Cycle 16 Core Operating Limits Report, Revision 1
ML032310428
Person / Time
Site: Nine Mile Point 
(DPR-063)
Issue date: 08/07/2003
From: Katz P
Constellation Energy Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NMPIL 1754
Download: ML032310428 (19)


Text

P.O. Box 63 Lycoming, New York 13093 Comsthfon Energy Group Nine Mile Point Nuclear Station August 7, 2003 NMP1L 1754 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

SUBJECT:

Nine Mile Point Unit 1 Docket No. 50-220 Facility Operating License No. DPR-63 Cycle 16 Core Operating Limits Report, Revision 1 Gentlemen:

Attached is a copy of the Cycle 16 Core Operating Limits Report (COLR), Revision 1, for Nine Mile Point Unit 1 (NMP1). Revision 1 to the Cycle 16 COLR incorporates a new section 5.0, "References for Technical Specifications," in accordance with Technical Specification (TS) 6.6.5.b (as recently revised by License Amendment No. 181). The COLR is being submitted pursuant to NMP1 TS 6.6.5.d.

Very truly yours, Peter E. Katz Vice President 1ne Mile Point PEKIDEV/bjh Attachment cc:

Mr. H. J. Miller, NRC Regional Administrator, Region I Mr. G. K. Hunegs, NRC Senior Resident Inspector Mr. P. S. Tam, Senior Project Manager, NRR (2 copies)

AM

ATTACHMENT Nine Mile Point Unit 1 Cycle 16 Core Operating Limits Report, Revision 1

o000x8W NINE MILE POINT UNIT I CORE OPEARATING LIMITS REPORT Document No.:

COLR1-16 Revision 1 Name Title Date Prepared by:

C. W.

LepIne C W. Lepine' Fuel Engineer Reviewed by:

Independently Reviewed by:

Approved by:

Fuel Engineer G.E d i m, Fuel Engineer M. A. Armenta Principal Engineer, Nuclear Fuels Services Approved by:

J. N. Darweesh 71/av 3 Supervisor, Reactor Engineering Approved by:

C

~

~~

Director, Nuclear Fuels Services This Controlled Document provides cycle specific core operating limits for use in conjunction with the NMe Mile Point Unit 1 Technical Specifications. Document pages may only be changed through a reissue of the entire document.

NINE MLE POINT UNIT 1 COLR1-16 Rev. 1 CORE OPERA TIG LIMITS REPORT Table of Contents Mage 1.0 AVERAGE PLANAR LlNEAR HEAT GENERATION RATE (APLHGR)...........-.. 1 1.1 Limits [or Technical Specification 3.1.7.a.....~........-...-...-......

I........._..._...

1.2 Limits for Technical Specification 3.l.7.e._

1 2.0 MINMIUM CRITICAL P OWER R ATIO (ICPR) 2 2.1 Limits for Technical Specification 3.1.7.c.

2 2.2 Limits for Technical Specification 3.1.7.e.....................................................

2 3.0 LEWAR HEAT GENERATION RATE GR)...............................3 3.1 Limits for Technical Specifications 3.1.7.b....

4.0 IPOWER/HFOW RELATIONSHIP DURING OPERATION........

4.1 Limits for Technical Specification Table 3.1.7.d and e..

5.O REFERENCES FOR TECINICAL SPECIFICATIONS.......................

6.0 SOUJRCE DOCUM.3

_S Page i

NINE MILE POINr UNiT 1 COLIU-16 Rev. 1 CORE OPERATING LIMITS REPORT 1.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR) 1.1 limits for Technical Specification 3.1.7.a(*)

During power operation, the APLHGR for each type of fuel as function of average planar exposure shall not exceed the limiting values shown in Tables lathrough le.

1.2 Limits for Technical Snoedfication 3.1.7.(*)

During partial loop operation with four recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceed 98 percent of the limiting values shown in Tables la through le.

During partial loop operation with three recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceed 98 percent of the limitng values shown in Tables la through le.

(*)

When hand calculations are required, the APLHGR for the respective fuel type as a fimcdon of average planar exposure, shall not exceed the limits shown in Table If during five recirculation loop operation or 98 percent of the Emits shown in Table If during four or three loop operation..

Page 1 of 15

NINE rME POINT UNIT I COLR1-16 Rev. 1 2.0 MINIMUM CRITICAL POWER RATIO (MICPR) 2.1 Limits for Technical Specification 3.1.7.c During power operation, the opcrating MCPR at rated power and flow shall be greater than or equal to the Operating Limit MCPR of 1.45(1).

For core flows other than rated, the MCPR limit shall be the Operating Limit MCPR identified above times Kf where Kf is as shown in Figure 2a If the feedwater pump configuration as defined by Nuclear Engineering Report No. NER-IM-02 is such that a fitewater controller filure could result in maimu feedwater flow greater than that for two feedwater pumps (i.e., the shaft-driven pump plus one motor-driven pump), then the Operating Limit MCPR shall be 1.59.

Conservative imits for operation between 45% and 90/o RTP° are required for operations without a backup pressure regulator. The MCPR based limit for operation without a backup pressure regulator is as shown in Figure 2b(4.

2.2 Limits for Technical Specification 3.1.7.e During 3 loop operation, the Operating Limit MCPR shall be increased by 0.02.

NOTES:

(1)

Based on a 1.07 MCPR Safety Limit (SLCPR).

)

Based on an Operatling Limit MCPR of 1.45.

° Below 45%. and above 90%/ RTP no additional limits are required for operation without a backup pressure regulator.

° These lirits are valid for 3, 4, or 5 loop operation..

Page 2 ofl5

NIE IL POINT UNIT 1 COLRI-16 Rev. I 3.0 LINEAR HEAT GENERATION RATE (LHGR) 3.1 Limits for Technical Specification 3.1.7.b During power operation, the Lnear Heat Generation Rate (LHGR) of any rod in any fuel assembly at any axial location shall not exceed 11.0 KWFET.

Conservative limits for operation between 45% and 90°/e RTP(l) are required for operations without a backup pressr reguator. The LHGR based limit for operation without a backup pressure regulatr is as shown in Figure 3.

NOTE:

(1)

Below 45% and above 90°/ RTP no additional Eimits are required for operation without a backup pressure regulator.

Page 3 of 15

NINE MELE POINT UNIT 1 COLR1-16 Rev. 1 4.0 POWER/FLOW RELATIONSHIP DURING OPERATION 4.1 imits for Technical Specification 3.1.7.d and e The power/flow relationship shall not exceed the limiting values shown in Figure 4.

5.0 REFERENCES

FOR TECHNICAL SPECIFICATIONS Technical Specification 6.6.5.b:

NEDE 2401I-P-A, 'General Electric Standard Application for Reactor Fuel,' U.S.

Supplement, Revision 14, June 2000.

Page 4 of 1S

NINE MELE POINT UNIT 1 COLR1-16 Rev. 1 6.0 SOURCE DOCUMENTS The Core Operating Limits contained in this report were obtained from the following documents:

CORE OPERATING LIMITS APLHGRLts (Section 1.0)

Table latdhnugh If andorpodingree and fiur loop multiplers BN~EFRECE_

GE 11 I-02962MAP, Revision 0, January 1997, Lattice Dqpndent MAPLHGR Report for Nine Mile Point Nuclear Power Station Unit 1, Reload 14 Cyclc 13 GE J1-02962SRLR, Revision 0, January 1997, Supplemetal Reload Licensing Report for Nine Mile Poit Nuclear Station Unit 1 Reload 14 Cycle 13 GNF J1 1-03785ER, Revision 0, February 2001, Engineering Report for Nine Mle Point Nuclear Station Unit 1 Reload 16 0000-0012-7557ER, Revision 0, March 2003 Engieeig Report for Nine Mile Point Nuclear Station Unit I Reload 17 MCPR Limts (Section 2)

Pressure Regulator Out-oP-Service Restriction LHGR Limits (Section 3)

Pressure Regulator Out-of-Service rertriction Powe/Flw Rlatansix,(Sedtion 4) 0000-0012-7557ER, Revision 0, March 2003 Fgineerng Report for Nine Mile Pont Nuclear Station Unit 1 Reload 17 GE-NE-JI 1-03433-16-01-00, "Pressure Regulator Out of Service Calculations forNine Mile Point Unit I Cycle 14", March 2001 0000-0012-7557ER, Revision 0, March 2003 Engeering Report for Nine Mile Point Nuclear Station Unit 1 Reload 17 GE-NE-I 1-03433-16-01-00, "Pressure Regulator Out of Service Calculations for Ninc Mile Point Unit I Cycle 14", March2001 NMP1 Technical Specfication Anirdmnat 92, Figue 3.1.7.aa Page 5 of 1S

NINE MILE POINT UNIT 1 COLR11-16, RevisionI Table Ia MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GE1I-P9DUB376-12GZ-1OOT-144-T-2583 (GE11)

Average Planar Exposure _

MAPLHGR Limits (kwlft)

GWd)ST Lattice Lattice Lattice Lattice Lattice 6662 6663 6664 6665 6666 0.00 9.28 8.47 8.50 9.31 9.77 0.20 9.21 8.51 8.54 9.28 9.75 1.00 9.07 8.58 8.62 9.14 9.67 2.00 9.04 8.69 8.74 9.12 9.66 3.00 9.07 8.80 8.87 9.14 9.69 4.00 9.11 8.93 9.01 9.19 9.73 5.00 9.16 9.07 9.16 9.23 9.77 6.00 9.20 9.17 9.32 9.28 9.75 7.00 9.23 9.24 9.48 9.31 9.71 8.00 9.26 9.31 9.57 9.34 9.68 9.00 9.28 9.39 9.64 9.36 9.64 10.00 9.29 9.47 9.61 9.38 9.61 12.50 9.31 9.57 9.57 9.39 9.57 15.00 9.30 9.53 9.53 9.39 9.53 17.50 8.97 9.53 9.53 9.08 9.53 20.00 8.64 9.08 9.08 8.75 9.08 25.00 7.98 8.83 8.83 8.09 8.70 30.00 7.34 8.33 8.40 7.45 6.05 35.00 6.70 7.78 7.85 6.81 7.42 40.00 6.07 7.24 7.29 6.18 6.80 45.00 5.45 6.70 6.72 5.56 6.17 45.02 5.44 45.48 5.50 48.07 5.79 49.34 ---

6.22 49.82 6.10 NOTE: A '-" Indicates that there Is no entry for this box and the limit can be determined by linearly Interpolating between the previous and next point In each column.

MAPLHGRs are Interpolated between exposure points for which explicit values are given. The exposure for the last MAPLHGR listed fora lattice is the maximum allowed nodal exposure for that lattice.

Page 6 of 15

NINE MILE POINT UNIT 1 COLR1-116, Revision 1 Table 1b MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEII -PBDUB376-12GZ-14 OT145-T.2584 (GE1 1)

Average Planar Exposure

_MAPLHGR ULmits (kwr)

GWdlST Lattice Lattice Lattice Lattice Lattice S662 6663 5667 5665 5666 0.00 9.26 8.47 8.54 9.31 9.77 0.20 9.21 8.51 8.58 9.26 9.75 1.00 9.07 8.58 8.67 9.14 9.67 2.00 9.04 8.69 8.81 9.12 9.66 3.00 9.07 8.80 8.97 9.14 9.69 4.00 9.11 8.93 9.13 9.19 9.73 5.00 9.16 9.07 9.31 9.23 9.70 6.00 9.20 9.17 A81 928 9.69 7.00 9.23 9.24 9.47 9.31 9.69 8.00 9.26 9.31 9.55 9.34 9.68 9.00 9.28 9.39 9.64 9.36 9.68 10.00 9.29 0.47 9.67 9.38 9.67 12.50 9.31 9.60 9.60 9.39 9.60 15.00 9.30 9.53 9.53 9.39 9.53 17.50 8.97 9.53 9.53 9.08 9.53 20.00 8.64 9.08 9.08 8.75 9.08 25.00 7.98 8.83 8.63 8.09 8.70 30.00 7.34 8.33 8.41 7.45 8.05 35.00 6.70 7.78 7.74 6.81 7.42 40.00 6.07 7.24 7.11 6.18 6.80 45.00 5.45 6.70 6.52 5.56 6.17 45.02 5.44 45A.8 5.50 48.07

__5.79 49.34 6.22 49.83 5.99 NOTE: A "-n indicates that there is no entry for this box and the limHt can be deternined by linearly Interpolating between the previous and next point in each column.

MAPLHGRs are interpolated between exposure points for which explicit values are gIven. The exposure for the last MAPLHGR listed fora lattice Is the maximum allowed nodal exposure for that lattice.

Page 7 of 15

NINE MILE POINT UNIT 1 COLR1-16, Revision I Table 1c MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GE1 -P9DUB362-43GZ-10OT-145-T-2414 (GE11)

Average Planar MAPLIGR wmits

)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice GWd/ST 8047 8048 8049 8050 8051 8052 0.00 8.80 8.66 8.79 6.64 8.60 8.80 0.20 8.82 8.71 8.82 8.67 8.82 8.82 1.00 8.89 8.79 8.89 8.74 8.89 8.89 2.00 8.97 8.90 8.97 8.82 8.97 8.97 3.00O 9.06 9.01 9.05 8.91 9.06 9.06 4.00 9.11 9.12 9.13 9.00 9.14 9.14 5.00 9.16 9.20 9.22 9.09 9.22 9.22 6.00 9.20 9.29 9.29 9.19 9.28 9.29 7.00 9.23 9.38 9.36 9.29 9.31 9.36 8.00 9.26 9.42 9.42 9.40 9.34 9.42 9.00 9.28 9.49 9.49 9.49 9.36 9.49 10.00 9.29 9.56 9.56 9.56 9.38 9.56 12.50 9.31 9.53 9.53 9.53 9.39 9.53 15.00 9.30 9.50 9.50 9.50 9.39 9.50 17.60 8.97 9.49 9.49 9.49 9.08 9.49 20.00 8.64 9.44 9.44 9.33 8.75 9.43 25.00 7.98 8.76 8.76 8.76 8.09 8.76 30.00 7.34 8.32 8.32 8.20 7.45 8.14 35.00 6.70 7.78 7.76 7.64 6.81 7.51 40.00 6.07 7.20 7.20 7.11 6.18 6.88 45.00 5.45 6.64 6.64 6.53 5.56 6.26 45.02 5.44 45.48 5.50 48.44 5.83 48.78 6.17 49.20 6.19 49.25 6.18 NOTE: A "-" Indicates that there Is no entry for this box and the limit can be determined by linearly interpolating between the previous and next point In each column.

MAPLHGRs are Interpolated between exposure points for which explicit values are given. The exposure for the last MAPLHGR listed for a lattice is the maximum allowed nodal exposure for that lattice.

Page 8 Of 15

NINE MILE POINT UNIT 1 COLR1-16, Revision I Table Id UAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEil-P9DUB3404-2GZ1-40T-1445-T (GEI 1)

Average Planar MAPLHGR Umits (kw/lt)

Exposure Lattice Lattice Lattice Lattice iattice Lattice GWd/ST 2361 2419 2420 2364 2366 2367 0.00 9.28 8.39 8.53 8.45 9.34 9.79 0.20 9.23 8.42 8.55 8.49 9.29 9.77 1.00 9.10 8.48 8.60 8.60 9.16 9.69 2.00 9.07 8.62 8.73 8.75 9.14 9.68 3.00 9.10 8.75 8.90 8.92 9.17 9.71 4.00 9.14 8.84 8.98 9.09 9.21 9.75 5.00 9.18 8.94 9.06 9.20 9.26 9.79 6.00 9.22 9.02 9.14 9.29 9

.30 9.82 7.00 9.26 9.10 9.21 9.37 9.34 9.85 8.00 9.28 9.19 9.28 9.45 9 36 9.87 9.00 9.30 9.27 9.34 9.51 9.38 9.89 10.00 9.32 9.34 9.40 9.55 9A0 9.90 12.50 9.33

.44 944 9.41 9.42 9.90 15.00-9.32 9.45 9.45 9.47 941 9.89 17.50 9.00 9818 9.18 9.29 911 9.70 20.00 8.67 8.90 8.91 9.00 8.77 9.37 25.00 8.01 8.35 8.36 8.42 8.12 8.71 30.00 7.37 7.82 7.83 7.88 7.48 8.07 35.00 6.73 7.31 7.31 7.36 6.84 7.44 40.00 6.10 6.80 6.81 6.84 6.21 6.82 45.00 5.48 6.29 6.30 6.33 5.59 6.19 45.18 5.45 45.64 5.51 47.13 6.07 47.21

_6.07 47.77 6.05 48.19 5.79 NOTE: A '-" indicates that there Is no entry for this box and the limit can be determined by linearly Interpolating between the previous and next point in each column.

MAPLiGRs are Interpolated between exposure points forwhich explicit values are given. The exposure for the last MAPLHGR listed for a lattice is the maximum allowed nodal exposure for that lattice.

Page 9 of 15

NINE MILE POINT UNIT I COLR1-16, Revision I Table 1e MAPLHtR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEI-119DUB339-12GZ-100T-145-T-2334 (GE11)

Average Planar iIMAPLHGR Limits (iwtm)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice GWdtST 2718 2719 2720 2721 2722 2723 0.00 8.88 8.72 8.85 8.60 8.88 8.88 0.20 8.90 8.75 8.90 8.65 8.90 8.90 1.00 8.96 8.81 8.96 8.76 8.96 8.96 2.00 9.04 8.88 9.03 8.92 9.05 9.05 3.00 9.07 8.96 9.10 9.08 9.14 9.14 4.00 9.11 9.04 9.17 9.23 9.19 9.23 5.00 9.16 9.12 9.24 9.32 9.23 9.32 6.00 9.20 9.20 9.32 9.39 9.28 9.39 7.00 9.23 9.29 9.39 9.48 9.31 9.46 8.00 9.26 9.38 9.47 9.52 9.34 9.52 9.00 9.28 9.47 9.55 9.59 9.36 9.59 10.00 9.29 9.56 9.63 9.66 9.38 9.66 12.50 9.31 9.62 9.62 9.62 9.39 9.62 15.00 9.30 9.57 9.57 9.57 9.39 9.57 17.50 8.97 9.33 9.33 9.33 9.08 9.33 20.00 8.64 8.85 8.85 8.85 8.75 8.85 25.00.

7.98 8.88 8.68 8.68 8.09 8.68 30.00 7.34 824 8.25 8.29 7.45 8.05 35.00 6.70 7.72 7.73 7.90 6.81 7.42 40.00 6.07 7.23 7.24 7.33 6.18 6.80 45.00 5.45 6.76 6.76 6.79 5.56 6.17 45.02 5.44 45.48 5.50 48.07 5.79 49.70 6.28 5

49.75 6.28 50.00 6.28 NOTE: A t-" indicates that there Is no entry for this box and the limit can be deterrnined by linearly Interpolating between the previous and next point In each column.

MAPLHGRs are Interpolated between exposure points for which explicit values are given. The exposure for the last MAPLHGR listed for a lattice is the maximum allowed nodal exposure for that lattice.

Page 10 of 15

NINE MILE POINT UNIT I COLR1-18, Revision 1 Table If Most Limiting MAPLHGR vs. Average Planar Exposure Average MAPLHGR Llimts (kwlft)

Planar Exposure P9DUB339 P9DU6362 P9DUB340 PgDUB376 P9DUB376 (GWdIST)

(2583)

(2584) 0.00 8.60 8.64 8.39 8.47 8.47 0.20 8.65 8.67 8.42 6.51 8.51 1.00 8.76 8.74 8.48 8.58 8.58 2.00 8.68 8.82 8.62 8.69 8.69 3.00 8.96 8.91 8.75 8.80 8.80 4.00 9.04 9.00 8.84 8.93 8.93 5.00 9.12 9.09 8.94 9.07 9.07 6.00 9.20 9.19 9.02 9.17 9.17 7.00 9.29 9.29 9.10 9.24 9.24 8.00 9.38 9.40 9.19 9.31 9.31 9.00 9.47 9.49 9.27 9.39 8.39.

10.00 9.66 9.56 9.34 9.47 9.47 12.50 9.62 9.53 9.41 9.57 9.60 15.00 9.57 9.50 9.45 9.53 9.53 17.50 9.33 9.49 9.18 9.53 9.53 20.00 8.85 9.33 8.90 9.08 9.08 25.00 8.68 8.76 8.35 8.83 8.83 30.00 8.24 8.20 7.82 8.33 8.33 35.00 7.72 7.64 7.31 7.78 7.74 40.00 7.23 7.11 6.80 7.24 7.11 45.00 6.76 6.53 6.29 6.70 6.52 47.13 6.07 47.16 48.78 6.17 49.34 6.16 6.04 49.82 49.83 49.70 6.28 NOTE: A *-"Indicates that there Is no entry for this box and the limit can be determined by linearly Interpolating between the previous and next point In each column.

MAPLHGRs are Interpolated between exposure points for which explicit values are given. The exposure for the last MAPLHGR listed for a lattice Is the maximum allowed nodal exposure for that lattice.

Page 11 of 15

NM MIE POINT UNIT f COLRI-16, Revision I Figure 2a NMP-1 K(f) Curve for MCPR 1.5 1.4 It IL 0

1.3 1.2 1.1 1

0.9 0

20 40 60 80 100 Core Flow (% of Rated) 120 Page 12 of 15

NINE MILE POINT UNIT 1 COLRI-16, Revision I Figur 2b: MCPR Limits for Operation Between 46% and 90% RTP Without a Backup Pressure Regulator 2.6

-=

MCPR Unit (P)

For 45% S P s 70% AND Core Flow s 75% Flow MCPR LUmt (P) a 11.6540124(O%-P)l OR za For45 70_

Far45SP57O% AND Core Flow 75% Flow 2.3 MCPR Limit (P) - [1.71 +0.01 6(70%-P)I For 70S% SP -90O S:

MCPR Ir it-1 A5 /FRTP i

~Opran iMCPR shan be i MCPR UmMt 2.1 1

\\

~~~COr FlOwH 7596 1.7 Co1 F.w s 75_

45 50 55 s0 65 70 75 so Core Thrmal Power (P) In units of % Rated Thermial Power (%RTPI 85 90 Page 13 of 15

NINE MILE POINT UNIT I COI^RI-16. Revision I Figure 3: LHGR Llmits for Operatlon Between 45% and 10% RTP WiAthut a Backup Pressure Regulator I

Core Flows 75%

0.8 o~~~~~~~~~e~~~ _

[~~~~

Dpn SMFU biXie s MFUPD Ci nit h 0.4 MFLPD Umft-For 45% S P S 70% AND Core Flow s 75%FlFbw MFLPD Urnfl a -[0.".01 (70%-P)j 02 ELSE For45% s P *go:

MFLPD LUit= FRTP 0

a a

a 45 60 55 60 a5 70 75 60 Core lbennad Power (P) In units of% Rated Thermal Power (%RTP) 85 90 Page 14 of 15

NINE MILE POIN UNIT 1 COLRI-16, Revision I Rgum 4 Lini~ng Pow/I Flow Line 120.00 "a-a.

i4~

0 40 Page 15 of 15 100