Submittal of Core Operating Limits Report
ML12156A368
Person / Time
Site: Nine Mile Point 
Issue date: 05/30/2012
From: Swift P
Constellation Energy Nuclear Group, EDF Group, Nine Mile Point
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML12156A368 (26)


Text

,~

CENGM a joint venture of 0Constelliatn 4.1e9.

Energy eDF NINE MILE POINT NUCLEAR STATION P.O. Box 63 Lycoming, NY 13093 May 30, 2012 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 ATTENTION:

SUBJECT:

Document Control Desk Nine Mile Point Nuclear Station Unit No. 1; Docket No. 50-220 Core Operating Limits Report Enclosed is a copy of the Core Operating Limits Report, COLR1-20, Revision 1 for Nine Mile Point Unit 1 (NMP 1). This report is being submitted pursuant to NMPI Technical Specification 6.6.5.d.

Should you have any questions regarding the information in this submittal, please contact John J. Dosa, Licensing Director, at (315) 349-5219.

Very truly yours, Paul M. Swift Manager, Engineering Services PMS/MHS

Enclosure:

Nine Mile Point Unit 1 Core Operating Limits Report cc:

NRC Regional Administrator, Region I NRC Project Manager NRC Senior Resident Inspector

ENCLOSURE Nine Mile Point Unit 1 Core Operating Limits Report Nine Mile Point Nuclear Station, LLC May 30, 2012

i NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Document No.:

COLRI-20 Revision 01 Name Title Date Prepared by:

Reviewed by:

Approved by:

Approved by:

Approved by:

Melisa Krick f'? 1f¶uel Engineer William Carter Robert Close V'

John Darweesh Fuel Engineer Supervisor, Nuclear Fuels Services Supervisor, Reactor Engineering General Supervisor, Nuclear Fuels Services

~(c~ ~

This Controlled Document provides cycle specific core operating limits for use in conjunction with the Nine Mile Point Unit I Technical Specifications. Document pages may only be changed through a reissue of the entire document.

I' COLRI -20 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT TERMS AND DEFINITIONS Average Planar Linear Heat Generation Rate (APLHGR)

The Average Planar Linear Heat Generation Rate (APLHGR) shall be applicable to a specific planar height and is equal to the sum of the heat generation rate per unit length of fuel rod for all fuel rods in the specified bundle at the specified height, divided by the number of fuel rods in the fuel bundle at that height BOC Beginning of Cycle Maxiumum Fraction of Limiting Power Density (MFLPD)

The highest value of the fraction of limiting power density which exists in the core EOR End of Rated Conditions (i.e. cycle exposure at 100% power, 100% flow, all rods-out, all feedwater heaters in service and equilibrium xenon)

KPfo MCPR flow dependent multiplier K(P)

MCPR power dependent multiplier LHGRFAC(P)

Power dependent LHGR correction factor Linear Heat Generation Rate (LHGR)

The heat generation per unit length of fuel rod. It is the integral of the heat flux over the heat transfer area associated with the fuel length MAPLHGR Maximum Average Planar Linear Heat Generation Rate Minimum Critical Power Ratio (MCPR)

The minimum in-core critical power ratio RSLD Reload Specific Lattice Data Document MDFWP Motor driven feedwater pump TDFWP Turbine driven feedwater pump Page i

t COLRI -20 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT Table of Contents Page 1.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR) 1 1.1 Limits for Technical Specification 3.1.7.a 1

1.2 Limits for Technical Specification 3.1.7.e 1

2.0 MINIMUM CRITICAL POWER RATIO (MCPR) 8 2.1 Limits for Technical Specification 3.1.7.c 8

2.2 Limits for Technical Specification 3.1.7.e 8

3.0 LINEAR HEAT GENERATION RATE (LHGR) 16 3.1 Limits for Technical Specifications 3.1.7.b 16 4.0 POWERIFLOW RELATIONSHIP DURING OPERATION 18 4.1 Limits for Technical Specification Table 3.1.7.d and e 18

5.0 REFERENCES

FOR TECHNICAL SPECIFICATIONS 20 6.0 SOURCE DOCUMENTS 21 Page ii

COLRI-20 NINE MILE POINT UNIT 1 Revision 01 CORE OPERATING LIMITS REPORT 1.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR) 1.1 Limits for Technical Specification 3.1.7.a During power operations, the APLHGR(s) for each fuel type as a function of AVERAGE PLANAR EXPOSURE shall not exceed the limiting values shown for GEl I in Table la, Ib, Ic, and Id, or the limiting values shown for GNF2 in Table le and If.

1.2 Limits for Technical Specification 3.1.7.e During partial loop operation with four recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceeed 98 percent of the limiting values shown for GEl 1 in Table la, Ib, Ic, and Id and 99 percent of the limiting values shown for GNF2 in Table 1 e and If.

During partial loop operation with three recirculation loops in operation, the APLHGR as a function of average planar exposure shall not exceeed 98 percent of the limiting values shown for GEl 1 in Table la, Ib, Ic, and Idand 99 percent of the limiting values shown for GNF2 in Table 1 e and 1 f.

Page 1 of 21

COLRI-20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Table la MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Average Planar Exposure MAPLHGR Limits (kW/ft) (1)

GWd/ST Bundle Bundle 2586 2831 0.00 9.63 9.51 0.20 9.63 9.51 1.00 9.60 9.48 5.00 9.40 9.35 10.00 9.37 9.20 15.00 9.24 9.07 20.00 8.76 8.60 25.00 8.34 8.15 35.00 8.10 8.05 45.00 8.03 8.06 55.00 8.02 8.11 65.00 6.18 8.20 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Bundle Type ID GE1 1-P9DUB376-12GZ-100T-145-T6-2586 GEl 1-P9DUB382-13GZ-10OT-145-T6-2831 2586 2831 Page 2 of 21

COLRI-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 Table lb MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl 1 -P9DUB381-13GZ-10OT-145-T6-2945 (GEl 1)

Average Planar MAPLHGR Limits'l (kwlft)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice Most GWd/ST 7433 7434 7435 7436 7437 7438 Limiting 0.00 9.61 9.61 9.57 9.57 9.57 9.57 9.57 0.20 9.61 9.61 9.57 9.57 9.57 9.57 9.57 1.00 9.57 9.57 9.56 9.56 9.56 9.56 9.56 5.00 9.42 9.42 9.46 9.46 9.46 9.46 9.42 10.00 9.37 9.37 9.34 9.34 9.34 9.34 9.34 15.00 9.22 9.22 9.23 9.23 9.23 9.23 9.22 20.00 9.18 9.18 9.19 9.19 9.19 9.19 9.18 25.00 8.50 8.50 8.47 8.47 8.47 8.47 8.47 35.00 8.19 8.19 8.28 8.28 8.28 8.28 8.19 45.00 8.27 8.27 8.27 8.27 8.27 8.27 8.27 55.00 8.31 8.31 8.31 8.31 8.31 8.31 8.31 65.00 8.38 8.38 8.38 8.38 8.38 8.38 8.38 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.

Page 3 of 21

COLR1 -20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Table Ic MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl 1 -P9DUB381-14GZ-10OT-145-T6-2946 (GEl 1)

Average Planar MAPLHGR Limits'" (kw/ft)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice Most GWdlST 7433 7439 7440 7441 7442 7443 Limiting 0.00 10.24 10.24 10.19 10.19 10.19 10.19 10.19 0.20 10.24 10.24 10.19 10.19 10.19 10.19 10.19 1.00 10.20 10.20 10.19 10.19 10.19 10.19 10.19 5.00 9.91 9.91 9.85 9.85 9.85 9.85 9.85 10.00 9.42 9.42 9.34 9.34 9.34 9.34 9.34 15.00 9.22 9.22 9.19 9.19 9.19 9.19 9.19 20.00 9.18 9.18 9.19 9.19 9.19 9.19 9.18 25.00 8.64 8.64 8.63 8.63 8.63 8.63 8.63 35.00 8.08 8.08 8.08 8.08 8.08 8.08 8.08 45.00 8.02 8.02 7.99 7.99 7.99 7.99 7.99 55.00 8.00 8.00 7.99 7.99 7.99 7.99 7.99 65.00 7.97 7.97 7.96 7.96 7.96 7.96 7.96 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.

Page 4 of 21

COLRI-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 Table ld MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GEl I -P9DUB380-13GZ-10OT-145-T6-2948 (GEl 1)

Average Planar MAPLHGR Limits"' (kw/ft)

Exposure Lattice Lattice Lattice Lattice Lattice Lattice Most GWdIST 7433 7449 7450 7451 7447 7448 Limiting 0.00 9.71 9.71 9.69 9.69 9.69 9.69 9.69 0.20 9.71 9.71 9.69 9.69 9.69 9.69 9.69 1.00 9.68 9.68 9.67 9.67 9.67 9.67 9.67 5.00 9.56 9.56 9.50 9.50 9.50 9.50 9.50 10.00 9.38 9.38 9.32 9.32 9.32 9.32 9.32 15.00 9.23 9.23 9.24 9.24 9.24 9.24 9.23 20.00 9.28 9.28 9.31 9.31 9.31 9.31 9.28 25.00 8.43 8.43 8.45 8.45 8.45 8.45 8.43 35.00 8.09 8.09 8.09 8.09 8.09 8.09 8.09 45.00 7.98 7.98 8.02 8.02 8.02 8.02 7.98 55.00 7.97 7.97 7.98 7.98 7.98 7.98 7.97 65.00 7.91 7.91 7.93 7.93 7.93 7.93 7.91 (1) These MAPLHGR are lattice dependent. The values shown in the Most Limiting Column correspond to the limiting value for the most limiting lattice for use when hand calculations are required. Lattice descriptions are contained in the FBIR.

Page 5 of 21

COLRI -20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 Table le MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-P10DG2B384-16GZ-100T2-145-T6-3351 (GNF2)

Average Planar Exposure MAPLHGR Limits (kW/ft) (1)

GWd/ST KW/ft 0.00 8.17 0.20 8.17 1.00 8.14 5.00 8.05 10.00 7.97 15.00 8.03 20.00 7.10 25.00 6.75 35.00 6.61 45.00 6.41 55.00 6.28 65.00 6.19 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Page 6 of 21

COLR1 -20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Table If MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Bundle Type: GNF2-PI0DG2B386-13GZ-100T2-145-T6-3352 (GNF2)

Average Planar Exposure MAPLHGR Limits (kWlft) (1)

GWd/ST KWlft 0.00 8.16 0.20 8.16 1.00 8.12 5.00 8.03 10.00 1.99 15.00 8.10 20.00 7.16 25.00 6.78 35.00 6.62 45.00 6.40 55.00 6.26 65.00 6.18 (1) These MAPLHGRs are not lattice dependent, therefore the values shown also correspond to the limiting value for the most limiting lattice for use when hand calculations are required.

Page 7 of 21

COLR1 -20 NINE MILE POINT UNIT I Revision 01 CORE OPERATING LIMITS REPORT 2.0 MINIMUM CRITICAL POWER RATIO (MCPR) 2.1 Limits for Technical Specification 3.1.7.c During power operation, the operating MCPR shall be greater than or equal to the Operating Limit MCPR determined as the maximum of either:

A) the appropriate MCPR(') from Figure (2a thru 2d)12,3 "5) times the K(f) shown in Figure 2e, Or, B) the appropriate MCPR(P)"4 ' from Figure 2f.

Additional MCPR(P) limits are required for operations without a backup pressure regulator.

These limits are shown in Figure 2g.

2.2 Limits for Technical Specification 3.1.7.e During 3 loop operation, the Operating Limit MCPR shall be increased by 0.02. No adjustment is needed during 4 loop operation.

NOTES:

I Based on a 1.07 MCPR Safety Limit (SLCPR) 2 For Figures 2a thru 2d tau (T) defined as follows:

= (r_, - rl)/(rA -

rB)

TA = 0.868 seconds, control rod average scram insertion time limit to notch 39 r, =.672 +1.65x N

/ Ni x.016

,= ZNri /

N n = number of surveillance tests performed in cycle Ni = number of active control rods measured in the lb surveillance test ti = average scram time to notch 39 of all rods measured in the lb surveillance test N, = total number of active rods measured 3 For the current exposure and feedwater pump configuration. "Pump Combinations" are also described in operating procedure N I -OP-16, attachment 13 4 Introduction of the GNF2 fuel type requires use of power dependent MCPR limits for all off-rated conditions, including operations without a backup pressure regulator. When power is greater than 45%, the K(P) multiplier from Figure 2f is applied to the applicable rated condition MCPR limits from Figures 2a thru 2d. At less than or equal to 45% power, the MCPR(P) limits in Figure 2f are applied directly. This discussion also applies to Figure 2g. Figure 2f and 2g are applicable to both GEl I and GNF2 fuel.

5 Option B OLMCPR limits for GEl I in Figures 2a-2c are set by the Detect and Suppress (Stability) Evaluation for Reload 21.

Page 8 of 21

COLRI -20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Figure 2a MCPR Operating Limits for Feedwater Pump Combination 1 maximum flows Beginning Of Cycle to EOR*-1448 MWd/ST (Bounds TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs) 1.61 1.59 1.57 I.

0 1.55 0

om 1.53 EE 1.51 1.49 (1, 1.59)

(1, 1.51) 1.47 0

0.2 0.4 0.6 0.81 Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 9 of 21

COLRI-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 1.69 1.67 1.65 1.63 c 1.61 M 1.59 o0 1.57

.2 1.55 E

E E 1.53 1.51 1.49 1.47 1.45 Figure 2b MCPR Operating Limits for Feedwater Pump Combination I maximum flows EOR*-1448 MWd/ST to End Of Cycle (Bounds TDFWP+MDFWP, TDFWP only, MDFWP only, two MDFWPs)

GNF2 (0, 1.57)

GEl11 (0, 1.47)

(1, 1.67)

(1, 1.54) 0 0.2 0.4 0.6 0.8 1

Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 10 of 21

COLR1 -20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Figure 2c MCPR Operating Limits for Feedwater Pump Combination 2 maximum flows Beginning of Cycle to EOR*-1448 MWd/ST (Bounds TDFWP+ two MDFWPs) 1.65 1.63 1.61 1.59 CL 1.57 I..

at 1.55 1i 2

.6~1.53 1.51 1.49 1.47 (1, 1.63)

(1, 1.55) 1.45 0

0.2 0.4 0.6 0.8 1

Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 11 of 21

COLRI -20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Figure 2d MCPR Operating Limits for Feedwater Pump Combination 2 maximum flows EOR*-1448 MWd/ST to End Of Cycle (Bounds TDFWP+ two MDFWPs) 1.73 1.71 1.69 1.67 1.65

[L L1.63 1.61 o 1.59

  • 1.57 E

E 1.55 1.53 1.51 1.49 1.47 1.45 GNF2 (0, 1.61)

GE(1 (0,11.47)

(1, 1.71)

(1, 1.58) 0 0.2 0.4 0.6 0.8 1

Tau

  • EOR is the end of rated exposure as defined in the Cycle Management Report Page 12 of 21

COLR1-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 Figure 2e NMP-1 K(f) Curve for MCPR 1.5 1.4 1.3 C.)

90 K(f) = 1.50 when 45% > Flow, Otherwise:

-102.5%

K(f) = MAX( 1.0, 1.33075 - 0.441

  • Flow / 100%)

-107.0%

K(f) = MAX( 1.0, 1.35280 - 0.441

  • Flow / 100%)

-,112.0%

K(f) = MAX( 1.0, 1.37926 - 0.441

  • Flow /100%)

-117.0%

K(f) = MAX( 1.0, 1.40352 - 0.441

  • Flow/ 100%)

-Automatic K(f) = MAX( 1.0, 1.441 - 0.441

  • Flow/ 100%)

Automatic Flow Control 117% Scoop Tube Setting 112% Scoop Tube Setting 107% Scoop Tube Setting 102.5% Scoot Tube Setting 1.2 1.1 0.9 0

20 40 60 80 100 120 Core Flow (% of Rated)

Page 13 of 21

COLRI-20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Figure 2f MCPR(P) Limits for Normal Operation 5

4 I

I I

For 25% : P _45%

  • MCPR(P) = [2.85+0.026(45%-P)] for Core Flow > 60% Flow
  • MCPR(P) = [2.35+0.048(45%-P)] for Core Flow !5 60% Flow MCPR(P) = K(P)
  • the appropriate MCPR Limit from Figures 2a through 2d for 45% 5 P _5 100%
  • K(P) = [1.216+0.00665(65%-P)] for 45% < P ! 65%
  • K(P) = [1.133+0.00415(85%-P)] for 65% ! P !5 85%
  • K(P) = [1.000+0.00887(100%-P)] for 85% ! P < 100%

+

I I

Core Flow > 60%

3 Ia-C.,

5£ 2

Core Flow < 60%

1 0

0 20 40 60 80 100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)

Page 14 of 21

COLR1-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 Figure 2g MCPR(P) Limits for Operation Without Backup Pressure Regulator 5

4 For 25% ! P _45%

OMCPR(P) = [2.85+0.026(45%-P)] for Core Flow > 60% Flow 0 MCPR(P) = [2.35+0.048(45%-P)] for Core Flow < 60% Flow MCPR(P) = K(P)

  • the appropriate MCPR Limit from Figures 2a through 2dfor45% 5 P_5 100%
  • K(P) = [1.336+0.01085(65%-P)] for 45% 5 P < 65%
  • K(P) = [1.198+0.00690(85%-P)] for 65% < P < 85%
  • K(P) = [1.000+0.00887(1 00%-P)] for 85% < P 5 100%

Core Flow > 60%

3 E.,

ca 2

1 0

Core Flow < 60%

0 20 40 60 80 100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)

Page 15 of 21

COLR1-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 3.0 LINEAR HEAT GENERATION RATE (LHGR) 3.1 Limits for Technical Specification 3.1.7.b During power operation, the Linear Heat Generation Rate (LHGR) of any rod in any fuel assembly at any axial location shall not exceed the maximum of 11.0kW/fit) or the limiting values shown in FBIR1-20, Revision 0, "Nine Mile Point Unit 1 Fuel Bundle Information Report". This document contains the LHGR limits for both U02 rods (which contain no gadolinium) and the most limiting gadolinium-bearing rods. Other gadolinium-bearing rods have LHGR limits which lie between these two curves.

Compliance with these limits will be monitored by the plant's process computer.

For power operations between 45% and 100% RTP(2) without a backup pressure regulator, operating MFLPD shall be _ LHGRFAC(P)"3 ).

NOTE:

1 PLHGR shall be maintained below 11.0 kW/ft during plant operating to assure the PCT remains below 1500°F under steam cooling mitigation strategies specified in the EOPs.

2 Introduction of the GNF2 fuel type requires use of a power dependent LHGR Correction Factor, or LHGRFAC(P) for power operations without a backup pressure regulator at greater than or equal to 45%

RTP. Below 45% RTP, no additional limits are required. Figure 3 is applicable to both GEI 1 and GNF2 fuel types.

3 LHGRFAC(P) limits are provided for option B and option A scram times. If scram times are slower than option B (i.e. - > 0), then option A limits must be applied.

Page 16 of 21

COLRI-20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 Figure 3 LHGRFAC(P) Limits for Operation Without Backup Pressure Regulator 1.2 1.0 0.8

" 0.6

.. I 0.4 0.2 0.0 Operating MFLPD shall be <_LHGRFAC(P)

Option B OOption A

Option A ! i > 0) mLHGRFAC(P) = [0.518] for 45% < P < 65%

mLHGRFAC(P) = [0.636 - 0.00590(85% - P)] for 65% < P _< 85%

OLHGRFAC(P) = [1.000 - 0.02427(100% - P)] for 85% !5 P < 100%

Option B (t = 0)

'LHGRFAC(P) = [0.867 - 0.00650(65% - P)] for 45% 5 P < 65%

ILHGRFAC(P) = [0.987 - 0.00600(85% - P)] for 65% < P 5 85%

eLHGRFAC(P) = [1.000 - 0.00087(100% - P)] for 85% 5 P 5 100%

45 50 55 60 65 70 75 80 85 90 95 100 Core Thermal Power (P) in units of % Rated Thermal Power (%RTP)

Page 17 of 21

COLRI -20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 4.0 POWER/FLOW RELATIONSHIP DURING OPERATION 4.1 Limits for Technical Specification 3.1.7.d and e The power/flow relationship shall not exceed the limiting values shown in Figure 4.

Page 18 of 21

COLR1-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Figure 4 Limiting Power/ Flow Line Revision 01 120.00 100.00 0i6 80.00 60.00 40.00 20.00 0.00 0

20 40 60 80 100 Core Flow (% of Rated) 120 Page 19 of 21

4 1 1 4

COLRI-20 NINE MILE POINT UNIT 1 CORE OPERATING LIMITS REPORT Revision 01 5.0 REFERENCE FOR TECHNICAL SPECIFICATIONS Technical Specification 6.6.5b:

NEDE 2401 1-P-A-17, "General Electric Standard Application for Reactor Fuel,"

September 2010 and the U.S. Supplement, NEDE-2401 l-P-A-17-US, September 2010.

Page 20 of 21

4 d

COLRI-20 NINE MILE POINT UNIT I CORE OPERATING LIMITS REPORT Revision 01 6.0 SOURCE DOCUMENTS The Core Operating Limits contained in this report were obtained from the following documents:

CORE OPERATING LIMITS REFERENCES APLHGR Limits (Section 1)

Table 1 and corresponding 3 and 4 loop multipliers Lattice Descriptions MCPR Limits (Section 2) 0000-01 08-3371-SRLR, Revision 0, February 2011, Supplemental Reload Licensing Report for Nine Mile Point 1, Reload 21, Cycle 20 MEF-NMP-EA11-049, Transmittal of Exposure-dependent GEl 1 and GNF2 Fuel MAPLHGR Limits for Cycle 22, April 15, 2011 MEF-NMP-12-065, Transmittal of Revised Exposure-dependent GNF2 Fuel MAPLHGR Limits for Nine Mile Point Unit 1 Cycle 22, May 9, 2012 0000-0108-3371-FBIR, Revison 0, February 2011 Fuel Bundle Information Report for Nine Mile Point 1, Reload 21, Cycle 20 0000-0108-3371-SRLR, Revision 0, February 2011, Supplemental Reload Licensing Report for Nine Mile Point 1, Reload 21, Cycle 20 0000-0130-4605-R1, Nine Mile Point 1 Cycle 22 Revised Operated Power Dependent Limits Below Pbypass with Turbine Bypass, April 5, 2011 0000-0131-9552-RO, Nine Mile Point 1 Cycle 22 GNF2 NFI PROOS Off-rated Limits with Option B Scram, April 12, 2011 NMP1CMR, Revision 20, Nine Mile Point Unit 1, Cycle 20, Cycle Management Report, April 2011 0000-0108-3371-FBIR, Revison 0, February 2011 Fuel Bundle Information Report for Nine Mile Point 1, Reload 21, Cycle 20 0000-0108-3371-SRLR, Revision 0, February 2011, Supplemental Reload Licensing Report for Nine Mile Point 1, Reload 21, Cycle 20 0000-0131-9552-RO, Nine Mile Point 1 Cycle 22 GNF2 NFI PROOS Off-rated Limits with Option B Scram, April 12, 2011 NMP1 Technical Specification Amendment 92, Figure 3.1.7.a EOR Definition LHGR Limits (Section 3)

Power/Flow Relationship (Section 4)

Page 21 of 21