ML13318A009: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
 
(5 intermediate revisions by the same user not shown)
Line 2: Line 2:
| number = ML13318A009
| number = ML13318A009
| issue date = 11/05/2013
| issue date = 11/05/2013
| title = Nine Mile Point Nuclear Station - Submittal of Core Operating Limits Report
| title = Submittal of Core Operating Limits Report
| author name = Swift P M
| author name = Swift P
| author affiliation = Constellation Energy Nuclear Group, LLC, EDF Group, Nine Mile Point Nuclear Station, LLC
| author affiliation = Constellation Energy Nuclear Group, LLC, EDF Group, Nine Mile Point Nuclear Station, LLC
| addressee name =  
| addressee name =  
Line 15: Line 15:


=Text=
=Text=
{{#Wiki_filter:CENG.a joint venture ofConstellation
{{#Wiki_filter:CENG.
~E~eDFEnergy* 0NINE MILE POINTNUCLEAR STATIONNovember 5, 2013U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 ATTENTION:
a joint venture of Constellation  ~E~eDF Energy*         0 NINE MILE POINT NUCLEAR STATION November 5, 2013 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 ATTENTION:               Document Control Desk


==SUBJECT:==
==SUBJECT:==
Document Control DeskNine Mile Point Nuclear StationRenewed Facility Operating License No. DPR-63Unit No. 1; Docket No. 50-220Core Operating Limits ReportEnclosed is a copy of the Core Operating Limits Report, COLR1-21, Revision 1 for Nine Mile Point Unit1 (NMP1). This report is being submitted pursuant to NMPI Technical Specification 6.6.5.d.
Nine Mile Point Nuclear Station Renewed Facility Operating License No. DPR-63 Unit No. 1; Docket No. 50-220 Core Operating Limits Report Enclosed is a copy of the Core Operating Limits Report, COLR1-21, Revision 1 for Nine Mile Point Unit 1 (NMP1). This report is being submitted pursuant to NMPI Technical Specification 6.6.5.d. The COLR is being revised to provide a more robust description of Linear Heat Generation Rates (LHGR) values and their source documentation based on an internal Quality Assurance observation.
TheCOLR is being revised to provide a more robust description of Linear Heat Generation Rates (LHGR)values and their source documentation based on an internal Quality Assurance observation.
Should you have any questions regarding the information in this submittal, please contact Everett P.
Should you have any questions regarding the information in this submittal, please contact Everett P.Perkins, Director  
Perkins, Director - Licensing, at (315) 349-5219.
-Licensing, at (315) 349-5219.
Very truly yours, Paul M. Swift Manager, Engineering Services PMS/MHS
Very truly yours,Paul M. SwiftManager, Engineering ServicesPMS/MHS


==Enclosure:==
==Enclosure:==
Nine Mile Point Unit 1 Core Operating Limits Report Nine Mile Point Nuclear Station, LLC P.O. Box 63, Lycoming, NY 13093


Nine Mile Point Unit 1 Core Operating Limits ReportNine Mile Point Nuclear Station, LLCP.O. Box 63, Lycoming, NY 13093 Document Control DeskNovember 5, 2013Page 2cc: NRC Regional Administrator, Region INRC Project ManagerNRC Senior Resident Inspector ENCLOSURE Nine Mile Point Unit 1Core Operating Limits ReportNine Mile Point Nuclear Station, LLCNovember 5, 2013 NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTDocument No.:COLRI-21Revision 01NameTitleDatePrepared by:Reviewed by:Approved by:Approved by:Approved by:obert CloseJohn DarweeshPhil Wengloski Pi'sA' LFuelsEngineerFuelsEngineerSupervisor, Nuclear FuelServicesSupervisor, ReactorEngineering GeneralSupervisor, Nuclear FuelServices/0/.22/13
Document Control Desk November 5, 2013 Page 2 cc:   NRC Regional Administrator, Region I NRC Project Manager NRC Senior Resident Inspector
/0 Z//ziol4.111-This Controlled Document provides cycle specific core operating limits for use in conjunction with the Nine Mile Point Unit I Technical Specifications.
Document pages may only be changedthrough a reissue of the entire document.
COLRI-21 NINE MILE POINT UNIT I Revision 01CORE OPERATING LIMITS REPORTTERMS AND DEFINITIONS Averaqe Planar Linear Heat Generation Rate (APLHGR)The Average Planar Linear Heat Generation Rate (APLHGR) shall be applicable to a specific planarheight and is equal to the sum of the heat generation rate per unit length of fuel rod for all fuel rodsin the specified bundle at the specified height, divided by the number of fuel rods in the fuel bundleat that heightBOCBeginning of CycleMaxiumum Fraction of Limiting Power Density (MFLPD)The highest value of the fraction of limiting power density which exists in the coreEOREnd of Rated Conditions (i.e. cycle exposure at 100% power, 100% flow, all rods-out, all feedwater heaters in service and equilibrium xenon)MCPR flow dependent multiplier K(P)MCPR power dependent multiplier LHGRFAC(P)
Power dependent LHGR correction factorLinear Heat Generation Rate (LHGR)The heat generation per unit length of fuel rod. It is the integral of the heat flux over the heattransfer area associated with the fuel lengthMAPLHGRMaximum Average Planar Linear Heat Generation RateMinimum Critical Power Ratio (MCPR)The minimum in-core critical power ratioFBIRFuel Bundle Information ReportMDFWPMotor driven feedwater pumpTDFWPTurbine driven feedwater pumpPage i COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Table of Contents1.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR)1.1 Limits for Technical Specification 3.1.7.a1.2 Limits for Technical Specification 3.1.7.e2.0 MINIMUM CRITICAL POWER RATIO (MCPR)2.1 Limits for Technical Specification 3.1.7.c2.2 Limits for Technical Specification 3.1.7.e3.0 LINEAR HEAT GENERATION RATE (LHGR]3.1 Limits for Technical Specifications 3.1.7.b4.0 POWER/FLOW RELATIONSHIP DURING OPERATION 4.1 Limits for Technical Specification Table 3.1.7.d and e


==5.0 REFERENCES==
ENCLOSURE Nine Mile Point Unit 1 Core Operating Limits Report Nine Mile Point Nuclear Station, LLC November 5, 2013


FOR TECHNICAL SPECIFICATIONS 6.0 SOURCE DOCUMENTS Pawe101010181820202223Page il COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 011.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR1.1 Limits for Technical Specification 3.1.7.aDuring power operations, the APLHGR(s) for each fuel type as a function of averageplanar exposure shall not exceed the limiting values shown for GEl 1 in Table la, lb,1c, and 1d, or the limiting values shown for GNF2 in Table le, 1f, 1g, and 1h.1.2 Limits for Technical Specification 3.1.7.eDuring partial loop operation with four recirculation loops in operation, the APLHGRas a function of average planar exposure shall not exceeed 98 percent of the limitingvalues shown for GEl 1 in Table la, lb, 1c, and ld and 99 percent of the limitingvalues shown for GNF2 in Table le, If, 1g, and lh.During partial loop operation with three recirculation loops in operation, the APLHGRas a function of average planar exposure shall not exceeed 98 percent of the limitingvalues shown for GEl 1 in Table la, 1b, 1c, and ld and 99 percent of the limitingvalues shown for GNF2 in Table le, If, 1g, and 1h.Page 1 of 23 COLR1 -21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTTable laMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GE11-P9DUB376-12GZ-10OT-145-T6-2586 Average Planar Exposure MAPLHGR Limits (kWlft) (1)GWdlST KWlft0.00 9.630.20 9.631.00 9.605.00 9.4010.00 9.3715.00 9.2420.00 8.7625.00 8.3435.00 8.1045.00 8.0355.00 8.0265.00 6.18(1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Document No.:              COLRI-21 Revision 01 Name                        Title                    Date Prepared by:                                                                              /0/.22/13 Fuels Engineer Reviewed by:                                                                            /0      Z//z Fuels Engineer Approved by:
Revision 01Page 2 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Table lbMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GE II-P9DUB381-13GZ-1OOT-145-T6-2945 (GEl 1)Average Planar MAPLHGR Limits"'
obert Close              Supervisor, Nuclear Fuel Services                    iol4.111-Approved by:
(kwlft)Exposure Lattice Lattice Lattice Lattice Lattice Lattice MostGWd/ST 7433 7434 7435 7436 7437 7438 Limiting0.00 9.61 9.61 9.57 9.57 9.57 9.57 9.570.20 9.61 9.61 9.57 9.57 9.57 9.57 9.571.00 9.57 9.57 9.56 9.56 9.56 9.56 9.565.00 9.42 9.42 9.46 9.46 9.46 9.46 9.4210.00 9.37 9.37 9.34 9.34 9.34 9.34 9.3415.00 9.22 9.22 9.23 9.23 9.23 9.23 9.2220.00 9.18 9.18 9.19 9.19 9.19 9.19 9.1825.00 8.50 8.50 8.47 8.47 8.47 8.47 8.4735.00 8.19 8.19 8.28 8.28 8.28 8.28 8.1945.00 8.27 8.27 8.27 8.27 8.27 8.27 8.2755.00 8.31 8.31 8.31 8.31 8.31 8.31 8.3165.00 8.38 8.38 8.38 8.38 8.38 8.38 8.38(1) These MAPLHGR are lattice dependent.
John Darweesh              Supervisor, Reactor Engineering Approved by:
The values shown in the Most Limiting Column correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
Phil Wengloski Pi'sA' L General Supervisor, Nuclear Fuel Services This Controlled Document provides cycle specific core operating limits for use in conjunction with the Nine Mile Point Unit I Technical Specifications. Document pages may only be changed through a reissue of the entire document.
Lattice descriptions are contained in the FBIR.Page 3 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Table IcMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GEl 1-P9DUB381-14GZ-1OOT-145-T6-2946 (GEl 1)Average Planar MAPLHGR Limits")
 
(kwlft)Exposure Lattice Lattice Lattice Lattice Lattice Lattice MostGWdiST 7433 7439 7440 7441 7442 7443 Limiting0.00 10.24 10.24 10.19 10.19 10.19 10.19 10.190.20 10.24 10.24 10.19 10.19 10.19 10.19 10.191.00 10.20 10.20 10.19 10.19 10.19 10.19 10.195.00 9.91 9.91 9.85 9.85 9.85 9.85 9.8510.00 9.42 9.42 9.34 9.34 9.34 9.34 9.3415.00 9.22 9.22 9.19 9.19 9.19 9.19 9.1920.00 9.18 9.18 9.19 9.19 9.19 9.19 9.1825.00 8.64 8.64 8.63 8.63 8.63 8.63 8.6335.00 8.08 8.08 8.08 8.08 8.08 8.08 8.0845.00 8.02 8.02 7.99 7.99 7.99 7.99 7.9955.00 8.00 8.00 7.99 7.99 7.99 7.99 7.9965.00 7.97 7.97 7.96 7.96 7.96 7.96 7.96(1) These MAPLHGR are lattice dependent.
COLRI-21                                NINE MILE POINT UNIT I                                  Revision 01 CORE OPERATING LIMITS REPORT TERMS AND DEFINITIONS Averaqe Planar Linear Heat Generation Rate (APLHGR)
The values shown in the Most Limiting Column correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
The Average Planar Linear Heat Generation Rate (APLHGR) shall be applicable to a specific planar height and is equal to the sum of the heat generation rate per unit length of fuel rod for all fuel rods in the specified bundle at the specified height, divided by the number of fuel rods in the fuel bundle at that height BOC Beginning of Cycle Maxiumum Fraction of Limiting Power Density (MFLPD)
Lattice descriptions are contained in the FBIR.Page 4 of 23 COLRI -21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 01Table IdMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GEl I -P9DUB380-13GZ-1 OOT-1 45-T6-2948 (GEl 1)Average Planar MAPLHGR Limits'1 (kwlft)Exposure Lattice Lattice Lattice Lattice Lattice Lattice MostGWdIST 7433 7449 7450 7451 7447 7448 Limiting0.00 9.71 9.71 9.69 9.69 9.69 9.69 9.690.20 9.71 9.71 9.69 9.69 9.69 9.69 9.691.00 9.68 9.68 9.67 9.67 9.67 9.67 9.675.00 9.56 9.56 9.50 9.50 9.50 9.50 9.5010.00 9.38 9.38 9.32 9.32 9.32 9.32 9.3215.00 9.23 9.23 9.24 9.24 9.24 9.24 9.2320.00 9.28 9.28 9.31 9.31 9.31 9.31 9.2825.00 8.43 8.43 8.45 8.45 8.45 8.45 8.4335.00 8.09 8.09 8.09 8.09 8.09 8.09 8.0945.00 7.98 7.98 8.02 8.02 8.02 8.02 7.9855.00 7.97 7.97 7.98 7.98 7.98 7.98 7.9765.00 7.91 7.91 7.93 7.93 7.93 7.93 7.91(1) These MAPLHGR are lattice dependent.
The highest value of the fraction of limiting power density which exists in the core EOR End of Rated Conditions (i.e. cycle exposure at 100% power, 100% flow, all rods-out, all feedwater heaters in service and equilibrium xenon)
The values shown in the Most Limiting Column correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
MCPR flow dependent multiplier K(P)
Lattice descriptions are contained in the FBIR.Page 5 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Table leMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-3351 (GNF2)Average Planar Exposure MAPLHGR Limits (kWift) (1)GWd/ST KW/ft0.00 8.060.20 8.061.00 7.995.00 7.9710.00 7.8415.00 7.8920.00 7.1925.00 6.9035.00 6.7445.00 6.5355.00 6.4065.00 6.30(1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
MCPR power dependent multiplier LHGRFAC(P)
Page 6 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTTable IfMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GNF2-P10DG2B386-13GZ-100T2-145-T6-3352 (GNF2)Average Planar Exposure MAPLHGR Limits (kW/ft) (1)GWdlST KWIft0.00 8.030.20 8.031.00 8.035.00 7.9610.00 7.8315.00 7.7920.00 7.2425.00 6.9035.00 6.7445.00 6.5455.00 6.3765.00 6.29(1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
Power dependent LHGR correction factor Linear Heat Generation Rate (LHGR)
Revision 01Page 7 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 01Table IgMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-4133 (GNF2)Average Planar Exposure MAPLHGR Limits (kW/ft) (1)GWd/ST KWIft0.00 8.070.20 8.071.00 8.065.00 7.9410.00 7.8615.00 7.It20.00 7.1825.00 6.9035.00 6.7345.00 6.5455.00 6.4065.00 6.29(1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the.limiting value for the most limiting lattice for use when hand calculations are required.
The heat generation per unit length of fuel rod. It is the integral of the heat flux over the heat transfer area associated with the fuel length MAPLHGR Maximum Average Planar Linear Heat Generation Rate Minimum Critical Power Ratio (MCPR)
Page 8 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Table lhMAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSUREBundle Type: GNF2-PI0DG2B386-13GZ-100T2-145-T6-4134 (GNF2)Average Planar Exposure MAPLHGR Limits (kWlft) (1)GWdlST KW/ft0.00 7.980.20 7.981.00 8.035.00 7.9710.00 7.8215.00 7.7920.00 7.2425.00 6.9035.00 6.7445.00 6.5255.00 6.3765.00 6.29(1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to thelimiting value for the most limiting lattice for use when hand calculations are required.
The minimum in-core critical power ratio FBIR Fuel Bundle Information Report MDFWP Motor driven feedwater pump TDFWP Turbine driven feedwater pump Pagei
Page 9 of 23 COLRI -21 NINE MILE POINT UNIT I Revision 01CORE OPERATING LIMITS REPORT2.0 MINIMUM CRITICAL POWER RATIO (MCPR)2.1 Limits for Technical Specification 3.1.7.cDuring power operation, the operating MCPR shall be greater than or equal to the Operating Limit MCPR determined as the maximum of either:A) the appropriate MCPR11) from Figure (2a thru 2d)(2'31) times the K(f) shown in Figure2e,Or,B) the appropriate MCPR(P)(4) from Figure 2f.Additional MCPR(P) limits are required for operations without a backup pressure regulator.
 
These limits are shown in Figure 2g.2.2 Limits for Technical Specification 3.1.7.eDuring 3 loop operation, the Operating Limit MCPR shall be increased by 0.03. Noadjustment is needed during 4 loop operation.
COLRI-21                                  NINE MILE POINT UNIT I    Revision 01 CORE OPERATING LIMITS REPORT Table of Contents Pawe 1.0      AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR) 1.1 Limits for Technical Specification 3.1.7.a 1.2 Limits for Technical Specification 3.1.7.e 2.0      MINIMUM CRITICAL POWER RATIO (MCPR)                            10 2.1 Limits for Technical Specification 3.1.7.c                  10 2.2 Limits for Technical Specification 3.1.7.e                  10 3.0      LINEAR HEAT GENERATION RATE (LHGR]                              18 3.1 Limits for Technical Specifications 3.1.7.b                18 4.0      POWER/FLOW RELATIONSHIP DURING OPERATION                        20 4.1 Limits for Technical Specification Table 3.1.7.d and e      20
NOTES:1 Based on a 1.06 MCPR Safety Limit (SLMCPR)2 For Figures 2a thru 2d tau (T) defined as follows:'r = (Z-.-,. -T-B)/(z-A
 
-"rB)TA = 0.868 seconds, control rod average scram insertion time limit to notch 39TB =.672+1.65x NI/ N 1N 2 x.016i=I i=1n = number of surveillance tests performed in cycleNi = number of active control rods measured in the ith surveillance testti = average scram time to notch 39 of all rods measured in the iP surveillance testN1 = total number of active rods measured3 For the current exposure and feedwater pump configuration.  
==5.0      REFERENCES==
"Pump Combinations" are also described inoperating procedure NI-OP-1 6, Attachment 13.4 Introduction of the GNF2 fuel type requires use of power dependent MCPR limits for all off-rated conditions, including operations without a backup pressure regulator.
FOR TECHNICAL SPECIFICATIONS                        22 6.0      SOURCE DOCUMENTS                                                23 Page il
When power is greater than 45%, the K(P) multiplier from Figure 2f is applied to the applicable rated condition MCPR limits from Figures 2a thru 2d. At less than orequal to 45% power, the MCPR(P) limits in Figure 2f are applied directly.
 
This discussion also applies to Figure2g. Figure 2f and 2g are applicable to both GEl 1 and GNF2 fuel.Page 10 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 01Figure 2aMCPR Operating Limitsfor Feedwater Pump Combination 1 maximum flowsBeginning Of Cycle to EOR*-3851 MWd/ST(Bounds TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs)1.561.540.C.,6o 1.52ILEi1.5(1, 1.55)(1, 1.50)1.480 0.2 0.4 0.6 0.8Tau* EOR is the end of rated exposure as defined in the Cycle Management ReportPage 11 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Figure 2bMCPR Operating Limitsfor Feedwater Pump Combination I maximum flowsEOR*-3851 MWd/ST to End Of Cycle(Bounds.TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs)1.661.641.62e 1.6' 1.580.1.56E*EEE 1.541.521.51.48(1, 1.64)(1, 1.52)0 0.2 0.4 0.6 0.81Tau* EOR is the end of rated exposure as defined in the Cycle Management ReportPage 12 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Figure 2cMCPR Operating Limitsfor Feedwater Pump Combination 2 maximum flowsBeginning of Cycle to EOR*-3851 MWd/ST(Bounds TDFWP+ two MDFWPs)1.621.61.58S1.560~C.,.21.54E1.521.5(1, 1.60)(1, 1.50)1.480 0.2 0.4 0.6 0.8 1Tau*EOR is the end of rated exposure as defined in the Cycle Management ReportPage 13 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Figure 2dMCPR Operating Limitsfor Feedwater Pump Combination 2 maximum flowsEOR*-3851 MWd/ST to End Of Cycle(Bounds TDFWP+ two MDFWPs)1.721.71.681.66e. 1.64U160 1.6.21.58EEE- 1.561.541.521.5(1, 1.70)(1, 1.56)1.480 0.2 0.4 0.6 0.81Tau* EOR is the end of rated exposure as defined in the Cycle Management ReportPage 14 of 23 COLR11-21 NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Figure 2e NMP-1 K(f) Curve for MCPR1.51.41.30.CL.0'IK(f) = 1.50 when Flow < 45%, Otherwise:
COLRI-21                                NINE MILE POINT UNIT I                            Revision 01 CORE OPERATING LIMITS REPORT 1.0    AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR 1.1 Limits for Technical Specification 3.1.7.a During power operations, the APLHGR(s) for each fuel type as a function of average planar exposure shall not exceed the limiting values shown for GEl 1 in Table la, lb, 1c, and 1d, or the limiting values shown for GNF2 in Table le, 1f, 1g, and 1h.
-102.5% K(f)= MAX( 1.0, 1.33075-0.441
1.2 Limits for Technical Specification 3.1.7.e During partial loop operation with four recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceeed 98 percent of the limiting values shown for GEl 1 in Table la, lb, 1c, and ld and 99 percent of the limiting values shown for GNF2 in Table le, If, 1g, and lh.
During partial loop operation with three recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceeed 98 percent of the limiting values shown for GEl 1 in Table la, 1b, 1c, and ld and 99 percent of the limiting values shown for GNF2 in Table le, If, 1g, and 1h.
Page 1 of 23
 
COLR1 -21                                NINE MILE POINT UNIT I                                          Revision 01 CORE OPERATING LIMITS REPORT Table la MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GE11-P9DUB376-12GZ-10OT-145-T6-2586 Average Planar Exposure                        MAPLHGR Limits (kWlft) (1)
GWdlST                                          KWlft 0.00                                          9.63 0.20                                          9.63 1.00                                           9.60 5.00                                          9.40 10.00                                          9.37 15.00                                          9.24 20.00                                           8.76 25.00                                          8.34 35.00                                          8.10 45.00                                          8.03 55.00                                           8.02 65.00                                           6.18 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.
Page 2 of 23
 
COLRI-21                                      NINE MILE POINT UNIT I                                    Revision 01 CORE OPERATING LIMITS REPORT Table lb MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GE II-P9DUB381-13GZ-1OOT-145-T6-2945 (GEl 1)
Average Planar                              MAPLHGR Limits"' (kwlft)
Exposure          Lattice          Lattice        Lattice      Lattice        Lattice        Lattice          Most GWd/ST            7433              7434          7435          7436            7437          7438          Limiting 0.00            9.61              9.61          9.57          9.57            9.57          9.57            9.57 0.20            9.61              9.61          9.57          9.57            9.57          9.57            9.57 1.00           9.57              9.57          9.56          9.56            9.56          9.56            9.56 5.00           9.42              9.42          9.46          9.46            9.46          9.46            9.42 10.00           9.37              9.37          9.34          9.34            9.34          9.34            9.34 15.00            9.22              9.22          9.23          9.23            9.23          9.23           9.22 20.00            9.18              9.18          9.19          9.19            9.19          9.19            9.18 25.00           8.50              8.50          8.47          8.47            8.47          8.47            8.47 35.00            8.19             8.19         8.28          8.28            8.28          8.28            8.19 45.00           8.27              8.27          8.27          8.27            8.27          8.27            8.27 55.00           8.31              8.31          8.31          8.31            8.31          8.31            8.31 65.00           8.38              8.38          8.38          8.38            8.38          8.38            8.38 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.
Page 3 of 23
 
COLRI-21                                      NINE MILE POINT UNIT I                                    Revision 01 CORE OPERATING LIMITS REPORT Table Ic MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl 1-P9DUB381-14GZ-1OOT-145-T6-2946 (GEl 1)
Average Planar                              MAPLHGR Limits") (kwlft)
Exposure          Lattice          Lattice        Lattice        Lattice      Lattice        Lattice          Most GWdiST            7433            7439          7440          7441          7442            7443          Limiting 0.00            10.24            10.24          10.19          10.19        10.19          10.19          10.19 0.20            10.24            10.24          10.19          10.19        10.19          10.19          10.19 1.00            10.20            10.20          10.19          10.19        10.19          10.19          10.19 5.00             9.91            9.91          9.85          9.85          9.85          9.85            9.85 10.00            9.42            9.42          9.34          9.34          9.34          9.34            9.34 15.00            9.22            9.22          9.19          9.19          9.19          9.19            9.19 20.00            9.18            9.18          9.19          9.19          9.19          9.19            9.18 25.00             8.64            8.64          8.63          8.63          8.63          8.63            8.63 35.00            8.08            8.08          8.08          8.08          8.08          8.08            8.08 45.00             8.02            8.02          7.99            7.99          7.99          7.99            7.99 55.00             8.00            8.00          7.99            7.99          7.99          7.99            7.99 65.00             7.97            7.97          7.96            7.96          7.96          7.96            7.96 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.
Page 4 of 23
 
COLRI -21                                      NINE MILE POINT UNIT 1                                    Revision 01 CORE OPERATING LIMITS REPORT Table Id MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl I -P9DUB380-13GZ-1 OOT-1 45-T6-2948 (GEl 1)
Average Planar                              MAPLHGR Limits'1 (kwlft)
Exposure          Lattice          Lattice        Lattice        Lattice      Lattice        Lattice          Most GWdIST            7433              7449          7450          7451          7447          7448          Limiting 0.00            9.71              9.71          9.69          9.69          9.69          9.69            9.69 0.20            9.71              9.71          9.69          9.69          9.69          9.69            9.69 1.00            9.68              9.68          9.67          9.67          9.67          9.67            9.67 5.00            9.56              9.56          9.50          9.50          9.50          9.50            9.50 10.00            9.38              9.38          9.32          9.32          9.32          9.32            9.32 15.00            9.23             9.23          9.24          9.24          9.24          9.24            9.23 20.00           9.28              9.28          9.31          9.31          9.31          9.31            9.28 25.00           8.43              8.43          8.45          8.45          8.45          8.45            8.43 35.00           8.09              8.09          8.09          8.09          8.09          8.09            8.09 45.00           7.98              7.98          8.02          8.02          8.02          8.02            7.98 55.00            7.97              7.97          7.98          7.98          7.98          7.98            7.97 65.00           7.91              7.91          7.93          7.93          7.93          7.93            7.91 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.
Page 5 of 23
 
COLRI-21                              NINE MILE POINT UNIT I                                          Revision 01 CORE OPERATING LIMITS REPORT Table le MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-3351 (GNF2)
Average Planar Exposure                         MAPLHGR Limits (kWift) (1)
GWd/ST                                         KW/ft 0.00                                         8.06 0.20                                         8.06 1.00                                         7.99 5.00                                         7.97 10.00                                         7.84 15.00                                         7.89 20.00                                         7.19 25.00                                         6.90 35.00                                         6.74 45.00                                         6.53 55.00                                         6.40 65.00                                         6.30 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.
Page 6 of 23
 
COLRI-21                                NINE MILE POINT UNIT I                                          Revision 01 CORE OPERATING LIMITS REPORT Table If MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B386-13GZ-100T2-145-T6-3352 (GNF2)
Average Planar Exposure                       MAPLHGR Limits (kW/ft) (1)
GWdlST                                           KWIft 0.00                                           8.03 0.20                                           8.03 1.00                                           8.03 5.00                                           7.96 10.00                                           7.83 15.00                                           7.79 20.00                                           7.24 25.00                                           6.90 35.00                                           6.74 45.00                                           6.54 55.00                                           6.37 65.00                                           6.29 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.
Page 7 of 23
 
COLRI-21                                 NINE MILE POINT UNIT 1                                          Revision 01 CORE OPERATING LIMITS REPORT Table Ig MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-4133 (GNF2)
Average Planar Exposure                        MAPLHGR Limits (kW/ft) (1)
GWd/ST                                          KWIft 0.00                                          8.07 0.20                                          8.07 1.00                                          8.06 5.00                                          7.94 10.00                                          7.86 15.00                                          7.It 20.00                                          7.18 25.00                                          6.90 35.00                                          6.73 45.00                                          6.54 55.00                                          6.40 65.00                                          6.29 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the.
limiting value for the most limiting lattice for use when hand calculations are required.
Page 8 of 23
 
COLRI-21                                    NINE MILE POINT UNIT I                                      Revision 01 CORE OPERATING LIMITS REPORT Table lh MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-PI0DG2B386-13GZ-100T2-145-T6-4134 (GNF2)
Average Planar Exposure                        MAPLHGR Limits (kWlft) (1)
GWdlST                                            KW/ft 0.00                                            7.98 0.20                                            7.98 1.00                                            8.03 5.00                                            7.97 10.00                                            7.82 15.00                                            7.79 20.00                                            7.24 25.00                                            6.90 35.00                                            6.74 45.00                                            6.52 55.00                                            6.37 65.00                                            6.29 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.
Page 9 of 23
 
COLRI -21                                              NINE MILE POINT UNIT I                                        Revision 01 CORE OPERATING LIMITS REPORT 2.0  MINIMUM CRITICAL POWER RATIO (MCPR) 2.1 Limits for Technical Specification 3.1.7.c During power operation, the operating MCPR shall be greater than or equal to the Operating Limit MCPR determined as the maximum of either:
A) the appropriate MCPR11 ) from Figure (2a thru 2d)( 2'31) times the K(f) shown in Figure 2e, Or, B) the appropriate MCPR(P)(4) from Figure 2f.
Additional MCPR(P) limits are required for operations without a backup pressure regulator.
These limits are shown in Figure 2g.
2.2 Limits for Technical Specification 3.1.7.e During 3 loop operation, the Operating Limit MCPR shall be increased by 0.03. No adjustment is needed during 4 loop operation.
NOTES:
1 Based on a 1.06 MCPR Safety Limit (SLMCPR) 2 For Figures 2a thru 2d tau  (T)  defined as follows:
                  'r = (Z-.-,. - T-B)/(z-A    -  "rB)
TA= 0.868 seconds, control rod average scram insertion time limit to notch 39 TB =.672+1.65x          NI/     N      2 1N x.016 i=I        i=1 n = number of surveillance tests performed in cycle Ni = number of active control rods measured in the ith surveillance test ti = average scram time to notch 39 of all rods measured in the iPsurveillance test N1 = total number of active rods measured 3 For the current exposure and feedwater pump configuration. "Pump Combinations" are also described in operating procedure NI-OP-1 6, Attachment 13.
4 Introduction of the GNF2 fuel type requires use of power dependent MCPR limits for all off-rated conditions, including operations without a backup pressure regulator. When power is greater than 45%, the K(P) multiplier from Figure 2f is applied to the applicable rated condition MCPR limits from Figures 2a thru 2d. At less than or equal to 45% power, the MCPR(P) limits in Figure 2f are applied directly. This discussion also applies to Figure 2g. Figure 2f and 2g are applicable to both GEl 1 and GNF2 fuel.
Page 10 of 23
 
COLRI-21                              NINE MILE POINT UNIT 1                            Revision 01 CORE OPERATING LIMITS REPORT Figure 2a MCPR Operating Limits for Feedwater Pump Combination 1 maximum flows Beginning Of Cycle to EOR*-3851 MWd/ST (Bounds TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs) 1.56 (1, 1.55) 1.54 0.
C.,
6 o 1.52 IL E
i 1.5                                                                                (1, 1.50) 1.48 0            0.2              0.4              0.6              0.8 Tau
* EOR is the end of rated exposure as defined in the Cycle Management Report Page 11 of 23
 
COLRI-21                                NINE MILE POINT UNIT I                            Revision 01 CORE OPERATING LIMITS REPORT Figure 2b MCPR Operating Limits for Feedwater Pump Combination I maximum flows EOR*-3851 MWd/ST to End Of Cycle (Bounds.TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs) 1.66 1.64                                                                                  (1, 1.64) 1.62 e    1.6
'  1.58 0
. 1.56 E*
E E
E 1.54 1.52                                                                                  (1, 1.52) 1.5 1.48 0            0.2              0.4              0.6              0.81 Tau
* EOR  is the end of rated exposure as defined in the Cycle Management Report Page 12 of 23
 
COLRI-21                                NINE MILE POINT UNIT I                              Revision 01 CORE OPERATING LIMITS REPORT Figure 2c MCPR Operating Limits for Feedwater Pump Combination 2 maximum flows Beginning of Cycle to EOR*-3851 MWd/ST (Bounds TDFWP+ two MDFWPs) 1.62 1.6                                                                                  (1, 1.60) 1.58 0~S1.56 C.,
.2 1.54 E
1.52 1.5 (1, 1.50) 1.48 0          0.2              0.4              0.6              0.8            1 Tau
            *EOR  is the end of rated exposure as defined in the Cycle Management Report Page 13 of 23
 
COLRI-21                              NINE MILE POINT UNIT I                            Revision 01 CORE OPERATING LIMITS REPORT Figure 2d MCPR Operating Limits for Feedwater Pump Combination 2 maximum flows EOR*-3851 MWd/ST to End Of Cycle (Bounds TDFWP+ two MDFWPs) 1.72 1.7                                                                                (1, 1.70) 1.68 1.66
: e. 1.64 U
16 0  1.6
.2 1.58 E
E E- 1.56                                                                                (1, 1.56) 1.54 1.52 1.5 1.48 0            0.2              0.4              0.6              0.81 Tau
* EOR is the end of rated exposure as defined in the Cycle Management Report Page 14 of 23
 
COLR11-21                              NINE MILE POINT UNIT I                                                  Revision 01 CORE OPERATING LIMITS REPORT Figure 2e    NMP-1      K(f) Curve for MCPR 1.5                                                   K(f) = 1.50 when Flow < 45%,     Otherwise:
                                              -     102.5% K(f)= MAX( 1.0, 1.33075-0.441
* Flow/.100%)
* Flow/.100%)
-107.0% K(f)= MAX( 1.0, 1.35280-0.441
                                              -     107.0% K(f)= MAX( 1.0, 1.35280- 0.441
* Flow/100%)
* Flow/100%)
-112.0% K(f) = MAX( 1.0, 1.37926-0.441
                                              -     112.0% K(f) = MAX( 1.0, 1.37926- 0.441
* Flow/100%)
* Flow/100%)
-117.0% K(f) =.MAX( 1.0, 1.40352 -0.441
1.4                                      -117.0%     K(f) =.MAX( 1.0, 1.40352 - 0.441
* Flow / 100%)-Automatic K(f) = MAX( 1.0, 1.441 -0.441
* Flow / 100%)
* Flow /100%)Automatic Flow Control.117% Scoop Tube Setting1 Scoop Tube Setting107% Scoop Tube Setting102.5% Scoof Tube Setting1.21.10.9020406080100120Core Flow (% of Rated)Page 15 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 01Figure 2fMCPR(P) Limits for Normal Operation 543I I I.[(For 25% < P < 45%* MCPR(P) = [2.91+0.0285(45%-P)]
                                              -Automatic     K(f) = MAX( 1.0, 1.441 -0.441
for Core Flow > 60% Flow* MCPR(P) = [2.33+0.0510(45%-P)]
* Flow /100%)
for Core Flow !5 60% FlowMCPR(P) = K(P)
1.3
* the appropriate MCPR Limit from Figures 2athrough 2d for 45% < P <100%* K(P) = [1.216+0.00665(65%-P)]
: 0.                                            Automatic Flow Control CL
for 45% !5 P !5 65%* K(P) = [1.133+0.00415(85%-P)]
  'I                                                  .117% Scoop Tube Setting
for 65% 5 P 5 85%* K(P) = [1.000+0.00887(1 00%-P)] for 85% s P !5 100%0~08210020406080100Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)Page 16 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 01Figure 2gMCPR(P) Limits for Operation Without Backup Pressure Regulator
  .0 1.2 1    Scoop Tube Setting 1.1 107% Scoop Tube Setting 102.5% Scoof Tube Setting 0.9 0 20              40                  60                    80                    100          120 Core Flow (% of Rated)
.54IFor 25% < P < 45%* MCPR(P) = [2.91+0.0285(45%-P)]
Page 15 of 23
for Core Flow > 60% Flow* MCPR(P) = [2.33+0.0510(45%-P)]
 
for Core Flow < 60% FlowMCPR(P) = K(P)
COLRI-21                    NINE MILE POINT UNIT I                                          Revision 01 CORE OPERATING LIMITS REPORT Figure 2f MCPR(P) Limits for Normal Operation 5
* the appropriate MCPR Limit from Figures 2a through2d for 45% < P < 100%* K(P) = [1.336+0.01085(65%-P)]
I                        I                     I.
for 45% < P < 65%* K(P) = [1.198+0.00690(85%-P)]
[(For 25% < P < 45%
for 65% < P < 85%* K(P) = [1.000+0.00887(1 00%-P)] for 85% < P 5 100%F ICore Flow > 60%3ILad,210Core Flow < 60%020406080100Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)Page 17 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 013.0 LINEAR HEAT GENERATION RATE (LHGR)3.1 Limits for Technical Specification 3.11.7.bDuring power operation, the Linear Heat Generation Rate (LHGR) for all fuel bundles at any rod at anyaxial location shall not exceed either 11.0kW/ft(1) or the U02 LHGR limits shown in FBIRI-21, Rev 01,"Nine Mile Point Unit 1 Fuel Bundle Information Report" or:-The limiting values shown in MFN 11-194, "GNF2 Advantage Generic Compliance with NEDE-2401 10POA (GESTAR II), NEDC-33270P, Revision 4, October 2011" for GNF2 fuel bundles; or-The limiting values shown in 0000-0144-8220, Rev 00, "NMP1 Cycle 23 GEl 1 LHGR Limits" forGEl 1 fuel bundles.Compliance with these limits will be monitored by the plant's process computer.
* MCPR(P) = [2.91+0.0285(45%-P)] for Core Flow > 60% Flow
For power operations between 45% and 100% RTP(2) without a backup pressure regulator, operating MFLPD shall be < LHGRFAC(P)(
* MCPR(P) = [2.33+0.0510(45%-P)] for Core Flow !560% Flow MCPR(P) = K(P) *the appropriate MCPR Limit from Figures 2a through 2d for 45% < P <100%
3).NOTE:1 GNF2 LHGR limit has been set down to a maximum value of 11 kW/ft to address Emergency Procedure Guidelines (EPG) requirements.
4
2 Introduction of the GNF2 fuel type requires use of a power dependent LHGR Correction Factor, or LHGRFAC(P) for power operations without a backup pressure regulator at greater than or equal to 45% RTP. Below 45% RTP,no additional limits are required.
* K(P) = [1.216+0.00665(65%-P)] for 45% !5P !565%
Figure 3 is applicable to both GEl 1 and GNF2 fuel types.3 LHGRFAC(P) limits are provided for option B and option A scram times. If scram times are slower than option B(i.e. T > 0), then option A limits must be applied.Page 18 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 01Figure 3LHGRFAC(P)
* K(P) = [1.133+0.00415(85%-P)] for 65% 5 P 5 85%
Limits for Operation Without Backup Pressure Regulator 1.21.00.8" 0.6"-J0.40.20.0I Operating MFLPD shall be-< LHGRFAC(P)  
* K(P) = [1.000+0.00887(1 00%-P)] for 85% s P !5100%
/i- iOption BOption AOption A (T > 0)ILHGRFAC(P)  
3 0~
= [0.518] for 45% < P < 65%mLHGRFAC(P)  
08 2
= [0.636 -0.00590(85%  
1 0
-P)] for 65% < P < 85%NLHGRFAC(P)  
0        20                40                      60                    80              100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)
= [1.000 -0.02427(100%  
Page 16 of 23
-P)] for 85% < P < 100%Option B (T = 0)*LHGRFAC(P)  
 
= [0.867 -0.00650(65%  
COLRI-21                              NINE MILE POINT UNIT 1                                                Revision 01 CORE OPERATING LIMITS REPORT Figure 2g MCPR(P) Limits for Operation Without Backup Pressure Regulator
-P)] for 45% < P < 65%LHGRFAC(P)  
    .5 I
= [0.987 -0.00600(85%  
For 25% < P < 45%
-P)] for 65% 5 P 5 85%LHGRFAC(P)  
* MCPR(P) = [2.91+0.0285(45%-P)] for Core Flow > 60% Flow
= [1.000 -0.00087(100%  
* MCPR(P) = [2.33+0.0510(45%-P)] for Core Flow < 60% Flow MCPR(P) = K(P) *the appropriate MCPR Limit from Figures 2a through 2d for 45% < P < 100%
-P)] for 85% < P < 100%45 50 55 60 65 70 75 80 85 90 95 100Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)Page 19 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 014.0 POWER/FLOW RELATIONSHIP DURING OPERATION 4.1 Limits for Technical Specification 3.1.7.d and eThe power/flow relationship shall not exceed the limiting values shown in Figure 4.Page 20 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTFigure 4 Limiting Power/ Flow LineRevision 01120.00100.000880.0060.0040.0020.000.000 20 40 60 80 100Core Flow (%of Rated)120Page 21 of 23 COLRI-21NINE MILE POINT UNIT ICORE OPERATING LIMITS REPORTRevision 015.0 REFERENCE FOR TECHNICAL SPECIFICATIONS Technical Specification 6.6.5b:NEDE 24011-P-A-19, "General Electric Standard Application for Reactor Fuel,"May 2012 and the U.S. Supplement, NEDE-2401 1-P-A-1 9-US, May 2012.Page 22 of 23 COLRI-21NINE MILE POINT UNIT 1CORE OPERATING LIMITS REPORTRevision 016.0 SOURCE DOCUMENTS The Core Operating Limits contained in this report were~obtained from the following documents:
* K(P) = [1.336+0.01085(65%-P)] for 45% < P < 65%
CORE OPERATING LIMITSREFERENCES APLHGR Limits (Section 1)Table la -hand corresponding 3 and 4 loop multipliers Lattice Descriptions MCPR Limits (Section 2)0000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload22 Cycle 21, March 2013FBIR1-21, Revision 1, Nine Mile Point Unit 1 FuelBundle Information Report, April 20130000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload22 Cycle 21, March 20130000-0156-5878, Revision 1, Nine Mile Point 1 Cycle23 Cycle-Specific Offrated Power Dependent LimitsBelow Pbypass with Turbine Bypass, April 2, 2013EOR Definition LHGR Limits (Section 3)(GEl 1)(GNF2)CMR1-21, Revision 0, Nine Mile Point Unit 1, Cycle21, Cycle Management Report, May 20130000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload22 Cycle 21, March 2013FBIR1-21, Revision 1, Nine Mile Point Unit 1 FuelBundle Information Report, April 20130000-0144-8220, Revision 0, NMPI. Cycle 23 GE11LHGR Limits, September 5,. 2013MFN 11-194, Letter from A.A. Lingenfelter (GNF) to.Document Control Desk (NRC),  
4
* K(P) = [1.198+0.00690(85%-P)] for 65% < P < 85%
* K(P) = [1.000+0.00887(1 00%-P)] for 85% < P 5 100%
F                       I Core Flow > 60%
3 IL Core Flow < 60%
ad, 2
1 0
0          20                  40                      60                    80                  100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)
Page 17 of 23
 
COLRI-21                                        NINE MILE POINT UNIT 1                                Revision 01 CORE OPERATING LIMITS REPORT 3.0   LINEAR HEAT GENERATION RATE (LHGR) 3.1 Limits for Technical Specification 3.11.7.b During power operation, the Linear Heat Generation Rate (LHGR) for all fuel bundles at any rod at any axial location shall not exceed either 11.0kW/ft(1) or the U02 LHGR limits shown in FBIRI-21, Rev 01, "Nine Mile Point Unit 1 Fuel Bundle Information Report" or:
              - The limiting values shown in MFN 11-194, "GNF2 Advantage Generic Compliance with NEDE-2401 10POA (GESTAR II), NEDC-33270P, Revision 4, October 2011" for GNF2 fuel bundles; or
              - The limiting values shown in 0000-0144-8220, Rev 00, "NMP1 Cycle 23 GEl 1 LHGR Limits" for GEl 1 fuel bundles.
Compliance with these limits will be monitored by the plant's process computer.
For power operations between 45% and 100% RTP(2) without a backup pressure regulator, operating MFLPD shall be < LHGRFAC(P)(3 ).
NOTE:
1 GNF2 LHGR limit has been set down to a maximum value of 11 kW/ft to address Emergency Procedure Guidelines (EPG) requirements.
2 Introduction of the GNF2 fuel type requires use of a power dependent LHGR Correction Factor, or LHGRFAC(P) for power operations without a backup pressure regulator at greater than or equal to 45% RTP. Below 45% RTP, no additional limits are required. Figure 3 is applicable to both GEl 1 and GNF2 fuel types.
3 LHGRFAC(P) limits are provided for option B and option A scram times. Ifscram times are slower than option B (i.e. T> 0), then option A limits must be applied.
Page 18 of 23
 
COLRI-21                              NINE MILE POINT UNIT 1                                            Revision 01 CORE OPERATING LIMITS REPORT Figure 3 LHGRFAC(P) Limits for Operation Without Backup Pressure Regulator 1.2 I Operating MFLPD shall be-< LHGRFAC(P)         /
1.0                                    i-               i Option B 0.8
"  0.6
"-J Option A 0.4 Option A (T> 0)
ILHGRFAC(P) = [0.518] for 45% < P < 65%
mLHGRFAC(P) = [0.636 - 0.00590(85% - P)] for 65% < P < 85%
NLHGRFAC(P) = [1.000 - 0.02427(100% - P)] for 85% < P < 100%
0.2 Option B (T= 0)
                                                        *LHGRFAC(P) = [0.867 - 0.00650(65% - P)] for 45% < P < 65%
LHGRFAC(P) = [0.987 - 0.00600(85% - P)] for 65% 5 P 5 85%
LHGRFAC(P) = [1.000 - 0.00087(100% - P)] for 85% < P < 100%
0.0 45   50       55     60         65         70           75       80         85         90         95     100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)
Page 19 of 23
 
COLRI-21                              NINE MILE POINT UNIT I                            Revision 01 CORE OPERATING LIMITS REPORT 4.0   POWER/FLOW RELATIONSHIP DURING OPERATION 4.1 Limits for Technical Specification 3.1.7.d and e The power/flow relationship shall not exceed the limiting values shown in Figure 4.
Page 20 of 23
 
COLRI-21                      NINE MILE POINT UNIT 1          Revision 01 CORE OPERATING LIMITS REPORT Figure 4   Limiting Power/ Flow Line 120.00 100.00 80.00 0  60.00 40.00 8
20.00 0.00 0 20       40                 60         80 100 120 Core Flow (%of Rated)
Page 21 of 23
 
COLRI-21                            NINE MILE POINT UNIT I                        Revision 01 CORE OPERATING LIMITS REPORT 5.0   REFERENCE FOR TECHNICAL SPECIFICATIONS Technical Specification 6.6.5b:
NEDE 24011-P-A-19, "General Electric Standard Application for Reactor Fuel,"
May 2012 and the U.S. Supplement, NEDE-2401 1-P-A-1 9-US, May 2012.
Page 22 of 23
 
COLRI-21                                NINE MILE POINT UNIT 1                                    Revision 01 CORE OPERATING LIMITS REPORT 6.0   SOURCE DOCUMENTS The Core Operating Limits contained in this report were~obtained from the following documents:
CORE OPERATING LIMITS                        REFERENCES APLHGR Limits (Section 1)                     0000-0144-8266-SRLR, Revision 1, Supplemental Table la - h                                  Reload Licensing Report for Nine Mile Point 1 Reload and corresponding 3 and 4 loop multipliers    22 Cycle 21, March 2013 Lattice Descriptions                          FBIR1-21, Revision 1, Nine Mile Point Unit 1 Fuel Bundle Information Report, April 2013 MCPR Limits (Section 2)                      0000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload 22 Cycle 21, March 2013 0000-0156-5878, Revision 1, Nine Mile Point 1 Cycle 23 Cycle-Specific Offrated Power Dependent Limits Below Pbypass with Turbine Bypass, April 2, 2013 EOR Definition                               CMR1-21, Revision 0, Nine Mile Point Unit 1, Cycle 21, Cycle Management Report, May 2013 LHGR Limits (Section 3)                      0000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload 22 Cycle 21, March 2013 FBIR1-21, Revision 1, Nine Mile Point Unit 1 Fuel Bundle Information Report, April 2013 (GEl 1) 0000-0144-8220, Revision 0, NMPI. Cycle 23 GE11 LHGR Limits, September 5,. 2013 MFN 11-194, Letter from A.A. Lingenfelter (GNF) to
                                                            .Document Control Desk (NRC),  


==Subject:==
==Subject:==
 
"GNF2 (GNF2)                  Advantage Generic Compliance with NEDE-24011-P-A (GESTAR II), NEDC-33270P, Revision 4, October 2011," October 21,:2011 Power/Flow Relationship (Section 4)          NMP1 Technical Specification Amendment 92, Figure 3.1.7.aa Page 23 of 23}}
"GNF2Advantage Generic Compliance with NEDE-24011-P-A (GESTAR II), NEDC-33270P, Revision 4, October2011," October 21,:2011NMP1 Technical Specification Amendment 92, Figure3.1.7.aaPower/Flow Relationship (Section 4)Page 23 of 23}}

Latest revision as of 12:19, 4 November 2019

Submittal of Core Operating Limits Report
ML13318A009
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 11/05/2013
From: Swift P
Constellation Energy Nuclear Group, EDF Group, Nine Mile Point
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML13318A009 (29)


Text

CENG.

a joint venture of Constellation ~E~eDF Energy* 0 NINE MILE POINT NUCLEAR STATION November 5, 2013 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 ATTENTION: Document Control Desk

SUBJECT:

Nine Mile Point Nuclear Station Renewed Facility Operating License No. DPR-63 Unit No. 1; Docket No. 50-220 Core Operating Limits Report Enclosed is a copy of the Core Operating Limits Report, COLR1-21, Revision 1 for Nine Mile Point Unit 1 (NMP1). This report is being submitted pursuant to NMPI Technical Specification 6.6.5.d. The COLR is being revised to provide a more robust description of Linear Heat Generation Rates (LHGR) values and their source documentation based on an internal Quality Assurance observation.

Should you have any questions regarding the information in this submittal, please contact Everett P.

Perkins, Director - Licensing, at (315) 349-5219.

Very truly yours, Paul M. Swift Manager, Engineering Services PMS/MHS

Enclosure:

Nine Mile Point Unit 1 Core Operating Limits Report Nine Mile Point Nuclear Station, LLC P.O. Box 63, Lycoming, NY 13093

Document Control Desk November 5, 2013 Page 2 cc: NRC Regional Administrator, Region I NRC Project Manager NRC Senior Resident Inspector

ENCLOSURE Nine Mile Point Unit 1 Core Operating Limits Report Nine Mile Point Nuclear Station, LLC November 5, 2013

NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Document No.: COLRI-21 Revision 01 Name Title Date Prepared by: /0/.22/13 Fuels Engineer Reviewed by: /0 Z//z Fuels Engineer Approved by:

obert Close Supervisor, Nuclear Fuel Services iol4.111-Approved by:

John Darweesh Supervisor, Reactor Engineering Approved by:

Phil Wengloski Pi'sA' L General Supervisor, Nuclear Fuel Services This Controlled Document provides cycle specific core operating limits for use in conjunction with the Nine Mile Point Unit I Technical Specifications. Document pages may only be changed through a reissue of the entire document.

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT TERMS AND DEFINITIONS Averaqe Planar Linear Heat Generation Rate (APLHGR)

The Average Planar Linear Heat Generation Rate (APLHGR) shall be applicable to a specific planar height and is equal to the sum of the heat generation rate per unit length of fuel rod for all fuel rods in the specified bundle at the specified height, divided by the number of fuel rods in the fuel bundle at that height BOC Beginning of Cycle Maxiumum Fraction of Limiting Power Density (MFLPD)

The highest value of the fraction of limiting power density which exists in the core EOR End of Rated Conditions (i.e. cycle exposure at 100% power, 100% flow, all rods-out, all feedwater heaters in service and equilibrium xenon)

MCPR flow dependent multiplier K(P)

MCPR power dependent multiplier LHGRFAC(P)

Power dependent LHGR correction factor Linear Heat Generation Rate (LHGR)

The heat generation per unit length of fuel rod. It is the integral of the heat flux over the heat transfer area associated with the fuel length MAPLHGR Maximum Average Planar Linear Heat Generation Rate Minimum Critical Power Ratio (MCPR)

The minimum in-core critical power ratio FBIR Fuel Bundle Information Report MDFWP Motor driven feedwater pump TDFWP Turbine driven feedwater pump Pagei

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table of Contents Pawe 1.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR) 1.1 Limits for Technical Specification 3.1.7.a 1.2 Limits for Technical Specification 3.1.7.e 2.0 MINIMUM CRITICAL POWER RATIO (MCPR) 10 2.1 Limits for Technical Specification 3.1.7.c 10 2.2 Limits for Technical Specification 3.1.7.e 10 3.0 LINEAR HEAT GENERATION RATE (LHGR] 18 3.1 Limits for Technical Specifications 3.1.7.b 18 4.0 POWER/FLOW RELATIONSHIP DURING OPERATION 20 4.1 Limits for Technical Specification Table 3.1.7.d and e 20

5.0 REFERENCES

FOR TECHNICAL SPECIFICATIONS 22 6.0 SOURCE DOCUMENTS 23 Page il

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT 1.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR 1.1 Limits for Technical Specification 3.1.7.a During power operations, the APLHGR(s) for each fuel type as a function of average planar exposure shall not exceed the limiting values shown for GEl 1 in Table la, lb, 1c, and 1d, or the limiting values shown for GNF2 in Table le, 1f, 1g, and 1h.

1.2 Limits for Technical Specification 3.1.7.e During partial loop operation with four recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceeed 98 percent of the limiting values shown for GEl 1 in Table la, lb, 1c, and ld and 99 percent of the limiting values shown for GNF2 in Table le, If, 1g, and lh.

During partial loop operation with three recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceeed 98 percent of the limiting values shown for GEl 1 in Table la, 1b, 1c, and ld and 99 percent of the limiting values shown for GNF2 in Table le, If, 1g, and 1h.

Page 1 of 23

COLR1 -21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table la MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GE11-P9DUB376-12GZ-10OT-145-T6-2586 Average Planar Exposure MAPLHGR Limits (kWlft) (1)

GWdlST KWlft 0.00 9.63 0.20 9.63 1.00 9.60 5.00 9.40 10.00 9.37 15.00 9.24 20.00 8.76 25.00 8.34 35.00 8.10 45.00 8.03 55.00 8.02 65.00 6.18 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Page 2 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table lb MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GE II-P9DUB381-13GZ-1OOT-145-T6-2945 (GEl 1)

Average Planar MAPLHGR Limits"' (kwlft)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice Most GWd/ST 7433 7434 7435 7436 7437 7438 Limiting 0.00 9.61 9.61 9.57 9.57 9.57 9.57 9.57 0.20 9.61 9.61 9.57 9.57 9.57 9.57 9.57 1.00 9.57 9.57 9.56 9.56 9.56 9.56 9.56 5.00 9.42 9.42 9.46 9.46 9.46 9.46 9.42 10.00 9.37 9.37 9.34 9.34 9.34 9.34 9.34 15.00 9.22 9.22 9.23 9.23 9.23 9.23 9.22 20.00 9.18 9.18 9.19 9.19 9.19 9.19 9.18 25.00 8.50 8.50 8.47 8.47 8.47 8.47 8.47 35.00 8.19 8.19 8.28 8.28 8.28 8.28 8.19 45.00 8.27 8.27 8.27 8.27 8.27 8.27 8.27 55.00 8.31 8.31 8.31 8.31 8.31 8.31 8.31 65.00 8.38 8.38 8.38 8.38 8.38 8.38 8.38 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.

Page 3 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table Ic MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl 1-P9DUB381-14GZ-1OOT-145-T6-2946 (GEl 1)

Average Planar MAPLHGR Limits") (kwlft)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice Most GWdiST 7433 7439 7440 7441 7442 7443 Limiting 0.00 10.24 10.24 10.19 10.19 10.19 10.19 10.19 0.20 10.24 10.24 10.19 10.19 10.19 10.19 10.19 1.00 10.20 10.20 10.19 10.19 10.19 10.19 10.19 5.00 9.91 9.91 9.85 9.85 9.85 9.85 9.85 10.00 9.42 9.42 9.34 9.34 9.34 9.34 9.34 15.00 9.22 9.22 9.19 9.19 9.19 9.19 9.19 20.00 9.18 9.18 9.19 9.19 9.19 9.19 9.18 25.00 8.64 8.64 8.63 8.63 8.63 8.63 8.63 35.00 8.08 8.08 8.08 8.08 8.08 8.08 8.08 45.00 8.02 8.02 7.99 7.99 7.99 7.99 7.99 55.00 8.00 8.00 7.99 7.99 7.99 7.99 7.99 65.00 7.97 7.97 7.96 7.96 7.96 7.96 7.96 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.

Page 4 of 23

COLRI -21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT Table Id MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl I -P9DUB380-13GZ-1 OOT-1 45-T6-2948 (GEl 1)

Average Planar MAPLHGR Limits'1 (kwlft)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice Most GWdIST 7433 7449 7450 7451 7447 7448 Limiting 0.00 9.71 9.71 9.69 9.69 9.69 9.69 9.69 0.20 9.71 9.71 9.69 9.69 9.69 9.69 9.69 1.00 9.68 9.68 9.67 9.67 9.67 9.67 9.67 5.00 9.56 9.56 9.50 9.50 9.50 9.50 9.50 10.00 9.38 9.38 9.32 9.32 9.32 9.32 9.32 15.00 9.23 9.23 9.24 9.24 9.24 9.24 9.23 20.00 9.28 9.28 9.31 9.31 9.31 9.31 9.28 25.00 8.43 8.43 8.45 8.45 8.45 8.45 8.43 35.00 8.09 8.09 8.09 8.09 8.09 8.09 8.09 45.00 7.98 7.98 8.02 8.02 8.02 8.02 7.98 55.00 7.97 7.97 7.98 7.98 7.98 7.98 7.97 65.00 7.91 7.91 7.93 7.93 7.93 7.93 7.91 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.

Page 5 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table le MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-3351 (GNF2)

Average Planar Exposure MAPLHGR Limits (kWift) (1)

GWd/ST KW/ft 0.00 8.06 0.20 8.06 1.00 7.99 5.00 7.97 10.00 7.84 15.00 7.89 20.00 7.19 25.00 6.90 35.00 6.74 45.00 6.53 55.00 6.40 65.00 6.30 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Page 6 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table If MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B386-13GZ-100T2-145-T6-3352 (GNF2)

Average Planar Exposure MAPLHGR Limits (kW/ft) (1)

GWdlST KWIft 0.00 8.03 0.20 8.03 1.00 8.03 5.00 7.96 10.00 7.83 15.00 7.79 20.00 7.24 25.00 6.90 35.00 6.74 45.00 6.54 55.00 6.37 65.00 6.29 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Page 7 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT Table Ig MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-4133 (GNF2)

Average Planar Exposure MAPLHGR Limits (kW/ft) (1)

GWd/ST KWIft 0.00 8.07 0.20 8.07 1.00 8.06 5.00 7.94 10.00 7.86 15.00 7.It 20.00 7.18 25.00 6.90 35.00 6.73 45.00 6.54 55.00 6.40 65.00 6.29 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the.

limiting value for the most limiting lattice for use when hand calculations are required.

Page 8 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table lh MAPLHGR LIMITS VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-PI0DG2B386-13GZ-100T2-145-T6-4134 (GNF2)

Average Planar Exposure MAPLHGR Limits (kWlft) (1)

GWdlST KW/ft 0.00 7.98 0.20 7.98 1.00 8.03 5.00 7.97 10.00 7.82 15.00 7.79 20.00 7.24 25.00 6.90 35.00 6.74 45.00 6.52 55.00 6.37 65.00 6.29 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Page 9 of 23

COLRI -21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT 2.0 MINIMUM CRITICAL POWER RATIO (MCPR) 2.1 Limits for Technical Specification 3.1.7.c During power operation, the operating MCPR shall be greater than or equal to the Operating Limit MCPR determined as the maximum of either:

A) the appropriate MCPR11 ) from Figure (2a thru 2d)( 2'31) times the K(f) shown in Figure 2e, Or, B) the appropriate MCPR(P)(4) from Figure 2f.

Additional MCPR(P) limits are required for operations without a backup pressure regulator.

These limits are shown in Figure 2g.

2.2 Limits for Technical Specification 3.1.7.e During 3 loop operation, the Operating Limit MCPR shall be increased by 0.03. No adjustment is needed during 4 loop operation.

NOTES:

1 Based on a 1.06 MCPR Safety Limit (SLMCPR) 2 For Figures 2a thru 2d tau (T) defined as follows:

'r = (Z-.-,. - T-B)/(z-A - "rB)

TA= 0.868 seconds, control rod average scram insertion time limit to notch 39 TB =.672+1.65x NI/ N 2 1N x.016 i=I i=1 n = number of surveillance tests performed in cycle Ni = number of active control rods measured in the ith surveillance test ti = average scram time to notch 39 of all rods measured in the iPsurveillance test N1 = total number of active rods measured 3 For the current exposure and feedwater pump configuration. "Pump Combinations" are also described in operating procedure NI-OP-1 6, Attachment 13.

4 Introduction of the GNF2 fuel type requires use of power dependent MCPR limits for all off-rated conditions, including operations without a backup pressure regulator. When power is greater than 45%, the K(P) multiplier from Figure 2f is applied to the applicable rated condition MCPR limits from Figures 2a thru 2d. At less than or equal to 45% power, the MCPR(P) limits in Figure 2f are applied directly. This discussion also applies to Figure 2g. Figure 2f and 2g are applicable to both GEl 1 and GNF2 fuel.

Page 10 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT Figure 2a MCPR Operating Limits for Feedwater Pump Combination 1 maximum flows Beginning Of Cycle to EOR*-3851 MWd/ST (Bounds TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs) 1.56 (1, 1.55) 1.54 0.

C.,

6 o 1.52 IL E

i 1.5 (1, 1.50) 1.48 0 0.2 0.4 0.6 0.8 Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 11 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Figure 2b MCPR Operating Limits for Feedwater Pump Combination I maximum flows EOR*-3851 MWd/ST to End Of Cycle (Bounds.TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs) 1.66 1.64 (1, 1.64) 1.62 e 1.6

' 1.58 0

. 1.56 E*

E E

E 1.54 1.52 (1, 1.52) 1.5 1.48 0 0.2 0.4 0.6 0.81 Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 12 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Figure 2c MCPR Operating Limits for Feedwater Pump Combination 2 maximum flows Beginning of Cycle to EOR*-3851 MWd/ST (Bounds TDFWP+ two MDFWPs) 1.62 1.6 (1, 1.60) 1.58 0~S1.56 C.,

.2 1.54 E

1.52 1.5 (1, 1.50) 1.48 0 0.2 0.4 0.6 0.8 1 Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 13 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Figure 2d MCPR Operating Limits for Feedwater Pump Combination 2 maximum flows EOR*-3851 MWd/ST to End Of Cycle (Bounds TDFWP+ two MDFWPs) 1.72 1.7 (1, 1.70) 1.68 1.66

e. 1.64 U

16 0 1.6

.2 1.58 E

E E- 1.56 (1, 1.56) 1.54 1.52 1.5 1.48 0 0.2 0.4 0.6 0.81 Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 14 of 23

COLR11-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Figure 2e NMP-1 K(f) Curve for MCPR 1.5 K(f) = 1.50 when Flow < 45%, Otherwise:

- 102.5% K(f)= MAX( 1.0, 1.33075-0.441

  • Flow/.100%)

- 107.0% K(f)= MAX( 1.0, 1.35280- 0.441

  • Flow/100%)

- 112.0% K(f) = MAX( 1.0, 1.37926- 0.441

  • Flow/100%)

1.4 -117.0% K(f) =.MAX( 1.0, 1.40352 - 0.441

  • Flow / 100%)

-Automatic K(f) = MAX( 1.0, 1.441 -0.441

  • Flow /100%)

1.3

0. Automatic Flow Control CL

'I .117% Scoop Tube Setting

.0 1.2 1 Scoop Tube Setting 1.1 107% Scoop Tube Setting 102.5% Scoof Tube Setting 0.9 0 20 40 60 80 100 120 Core Flow (% of Rated)

Page 15 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Figure 2f MCPR(P) Limits for Normal Operation 5

I I I.

[(For 25% < P < 45%

  • MCPR(P) = [2.91+0.0285(45%-P)] for Core Flow > 60% Flow
  • MCPR(P) = [2.33+0.0510(45%-P)] for Core Flow !560% Flow MCPR(P) = K(P) *the appropriate MCPR Limit from Figures 2a through 2d for 45% < P <100%

4

  • K(P) = [1.216+0.00665(65%-P)] for 45% !5P !565%
  • K(P) = [1.133+0.00415(85%-P)] for 65% 5 P 5 85%
  • K(P) = [1.000+0.00887(1 00%-P)] for 85% s P !5100%

3 0~

08 2

1 0

0 20 40 60 80 100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)

Page 16 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT Figure 2g MCPR(P) Limits for Operation Without Backup Pressure Regulator

.5 I

For 25% < P < 45%

  • MCPR(P) = [2.91+0.0285(45%-P)] for Core Flow > 60% Flow
  • MCPR(P) = [2.33+0.0510(45%-P)] for Core Flow < 60% Flow MCPR(P) = K(P) *the appropriate MCPR Limit from Figures 2a through 2d for 45% < P < 100%
  • K(P) = [1.336+0.01085(65%-P)] for 45% < P < 65%

4

  • K(P) = [1.198+0.00690(85%-P)] for 65% < P < 85%
  • K(P) = [1.000+0.00887(1 00%-P)] for 85% < P 5 100%

F I Core Flow > 60%

3 IL Core Flow < 60%

ad, 2

1 0

0 20 40 60 80 100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)

Page 17 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT 3.0 LINEAR HEAT GENERATION RATE (LHGR) 3.1 Limits for Technical Specification 3.11.7.b During power operation, the Linear Heat Generation Rate (LHGR) for all fuel bundles at any rod at any axial location shall not exceed either 11.0kW/ft(1) or the U02 LHGR limits shown in FBIRI-21, Rev 01, "Nine Mile Point Unit 1 Fuel Bundle Information Report" or:

- The limiting values shown in MFN 11-194, "GNF2 Advantage Generic Compliance with NEDE-2401 10POA (GESTAR II), NEDC-33270P, Revision 4, October 2011" for GNF2 fuel bundles; or

- The limiting values shown in 0000-0144-8220, Rev 00, "NMP1 Cycle 23 GEl 1 LHGR Limits" for GEl 1 fuel bundles.

Compliance with these limits will be monitored by the plant's process computer.

For power operations between 45% and 100% RTP(2) without a backup pressure regulator, operating MFLPD shall be < LHGRFAC(P)(3 ).

NOTE:

1 GNF2 LHGR limit has been set down to a maximum value of 11 kW/ft to address Emergency Procedure Guidelines (EPG) requirements.

2 Introduction of the GNF2 fuel type requires use of a power dependent LHGR Correction Factor, or LHGRFAC(P) for power operations without a backup pressure regulator at greater than or equal to 45% RTP. Below 45% RTP, no additional limits are required. Figure 3 is applicable to both GEl 1 and GNF2 fuel types.

3 LHGRFAC(P) limits are provided for option B and option A scram times. Ifscram times are slower than option B (i.e. T> 0), then option A limits must be applied.

Page 18 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT Figure 3 LHGRFAC(P) Limits for Operation Without Backup Pressure Regulator 1.2 I Operating MFLPD shall be-< LHGRFAC(P) /

1.0 i- i Option B 0.8

" 0.6

"-J Option A 0.4 Option A (T> 0)

ILHGRFAC(P) = [0.518] for 45% < P < 65%

mLHGRFAC(P) = [0.636 - 0.00590(85% - P)] for 65% < P < 85%

NLHGRFAC(P) = [1.000 - 0.02427(100% - P)] for 85% < P < 100%

0.2 Option B (T= 0)

  • LHGRFAC(P) = [0.867 - 0.00650(65% - P)] for 45% < P < 65%

LHGRFAC(P) = [0.987 - 0.00600(85% - P)] for 65% 5 P 5 85%

LHGRFAC(P) = [1.000 - 0.00087(100% - P)] for 85% < P < 100%

0.0 45 50 55 60 65 70 75 80 85 90 95 100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)

Page 19 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT 4.0 POWER/FLOW RELATIONSHIP DURING OPERATION 4.1 Limits for Technical Specification 3.1.7.d and e The power/flow relationship shall not exceed the limiting values shown in Figure 4.

Page 20 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT Figure 4 Limiting Power/ Flow Line 120.00 100.00 80.00 0 60.00 40.00 8

20.00 0.00 0 20 40 60 80 100 120 Core Flow (%of Rated)

Page 21 of 23

COLRI-21 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT 5.0 REFERENCE FOR TECHNICAL SPECIFICATIONS Technical Specification 6.6.5b:

NEDE 24011-P-A-19, "General Electric Standard Application for Reactor Fuel,"

May 2012 and the U.S. Supplement, NEDE-2401 1-P-A-1 9-US, May 2012.

Page 22 of 23

COLRI-21 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT 6.0 SOURCE DOCUMENTS The Core Operating Limits contained in this report were~obtained from the following documents:

CORE OPERATING LIMITS REFERENCES APLHGR Limits (Section 1) 0000-0144-8266-SRLR, Revision 1, Supplemental Table la - h Reload Licensing Report for Nine Mile Point 1 Reload and corresponding 3 and 4 loop multipliers 22 Cycle 21, March 2013 Lattice Descriptions FBIR1-21, Revision 1, Nine Mile Point Unit 1 Fuel Bundle Information Report, April 2013 MCPR Limits (Section 2) 0000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload 22 Cycle 21, March 2013 0000-0156-5878, Revision 1, Nine Mile Point 1 Cycle 23 Cycle-Specific Offrated Power Dependent Limits Below Pbypass with Turbine Bypass, April 2, 2013 EOR Definition CMR1-21, Revision 0, Nine Mile Point Unit 1, Cycle 21, Cycle Management Report, May 2013 LHGR Limits (Section 3) 0000-0144-8266-SRLR, Revision 1, Supplemental Reload Licensing Report for Nine Mile Point 1 Reload 22 Cycle 21, March 2013 FBIR1-21, Revision 1, Nine Mile Point Unit 1 Fuel Bundle Information Report, April 2013 (GEl 1) 0000-0144-8220, Revision 0, NMPI. Cycle 23 GE11 LHGR Limits, September 5,. 2013 MFN 11-194, Letter from A.A. Lingenfelter (GNF) to

.Document Control Desk (NRC),

Subject:

"GNF2 (GNF2) Advantage Generic Compliance with NEDE-24011-P-A (GESTAR II), NEDC-33270P, Revision 4, October 2011," October 21,:2011 Power/Flow Relationship (Section 4) NMP1 Technical Specification Amendment 92, Figure 3.1.7.aa Page 23 of 23