November 8, 2006 (in-office review)
Inspector: Peter J. Lee, Ph.D., CHP, Health Physicist
Approved by: Jamnes L. Cameron, Chief
Decommissioning Branch
Enclosure 2
EXECUTIVE SUMMARY
La Crosse Boiling Water Reactor (LACBWR)
NRC Inspection Report 050-00409/06-03(DNMS)
This was a special, reactive inspection, performed in response to the licensees October 16,
2006 Notification of Unusual Event. The licensees basis for the emergency declaration was
the identification of airborne concentrations in the general areas of the reactor building that
exceeded 10 times the normal level. On October 13, 2006, the licensee identified 3 to 5
derived air concentrations (DACs) of americium-241 in the reactor building, outside of the area
in the lower levels of the building where licensee staff were cutting piping associated with the
control rod drive mechanisms. The licensee did not normally observe any detectable
concentrations of americium-241 in the reactor building, however, the minimum detectable
concentration of americium-241 for the licensees radioanalytical counting equipment was
approximately 1.0 DAC.
Subsequent investigation by the licensee determined that the counting equipment was
contaminated with americium-241, which resulted in false indications of airborne
americium-241. Recounting of the air samples taken between October 13 and 17, 2006,
determined that airborne concentrations were below the minimum detectable concentration.
Notwithstanding the licensees subsequent determination that the results of earlier air sampling
in the reactor building were not valid, the licensee made a declaration of an Unusual Event on
October 16, 2006, based on airborne concentrations of americium-241 that it had identified on
every air sample taken since October 13. As a result, the licensee should have made the
declaration based on those conditions on October 13, rather than waiting until October 16.
The licensees failure to make a timely emergency declaration constitutes a violation of
The licensees actions following the declaration were timely and appropriate, including
notification to the NRC and the subsequent recovery from the event. The event did not result
in any exposures to workers or release of radioactive material to the environment.
2 Enclosure 2
Report Details1
1.0 Radiological Safety
1.1 Occupational Radiation Exposure (83750)
a. Inspection Scope
The inspector reviewed the sequence of events associated with the licensees
October 16, 2006, declaration of a Notification of Unusual Event. The review included
interviews of licensee personnel, evaluation of the results of air sampling taken
between October 13 and 17, 2006, and examination of the licensees counting system
used to analyze the samples.
b. Observations and Findings
On October 12, 2006, the licensee removed the reactor expansion ring, the cover for
the failed fuel system located in the upper cavity, and the leak off tubes for the upper
control rod drive mechanisms. Air samples taken from the main floor of the reactor
building indicated the presence of airborne americium-241 at approximately 8 derived
air concentrations (DACs). The licensee verified the results on October 13, 2006, by
gamma analysis.
At this time the licensee postulated that the americium-241 was caused by the work in
the cavity. However, when setting up for the lower cavity work, the licensee built an
enclosure around the work area, which included dedicated ventilation using high
efficiency particulate air (HEPA) filters. The licensee could not explain the presence of
americium-241 outside the enclosed work and on the main floor of the reactor building.
The licensee stopped all work on the expansion ring, however, other work in the reactor
building continued. Surveys, including large area surface wipes for removable
contamination, did not identify the presence of americium-241. An air sample taken on
the main floor of the reactor building taken late October 13, 2006, continued to indicate
airborne americium-241 at about the 3 DACs level. At this time, the licensee declared
the reactor building an airborne radioactivity area and restricted access to only those
personnel qualified to wear respiratory protection. As an additional measure, the
licensee installed HEPA filtration units to draw air from the upper cavity in an attempt to
remove the airborne radioactivity.
On October 14, 2006, air sampling continued to indicate airborne americium-241 levels
in the building in the 3 to 5 DACs range. The licensee closed all drain valves to the
expansion ring and shut off the HEPA filtration units, which were still taking a draw on
the upper cavity, in an attempt to locate the source of the americium-241. The licensee
maintained normal reactor building ventilation to try and clear the airborne radioactivity.
On October 15, 2006, the levels of airborne radioactivity remained at 3 to 5 DACs.
1
NOTE: A list of acronyms used in the report is included at the end of the report.
3 Enclosure 2
An air sample taken in the early morning of October 16, 2006, indicated no change in
the reactor building airborne concentration of americium-241. The licensee put all work
in the reactor building on hold. and declared an Unusual Event and notified NRC. The
licensee based its decision on an emergency action level of airborne concentrations
greater than 10 times normal levels in the plant, as described in Table 4.1 of the
licensees emergency plan.
Surveys in the basement of the reactor building indicated high levels of americium-241
contamination. The licensee decontaminated the basement area and continued normal
ventilation. However, air samples taken in the afternoon of October 16 continued to
indicate americium-241 concentrations at 3 to 5 DACs. The licensee started another
stack fan to increase the air flow through the reactor building and the building ventilated
overnight.
On October 17, 2006, early morning air samples indicated no change in the
americium-241 concentrations. The licensee examined its air sample counting
equipment and discovered that the sample holder was contaminated with
americium-241. On October 12, 2006, the licensee calibrated the gas proportional
counter using an americium-241 counting standard that it had made. Evidently, a small
piece of this source likely broke free and remained on the sample holder. The
licensee had not noticed the contaminated sample holder previously, since the holder
was not used during analyses for background radiation levels. The licensee surveyed
the counting room and did not identify any contamination. The licensee re-analyzed
the air samples taken from October 12 through 17. The results indicated only
background levels.
On the morning of October 17, 2006, the inspector observed the sample analyses and
evaluated the analytical results. Based on the review of analytical results of all the air
samples, no detectable airborne americium-241 actually existed in the reactor building.
Title 10 CFR 50.54 (q) requires, in part, that a licensee authorized to possess and
operate a nuclear power reactor follow and maintain in effect emergency plans which
meet the standards in 10 CFR 50.47 (b) and the requirements in Appendix E to 10 CFR
Part 50. The licensee maintained an emergency plan, "LACBWR Emergency Plan,"
Revision 25, dated December 2004. Section 1.0 of the LACBWR Emergency Plan,
"DPC Emergency Organization And Responsibilities," requires, in part, that the
emergency response organization provide immediate response to an emergency
condition at LACBWR. Section 4.0 of the Emergency Plan, "Emergency Action
Levels," Table 4.1, lists potential plant conditions and their emergency classifications.
For the plant condition involving unplanned airborne concentrations greater than 10
times normal levels, the corresponding emergency classification in Table 4.1 is a
Notification of Unusual Event. The licensees failure to provide immediate response, by
delaying declaration of the Unusual Event until October 16, 2006, rather than on
October 13, 2006, constitutes a violation of 10 CFR 50.54(q). This is a Severity
Level IV violation (VIO 05000409/2006003).
c. Conclusions
The inspector concluded that the licensees October 16, 2006, declaration of an
Unusual Event was based on erroneous information, due to contamination of the
4 Enclosure 2
equipment used to analyze air samples. Although the licensees classification of the
event as an Unusual Event was conservative, based on plant conditions indicated by
the air sample analysis results, the decision to declare was not timely. The licensees
failure to make a timely event declaration constitutes a violation of 10 CFR 50.54(q).
Based on subsequent re-analysis of the air samples in question, the licensee
determined that no detectable airborne contamination existed. As such, there was no
detectable exposure to workers or releases to the environment. The licensees
corrective actions will be evaluated following receipt of the response to the Notice of
Violation and during a future inspection.
2.0 Exit Meeting
The inspector presented the preliminary inspection results to members of the licensees
staff at the conclusion of the inspection on October 17, 2006. An additional telephone
exit meeting was conducted on November 8, 2006. The licensee did not identify any of
the documents or processes reviewed by the inspector as proprietary.
ATTACHMENT: SUPPLEMENTAL INFORMATION
Enclosure 2
SUPPLEMENTAL INFORMATION
PARTIAL LIST OF PERSONS CONTACTED
- R. Christians, Plant Manager
- R. Cota, Training/Security Supervisor
- J. Henkelman, Quality Assurance Specialist
- M. Johnsen, Tech Support Engineer
- L. Nelson, Health and Safety Supervisor
- S. Rafferty, Reactor Engineer
- M. Moe, Captain, Burns Security
- D. Egge, Quality Assurance Supervisor
- R. Lewton, Electrician & Instrument Technician
- J. McRill, Tech Support Engineer
- Persons present at the exit meeting.
INSPECTION PROCEDURES USED
IP 83750: Occupational Radiation Exposure
LIST OF DOCUMENTS REVIEWED
The licensee documents reviewed and utilized during the course of this inspection are
specifically identified in the Report Details above.
ITEMS OPENED, CLOSED, AND DISCUSSED
Opened
050-00409/2006-003 VIO Failure to make a timely declaration of an Unusual Event
in accordance with emergency plan following identification
of airborne concentration in the main floor of the reactor
building exceeding the emergency action level.
Closed None
Discussed None
Attachment
INITIALISMS AND ACRONYMS
ACP Administrative Control Procedure
ADAMS Agencywide Documents Access and Management System
CFR Code of Federal Regulations
DAC Derived Air Concentration
DNMS Division of Nuclear Materials Safety
HEPA High Efficiency Particulate Air
LACBWR La Crosse Boiling Water Reactor
NRC Nuclear Regulatory Commission
PARS Publicly Available Records
VIO Violation
2 Attachment