WO 20-0041, Rev. 32 to Equipment Qualification Summary Document-II (EQSD-II)

From kanterella
(Redirected from WO 20-0041)
Jump to navigation Jump to search
Rev. 32 to Equipment Qualification Summary Document-II (EQSD-II)
ML20290A620
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 01/15/2020
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20290A562 List:
References
WO 20-0041
Download: ML20290A620 (95)


Text

Revision 32 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT Page 1 of 6 EQSD-II COVER SHEET















EQSD-II EQ PROGRAM MASTER LIST (Table 1)

Plus Mild Environment SR Electrical Equipment List (Table 2)





Revision History Revision Description 32 See Revision Summary





Prepared by:

(Qualified) Date: 1/15/2020 William M. Wilkins/ Brian Masters Qualification Required: ES9280907 Verified by:

Date: 01/21/2020 Qualification Required: ES9280907 Approved by:

Date: 01/21/2020 Document Service DC7 Release by: 01/22/2020 Date:

Revision 32 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT Page 2 of 6 EQSD-II COVER SHEET



EQSD-II R32 Revision

Description:



EQSD-II Change Notices Addressed:

EQSD Change Sequence Number Date Status EQSD-II-31-06 7/11/2019 Incorporated EQSD-II-31-05 2/18/2019 Incorporated EQSD-II-31-04 12/13/2018 Incorporated EQSD-II-31-03 Per CR 128300 the positioners (ABZC0001, 2, 3 10/3/2018 Incorporated and 4) are mechanical components and thus not EQ program components. However, Table 2 includes old mechanical MEQ equipment that has a shutdown function. The equipment on this CN has both hot and cold shutdown functions, therefore they are included in Table 2.

Clarification of MEQ equipment in Table 2 added below in Sections 1.0 and 3.0. (also ref. CP 20361).

EQSD-II-31-02 10/25/2018 Incorporated EQSD-II-31-01 7/10/2018 Incorporated EQSD-II-28-01: CP15142 was implemented, CR 139683 identified 11/30/2017 Incorporated that EQSD-II-28-01 incorrectly identified that relay 3XSJ31 should be removed from EQSD-II, thus that was not done.

EQSD-II-31-07 is reserved. Intended use is changes for PQE- N/A RESERVED ESE-44A-P01 R/0

Revision 32 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT Page 3 of 6 EQSD-II COVER SHEET



Other Noted Revisions for R32:

Items Affected Reason for Change Changes Made 3XBM13 CR 133351 identified discrepancies in the Changed Model Number to show the 3XBM14 model numbers between the associated first three digits, identify the relays are 3XBM15 PQE, EQSD-II, and design drawing E- NE type material relays (last two 3XBM16 11012 for the identified relays. digits) and then reference the user to 3XBM17 design drawing E-11012 for the 3XBM18 PQE-E-093-P01 R3 identifies in the complete model number.

3XBM19 Installation Information section of the 3XBM20 Maintenance part on page 24 that the relay 3XBM42 P/N will have a 219XXXabcNE designator.

3XBM43 It identifies that the "XXX" part represents 3XBM44 the three-letter designator for the relay's 3XBM45 function. The "NE" represents a material 3XEG20 changes to extend the qualified life of the 3XEJ01 normally energized relay.

3XEN03 3XGE05 Thus, the important parts of the model 3XGE07 number for qualification for determining the 3XGE09 right qualification are to show the frame 3XGE11 type (first 3 digits) - 219 (Momentary), 236 3XGE13 (Delay on operate) and 237 (Delay on 3XGE15 release) and to identify that the relays are 3XGK16 the NE material. the last two digits to 3XGK17 show the nuclear grade material changes 3XGN03 as being used.

3XGN05 3XGN07 Therefore, to limit the potential for future 3XGN09 errors and to limit the need to update the 3XGS01 EQSD-II for all model number changes.

3XGS03 The numbers that are not needed for the 3XGS05 qualification of the relays have been 3XGS07 removed from Table one and the user is 3XGS09 instead referenced to E-11012 design 3XGS11 drawing that has the full model number.

3XGS13 3XGS15 3XGS17 3XGS19 3XGS21 3XGS25 3XGS27 3XGS29 3XGS31 3XGS33 3XGS35 3XGS37 3XGS39 3XGS41 3XGS43 3XGS45 3XGS47 3XGS49 3XSJ01 3XSJ03 3XSJ05 3XSJ07 3XSJ09

 

Revision 32 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT Page 4 of 6 EQSD-II COVER SHEET



Revision Summary (Continuation Sheet)

3XSJ11 (Continuation of reason for changes (Continuation of changes made 3XSJ13 statement above) statement above) 3XSJ25 3XSJ27 Note:

3XSJ29 CR 139683 identified EQSD-II-28-01 3XSJ31 remains and is not removed per 3XSJ31 erroneously noted to remove 3XSJ31 from EQSD-II-28-01.

3XSJ33 EQSD-II.

3XSJ35 62TDDAL01 62TDEEN1 62TDEGN11 62TDEGN13 62TDENB01 62TDENB02 62TDENB05 62TDENB06 94XAB05 95XGE01 95XGE03 95XKA004 ABPT0001 CR 132935 noted Table 1 components ABPT0001, 4 moved from Table ABPT0004 ABFT0001,4 should be Table 2 1 to Table 2. LOCA category components. corrected to Category D.

GKHZ0184E CR 134609 identified that the MC column Changed the MC column from Y to N.

was marked Y. However, based on PQE-M-627A-P01 the qualified life is now 60 years and as a result this component does not need a PM.

Cover Sheet CR 134609 identified need for clarification MC Field wording clarified that in the MC Field wording in regard to components with gasket or o-ring applicability for gasket/O-ring only replacement are also listed with a Y replacements. and identified in EQSD-III Table 2.

GNTE0060 CR 134609. Change Notice EQSD-III The MC column for these components GNTE0061 04 added these components to EQSD-III changed from N to Y.

GNTE0062 Table 2. With the MC field clarification GNTE0063 changes made by this CR review these components need to have the MC column marked Y.

ABPY0001 CR 128300 determined that these Added ABPY0001, 2, 3 and 4 to EQSD-ABPY0002 components should be in the EQ program II Table 1 with the applicable ABPY0003 (also reference CP 20361). information.

ABPY0004 EQSD-II Cover Sheet Instructions

1.0 PURPOSE The EQUIPMENT QUALIFICATION (EQ) MASTER LIST is Table 1 only. Table 1 is used to maintain a listing of components at WCGS that require EQ program documents to maintain qualification of the equipment. This list also identifies if there are any maintenance contingencies required to maintain the identified equipment qualification. It is noted that the Engineering Information System (EIS) and MPAC maintenance databases can be used to identify components that are in the EQ program.



Table 1:

This is the EQ program Master List. It identifies the safety related electrical components that are located in a harsh environment and are required to have an EQ program document. This table is list of equipment that is required to function during an accident and is identified as

Revision 32 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT Page 5 of 6 EQSD-II COVER SHEET



Category A or B in the LOCA/ HELB/ MSLB fields.



Table 2:

List of safety related electrical components that are either located in a mild environment or not required to function during a design bases accident (DBA). These components, while still needing to be qualified, are not required to have an EQ program file/ document. The equipment is identified as Category C or D in the LOCA/ HELB/ MSLB fields. In some cases, Category C is listed for what was ultimately determined to be a Category D mild environment. This Category C is maintained to retain the knowledge for breach door and/or future EQ related analysis. Mechanical equipment that was originally in the EQ program and had MEQ type files with a HOT, COLD or BOTH shutdown function is also included.



2.0 FIELDS USED:

The underlined fields below are only used in Table 1. This additional information is not necessary for the equipment not required to have an EQ program document. The EQ program documents are either an Equipment Qualification Work Package (EQWP) or the new electronic version Plant Qualification Evaluation (PQE).



Component Number:

The number used to identify the equipment that is to be created, updated and deleted to track the EQ program activities.



MC: (Maintenance Contingency required)

Components that require an EQ program qualified replacement preventive maintenance (PM) activity to replace the component are identified with a Y (Yes) and listed in EQSD-III Table 1.

Equipment qualified longer than the 60-year life of the plant are identified with a N (No).

Equipment qualified for less than 60 years but has been replaced such that the qualified life now extends past the 60-year life of the plant may also be identified as an N. The components that have a gasket or o-ring replacement required if opened are listed with a Y and identified in EQSD-III Table 2.



Equipment Qualification

Description:

The description of the component



Installed Elevation:

Additional information on the location of the equipment, this includes the building, level and area (BLA) identifier to help locate the equipment.



EQ Room:

The room environment the equipment is installed in. Environmental conditions (temperature, pressure, humidity, radiation and flooding) are identified in EQSD-I, Attachment A and B.



EQ Spec:

On Table 1 the identified specification what is use to find the applicable EQWP or PQE program document. On Table 2 it is the associated specification that the equipment was bought to.



Model #:

The installed part number



Manufacturer:

The name of the manufacture for the model number identified



LOCA:

Describes the mode in which the component is to function when there is a loss of coolant accident.



Revision 32 EQUIPMENT QUALIFICATION

SUMMARY

DOCUMENT Page 6 of 6 EQSD-II COVER SHEET



HELB:

Describes the mode in which the component is to function when there is a high energy line break.



MSLB:

Describes the mode in which the component is to function when there is a main steam line break.



System:

The system the equipment is part of, for more detail on the system go to the system description.



HOT/ COLD:

HOT SHUTDOWN specifies that the component is required for hot shutdown.

COLD SHUTDOWN specifies that the component is required for cold shutdown.



Notes:

Specifies the number of the note at the end of the list that is related to the component



3.0 EQSD-II, General Notes Section The notes in this section are applicable to both Table 1 and Table 2. It is noted that there are additional notes that are provided at the end of each table. Those notes are typically specific notes to the equipment for those tables.



General Notes Applicable to All of EQSD-II Tables 1 and 2:



A. The Hot and Cold Shutdown designations are based on a normal shutdown assuming a loss of offsite power and a safe shutdown earthquake. Components located in a harsh environment which are required for safe shutdown because of a LOCA, MSLB, or HELB are identified as Category A or B, except for mechanical equipment with a shutdown function listed as Category C or D listed in Table 2.

B. The normal and accident environment temperature, pressure, radiation, humidity and spray information can be found in EQSD-I Attachments A and B under the room number the equipment is located in.

C. A suffix (i.e. -E01 or -E02) has been added to some component numbers to allow additional EQ information related to the component to be listed in the table. This additional information may include subcomponents qualified to a different Equipment Qualification Work Package (EQWP) or, in some cases, identifies an approved alternative component (for example, a Barton and a Rosemount gauge approved for the identified component application).





EQSD-II Rev. 32 EQSD-II Table 1: 1 of 58 EQ Harsh Environment Equipment List Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM13 (BMHV0001) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM14 (BMHV0002) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM15 (BMHV0003) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM16 (BMHV0004) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM17 (BMHV0065) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM18 (BMHV0066) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM19 (BMHV0067) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM20 (BMHV0068) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM42 (BMHV0065/ 66/ 67/ 68) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM43 (BMHV0065/ 66/ 67/ 68) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM44 (BMHV0065/ 66/ 67/ 68) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D BM BOTH 16 30 3XBM45 (BMHV0065/ 66/ 67/ 68) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D EG BOTH 17 30 3XEG20 (EGTV0029) ELEV 2000-0 Ref. E-11012 N EJHV0014 OPEN AND SEAL IN AUX 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D EJ BOTH 16 30 3XEJ01 RELAY IN RP209 (EJHV0014) ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D EN BOTH 18 30 3XEN03 ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 (GEHZ0101, 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 3XGE05 102, 103, 104) ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 (GEHZ0101, 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 3XGE07 102, 103, 104) ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 (GEHZ0101, 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 3XGE09 102, 103, 104) ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 (GEHZ0101, 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 3XGE11 102, 103, 104) ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 (GEHZ0101, 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 3XGE13 102, 103, 104) ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 (GEHZ0101, 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 3XGE15 102, 103, 104) ELEV 2000-0 Ref. E-11012

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 2 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N AUX RELAY PANEL RP330 (SGK04A ) 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GK BOTH 17 30 3XGK16 ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP330 (SGK05A ) 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GK BOTH 17 30 3XGK17 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GN BOTH 17 30 3XGN03 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GN BOTH 17 30 3XGN05 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GN BOTH 17 30 3XGN07 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GN BOTH 17 30 3XGN09 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS01 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS03 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS05 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS07 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS09 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS11 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS13 ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS15 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS17 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS19 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 16 30 3XGS21 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS25 ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS27 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS29 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS31 ELEV 2000-0 Ref. E-11012

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 3 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS33 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS35 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS37 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS39 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS41 ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS43 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS45 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS47 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GS BOTH 18 30 3XGS49 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN RP209 FOR 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ01 SJHV006, 13, 19 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN RP209 FOR 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ03 SJHV0006 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN RP209 FOR 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ05 SJHV0006 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN RP209 FOR 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ07 SJHV0013 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN PANEL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ09 FOR SJHV0013 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN RP209 FOR 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ11 SJHV0019 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN RP209 FOR 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 16 30 3XSJ13 SJHV0019 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 18 30 3XSJ25 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PNL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 18 30 3XSJ27 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PNL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 18 30 3XSJ29 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 18 30 3XSJ31 FOR SJHV0128, 130 ELEV 2000-0 Ref. E-11012 N 120 VAC AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 18 30 3XSJ33 FOR SJHV0128 ELEV 2000-0 Ref. E-11012

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 4 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N 120 VAC AUX RELAY IN PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D SJ BOTH 18 30 3XSJ35 FOR SJHV0128 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 237NE Struthers-Dunn A B D AL BOTH 18 30 62TDDAL1 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN RP332 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EN BOTH 18 30 62TDEEN1 ELEV 2000-0 See E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EG BOTH 17 30 62TDEGN11 ELEV 2000-0 See E-11012 N AUX RELAY IN PANEL RP330 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EG BOTH 17 30 62TDEGN13 ELEV 2000-0 See E-11012 N NB01 DEGRADED VOLTAGE TRIP 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EN BOTH 18 30 62TDENB01 RELAY (NB0112) IN RP332 ELEV 2000-0 See E-11012 N NB01 DEGRADED VOLTAGE TRIP 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EN BOTH 18 30 62TDENB02 RELAY (NB0109) IN RP332 ELEV 2000-0 See E-11012 N NB01 DEGRADED VOLTAGE 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EN BOTH 18 30 62TDENB05 ANNUNCIATOR RELAY (NB0112) IN ELEV 2000-0 See E-11012 RP332 N NB01 DEGRADED VOLTAGE 134 AUX BLDG/ 1320 E-093 236NE Struthers-Dunn A B D EN BOTH 18 30 62TDENB06 ANNUNCIATOR RELAY (NB0109) IN ELEV 2000-0 See E-11012 RP332 N AUX RELAY IN PNL RP209 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D AB BOTH 16 30 94XAB05 ELEV 2000-0 Ref. E-11012 Y AUX RELAY PANEL RP330 (GEHZ0103) 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 17 30 95XGE01 ELEV 2000-0 Ref. E-11012 N AUX RELAY PANEL RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D GE BOTH 18 30 95XGE03 ELEV 2000-0 Ref. E-11012 N AUX RELAY IN RP332 134 AUX BLDG/ 1320 E-093 219NE Struthers-Dunn A B D KA BOTH 18 30 95XKA004 ELEV 2000-0 Ref. E-11012 N VALVE TERMINAL BOX 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) C D A AB BOTH ABHV0005-E01 ELEV 2026-0 N VALVE TERMINAL BOX 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) C D A AB BOTH ABHV0006-E01 ELEV 2026-0 Y LOOP 4 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0011-MV1 CONTROL SOLENOID VALVE MV-1 ELEV 2026-0 Y LOOP 4 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0011-MV2 CONTROL SOLENOID VALVE MV-2 ELEV 2026-0 Y LOOP 4 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0011-MV3 CONTROL SOLENOID VALVE MV-3 ELEV 2026-0 Y LOOP 4 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0011-MV4 CONTROL SOLENOID VALVE MV-4 ELEV 2026-0 Y LOOP 4 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0011-MV5 CONTROL SOLENOID VALVE MV-5 ELEV 2026-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 5 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y LOOP 4 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0011-MV6 CONTROL SOLENOID VALVE MV-6 ELEV 2026-0 Y LOOP 1 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0014-MV1 CONTROL SOLENOID VALVE MV-1 ELEV 2026-0 Y LOOP 1 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0014-MV2 CONTROL SOLENOID VALVE MV-2 ELEV 2026-0 Y LOOP 1 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0014-MV3 CONTROL SOLENOID VALVE MV-3 ELEV 2026-0 Y LOOP 1 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0014-MV4 CONTROL SOLENOID VALVE MV-4 ELEV 2026-0 Y LOOP 1 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0014-MV5 CONTROL SOLENOID VALVE MV-5 ELEV 2026-0 Y LOOP 1 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1508 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0014-MV6 CONTROL SOLENOID VALVE MV-6 ELEV 2026-0 Y LOOP 2 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0017-MV1 CONTROL SOLENOID VALVE MV-1 ELEV 2026-0 Y LOOP 2 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0017-MV2 CONTROL SOLENOID VALVE MV-2 ELEV 2026-0 Y LOOP 2 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0017-MV3 CONTROL SOLENOID VALVE MV-3 ELEV 2026-0 Y LOOP 2 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0017-MV4 CONTROL SOLENOID VALVE MV-4 ELEV 2026-0 Y LOOP 2 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0017-MV5 CONTROL SOLENOID VALVE MV-5 ELEV 2026-0 Y LOOP 2 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0017-MV6 CONTROL SOLENOID VALVE MV-6 ELEV 2026-0 Y LOOP 3 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0020-MV1 CONTROL SOLENOID VALVE MV-1 ELEV 2026-0 Y LOOP 3 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0020-MV2 CONTROL SOLENOID VALVE MV-2 ELEV 2026-0 Y LOOP 3 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0020-MV3 CONTROL SOLENOID VALVE MV-3 ELEV 2026-0 Y LOOP 3 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0020-MV4 CONTROL SOLENOID VALVE MV-4 ELEV 2026-0 Y LOOP 3 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0020-MV5 CONTROL SOLENOID VALVE MV-5 ELEV 2026-0 Y LOOP 3 MAIN STEAM ISO VALVE 145 AUX BLDG/ 1509 M-630 MV-1 CCI A D A AB BOTH 31 ABHV0020-MV6 CONTROL SOLENOID VALVE MV-6 ELEV 2026-0 N VALVE TERMINAL BOX 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) C D A AB BOTH ABHV0048-E01 ELEV 2026-0 N VALVE TERMINAL BOX 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) C D A AB BOTH ABHV0049-E01 ELEV 2026-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 6 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ABHV0012 SOLENOID VALVE 145 AUX BLDG/ 1508 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0012A ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0012A) 145 AUX BLDG/ 1508 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0012A-E01 ELEV 2026-0 N ABHV0012 SOLENOID VALVE 145 AUX BLDG/ 1508 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0012B ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0012B) 145 AUX BLDG/ 1508 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0012B-E01 ELEV 2026-0 N ABHV0015 SOLENOID VALVE 145 AUX BLDG/ 1508 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0015A ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0015A) 145 AUX BLDG/ 1508 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0015A-E01 ELEV 2026-0 N ABHV0015 SOLENOID VALVE 145 AUX BLDG/ 1508 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0015B ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0015B) 145 AUX BLDG/ 1508 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0015B-E01 ELEV 2026-0 N ABHV0018 SOLENOID VALVE 145 AUX BLDG/ 1509 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0018A ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0018A) 145 AUX BLDG/ 1509 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0018A-E01 ELEV 2026-0 N ABHV0018 SOLENOID VALVE 145 AUX BLDG/ 1509 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0018B ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0018B) 145 AUX BLDG/ 1509 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0018B-E01 ELEV 2026-0 N ABHV0021 SOLENOID VALVE 145 AUX BLDG/ 1509 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0021A ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0021A) 145 AUX BLDG/ 1509 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0021A-E01 ELEV 2026-0 N ABHV0021 SOLENOID VALVE 145 AUX BLDG/ 1509 M-237 NP8320A187E ASCO A D C AB BOTH 31 ABHY0021B ELEV 2026-0 N VALVE TERMINAL BOX (ABZS0021B) 145 AUX BLDG/ 1509 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH 31 ABHY0021B-E01 ELEV 2026-0 N ABLV0007 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0007A ELEV 2026-0 N VALVE TERMINAL BOX (ABLY0008B) 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH ABLY0007A-E01 ELEV 2026-0 N ABLV0007 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0007B ELEV 2026-0 N VALVE TERMINAL BOX (ABLY0008A) 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH ABLY0007B-E01 ELEV 2026-0 N ABLV0008 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0008A ELEV 2026-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 7 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ABLV0008 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0008B ELEV 2026-0 N ABLV0009 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0009A ELEV 2026-0 N VALVE TERMINAL BOX (ABLY0010B) 145 AUX BLDG/ 1411 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH ABLY0009A-E01 ELEV 2026-0 N ABLV0009 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0009B ELEV 2026-0 N VALVE TERMINAL BOX (ABLY0010A) 145 AUX BLDG/ 1411 E-093 NQB. 616822 Buchanan (Amerace) A D A AB BOTH ABLY0009B-E01 ELEV 2026-0 N ABLV0010 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0010A ELEV 2026-0 N ABLV0010 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8320A189E ASCO A D C AB BOTH ABLY0010B ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 1 145 AUX BLDG/ 1411 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0514 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 1 145 AUX BLDG/ 1411 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0515 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 1 145 AUX BLDG/ 1411 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0516 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 2 145 AUX BLDG/ 1412 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0524 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 2 145 AUX BLDG/ 1412 ESE-1A 763A ITT Barton A D B AB BOTH 41 42 ABPT0525 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 2 145 AUX BLDG/ 1412 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0526 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 3 145 AUX BLDG/ 1412 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0534 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 3 145 AUX BLDG/ 1412 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0535 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 3 145 AUX BLDG/ 1412 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0536 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 4 145 AUX BLDG/ 1411 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0544 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 4 145 AUX BLDG/ 1411 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0545 ELEV 2026-0 Y MAIN STEAM PRESSURE LOOP 4 145 AUX BLDG/ 1411 ESE-1A 763 ITT Barton A D B AB BOTH 41 ABPT0546 ELEV 2026-0 ABPY0001 N ABPV0001 I/P converter/ transducer 145 AUX BLDG/ 1508 J-601B 8005N Masoneilan B D A AB BOTH 31 ELEV 2026-0 ABPV0001-E01 N VALVE TERMINAL BOX 145 AUX BLDG/ 1508 E-093 NQB. 616822 Buchanan (Amerace) B D A AB BOTH 31 ELEV 2026-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 8 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN ABPY0002 N ABPV0002 I/P converter/ transducer 145 AUX BLDG/ 1509 J-601B 8005N Masoneilan B D A AB BOTH 31 ELEV 2026-0 ABPV0002-E01 N VALVE TERMINAL BOX 145 AUX BLDG/ 1509 E-093 NQB. 616822 Buchanan (Amerace) B D A AB BOTH 31 ELEV 2026-0 ABPY0003 N ABPV0003 I/P converter/ transducer 145 AUX BLDG/ 1509 J-601B 8005N Masoneilan B D A AB BOTH 31 ELEV 2026-0 ABPV0003-E01 N VALVE TERMINAL BOX 145 AUX BLDG/ 1509 E-093 NQB. 616822 Buchanan (Amerace) B D A AB BOTH 31 ELEV 2026-0 ABPY0004 N ABPV0004 I/P converter/ transducer 145 AUX BLDG/ 1508 J-601B 8005A Masoneilan B D A AB BOTH 31 ELEV 2026-0 Y ABPV0001 LIMIT SWITCH 145 AUX BLDG/ 1508 NAMCO EA180-11302 NAMCO B D A AB BOTH 31 ABZS0001 ELEV 2026-0 EA180-12302 Y ABPV0002 LIMIT SWITCH 145 AUX BLDG/ 1509 NAMCO EA180-11302 NAMCO B D A AB BOTH 31 ABZS0002 ELEV 2026-0 EA180-12302 Y ABPV0003 LIMIT SWITCH 145 AUX BLDG/ 1509 NAMCO EA180-11302 NAMCO B D A AB BOTH 31 ABZS0003 ELEV 2026-0 EA180-12302 Y ABPV0004 LIMIT SWITCH 145 AUX BLDG/ 1508 NAMCO EA180-11302 NAMCO B D A AB BOTH 31 ABZS0004 ELEV 2026-0 EA180-12302 Y ABLV0007 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0007A ELEV 2026-0 EA180-12302 Y ABLV0007 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0007B ELEV 2026-0 Y ABLV0008 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0008A ELEV 2026-0 EA180-12302 Y ABLV0008 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0008B ELEV 2026-0 Y ABLV0009 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0009A ELEV 2026-0 EA180-12302 Y ABLV0009 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0009B ELEV 2026-0 Y ABLV0010 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0010A ELEV 2026-0 EA180-12302 Y ABLV0010 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C AB BOTH ABZS0010B ELEV 2026-0 Y ABHV0012 LIMIT SWITCH 145 AUX BLDG/ 1508 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0012A ELEV 2026-0 EA180-12302 Y ABHV0012 LIMIT SWITCH 145 AUX BLDG/ 1508 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0012B ELEV 2026-0 Y ABHV0015 LIMIT SWITCH 145 AUX BLDG/ 1508 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0015A ELEV 2026-0 EA180-12302 Y ABHV0015 LIMIT SWITCH 145 AUX BLDG/ 1508 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0015B ELEV 2026-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 9 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y ABHV0018 LIMIT SWITCH 145 AUX BLDG/ 1509 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0018A ELEV 2026-0 EA180-12302 Y ABHV0018 LIMIT SWITCH 145 AUX BLDG/ 1509 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0018B ELEV 2026-0 Y ABHV0021 LIMIT SWITCH 145 AUX BLDG/ 1509 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0021A ELEV 2026-0 EA180-12302 Y ABHV0021 LIMIT SWITCH 145 AUX BLDG/ 1509 NAMCO EA180-11302 NAMCO A D C AB BOTH 31 ABZS0021B ELEV 2026-0 Y LOOP 1 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0039-MV1 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-1 Y LOOP 1 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0039-MV2 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-2 Y LOOP 1 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0039-MV3 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-3 Y LOOP 1 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0039-MV4 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-4 Y LOOP 1 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0039-MV5 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-5 Y LOOP 1 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0039-MV6 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-6 Y LOOP 2 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0040-MV1 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-1 Y LOOP 2 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0040-MV2 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-2 Y LOOP 2 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0040-MV3 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-3 Y LOOP 2 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0040-MV4 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-4 Y LOOP 2 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0040-MV5 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-5

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 10 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y LOOP 2 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0040-MV6 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-6 Y LOOP 3 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0041-MV1 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-1 Y LOOP 3 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0041-MV2 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-2 Y LOOP 3 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0041-MV3 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-3 Y LOOP 3 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0041-MV4 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-4 Y LOOP 3 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0041-MV5 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-5 Y LOOP 3 MAIN FEEDWATER ISO 145 AUX BLDG/ 1412 M-630 MV-1 CCI A D A AE BOTH AEFV0041-MV6 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-6 Y LOOP 4 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0042-MV1 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-1 Y LOOP 4 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0042-MV2 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-2 Y LOOP 4 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0042-MV3 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-3 Y LOOP 4 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0042-MV4 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-4 Y LOOP 4 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0042-MV5 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-5 Y LOOP 4 MAIN FEEDWATER ISO 145 AUX BLDG/ 1411 M-630 MV-1 CCI A D A AE BOTH AEFV0042-MV6 VALVE CONTROL SOLENOID VALVE ELEV 2026-0 MV-6 Y SG LEVEL WIDE RANGE LOOP 1 231 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0501 ELEV 1998-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 11 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y SG LEVEL WIDE RANGE LOOP 2 232 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0502 ELEV 1998-6 Y SG LEVEL WIDE RANGE LOOP 3 232 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0503 ELEV 1998-6 Y SG LEVEL WIDE RANGE LOOP 4 231 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0504 ELEV 1998-6 Y SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0517 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0518 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0519 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0527 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0528 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0529 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0537 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0538 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0539 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0547 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0548 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0549 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 1 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0551 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 2 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0552 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 3 242 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH AELT0553 ELEV 2026-0 Y SG LEVEL NARROW RANGE LOOP 4 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A AE BOTH 9 AELT0554 ELEV 2026-0 Y TC REFERENCE JUNCTION BOX 251 RX BLDG/ 2000 ESE-44A WX-34794 Westinghouse A D A BB ---

BB004A ELEV 2047-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 12 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N TC REFERENCE JUNCTION BOX 231 RX BLDG/ 2000 ESE-43G 4-Wire Cu Westinghouse A D A BB --- 43 SPLICES - RTD ELEV 1998-6 Wire/Brass at the BB004A-E01 reference junction box N TC REFERENCE JUNCTION BOX 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB ---

BB004A-E02 SPLICES - THERMOCOUPLE ELEV 1998-6 cable assemblies Engineering Y TC REFERENCE JUNCTION BOX 251 RX BLDG/ 2000 ESE-44A WX-34794 Westinghouse A D A BB ---

BB004B ELEV 2047-6 N TC REFERENCE JUNCTION BOX 231 RX BLDG/ 2000 ESE-43G 4-Wire Cu Westinghouse A D A BB --- 43 SPLICES - RTD ELEV 1998-6 Wire/Brass at the BB004B-E01 reference junction box N TC REFERENCE JUNCTION BOX 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB ---

BB004B-E02 SPLICES - THERMOCOUPLE ELEV 1998-6 cable assemblies Engineering Y RCP 1A THRM BARR CLG FLOW 241 RX BLDG/ 2000 J-301 1153DD4RA Rosemount Nuclear B D B BB BOTH BBFT0017 ELEV 2026-0 Y RCP 1B THRM BARR CLG FLOW 232 RX BLDG/ 2000 J-301 1153DD4RA Rosemount Nuclear B D B BB BOTH BBFT0018 ELEV 1998-6 Y RCP 1C THRM BARR CLG FLOW 242 RX BLDG/ 2000 J-301 1153DD4RA Rosemount Nuclear B D B BB BOTH BBFT0019 ELEV 2026-0 Y RCP 1D THRM BARR CLG FLOW 241 RX BLDG/ 2000 J-301 1153DD4RA Rosemount Nuclear B D B BB BOTH BBFT0020 ELEV 2026-0 N RCP THERMAL BARRIER COOLER 2026' CTMT 2000 LIMITORQU SB-00 LIMITORQUE B D B BB BOTH BBHV0013 ISOLATION VALVE BLDG E N RCP THERMAL BARRIER COOLER 2000' CTMT 2000 LIMITORQU SB-00 LIMITORQUE B D B BB BOTH BBHV0014 ISOLATION VALVE BLDG. E N RCP THERMAL BARRIER COOLER 2026' CTMT 2000 LIMITORQU SB-00 LIMITORQUE B D B BB BOTH BBHV0015 ISOLATION VALVE BLDG E N RCP THERMAL BARRIER COOLER 232 RX BLDG/ 2000 LIMITORQU SB-00 LIMITORQUE B D B BB BOTH BBHV0016 ISOLATION VALVE ELEV 1998-6 E N PRESSURIZER PORV ISOLATION 261 RX BLDG/ 2601 LIMITORQU SB-00 LIMITORQUE A D A BB BOTH BBHV8000A VALVE ELEV 2068-8 E N PRESSURIZER PORV ISOLATION 261 RX BLDG/ 2601 LIMITORQU SB-00 LIMITORQUE A D A BB BOTH BBHV8000B VALVE ELEV 2068-8 E Y REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. A D A BB COLD 20 BBHV8001A VALVE ELEV 2047-6 N REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-8 N11085 Conax A D A BB COLD 20 BBHV8001A-E01 VALVE CONNECTOR ELEV 2047-6 N VALVE TERMINAL BOX 252 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB --- 20 BBHV8001A-E02 ELEV 2047-6 Products Y REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. A D A BB COLD 20 BBHV8001B VALVE ELEV 2047-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 13 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-8 N11085 Conax A D A BB COLD 20 BBHV8001B-E01 VALVE CONNECTOR ELEV 2047-6 N VALVE TERMINAL BOX 252 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB --- 20 BBHV8001B-E02 ELEV 2047-6 Products Y REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. A D A BB COLD 20 BBHV8002A VALVE ELEV 2047-6 N REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-8 N11085 Conax A D A BB COLD 20 BBHV8002A-E01 VALVE CONNECTOR ELEV 2047-6 N VALVE TERMINAL BOX 252 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB --- 20 BBHV8002A-E02 ELEV 2047-6 Products Y REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. A D A BB COLD 20 BBHV8002B VALVE ELEV 2047-6 N REACTOR VESSEL HEAD VENT 252 RX BLDG/ 2000 HE-8 N11085 Conax A D A BB COLD 20 BBHV8002B-E01 VALVE CONNECTOR ELEV 2047-6 N VALVE TERMINAL BOX 252 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB --- 20 BBHV8002B-E02 ELEV 2047-6 Products N VALVE TERMINAL BOX 261 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB BOTH BBHV8010A-E01 ELEV 2068-8 Products N VALVE TERMINAL BOX 261 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB BOTH BBHV8010B-E01 ELEV 2068-8 Products N VALVE TERMINAL BOX 261 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A BB BOTH BBHV8010C-E01 ELEV 2068-8 Products N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A BB ---

BBHV8026-E01 ELEV 1998-6 604-JJ N VALVE TERMINAL BOX 133 AUX BLDG/ 1322 E-035B 601-JJ, 602-JJ, Kulka A D D BB ---

BBHV8027-E01 ELEV 2000-0 604-JJ N RCP SEAL INJECTION CONTAINMENT 133 AUX BLDG/ 1322 LIMITORQU SMB-00 LIMITORQUE A D D BB BOTH BBHV8351A ISOLATION VALVE ELEV 2000-0 E N RCP SEAL INJECTION CONTAINMENT 133 AUX BLDG/ 1322 LIMITORQU SMB-00 LIMITORQUE A D D BB BOTH BBHV8351B ISOLATION VALVE ELEV 2000-0 E N RCP SEAL INJECTION CONTAINMENT 133 AUX BLDG/ 1322 LIMITORQU SMB-00 LIMITORQUE A D D BB BOTH BBHV8351C ISOLATION VALVE ELEV 2000-0 E N RCP SEAL INJECTION CONTAINMENT 133 AUX BLDG/ 1322 LIMITORQU SMB-00 LIMITORQUE A D D BB BOTH BBHV8351D ISOLATION VALVE ELEV 2000-0 E N CONTAINMENT ISOL VALVE 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A BB ---

BBHY8026 NITROGEN SUPPLY TO PRT ELEV 1998-6 N CONT ISOL VLV NITROGEN SUPPLY 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A BB ---

BBHY8026-E01 TO PRT CONNECTOR ELEV 1998-6 N CONTAINMENT ISOL VALVE 133 AUX BLDG/ 1322 M-237 NPK831654E ASCO A D D BB ---

BBHY8027 NITROGEN SUPPLY TO PRT ELEV 2000-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 14 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y RVLIS HYDRAULIC ISOLATOR 134 AUX BLDG/ 1323 ESE-49A 581-4 ITT Barton A D D BB --- 26 BBLIS1311 ELEV 2000-0 Y RVLIS HYDRAULIC ISOLATOR 134 AUX BLDG/ 1323 ESE-49A 581-4 ITT Barton A D D BB --- 26 BBLIS1312 ELEV 2000-0 Y RVLIS HYDRAULIC ISOLATOR 133 AUX BLDG/ 1322 ESE-49A 581-4 ITT Barton A D D BB --- 26 BBLIS1321 ELEV 2000-0 Y RVLIS HYDRAULIC ISOLATOR 133 AUX BLDG/ 1322 ESE-49A 581-4 ITT Barton A D D BB --- 26 BBLIS1322 ELEV 2000-0 Y PRESSURIZER LEVEL TRANSMITTER 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A BB BOTH BBLT0459 ELEV 2026-0 Y PRESSURIZER LEVEL TRANSMITTER 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A BB BOTH BBLT0460 ELEV 2026-0 Y PRESSURIZER LEVEL TRANSMITTER 241 RX BLDG/ 2201 ESE-3A 764 ITT Barton A D A BB BOTH BBLT0461 ELEV 2026-0 N REACTOR VESSEL LEVEL 134 AUX BLDG/ 1320 ESE-4A 752 ITT Barton A C D BB --- 26 BBLT1311 TRANSMITTER NARROW RANGE ELEV 2000-0 N REACTOR VESSEL LEVEL 134 AUX BLDG/ 1320 ESE-4A 752 ITT Barton A C D BB --- 26 BBLT1312 TRANSMITTER WIDE RANGE ELEV 2000-0 N REACTOR VESSEL LEVEL 121 AUX BLDG/ 1202 ESE-4A 752 ITT Barton A C D BB --- 26 BBLT1321 TRANSMITTER NARROW RANGE ELEV 1988-0 N REACTOR VESSEL LEVEL 123 AUX BLDG/ 1202 ESE-4A 752 ITT Barton A C D BB --- 26 BBLT1322 TRANSMITTER WIDE RANGE ELEV 1988-0 Y PRESSURIZER POWER OPERATED 261 RX BLDG/ 2601 HE-9 3750014 Westinghouse/ A D A BB BOTH BBPCV0455A RELIEF VALVE ELEV 2068-8 Garrett N PRESSURIZER POWER OPERATED 241 RX BLDG/ 2601 HE-8 N11007 Conax A D A BB BOTH BBPCV0455A-E01 RELIEF VLV CONNECTOR ELEV 2026-0 N VALVE TERMINAL BOX 261 RX BLDG/ 2601 E-028 1600-NUC Marathon Special A D A BB BOTH BBPCV0455A-E02 ELEV 2068-8 Products Y PRESSURIZER POWER OPERATED 261 RX BLDG/ 2601 HE-9 3750014 Westinghouse/ A D A BB BOTH BBPCV0456A RELIEF VALVE ELEV 2068-8 Garrett N PRESSURIZER POWER OPERATED 261 RX BLDG/ 2601 HE-8 N11007 Conax A D A BB BOTH BBPCV0456A-E01 RELIEF VLV CONNECTOR ELEV 2068-8 N VALVE TERMINAL BOX 261 RX BLDG/ 2601 E-028 1600-NUC Marathon Special A D A BB BOTH BBPCV0456A-E02 ELEV 2068-8 Products Y REACTOR COOLANT SYSTEM 123 AUX BLDG/ 1202 ESE-1A 763 ITT Barton A A D BB BOTH 41 BBPT0403 PRESSURE WIDE RANGE ELEV 1988-0 Y REACTOR COOLANT SYSTEM 134 AUX BLDG/ 1320 ESE-1B 76PHSS Veritrak A A D BB BOTH 30 BBPT0405 PRESSURE WIDE RANGE ELEV 2000-0 Y REACTOR COOLANT SYSTEM 123 AUX BLDG/ 1202 ESE-1A 763 ITT Barton A A D BB BOTH 41 BBPT0406 PRESSURE WIDE RANGE ELEV 1988-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 15 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y PRESSURIZER PRESSURE 241 RX BLDG/ 2201 J-301 1154SH9RA Rosemount Nuclear A D A BB BOTH BBPT0455 TRANSMITTER ELEV 2026-0 Y PRESSURIZER PRESSURE 241 RX BLDG/ 2201 J-301 1154SH9RA Rosemount Nuclear A D A BB BOTH BBPT0456 TRANSMITTER ELEV 2026-0 Y PRESSURIZER PRESSURE 251 RX BLDG/ 2201 J-301 1154SH9RA Rosemount Nuclear A D A BB BOTH BBPT0457 TRANSMITTER ELEV 2047-6 Y PRESSURIZER PRESSURE 251 RX BLDG/ 2201 J-301 1154SH9RA Rosemount Nuclear A D A BB BOTH BBPT0458 TRANSMITTER ELEV 2047-6 N RHR PUMP SUCTION ISOLATION 231 RX BLDG/ 2000 LIMITORQU SMB-2 LIMITORQUE C D A BB BOTH BBPV8702A VALVE ELEV 1998-6 E N RHR PUMP SUCTION ISOLATION 231 RX BLDG/ 2000 LIMITORQU SMB-2 LIMITORQUE C D A BB BOTH BBPV8702B VALVE ELEV 1998-6 E N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0001 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0001-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0002 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE CONNECTOR/ 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0002-E01 CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0003 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0003-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0004 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0004-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0005 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0005-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0006 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0006-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0007 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0007-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0008 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 16 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0008-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 241 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0009 INCORE THERMOCOUPLES ELEV 2026-0 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0009-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0010 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0010-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0012 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0012-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0013 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0013-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0014 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0014-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0015 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0015-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0017 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0017-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0018 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0018-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0019 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0019-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0020 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0020-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 17 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0021 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0021-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0022 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0022-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0023 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0023-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0024 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0024-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0025 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0025-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0026 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0026-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0027 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0027-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0028 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0028-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0029 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0029-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0030 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0030-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0031 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 18 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0031-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0032 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0032-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0033 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0033-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0034 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0034-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0036 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0036-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0037 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0037-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0038 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0038-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0039 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0039-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0040 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0040-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0041 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0041-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0042 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0042-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 19 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0043 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0043-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0044 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0044-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0045 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0045-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0046 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0046-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0047 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0047-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0048 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0048-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0049 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0049-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering N RV CORE SUBCOOLING MONITOR 231 RX BLDG/ 2000 ESE-43A Type K Westinghouse/ CKB A D A BB --- 26 BBT/C0050 INCORE THERMOCOUPLES ELEV 1998-6 Inc.

N THERMOCOUPLE 231 RX BLDG/ 2000 J-565 Mineral insulated Combustion A D A BB --- 26 BBT/C0050-E01 CONNECTOR/CABLE ASSEMBLIES ELEV 1998-6 cable assemblies Engineering Y RCS HOT LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0410A1 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0410A2 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0410A3 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0410B (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0411A1 LOOP 1 ELEV 1998-6 Inc.

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 20 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y RCS HOT LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0411A2 LOOP 1 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0411A3 LOOP 1 ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0411B LOOP 1 ELEV 1998-6 Inc.

N RCS HOT LEG TEMPERATURE 231 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0413A ELEMENT (WR) LOOP 1 ELEV 1998-6 N RCS HOT LEG RTD CONNECTOR (WR) 231 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0413A-E01 LOOP 1 ELEV 1998-6 N RCS COLD LEG TEMP ELEMENT (WR) 231 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0413B LOOP 1 ELEV 1998-6 N RCS COLD LEG RTD CONNECTOR 231 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0413B-E01 (WR) LOOP 1 ELEV 1998-6 Y RCS HOT LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0420A1 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0420A2 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0420A3 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0420B (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0421A1 LOOP 2 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0421A2 LOOP 2 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0421A3 LOOP 2 ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0421B LOOP 2 ELEV 1998-6 Inc.

N RCS HOT LEG TEMP ELEMENT (WR) 232 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0423A LOOP 2 ELEV 1998-6 N RCS HOT LEG RTD CONNECTOR (WR) 232 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0423A-E01 LOOP 2 ELEV 1998-6 N RCS COLD LEG TEMP ELEMENT (WR) 232 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0423B LOOP 2 ELEV 1998-6 N RCS COLD LEG RTD CONNECTOR 232 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0423B-E01 (WR) LOOP 2 ELEV 1998-6 Y RCS HOT LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0430A1 LOOP 3 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0430A2 (INSTALLED SPARE) ELEV 1998-6 Inc.

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 21 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y RCS HOT LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0430A3 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0430B (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0431A1 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0431A2 LOOP 3 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0431A3 LOOP 3 ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELEMENT 232 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0431B LOOP 3 ELEV 1998-6 Inc.

N RCS HOT LEG TEMPERATURE 232 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0433A ELEMENT (WR) LOOP 3 ELEV 1998-6 N RCS HOT LEG RTD CONNECTOR (WR) 232 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0433A-E01 LOOP 3 ELEV 1998-6 N RCS COLD LEG TEMPERATURE 232 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0433B ELEMENT (WR) LOOP 3 ELEV 1998-6 N RCS COLD LEG RTD CONNECTOR 232 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0433B-E01 (WR) LOOP 3 ELEV 1998-6 Y RCS HOT LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0440A1 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0440A2 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0440A3 (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELE 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB ---

BBTE0440B (INSTALLED SPARE) ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0441A1 LOOP 4 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0441A2 LOOP 4 ELEV 1998-6 Inc.

Y RCS HOT LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0441A3 LOOP 4 ELEV 1998-6 Inc.

Y RCS COLD LEG RTD TEMP ELEMENT 231 RX BLDG/ 2201 J-564 N9004E-2A-SP Weed Instrument Co., C D A BB BOTH BBTE0441B LOOP 4 ELEV 1998-6 Inc.

N RCS HOT LEG TEMPERATURE 231 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0443A ELEMENT (WR) LOOP 4 ELEV 1998-6 N RCS HOT LEG RTD CONNECTOR (WR) 231 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0443A-E01 LOOP 4 ELEV 1998-6 N RCS COLD LEG TEMPERATURE 231 RX BLDG/ 2201 ESE-6 21205 RDF Corp. A D A BB BOTH BBTE0443B ELEMENT (WR) LOOP 4 ELEV 1998-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 22 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N RCS COLD LEG RTD CONNECTOR 231 RX BLDG/ 2201 HE-8 N11007 Conax A D A BB BOTH BBTE0443B-E01 (WR) LOOP 4 ELEV 1998-6 N RVLIS HEAD IMPULSE LINE TEMP 242 RX BLDG/ 2000 ESE-42A S8809 MINCO/ A D A BB --- 26 BBTE1313 ELEMENT ELEV 2026-0 Westinghouse N RVLIS HEAD IMPULSE LINE TEMP 242 RX BLDG/ 2000 ESE-42A S8809 MINCO/ A D A BB --- 26 BBTE1314 ELEMENT ELEV 2026-0 Westinghouse N RVLIS SEAL IMPULSE LINE TEMP 241 RX BLDG/ 2000 ESE-42A S8810 MINCO/ A D A BB --- 26 BBTE1317 ELEMENT ELEV 2026-0 Westinghouse N RVLIS SEAL IMPULSE LINE TEMP 241 RX BLDG/ 2000 ESE-42A S8810 MINCO/ A D A BB --- 26 BBTE1318 ELEMENT ELEV 2026-0 Westinghouse N RVLIS HEAD IMPULSE LINE TEMP 241 RX BLDG/ 2000 ESE-42A S8809 MINCO/ A D A BB --- 26 BBTE1323 ELEMENT ELEV 2026-0 Westinghouse N RVLIS HEAD IMPULSE LINE TEMP 241 RX BLDG/ 2000 ESE-42A S8809 MINCO/ A D A BB --- 26 BBTE1324 ELEMENT ELEV 2026-0 Westinghouse N RVLIS SEAL IMPULSE LINE TEMP 242 RX BLDG/ 2000 ESE-42A S8810 MINCO/ A D A BB --- 26 BBTE1327 ELEMENT ELEV 2026-0 Westinghouse N RVLIS SEAL IMPULSE LINE TEMP 242 RX BLDG/ 2000 ESE-42A S8810 MINCO/ A D A BB --- 26 BBTE1328 ELEMENT ELEV 2026-0 Westinghouse N RVLIS HEAD IMPULSE LINE TEMP 241 RX BLDG/ 2000 ESE-42A S8809 MINCO/ A D A BB --- 26 BBTE1329 ELEMENT ELEV 2026-0 Westinghouse Y PRESSURIZER PORV LIMIT SWITCH 261 RX BLDG/ 2601 HE-9 3760060 Westinghouse/ A D A BB BOTH 22 BBZS0455A ELEV 2068-8 Garrett N PRESSURIZER PORV LIMIT SWITCH 261 RX BLDG/ 2601 HE-8 N11007 Conax A D A BB BOTH 22 BBZS0455A-E01 CONNECTOR ELEV 2068-8 Y PRESSURIZER PORV LIMIT SWITCH 261 RX BLDG/ 2601 HE-9 3760060 Westinghouse/ A D A BB BOTH 22 BBZS0456A ELEV 2068-8 Garrett N PRESSURIZER PORV LIMIT SWITCH 261 RX BLDG/ 2601 HE-8 N11007 Conax A D A BB BOTH 22 BBZS0456A-E01 CONNECTOR ELEV 2068-8 Y PRESSURIZER SAFETY RELIEF 261 RX BLDG/ 2602 HE-7 65322 Westinghouse/ A D A BB BOTH 22 BBZS8010A VALVE LIMIT SWITCH ELEV 2068-8 Garrett N PRESSURIZER SAFETY RELIEF 261 RX BLDG/ 2602 HE-8 N11007 Conax A D A BB BOTH 22 BBZS8010A-E01 VALVE LS CONNECTOR ELEV 2068-8 Y PRESSURIZER SAFETY RELIEF 261 RX BLDG/ 2602 HE-7 65322 Westinghouse/ A D A BB BOTH 22 BBZS8010B VALVE LIMIT SWITCH ELEV 2068-8 Garrett N PRESSURIZER SAFETY RELIEF 261 RX BLDG/ 2602 HE-8 N11007 Conax A D A BB BOTH 22 BBZS8010B-E01 VALVE LS CONNECTOR ELEV 2068-8 Y PRESSURIZER SAFETY RELIEF 261 RX BLDG/ 2602 HE-7 65322 Westinghouse/ A D A BB BOTH 22 BBZS8010C VALVE LIMIT SWITCH ELEV 2068-8 Garrett N PRESSURIZER SAFETY RELIEF 261 RX BLDG/ 2602 HE-8 N11007 Conax A D A BB BOTH 22 BBZS8010C-E01 VALVE LS CONNECTOR ELEV 2068-8 Y CONTMN ISOL VLV NIT SUPPLY TO 231 RX BLDG/ 2000 HE-3/6 EA180-14303 NAMCO A D A BB ---

BBZS8026 PRT LIMIT SWITCH ELEV 1998-6 EA180-15303

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 23 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N CONT ISOL VLV NIT SUPPLY TO PRT 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A BB ---

BBZS8026-E01 LS CONNECTOR ELEV 1998-6 Y CONTMN ISOL VLV NIT SUPPLY TO 231 RX BLDG/ 1322 HE-3/6 EA180-35303 NAMCO A D D BB ---

BBZS8027 PRT LIMIT SWITCH ELEV 1998-6 EA180-34303 Y RHR PUMP SUCTION ISOLATION 231 RX BLDG/ 2000 HE-3/6 EA180-12303 NAMCO C D A BB BOTH BBZS8702AA VALVE LIMIT SWITCH ELEV 1998-6 EA180-12303 N VALVE TERMINAL BOX (BBZS8702AB) 231 RX BLDG/ 2000 E-028 1600-NUC Marathon Special A D A BB BOTH BBZS8702AA-E01 ELEV 1998-6 Products N RHR PUMP SUCTION ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax C D A BB BOTH BBZS8702AA-E02 VALVE LS CONNECTOR ELEV 1998-6 Y RHR PUMP SUCTION ISOLATION 231 RX BLDG/ 2000 HE-3/6 EA180-12303 NAMCO C D A BB BOTH BBZS8702AB VALVE LIMIT SWITCH ELEV 1998-6 EA180-12303 N RHR PUMP SUCTION ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax C D A BB BOTH BBZS8702AB-E01 VALVE LS CONNECTOR ELEV 1998-6 Y RCP SEAL INJECTION FLOW 123 AUX BLDG/ 1202 J-301 1153HB5RCN0012 Rosemount Nuclear A C D BG BOTH BGFT0215A TRANSMITTER ELEV 1988-0 N RCP SEAL INJECTION FLOW 123 AUX BLDG/ 1202 ESE-4A 752 ITT Barton A C D BG BOTH BGFT0215B TRANSMITTER ELEV 1988-0 N RCP SEAL INJECTION FLOW 123 AUX BLDG/ 1202 ESE-4D 1153HB5RC Rosemount Nuclear A C D BG BOTH BGFT0215B-E01 TRANSMITTER ELEV 1988-0 N SEAL WATER RETURN 133 AUX BLDG/ 1322 LIMITORQU SMB-00 LIMITORQUE A D D BG ---

BGHV8100 CONTAINMENT ISOLATION VALVE ELEV 2000-0 E N CHARGING LINE CONTAINMENT 134 AUX BLDG/ 1323 LIMITORQU SB-00 LIMITORQUE A D D BG BOTH BGHV8105 ISOLATION VALVE ELEV 2000-0 E N CHARGING LINE ISOLATION VALVE 134 AUX BLDG/ 1323 LIMITORQU SB-00 LIMITORQUE A D D BG BOTH BGHV8106 ELEV 2000-0 E N CCP A MINIFLOW ISOLATION VALVE 112 AUX BLDG/ 1114 LIMITORQU SMB-00 LIMITORQUE A D D BG BOTH 29 BGHV8110 ELEV 1974-0 E N CCP B MINIFLOW ISOLATION VALVE 111 AUX BLDG/ 1107 LIMITORQU SMB-00 LIMITORQUE A D D BG BOTH 28 BGHV8111 ELEV 1974-0 E N SEAL WATER RETURN 231 RX BLDG/ 2000 LIMITORQU SMB-00 LIMITORQUE A D A BG ---

BGHV8112 CONTAINMENT ISOL VALVE ELEV 1998-6 E N VALVE TERMINAL BOX 133 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D BG ---

BGHV8152-E01 ELEV 2000-0 Y EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. C D B BG BOTH 45 BGHV8153A VALVE ELEV 1998-6 N EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax C D B BG BOTH BGHV8153A-E01 VALVE CONNECTOR ELEV 1998-6 Y EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. C D B BG BOTH 45 BGHV8153B VALVE ELEV 1998-6 N EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax C D B BG BOTH BGHV8153B-E01 VALVE CONNECTOR ELEV 1998-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 24 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. B D B BG BOTH 45 BGHV8154A VALVE ELEV 1998-6 N EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax B D B BG BOTH BGHV8154A-E01 VALVE CONNECTOR ELEV 1998-6 Y EXCESS LETDOWN/RCS ISOLATION 231 CTMT BLDG/ 2000 HE-10A 79AB-001BB Target Rock Corp. B D B BG BOTH 45 BGHV8154B VALVE ELEV 2006 N EXCESS LETDOWN/RCS ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax B D B BG BOTH BGHV8154B-E01 VALVE CONNECTOR ELEV 1998-6 N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A BG ---

BGHV8160-E01 ELEV 1998-6 604-JJ Y LETDOWN CONTAINMENT ISOLATION 133 AUX BLDG/ 1322 M-237 NPK831654E ASCO A D D BG ---

BGHY8152 VALVE (BGHV8152) ELEV 2000-0 Y LETDOWN CONTAINMENT ISOLATION 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A BG ---

BGHY8160 VALVE ELEV 1998-6 N LETDOWN CONTAINMENT ISOLATION 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A BG ---

BGHY8160-E01 VALVE CONNECTOR ELEV 1998-6 N VCT ISOLATION VALVE FROM 132 AUX BLDG/ 1318 LIMITORQU SB-00 LIMITORQUE A C D BG BOTH BGLCV0112B CHARGING PUMP SUCTION ELEV 2000-0 E N VCT ISOLATION VALVE FROM 132 AUX BLDG/ 1318 LIMITORQU SB-00 LIMITORQUE A C D BG BOTH BGLCV0112C CHARGING PUMP SUCTION ELEV 2000-0 E Y LETDOWN CONTAINMENT ISOL VLV 133 AUX BLDG/ 1322 NAMCO EA180-11302 NAMCO A D D BG ---

BGZS8152 LMT SWITCH ELEV 2000-0 HE-3/6 EA180-12303 Y LETDOWN CONTAINMENT ISOL VLV 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D A BG ---

BGZS8160 LIMIT SWITCH ELEV 1998-6 EA180-12303 N LETDOWN CONTAINMENT ISOL VLV 231 RX BLDG/ 2000 HE-8 EA180-12303 Conax A D A BG ---

BGZS8160-E01 LS CONNECTOR ELEV 1998-6 N VALVE TERMINAL BOX 133 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D BL ---

BLHV8047-E01 ELEV 2000-0 Y CONTAINMENT ISOLATION VALVE 133 AUX BLDG/ 1322 M-237 NPK831654E ASCO A D D BL ---

BLHY8047 ELEV 2000-0 Y CONTAINMENT ISOLATION VALVE 133 AUX BLDG/ 1322 HE-3/6 EA180-14303 NAMCO A D D BL ---

BLZS8047 LIMIT SWITCH ELEV 2000-0 EA180-15303 N VALVE TERMINAL BOX 145 AUX BLDG/ 1411 E-093 NQB. 616822 Buchanan (Amerace) A D A BM HOT BMHV0001-E01 ELEV 2026-0 N VALVE TERMINAL BOX (AEFV0044) 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) A D A BM HOT BMHV0002-E01 ELEV 2026-0 N VALVE TERMINAL BOX 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) A D A BM HOT BMHV0003-E01 ELEV 2026-0 N VALVE TERMINAL BOX (AEFV0046) 145 AUX BLDG/ 1411 E-093 NQB. 616822 Buchanan (Amerace) A D A BM HOT BMHV0004-E01 ELEV 2026-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 25 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y BMHV0001 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8321A6E ASCO A D C BM HOT BMHY0001A ELEV 2026-0 Y BMHV0001 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8321A6E ASCO A D C BM HOT BMHY0001B ELEV 2026-0 N VALVE TERMINAL BOX (AEFV0043, 145 AUX BLDG/ 1411 E-093 NQB. 616822 Buchanan (Amerace) A D A BM BOTH BMHY0001B-E01 BMZS0001B) ELEV 2026-0 Y BMHV0002 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8321A6E ASCO A D C BM HOT BMHY0002A ELEV 2026-0 Y BMHV0002 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8321A6E ASCO A D C BM HOT BMHY0002B ELEV 2026-0 N VALVE TERMINAL BOX (BMZS0002B) 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) A D A BM HOT BMHY0002B-E01 ELEV 2026-0 Y BMHV0003 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8321A6E ASCO A D C BM HOT BMHY0003A ELEV 2026-0 Y BMHV0003 SOLENOID VALVE 145 AUX BLDG/ 1412 M-237 NP8321A6E ASCO A D C BM HOT BMHY0003B ELEV 2026-0 N VALVE TERMINAL BOX (AEFV0045, 145 AUX BLDG/ 1412 E-093 NQB. 616822 Buchanan (Amerace) A D A BM BOTH BMHY0003B-E01 BMZS0003B) ELEV 2026-0 Y BMHV0004 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8321A6E ASCO A D C BM HOT BMHY0004A ELEV 2026-0 Y BMHV0004 SOLENOID VALVE 145 AUX BLDG/ 1411 M-237 NP8321A6E ASCO A D C BM HOT BMHY0004B ELEV 2026-0 N VALVE TERMINAL BOX (BMZS0004B) 145 AUX BLDG/ 1411 E-093 NQB. 616822 Buchanan (Amerace) A D A BM HOT BMHY0004B-E01 ELEV 2026-0 Y BMHV0001 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0001A ELEV 2026-0 EA180-12302 Y BMHV0001 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0001B ELEV 2026-0 Y BMHV0002 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0002A ELEV 2026-0 EA180-12302 Y BMHV0002 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0002B ELEV 2026-0 Y BMHV0003 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0003A ELEV 2026-0 EA180-12302 Y BMHV0003 LIMIT SWITCH 145 AUX BLDG/ 1412 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0003B ELEV 2026-0 Y BMHV0004 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0004A ELEV 2026-0 EA180-12302 Y BMHV0004 LIMIT SWITCH 145 AUX BLDG/ 1411 NAMCO EA180-11302 NAMCO A D C BM HOT BMZS0004B ELEV 2026-0 N VALVE TERMINAL BOX 121 AUX BLDG/ 1202 E-093 NQB. 616822 Buchanan (Amerace) A C D BN BOTH BNHCV8800A-E01 ELEV 1988-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 26 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N VALVE TERMINAL BOX 121 AUX BLDG/ 1202 E-093 NQB. 616822 Buchanan (Amerace) A C D BN BOTH BNHCV8800B-E01 ELEV 1988-0 N CONTAINMENT SPRAY PUMP 111 AUX BLDG/ 1110 LIMITORQU SMB-00 LIMITORQUE A D D BN ---

BNHV0003 SUCTION ISO VALVE ELEV 1974-0 E N CONTAINMENT SPRAY PUMP 112 AUX BLDG/ 1112 LIMITORQU SMB-00 LIMITORQUE A D D BN ---

BNHV0004 SUCTION ISO VALVE ELEV 1974-0 E N SAFETY INJECTION PUMP RWST 112 AUX BLDG/ 1113 LIMITORQU SB-00 LIMITORQUE A D D BN --- 29 BNHV8806A SUCTION VALVE ELEV 1974-0 E N SAFETY INJECTION PUMP RWST 111 AUX BLDG/ 1108 LIMITORQU SB-00 LIMITORQUE A D D BN --- 28 BNHV8806B SUCTION VALVE ELEV 1974-0 E N RHR PUMP RWST SUCTION VALVE 112 AUX BLDG/ 1111 LIMITORQU SB-1 LIMITORQUE A D D BN COLD BNHV8812A ELEV 1974-0 E N RHR PUMP RWST SUCTION VALVE 111 AUX BLDG/ 1109 LIMITORQU SB-1 LIMITORQUE A D D BN COLD BNHV8812B ELEV 1974-0 E N ISOLATION VALVE FOR SI PUMPS MIN 111 AUX BLDG/ 1108 LIMITORQU SMB-00 LIMITORQUE A D D BN --- 28 BNHV8813 RECIRCULATION ELEV 1974-0 E N RWST ISOLATION VALVE FOR FUEL 121 AUX BLDG/ 1202 M-237 NP831655E ASCO A C D BN BOTH BNHY8800A POOL CLEANUP PUMPS ELEV 1988-0 N RWST ISOLATION VALVE FOR FUEL 121 AUX BLDG/ 1202 M-237 NP831655E ASCO A C D BN BOTH BNHY8800B POOL CLEANUP PUMPS ELEV 1988-0 N CHARGING PUMP RWST SUCTION 112 AUX BLDG/ 1114 LIMITORQU SB-00 LIMITORQUE A D D BN BOTH 29 BNLCV0112D VALVE ELEV 1974-0 E N CHARGING PUMP RWST SUCTION 111 AUX BLDG/ 1107 LIMITORQU SB-00 LIMITORQUE A D D BN BOTH 28 BNLCV0112E VALVE ELEV 1974-0 E Y RWST ISOL VLV FOR FUEL POOL 121 AUX BLDG/ 1202 NAMCO EA180-12302 NAMCO A C D BN COLD BNZS8800A CLEANUP PUMPS LMT SW ELEV 1988-0 HE-3/6 EA180-11303 Y RWST ISOL VLV FOR FUEL POOL 121 AUX BLDG/ 1202 NAMCO EA180-11302 NAMCO A C D BN COLD BNZS8800B CLEANUP PUMPS LMT SW ELEV 1988-0 EA180-11302 Y RHR PUMP RWST SUCTION VALVE 112 AUX BLDG/ 1111 HE-3/6 EA180-12303 NAMCO A D D BN COLD 39 BNZS8812AA LIMIT SWITCH ELEV 1974-0 EA180-12303(spare)

Y RHR PUMP RWST SUCTION VALVE 111 AUX BLDG/ 1109 HE-3/6 EA180- NAMCO A D D BN COLD 39 BNZS8812BA LIMIT SWITCH ELEV 1974-0 NAMCO 12303(spare)

EA180-12302 Y ISOL VLV FOR SI PUMPS MIN. RECIRC 111 AUX BLDG/ 1108 NAMCO EA180-21302 NAMCO A D D BN --- 28 BNZS8813 LIMIT SWITCH ELEV 1974-0 HE-3/6 EA180-21303 N CENTRIFUGAL CHARGING PUMP A 112 AUX BLDG/ 1114 AE-2 FRAME-5808-P39 Westinghouse A D D BG BOTH 29 DPBG05A MOTOR ELEV 1974-0 500 HP

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 27 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N CENTRIFUGAL CHARGING PUMP A 112 AUX BLDG/ 1114 E-029-P02 DS-7445/ P/N Kerite/ EGS (option) A C D BG BOTH 29 MOTOR TERMINATE KIT ELEV 1974-0 3.99.16-3x250MCM-DPBG05A-E01 HVNS N CENTRIFUGAL CHARGING PUMP B 111 AUX BLDG/ 1107 AE-2 FRAME-5808-P39 Westinghouse A D D BG BOTH 28 DPBG05B MOTOR ELEV 1974-0 500 HP N CENTRIFUGAL CHARGING PUMP B 111 AUX BLDG/ 1107 E-029-P02 P/N 3.99.16- EGS A D D BG BOTH 28 DPBG05B-E01 MOTOR TERMINATE KIT ELEV 1974-0 3x250MCM-HVNS N RHR PUMP A MOTOR 112 AUX BLDG/ 1111 AE-2 FRAME-5808-P39 Westinghouse A D D EJ COLD DPEJ01A ELEV 1974-0 500 HP N RHR PUMP A MOTOR TERMINATION 112 AUX BLDG/ 1111 E-029-P02 P/N 3.99.16- EGS A D D EJ COLD DPEJ01A-E01 KIT ELEV 1974-0 3x250MCM-HVNS N RHR PUMP B MOTOR 111 AUX BLDG/ 1109 AE-2 FRAME-5808-P39 Westinghouse A D D EJ COLD DPEJ01B ELEV 1974-0 500 HP N RHR PUMP B MOTOR TERMINATION 111 AUX BLDG/ 1109 E-029-P02 P/N 3.99.16- EGS A D D EJ COLD DPEJ01B-E01 KIT ELEV 1974-0 3x250MCM-HVNS N SI PUMP A MOTOR 112 AUX BLDG/ 1113 AE-2 LIFELINE D, Westinghouse A D D EM - 29 DPEM01A ELEV 1974-0 FRAME 5808H N SI PUMP A MOTOR TERMINATION KIT 112 AUX BLDG/ 1113 E-029-P02 P/N 3.99.16- EGS A D D EM --- 29 DPEM01A-E01 ELEV 1974-0 3x250MCM-HVNS N SI PUMP B MOTOR 111 AUX BLDG/ 1108 AE-2 LIFELINE D, Westinghouse A D D EM - 28 DPEM01B ELEV 1974-0 FRAME 5808H N SI PUMP B MOTOR TERMINATION KIT 111 AUX BLDG/ 1108 E-029-P02 P/N 3.99.16- EGS A D D EM --- 28 DPEM01B-E01 ELEV 1974-0 3x250MCM-HVNS N CONTAINMENT SPRAY PUMP A 112 AUX BLDG/ 1112 M-088 Motor info on Westinghouse A D D EN ---

DPEN01A MOTOR ELEV 1974-0 drawing M-088-00051 N CONTAINMENT SPRAY PUMP A 112 AUX BLDG/ 1112 E-029-P02 DS-7445/ P/N Kerite/ EGS (option) A D D EN ---

MOTOR TERMINATION KIT ELEV 1974-0 3.99.16-3x250MCM-DPEN01A-E01 HVNS N CONTAINMENT SPRAY PUMP B 112 AUX BLDG/ 1110 M-088 Motor info on Westinghouse A D D EN ---

DPEN01B MOTOR ELEV 1974-0 drawing M-088-00051

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 28 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N CONTAINMENT SPRAY PUMP B 112 AUX BLDG/ 1110 E-029-P02 DS-7445/ P/N Kerite/ EGS (option) A D D EN ---

MOTOR TERMINATION KIT ELEV 1974-0 3.99.16-3x250MCM-DPEN01B-E01 HVNS Y SI PUMP ROOM COOLER MOTOR 112 AUX BLDG/ 1113 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL --- 29 DSGL09A ELEV 1974-0 256T Y SI PUMP ROOM COOLER MOTOR 111 AUX BLDG/ 1108 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL --- 28 DSGL09B ELEV 1974-0 256T Y RHR PUMP ROOM COOLER MOTOR 112 AUX BLDG/ 1111 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL COLD DSGL10A ELEV 1974-0 256T Y RHR PUMP ROOM COOLER MOTOR 111 AUX BLDG/ 1109 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL COLD DSGL10B ELEV 1974-0 256T Y CENT. CHARGING PUMP ROOM 112 AUX BLDG/ 1114 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL BOTH 29 DSGL12A COOLER MOTOR ELEV 1974-0 256T Y CENT. CHARGING PUMP ROOM 112 AUX BLDG/ 1107 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL BOTH 28 DSGL12B COOLER MOTOR ELEV 1974-0 256T Y CTMT. SPRAY PUMP ROOM COOLER 112 AUX BLDG/ 1112 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL ---

DSGL13A MOTOR ELEV 1974-0 256T Y CTMT. SPRAY PUMP ROOM COOLER 111 AUX BLDG/ 1110 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL ---

DSGL13B MOTOR ELEV 1974-0 256T Y PENETRATION ROOM COOLER 144 AUX BLDG/ 1410 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL BOTH DSGL15A MOTOR ELEV 2026-0 258T Y PENETRATION ROOM COOLER 143 AUX BLDG/ 1409 M-612 Lifeline T: Frame Westinghouse/ Carrier A D D GL BOTH MOTOR ELEV 2026-0 258T DSGL15B N CONTAINMENT COOLER FAN MOTOR 262 RX BLDG/ 2000 M-620 600287-43 American Air Filter A D A GN BOTH ELEV 2068-8 MOTOR, 150/75 (Joy/Reliance)

HP NOMINAL, 460 DSGN01A VAC, 3 PHASE, 60 HZ, RELIANCE, 5005UCZ FRAME N CONTAINMENT COOLER FAN MOTOR 262 RX BLDG/ 2000 M-620 600287-43 American Air Filter A D A GN BOTH ELEV 2068-8 MOTOR, 150/75 (Joy/Reliance)

HP NOMINAL, 460 DSGN01B VAC, 3 PHASE, 60 HZ, RELIANCE, 5005UCZ FRAME

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 29 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N CONTAINMENT COOLER FAN MOTOR 261 RX BLDG/ 2000 M-620 600287-43 American Air Filter A D A GN BOTH ELEV 2068-8 MOTOR, 150/75 (Joy/Reliance)

HP NOMINAL, 460 DSGN01C VAC, 3 PHASE, 60 HZ, RELIANCE, 5005UCZ FRAME N CONTAINMENT COOLER FAN MOTOR 261 RX BLDG/ 2000 M-620 600287-43 American Air Filter A D A GN BOTH ELEV 2068-8 MOTOR, 150/75 (Joy/Reliance)

HP NOMINAL, 460 DSGN01D VAC, 3 PHASE, 60 HZ, RELIANCE, 5005UCZ FRAME N CONTAINMENT COOLER ISOLATION 134 AUX BLDG/ 1323 LIMITORQU SMB-000 LIMITORQUE B D D EF BOTH EFHV0031 VALVE ELEV 2000-0 E N CONTAINMENT COOLER ISOLATION 133 AUX BLDG/ 1322 LIMITORQU SMB-000 LIMITORQUE B D D EF BOTH EFHV0032 VALVE ELEV 2000-0 E N CONTAINMENT COOLER ISOLATON 231 RX BLDG/ 2000 LIMITORQU SMB-000 LIMITORQUE B D B EF BOTH EFHV0033 VALVE ELEV 1998-6 E N CONTAINMENT COOLER ISOLATION 231 RX BLDG/ 2000 LIMITORQU SMB-000 LIMITORQUE B D B EF BOTH EFHV0034 VALVE ELEV 1998-6 E N VALVE TERMINAL BOX 134 AUX BLDG/ 1320 E-093 NQB. 616822 Buchanan (Amerace) A A D EF BOTH 30 EFHV0043-E01 ELEV 2000-0 N VALVE TERMINAL BOX 134 AUX BLDG/ 1320 E-093 NQB. 616822 Buchanan (Amerace) A A D EF BOTH 30 EFHV0044-E01 ELEV 2000-0 N CONTAINMENT COOLER ISOLATION 231 RX BLDG/ 2000 LIMITORQU SMB-000 LIMITORQUE B B D EF BOTH EFHV0045 VALVE ELEV 1998-6 E N CONTAINMENT COOLER ISOLATION 231 RX BLDG/ 2000 LIMITORQU SMB-000 LIMITORQUE B B D EF BOTH EFHV0046 VALVE ELEV 1998-6 E N CONTAINMENT COOLER ISOLATION 134 AUX BLDG/ 1323 LIMITORQU SMB-000 LIMITORQUE A D D EF BOTH EFHV0049 VALVE ELEV 2000-0 E N CONTAINMENT COOLER ISOLATION 133 AUX BLDG/ 1322 LIMITORQU SMB-000 LIMITORQUE A D D EF BOTH EFHV0050 VALVE ELEV 2000-0 E Y EFHV0043 SOLENOID VALVE 134 AUX BLDG/ 1320 M-237 NP8320A187E ASCO A A D EF BOTH 30 EFHY0043 ELEV 2000-0 Y EFHV0044 SOLENOID VALVE 134 AUX BLDG/ 1320 M-237 NP8320A187E ASCO A A D EF BOTH 30 EFHY0044 ELEV 2000-0 Y ESW TO AIR COMPRESOR ISO 134 AUX BLDG/ 1320 J-301 1153DB6R Rosemount Nuclear A C D EF BOTH 30 EFPDT0043 ELEV 2000-0 Y ESW TO AIR COMPRESOR ISO 134 AUX BLDG/ 1320 J-301 1153DB6R Rosemount Nuclear A C D EF BOTH 30 EFPDT0044 ELEV 2000-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 30 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y EFHV0043 LIMIT SWITCH 134 AUX BLDG/ 1320 NAMCO EA180-11302 NAMCO A A D EF BOTH 30 EFZS0043 ELEV 2000-0 EA180-12302 Y EFHV0044 LIMIT SWITCH 134 AUX BLDG/ 1320 NAMCO EA180-11302 NAMCO A A D EF BOTH 30 EFZS0044 ELEV 2000-0 EA180-12302 Y RCP THERMAL BARRIER (TOTAL) 134 AUX BLDG/ 1127 J-301 1153DB4R Rosemount Nuclear A D D EG BOTH EGFT0062 OUTLET FLOW ELEV 2000-0 Y CCW HX OUT TO RCP BY-PASS 134 AUX BLDG/ 1320 J-301 1153DB5R Rosemount Nuclear B C D EG BOTH 30 EGFT0128 ELEV 2000-0 Y CCW HX OUT TO RCP BY-PASS 134 AUX BLDG/ 1320 J-301 1153DB5R Rosemount Nuclear B C D EG BOTH 30 EGFT0129 ELEV 2000-0 N RC PUMP CCW SUPPLY CONT ISO 134 AUX BLDG/ 1323 LIMITORQU SB-0 LIMITORQUE A D D EG BOTH EGHV0058 ELEV 2000-0 E N RC PUMP CCW RETURN CONT ISO 134 AUX BLDG/ 1323 LIMITORQU SMB-0 LIMITORQUE A D D EG BOTH EGHV0059 ELEV 2000-0 E N RC PUMP CCW RETURN CONT ISO 231 RX BLDG/ 2000 LIMITORQU SMB-0 LIMITORQUE A D A EG BOTH EGHV0060 ELEV 1998-6 E N CONT ISO VLV CCW RTN FROM RC 134 AUX BLDG/ 1323 LIMITORQU SMB-000 LIMITORQUE A D D EG BOTH EGHV0061 PMP THER BARR ELEV 2000-0 E N CONT ISO VLV CCW RTN FROM RC 231 RX BLDG/ 2000 LIMITORQU SMB-00 LIMITORQUE A D A EG BOTH EGHV0062 PMP THER BARR ELEV 1998-6 E N ISO VALVE CCW SUPPLY TO RC 134 AUX BLDG/ 1323 LIMITORQU SB-0 LIMITORQUE A D D EG BOTH EGHV0071 PUMP ELEV 2000-0 E N RHR MINI FLOW ISOLATION VALVE 111 AUX BLDG/ 1111 LIMITORQU SMB-000 LIMITORQUE A D D EJ COLD EJFCV0610 LOOP A ELEV 1974-0 E N RHR MINI FLOW ISOLATION VALVE 111 AUX BLDG/ 1109 LIMITORQU SMB-000 LIMITORQUE A D D EJ COLD EJFCV0611 LOOP B ELEV 1974-0 E Y RHR PUMP B MIN. FLOW INDICATING 131 AUX BLDG/ 1107 ESE-40A 581A-0 ITT Barton A D D EJ COLD 28 EJFIS0611 SWITCH ELEV 2000-0 N RHR TO SIS TEST LINE ISO VLV 231 RX BLDG/ 2000 E-028 51-35 Ametek Staza Division A D A EJ ---

EJHCV8825 ELEV 1998-6 N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A EJ ---

EJHCV8825-E01 ELEV 1998-6 604-JJ N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A EJ COLD EJHCV8890A-E01 ELEV 1998-6 604-JJ N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A EJ COLD EJHCV8890B-E01 ELEV 1998-6 604-JJ N RHR 1A TO NUC SAM SYS 132 AUX BLDG/ 1310 J-603A V52600-6040-7 Valcor Engineering B D D EJ ---

EJHV0014 ELEV 2000-0 N RHR 1B TO NUC SAM SYS 131 AUX BLDG/ 1309 J-603A V52600-6040-7 Valcor Engineering B D D EJ ---

EJHV0015 ELEV 2000-0 N RHR SHUTDOWN SUCTION LINE 231 RX BLDG/ 2000 LIMITORQU SMB-2 LIMITORQUE B D A EJ BOTH EJHV8701A ISOLATION VALVE LOOP A ELEV 1998-6 E

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 31 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N RHR SHUTDOWN SUCTION LINE 231 RX BLDG/ 2000 LIMITORQU SMB-2 LIMITORQUE B D A EJ BOTH EJHV8701B ISOLATION VALVE LOOP B ELEV 1998-6 E N RHR INJECTION BALANCE LINE/HL 132 AUX BLDG/ 1310 LIMITORQU SB-1 LIMITORQUE A D D EJ COLD EJHV8716A FEED LINE VALVE ELEV 2000-0 E N RHR INJECTION BALANCE LINE/HL 131 AUX BLDG/ 1309 LIMITORQU SB-1 LIMITORQUE A D D EJ COLD EJHV8716B FEED LINE VALVE ELEV 2000-0 E N RHR TO CHARGING SI PUMP 132 AUX BLDG/ 1310 LIMITORQU SB-00 LIMITORQUE A D D EJ COLD EJHV8804A SUCTIONS ELEV 2000-0 E N RHR TO CHARGING/SI PUMP 111 AUX BLDG/ 1108 LIMITORQU SB-00 LIMITORQUE A D D EJ COLD 28 EJHV8804B SUCTIONS ELEV 1974-0 E N RHR ISOL VALVE TO COLD LEG RCS 134 AUX BLDG/ 1323 LIMITORQU SBD-3 LIMITORQUE A D D EJ COLD EJHV8809A LOOPS 1 AND 2 ELEV 2000-0 E N RHR ISOL VALVE TO COLD LEG RCS 133 AUX BLDG/ 1322 LIMITORQU SBD-3 LIMITORQUE A D D EJ COLD EJHV8809B LOOPS 3 AND 4 ELEV 2000-0 E N CONT RECIRC SUMP ISOLATION 124 AUX BLDG/ 1204 LIMITORQU SB-1 LIMITORQUE A B D EJ COLD EJHV8811A VALVE (ENCAPSULATED) ELEV 1988-0 E N CONT RECIRC SUMP ISOLATION 123 AUX BLDG/ 1203 LIMITORQU SB-1 LIMITORQUE A B D EJ COLD EJHV8811B VALVE (ENCAPSULATED) ELEV 1988-0 E N RHR ISOL VALVE TO HOT LEGS RCS 133 AUX BLDG/ 1322 LIMITORQU SBD-3 LIMITORQUE A D D EJ COLD EJHV8840 LOOPS 2 AND 3 ELEV 2000-0 E N TEST LINE ISOL VLV HOT LEG INJ 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A EJ ---

EJHY8825 LINE SOL ELEV 1998-6 N TEST LINE ISO VLV HOT LEG INJ LINE 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EJ ---

EJHY8825-E01 SOL CONNECTOR ELEV 1998-6 N TEST LINE ISOLATION VALVE COLD 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A EJ COLD EJHY8890A LEG INJ LINE SOL ELEV 1998-6 N TEST LINE ISO VLV COLD LEG INJ 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EJ COLD EJHY8890A-E01 LINE SOL CONNECTOR ELEV 1998-6 N TEST LINE ISOLATION VALVE COLD 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A EJ COLD EJHY8890B LEG INJ LINE SOL ELEV 1998-6 N TEST LINE ISO VLV COLD LEG INJ 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EJ COLD LINE SOL CONNECTOR ELEV 1998-6 EJHY8890B-E01 Y CTMT RECIRC SUMP LEVEL REACTOR BLDG 2000 J-301 1154DP4RG Rosemount Nuclear A D C EJ --- 25 TRANSMITTER 2000' EL 90 DEG EJLT0007 WEST OF N/S CENTER LINE

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 32 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y CTMT RECIRC SUMP LEVEL REACTOR BLDG 2000 J-301 1154DP4RG Rosemount Nuclear A D C EJ --- 25 TRANSMITTER 2000' EL 90 DEG EJLT0008 WEST OF N/S CENTER LINE Y RHR SHUTDOWN SUCT LINE ISOL 231 RX BLDG/ 2000 HE-3/6 EA180-12303 NAMCO B D A EJ BOTH EJZS8701BA VLV LOOP B LMT SW ELEV 1998-6 EA180-12303 N VALVE TERMINAL BOX (EJZS8701BB) 231 RX BLDG/ 2000 E-028 1600-NUC Marathon Special A D A EJ BOTH EJZS8701BA-E01 ELEV 1998-6 Products N RHR PUMP SUCT LINE ISOL VLV 231 RX BLDG/ 2000 HE-8 N11007 Conax B D A EJ BOTH EJZS8701BA-E02 LOOP B LS CONNECTOR ELEV 1998-6 Y RHR SHUTDOWN SUCT LINE ISOL 231 RX BLDG/ 2000 HE-3/6 EA180-12303 NAMCO B D A EJ BOTH EJZS8701BB VLV LOOP B LMT SW ELEV 1998-6 EA180-12303 N RHR PUMP SUCT LINE ISOL VLV 231 RX BLDG/ 2000 HE-3/6 N11007 Conax B D A EJ BOTH EJZS8701BB-E01 LOOP B LS CONNECTOR ELEV 1998-6 Y RHR TO CHARGING/SI PUMP 132 AUX BLDG/ 1310 HE-3/6 EA180-12303 NAMCO A D D EJ COLD 39 EJZS8804A SUCTIONS LIMIT SWITCH ELEV 2000-0 NAMCO EA180-12302 Y RHR TO CHARGING/SI PUMP 111 AUX BLDG/ 1108 HE-3/6 EA180-12303 NAMCO A D D EJ COLD 28 EJZS8804BA SUCTIONS LIMIT SWITCH ELEV 1974-0 EA180- 39 12303(spare)

Y RHR TO CHARGING/SI PUMP 111 AUX BLDG/ 1108 HE-3/6 EA180-12303 NAMCO A D D EJ COLD 28 EJZS8804BB SUCTIONS LIMIT SWITCH ELEV 1974-0 EA180- 39 12303(spare)

Y RHR ISOL VLV TO COLD LEG RCS 134 AUX BLDG/ 1323 HE-3/6 EA180-12303 NAMCO A D D EJ COLD EJZS8809AA LOOPS 1&2 LIMIT SW ELEV 2000-0 EA180-12303 Y RHR ISOL VLV TO COLD LEG RCS 133 AUX BLDG/ 1322 HE-3/6 EA180-12303 NAMCO A D D EJ COLD EJZS8809BA LOOPS 3&4 LIMIT SW ELEV 2000-0 NAMCO EA180-12302 Y CONT RECIRC SUMP ISOLATION 124 AUX BLDG/ 1204 HE-3/6 EA180- NAMCO A B D EJ COLD 39 EJZS8811A VALVE LIMIT SWITCH ELEV 1988-0 NAMCO 12303(spare)

EA180-12302 N CONT RECIRC SUMP ISOLATION 124 AUX BLDG/ 1204 HE-8 N11007 Conax A B D EJ COLD EJZS8811A-E01 VALVE LS CONNECTOR ELEV 1988-0 Y CONT RECIRC SUMP ISOLATION 123 AUX BLDG/ 1203 NAMCO EA180- NAMCO A B D EJ COLD 39 EJZS8811B VALVE LIMIT SWITCH ELEV 1988-0 HE-3/6 12303(spare)

EA180-12302 N CONT RECIRC SUMP ISOLATION 123 AUX BLDG/ 1203 HE-8 N11007 Conax A B D EJ COLD EJZS8811B-E01 VALVE LS CONNECTOR ELEV 1988-0 Y TEST LINE ISO VLV HOT LEG INJ LINE 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D A EJ ---

EJZS8825 LIMIT SW ELEV 1998-6 EA180-12303 N TEST LINE ISO VLV HOT LEG INJ LINE 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EJ ---

EJZS8825-E01 LS CONNECTOR ELEV 1998-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 33 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y RHR ISOL VLV TO HOT LEGS RCS 133 AUX BLDG/ 1322 HE-3/6 EA180-12303 NAMCO A D D EJ COLD EJZS8840A LOOPS 2&3 LIMIT SW ELEV 2000-0 NAMCO EA180-12302 Y TEST LINE ISOL VLV COLD LEG INJ 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D A EJ COLD EJZS8890A LINE LIMIT SW ELEV 1998-6 EA180-12303 N TEST LINE ISO VLV COLD LEG INJ 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EJ COLD EJZS8890A-E01 LINE LS CONNECTOR ELEV 1998-6 Y TEST LINE ISOL VLV COLD LEG INJ 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D A EJ COLD EJZS8890B LINE LIMIT SW ELEV 1998-6 EA180-12303 N TEST LINE ISO VLV COLD LEG INJ 231 RX BLDG/ 2000 HE-8 EA180-12303 Conax A D A EJ COLD EJZS8890B-E01 LINE LS CONNECTOR ELEV 1998-6 N BIT DISCHARGE VALVE TO RCS 134 AUX BLDG/ 1323 LIMITORQU SBD-00 LIMITORQUE A D D EM BOTH EMHV8801A ELEV 2000-0 E N BIT DISCHARGE VALVE TO RCS 134 AUX BLDG/ 1323 LIMITORQU SBD-00 LIMITORQUE A D D EM BOTH EMHV8801B ELEV 2000-0 E N SI PUMP A DISCHARGE VALVE TO 134 AUX BLDG/ 1323 LIMITORQU SBD-00 LIMITORQUE A D D EM ---

EMHV8802A HOT LEGS 2 & 3 ELEV 2000-0 E N SI PUMP B DISCHARGE VALVE TO 133 AUX BLDG/ 1322 LIMITORQU SBD-00 LIMITORQUE A D D EM ---

EMHV8802B HOT LEGS 1 & 4 ELEV 2000-0 E N CHARGING PUMP DISCHARGE VALVE 111 AUX BLDG/ 1126 LIMITORQU SBD-00 LIMITORQUE A D D EM BOTH EMHV8803A TO BIT ELEV 1974-0 E N CHARGING PUMP DISCHARGE VALVE 111 AUX BLDG/ 1126 LIMITORQU SBD-00 LIMITORQUE A D D EM BOTH EMHV8803B TO BIT ELEV 1974-0 E N RHR TO CVCS AND SI PUMPS ISOL 112 AUX BLDG/ 1113 LIMITORQU SB-00 LIMITORQUE A D D EM COLD 29 EMHV8807A VALVE ELEV 1974-0 E N RHR TO CVCS AND SI PUMPS ISOL 111 AUX BLDG/ 1108 LIMITORQU SB-00 LIMITORQUE A D D EM COLD 28 EMHV8807B VALVE ELEV 1974-0 E N ISOLATION VALVE MINIFLOW LINE OF 112 AUX BLDG/ 1113 LIMITORQU SMB-00 LIMITORQUE A D D EM --- 29 EMHV8814A SI PUMP A ELEV 1974-0 E N ISOLATION VALVE MINIFLOW LINE OF 112 AUX BLDG/ 1113 LIMITORQU SMB-00 LIMITORQUE A D D EM --- 29 EMHV8814B SI PUMP B ELEV 1974-0 E N SI PUMP A DISCHARGE VALVE TO 112 AUX BLDG/ 1113 LIMITORQU SB-00 LIMITORQUE A D D EM --- 29 EMHV8821A RCS COLD LEGS ELEV 1974-0 E N SI PUMP B DISCHARGE VALVE TO 111 AUX BLDG/ 1108 LIMITORQU SB-00 LIMITORQUE A D D EM --- 28 EMHV8821B RCS COLD LEGS ELEV 1974-0 E N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D C EM ---

EMHV8823-E01 ELEV 1998-6 604-JJ N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D C EM ---

EMHV8824-E01 ELEV 1998-6 604-JJ N SI PUMPS A & B DISCHARGE VALVE 133 AUX BLDG/ 1322 LIMITORQU SBD-00 LIMITORQUE A D D EM ---

EMHV8835 TO RCS COLD LEGS ELEV 2000-0 E N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A EM BOTH EMHV8843-E01 ELEV 1998-6 604-JJ

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 34 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A EM ---

EMHV8871-E01 ELEV 1998-6 604-JJ N VALVE TERMINAL BOX 232 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D C EM ---

EMHV8881-E01 ELEV 1998-6 604-JJ N VALVE TERMINAL BOX 133 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D EM ---

EMHV8888-E01 ELEV 2000-0 N RWST SUCTION VALVE TO SI PUMP A 112 AUX BLDG/ 1113 LIMITORQU SB-00 LIMITORQUE A D D EM --- 29 EMHV8923A ELEV 1974-0 E N RWST SUCTION VALVE TO SI PUMP B 111 AUX BLDG/ 1108 LIMITORQU SB-00 LIMITORQUE A D D EM --- 28 EMHV8923B ELEV 1974-0 E N RHR TO CVCS AND SI PUMPS ISOL 112 AUX BLDG/ 1108 LIMITORQU SMB-000 LIMITORQUE B D D EM --- 28 EMHV8924 VALVE ELEV 1974-0 E N VALVE TERMINAL BOX 134 AUX BLDG/ 1323 E-093 NQB. 616822 Buchanan (Amerace) A D D EM ---

EMHV8964-E01 ELEV 2000-0 N TESTLINE/CONTAINMENT ISOL 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D C EM ---

EMHY8823 VALVE SI COLD LEGS ELEV 1998-6 N TEST LINE CONT ISOL VLV SI COLD 231 RX BLDG/ 2000 HE-8 N11007 Conax A D C EM ---

EMHY8823-E01 LEGS CONNECTOR ELEV 1998-6 N TESTLINE/ CONTAINMENT ISOL VLV 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D C EM ---

EMHY8824 RCS HOT LEGS 1 & 4 ELEV 1998-6 N TEST LINE CONT ISOL VLV RCS HOT 231 RX BLDG/ 2000 HE-8 N11007 Conax A D C EM ---

EMHY8824-E01 LEGS 1 & 4 CONNECTOR ELEV 1998-6 N BIT TEST LINE AND CONTAINMENT 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A EM BOTH EMHY8843 ISOLATION VALVE ELEV 1998-6 N BIT TEST LINE AND CONT ISOL 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EM BOTH EMHY8843-E01 VALVE CONNECTOR ELEV 1998-6 N SI TESTLINE/CONTAINMENT 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A EM ---

EMHY8871 ISOLATION VALVE ELEV 1998-6 N SI TEST LINE CONT ISOL VALVE 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EM ---

EMHY8871-E01 CONNECTOR ELEV 1998-6 N TESTLINE/CONTAINMENT ISOL VLV 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D C EM ---

EMHY8881 RCS HOT LEGS 2 & 3 ELEV 1998-6 N TEST LINE CONT ISOL VLV RCS HOT 231 RX BLDG/ 2000 HE-8 N11007 Conax A D C EM ---

EMHY8881-E01 LEGS 2 & 3 CONNECTOR ELEV 1998-6 N ACC FILL LINE CONTAINMENT ISO 133 AUX BLDG/ 1322 M-237 NP831655E ASCO A D D EM ---

EMHY8888 VALVE ELEV 2000-0 N SI TESTLINE/CONTAINMENT 133 AUX BLDG/ 1323 M-237 NPK831654E ASCO A D D EM ---

EMHY8964 ISOLATION VALVE ELEV 2000-0 Y SI PUMP A DISCH VLV TO HOT LEGS 134 AUX BLDG/ 1323 HE-3/6 EA180-12303 NAMCO A D D EM ---

EMZS8802AA 2&3 LIMIT SWITCH ELEV 2000-0 EA180-12303 Y SI PUMP B DISCH VLV TO HOT LEGS 133 AUX BLDG/ 1322 HE-3/6 EA180-12303 NAMCO A D D EM ---

EMZS8802BA 1&4 LIMIT SWITCH ELEV 2000-0 EA180-12303

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 35 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y ISOL VLV MINIFLOW LINE OF SI PUMP 112 AUX BLDG/ 1113 HE-3/6 EA180-21303 NAMCO A D D EM --- 29 EMZS8814A A LIMIT SWITCH ELEV 1974-0 EA180- 39 21303(spare)

Y ISOL VLV MINIFLOW LINE OF SI PUMP 112 AUX BLDG/ 1113 NAMCO EA180-21302 NAMCO A D D EM --- 29 EMZS8814B B LIMIT SWITCH ELEV 1974-0 HE-3/6 EA180- 39 21303(spare)

Y TEST/LINE/CONTAINMENT ISOL VLV 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D C EM ---

EMZS8823 SI COLD LEGS LMT SW ELEV 1998-6 EA180-12303 N TEST LINE CONT ISO VLV SI COLD 231 RX BLDG/ 2000 HE-8 N11007 Conax A D C EM ---

EMZS8823-E01 LEGS LS CONNECTOR ELEV 1998-6 Y TESTLINE/CONT ISOL VLV RCS HOT 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D C EM ---

EMZS8824 LEGS 1&4 LIMIT SW ELEV 1998-6 EA180-12303 N TEST LINE CONT ISO VLV HOT LEGS 231 RX BLDG/ 2000 HE-8 N11007 Conax A D C EM ---

EMZS8824-E01 1 & 4 LS CONNECTOR ELEV 1998-6 Y SI PMPS A&B DISCH VLV TO RCS 133 AUX BLDG/ 1322 HE-3/6 EA180-12303 NAMCO A D D EM ---

EMZS8835A COLD LEGS LIMIT SW ELEV 2000-0 NAMCO EA180-12302 Y BIT TESTLINE AND CONTAINMENT 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D A EM BOTH EMZS8843 ISOL VLV LIMIT SW ELEV 1998-6 EA180-12303 N BIT TEST LINE CONT ISOL VLV LS 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EM BOTH EMZS8843-E01 CONNECTOR ELEV 1998-6 Y SI TESTLINE/CONTAINMENT ISOL 231 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D A EM ---

EMZS8871 VALVE LIMIT SWITCH ELEV 1998-6 EA180-12303 N SI TEST LINE CONT ISOL VLV LS 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EM ---

EMZS8871-E01 CONNECTOR ELEV 1998-6 Y TESTLINE/CONT ISOL VLV RCS HOT 232 RX BLDG/ 2000 HE-3/6 EA180-11303 NAMCO A D C EM ---

EMZS8881 LEGS 2&3 LIMIT SW ELEV 1998-6 EA180-12303 N TEST LINE CONT ISO VLV HOT LEGS 232 RX BLDG/ 2000 HE-8 N11007 Conax A D C EM ---

EMZS8881-E01 2 & 3 LS CONNECTOR ELEV 1998-6 Y ACC FILL LINE CONTAINMENT ISOL 133 AUX BLDG/ 1322 HE-3/6 EA180-11303 NAMCO A D D EM ---

EMZS8888 VLV LIMIT SWITCH ELEV 2000-0 NAMCO EA180-12302 Y SI TESTLINE/CONTAINMENT ISOL 133 AUX BLDG/ 1323 NAMCO EA180-11302 NAMCO A D D EM ---

EMZS8964 VALVE LIMIT SWITCH ELEV 2000-0 EA180-12302 N CONTAINMENT ISOLATION 124 AUX BLDG/ 1204 LIMITORQU SMB-00 LIMITORQUE A C D EN ---

ENHV0001 (ENCAPSULATED) ELEV 1988-0 E N CONTAINMENT ISOLATION 134 AUX BLDG/ 1323 LIMITORQU SMB-00 LIMITORQUE A D D EN ---

ENHV0006 ELEV 2000-0 E N CONTAINMENT ISOLATION 123 AUX BLDG/ 1203 LIMITORQU SMB-00 LIMITORQUE A C D EN ---

ENHV0007 (ENCAPSULATED) ELEV 1988-0 E N CONTAINMENT ISOLATION 133 AUX BLDG/ 1322 LIMITORQU SMB-00 LIMITORQUE A D D EN ---

ENHV0012 ELEV 2000-0 E N SPRAY ADD TANK TO SPRAY ADD 132 AUX BLDG/ 1315 LIMITORQU SMB-00 LIMITORQUE A D D EN --- 30 ENHV0015 EDUCTOR ELEV 2000-0 E

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 36 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N SPRAY ADD TANK TO SPRAY ADD 132 AUX BLDG/ 1315 LIMITORQU SMB-00 LIMITORQUE A D D EN --- 30 ENHV0016 EDUCTOR ELEV 2000-0 E Y CTMT SPRAY ADD TK LEVEL 132 AUX BLDG/ 1315 J-301 1153DB3RA Rosemount Nuclear A D D EN --- 30 ENLT0015 ELEV 2000-0 Y CTMT SPRAY ADD TK LEVEL 132 AUX BLDG/ 1315 J-301 1153DB3RA Rosemount Nuclear A D D EN --- 30 ENLT0016 ELEV 2000-0 Y SPRAY ADD TANK LEVEL 132 AUX BLDG/ 1315 J-301 1153DB5R Rosemount Nuclear A D D EN --- 30 ENLT0017 ELEV 2000-0 Y SPRAY ADD TANK LEVEL 132 AUX BLDG/ 1315 J-301 1153DB5R Rosemount Nuclear A D D EN --- 30 ENLT0019 ELEV 2000-0 N ACCUMULATOR TANK A ISOLATION 231 RX BLDG/ 2000 LIMITORQU SBD-3 LIMITORQUE C D A EP COLD EPHV8808A VALVE ELEV 1998-6 E N ACCUMULATOR TANK D ISOLATION 232 RX BLDG/ 2000 LIMITORQU SBD-3 LIMITORQUE C D A EP COLD EPHV8808D VALVE ELEV 1998-6 E N VALVE TERMINAL BOX 133 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D EP ---

EPHV8880-E01 ELEV 2000-0 Y ACCUMULATOR TANK A VENT VALVE 241 RX BLDG/ 2000 HE-10A 79AB-004-3 Target Rock Corp. B D A EP COLD 44 EPHV8950A ELEV 2026-0 N ACCUMULATOR TANK A VENT VALVE 241 RX BLDG/ 2000 HE-8 N11007 Conax B D A EP COLD EPHV8950A-E01 CONNECTOR ELEV 2026-0 Y ACCUMULATOR TANK B VENT VALVE 242 RX BLDG/ 2000 HE-10A 79AB-004-3 Target Rock Corp. B D A EP COLD 44 EPHV8950B ELEV 2026-0 N ACCUMULATOR TANK B VENT VALVE 242 RX BLDG/ 2000 HE-8 N11007 Conax B D A EP COLD EPHV8950B-E01 CONNECTOR ELEV 2026-0 Y ACCUMULATOR TANK B VENT VALVE 242 RX BLDG/ 2000 HE-10A 79AB-004-3 Target Rock Corp. B D A EP COLD 44 EPHV8950C ELEV 2026-0 N ACCUMULATOR TANK B VENT VALVE 242 RX BLDG/ 2000 HE-8 N11007 Conax B D A EP COLD EPHV8950C-E01 CONNECTOR ELEV 2026-0 Y ACCUMULATOR TANK C VENT VALVE 242 RX BLDG/ 2000 HE-10A 79AB-004-3 Target Rock Corp. B D A EP COLD 44 EPHV8950D ELEV 2026-0 N ACCUMULATOR TANK C VENT VALVE 242 RX BLDG/ 2000 HE-8 N11007 Conax B D A EP COLD EPHV8950D-E01 CONNECTOR ELEV 2026-0 Y ACCUMULATOR TANK C VENT VALVE 242 RX BLDG/ 2000 HE-10A 79AB-004-3 Target Rock Corp. B D A EP COLD 44 EPHV8950E ELEV 2026-0 N ACCUMULATOR TANK C VENT VALVE 242 RX BLDG/ 2000 HE-8 N11007 Conax B D A EP COLD EPHV8950E-E01 CONNECTOR ELEV 2026-0 Y ACCUMULATOR TANK D VENT VALVE 241 RX BLDG/ 2000 HE-10A 79AB-004-3 Target Rock Corp. B D A EP COLD 44 EPHV8950F ELEV 2026-0 N ACCUMULATOR TANK D VENT VALVE 241 RX BLDG/ 2000 HE-8 N11007 Conax B D A EP COLD EPHV8950F-E01 CONNECTOR ELEV 2026-0 N N2 SUPPLY CONT ISOL VALVE 231 RX BLDG/ 1322 M-237 NP831655E ASCO A D D EP ---

EPHY8880 ELEV 1998-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 37 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y ACCUMULATOR TANK A ISOLATION 231 RX BLDG/ 2000 HE-3/6 EA180-12303 NAMCO A D A EP COLD EPZS8808AB VALVE LIMIT SWITCH ELEV 1998-6 EA180-12303 N ACCUMULATOR TANK A ISOL VLV LS 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EP COLD EPZS8808AB-E01 CONNECTOR ELEV 1998-6 N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A EP COLD EPZS8808AB-E02 ELEV 1998-6 Products Y ACCUMULATOR TANK D ISOLATION 231 RX BLDG/ 2000 HE-3/6 EA180-12303 NAMCO A D A EP COLD EPZS8808DB VALVE LIMIT SWITCH ELEV 1998-6 EA180-12303 N ACCUMULATOR TANK D ISOL VLV LS 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A EP COLD EPZS8808DB-E01 CONNECTOR ELEV 1998-6 N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A EP COLD EPZS8808DB-E02 ELEV 1998-6 Products Y N2 SUPPLY CONT ISOL VALVE LIMIT 231 CTMT BLDG/ 1322 HE-3/6 EA180-11303 NAMCO A D D EP ---

EPZS8880 SWITCH ELEV 1998-6 EA180-12303 Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GE --- 34 GED0047 - ELEC SPLY AIR HDLG and Ventilating GEHZ0101 UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GE --- 34 GED0046 - ELEC SPLY AIR HDLG and Ventilating GEHZ0102 UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1122 GENERAL 1122 M-627A MAR-25 American Warming A C D GF --- 27 GFD0033 - ELEC FLOOR AREA and Ventilating GFHZ0011 (NO. 3) (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1122 GENERAL 1122 M-627A MAR-25 American Warming A C D GF --- 27 GFD0034 - ELEC FLOOR AREA and Ventilating GFHZ0012 (NO. 3) (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1122 GENERAL 1122 M-627A MAR-25 American Warming A C D GF --- 27 GFD0035 - ELEC FLOOR AREA and Ventilating GFHZ0013 (NO. 3) (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1122 GENERAL 1122 M-627A MAR-25 American Warming A C D GF --- 27 GFD0036 - ELEC FLOOR AREA and Ventilating GFHZ0014 (NO. 3) (Raymond Control Systems)

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 38 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GF --- 34 GFD0029 - ELEC SPLY AIR HDLG and Ventilating GFHZ0020 UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1504 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GF --- 34 GFD0028 - ELEC EXH & MECH and Ventilating GFHZ0021 EQUIP RM B (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 144 AUX BLDG/ 1410 M-627A MAR-25 American Warming A D D GF ---

GFD0066 - ELEC ELEV 2026-0 and Ventilating GFHZ0030A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1127 M-627A MAR-25 American Warming A D D GF --- 31 GFD0062 - ELEC SPLY AIR HDLG and Ventilating GFHZ0030B UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 144 AUX BLDG/ 1410 M-627A MAR-25 American Warming A D D GF ---

GFD0065 - ELEC ELEV 2026-0 and Ventilating GFHZ0031A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1127 M-627A MAR-25 American Warming A D D GF --- 31 GFHZ0031B GFD0063 - ELEC SPLY AIR HDLG and Ventilating UNIT RM A (Raymond Control Systems)

Y GKHZ0184E SOLENOID VALVE 1506 CTMT PRG 1506 M-237 WPHCX8320A182 ASCO A D D GK --- 34 GKHY0184E SPLY AIR HDLG E UNIT RM A Y CTRL BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GK --- 34 GKD0129 - ELEC SPLY AIR HDLG and Ventilating GKHZ0150 UNIT RM A (Raymond Control Systems)

Y CTRL BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GK --- 34 GKD0128 - ELEC SPLY AIR HDLG and Ventilating GKHZ0151 UNIT RM A (Raymond Control Systems)

N CTRL BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A PAS-111 American Warming A D D GK --- 34 GKD0314 - PNEU SPLY AIR HDLG and Ventilating GKHZ0184E UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GL --- 34 GLD0046 - ELEC SPLY AIR HDLG and Ventilating GLHZ0013 UNIT RM A (Raymond Control Systems)

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 39 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GL --- 34 GLD0047 - ELEC SPLY AIR HDLG and Ventilating GLHZ0014 UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1507 1507 M-627A MAR-25 American Warming A D D GL --- 34 GLD0058 - ELEC PERSONNEL and Ventilating GLHZ0062 HATCH AREA (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1314 AUX BLDG/ 1314 M-627A MAR-25 American Warming A D D GL --- 30 GLD0030 - ELEC CORRIDOR NO. and Ventilating GLHZ0069 3 OUTSIDE HMS (Raymond Control DOOR Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1314 AUX BLDG/ 1314 M-627A MAR-25 American Warming A D D GL --- 30 GLD0031 - ELEC CORRIDOR NO. and Ventilating GLHZ0070 3 OUTSIDE HMS (Raymond Control DOOR Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1314 AUX BLDG/ 1314 M-627A MAR-25 American Warming A D D GL --- 30 GLD0032 - ELEC CORRIDOR NO. and Ventilating GLHZ0071 3 OUTSIDE HMS (Raymond Control DOOR Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1314 AUX BLDG/ 1314 M-627A MAR-25 American Warming A D D GL --- 30 GLD0033 - ELEC CORRIDOR NO. and Ventilating GLHZ0072 3 OUTSIDE HMS (Raymond Control DOOR Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1308 AUX BLDG/ 1307 M-627A MAR-25 American Warming A D D GL ---

GLD0132 - ELEC DEMIN ALLEY and Ventilating GLHZ0085 (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1308 AUX BLDG/ 1307 M-627A MAR-25 American Warming A D D GL ---

GLD0134 - ELEC DEMIN ALLEY and Ventilating GLHZ0086 (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1308 AUX BLDG/ 1308 M-627A MAR-25 American Warming A D D GL ---

GLD0133 - ELEC DEMIN ALLEY and Ventilating GLHZ0087 (Raymond Control Systems)

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 40 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y AUX BLDG ISO DAMPER ACTUATOR - 1308 AUX BLDG/ 1308 M-627A MAR-25 American Warming A D D GL ---

GLD0135 - ELEC DEMIN ALLEY and Ventilating GLHZ0088 (Raymond Control Systems)

Y CONTAINMENT PRESSURE SENSOR 143 AUX BLDG/ 1409 J-301 1153DB6PAN0073 Rosemount Nuclear A D D GN ---

GNPT0934 ELEV 2026-0 N CONTAINMENT PRESSURE 144 AUX BLDG/ 1410 ESE-4A 752 ITT Barton A D D GN ---

GNPT0935 TRANSMITTER ELEV 2026-0 N CONTAINMENT PRESSURE 143 AUX BLDG/ 1409 ESE-4A 752 ITT Barton A D D GN ---

GNPT0936 TRANSMITTER ELEV 2026-0 N CONTAINMENT PRESSURE 144 AUX BLDG/ 1410 ESE-4A 752 ITT Barton A D D GN ---

GNPT0937 TRANSMITTER ELEV 2026-0 N CONTAINMENT PRESSURE 144 AUX BLDG/ 1410 ESE-4A 752 ITT Barton A D D GN HOT 25 GNPT0938 TRANSMITTER WIDE RANGE ELEV 2026-0 N CONTAINMENT PRESSURE 143 AUX BLDG/ 1409 ESE-4A 752 ITT Barton A D D GN HOT 25 GNPT0939 TRANSMITTER WIDE RANGE ELEV 2026-0 Y CTMT COOLER A TEMP 262 RX BLDG/ 2000 J-558B 611-1B-C-4-C-2-A2- Weed Instrument Co., A D A GN BOTH GNTE0060 ELEV 2068-8 0 Inc.

Y CTMT COOLER B TEMP 261 RX BLDG/ 2000 J-558B 611-1B-C-4-C-2-A2- Weed Instrument Co., A D A GN BOTH GNTE0061 ELEV 2068-8 0 Inc.

Y CTMT COOLER C TEMP 261 RX BLDG/ 2000 J-558B 611-1B-C-4-C-2-A2- Weed Instrument Co., A D A GN BOTH GNTE0062 ELEV 2068-8 0 Inc.

Y CTMT COOLER D TEMP 262 RX BLDG/ 2000 J-558B 611-1B-C-4-C-2-A2- Weed Instrument Co., A D A GN BOTH ELEV 2068-8 0 Inc.

GNTE0063 N HYDROGEN ANALYZER CTMT 2047 AUX BLDG 1507 J-603A V52600-5940-2 Valcor Engineering A D D GS --- 34 SAMPLE EAST OF RE-31 GSHV0003 ABOUT 6' OFF OF THE FLOOR N HYDROGEN ANALYZER CTMT 251 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0004 SAMPLE ELEV 2047-6 N HYDROGEN ANALYZER CTMT 251 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0005 SAMPLE ELEV 2047-6 N HYDROGEN ANAL SAMPLE RETURN 133 AUX BLDG/ 1322 J-603A V52660-5940-2 Valcor Engineering A D D GS ---

GSHV0008 TO CTMT ELEV 2000-0 N HYDROGEN ANAL SAMPLE RETURN 242 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

TO CTMT ELEV 2026-0 GSHV0009

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 41 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N HYDROGEN ANALYZER CTMT 2047 AUX BLDG 1506 J-603A V52660-5940-2 Valcor Engineering A D D GS --- 34 SAMPLE NE OF RE-32 GSHV0012 ABOUT 6' OFF OF THE FLOOR N HYDROGEN ANALYZER CTMT 252 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0013 SAMPLE ELEV 2047-6 N HYDROGEN ANALYZER CTMT 251 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0014 SAMPLE ELEV 2047-6 N HYDROGEN ANAL SAMPLE RETURN 134 AUX BLDG/ 1323 J-603A V52660-5940-2 Valcor Engineering A D D GS ---

GSHV0017 TO CTMT ELEV 2000-0 N HYDROGEN ANAL SAMP RETURN TO 242 RX BLDG/ 2000 J-603A V52660-5940-2A Valcor Engineering A D A GS ---

GSHV0018 CTMT ELEV 2026-0 N CTMT ISO ON AUX BUILDING ESF 231 RX BLDG/ 2000 LIMITORQU SMB-000 LIMITORQUE A A D GS ---

GSHV0020 FILTERS INLET ELEV 1998-6 E N CONTAINMENT ISOLATION 133 AUX BLDG/ 1322 LIMITORQU SMB-000 LIMITORQUE A D D GS ---

ELEV 2000-0 E GSHV0021 N PASS ISOLATION 2047 AUX BLDG 1506 J-603A V52660-5940-2 Valcor Engineering A D D GS --- 21 34 NE OF RE-32 GSHV0030 ABOUT 6' OFF OF THE FLOOR N CTMT ATM MONITOR ISOL VALVE 251 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0031 ELEV 2047-6 N CTMT ATM MONITOR ISOL VALVE 154 AUX BLDG/ 1506 J-603A V52660-5940-2 Valcor Engineering A D D GS --- 34 GSHV0032 ELEV 2047-6 N CTMT ATM MONITOR ISOL VALVE 133 AUX BLDG/ 1323 J-603A V52600-5940-2 Valcor Engineering A D D GS ---

GSHV0033 ELEV 2000-0 N CTMT ATM MONITOR ISOL VALVE 231 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0034 ELEV 1998-6 N PASS ISOLATION 251 RX BLDG/ 1507 J-603A V52600-5940-2 Valcor Engineering A D D GS --- 21 34 GSHV0035 ELEV 2047-6 N CTMT ATM MONITOR ISOL VALVE 252 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0036 ELEV 2047-6 N 2047 AUX BLDG EAST OF RE-31 153 AUX BLDG/ 1507 J-603A V52600-5940-2 Valcor Engineering A D D GS --- 34 GSHV0037 ABOUT 6' OFF OF THE FLOOR. ELEV 2047-6 N CTMT ATM MONITOR ISOL VALVE 133 AUX BLDG/ 1322 J-603A V52600-5940-2 Valcor Engineering A D D GS ---

GSHV0038 ELEV 2000-0 N CTMT ATM MONITOR ISOL VALVE 231 RX BLDG/ 2000 J-603A V52600-5940-2A Valcor Engineering A D A GS ---

GSHV0039 ELEV 1998-6

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 42 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N GTHZ0004 SOLENOID VALVE 154 AUX BLDG/ 1506 M-237 NP8320A185V ASCO A D D GT --- 34 GTHY0004 ELEV 2047-6 N GTHZ0005 SOLENOID VALVE 252 RX BLDG/ 2000 M-237 NP8320A185V ASCO A D A GT ---

GTHY0005 ELEV 2047-6 N GTHZ0006 SOLENOID VALVE 154 AUX BLDG/ 1506 M-237 NP8320A185V ASCO A D D GT --- 34 GTHY0006 ELEV 2047-6 N GTHZ0007 SOLENOID VALVE 252 RX BLDG/ 2000 M-237 NP8320A185V ASCO A D A GT ---

GTHY0007 ELEV 2047-6 N GTHZ0008 SOLENOID VALVE 252 RX BLDG/ 2000 M-237 NP8320A185V ASCO A D A GT ---

GTHY0008 ELEV 2047-6 N GTHZ0009 SOLENOID VALVE 153 AUX BLDG/ 1507 M-237 NP8320A185V ASCO A D D GT --- 34 GTHY0009 ELEV 2047-6 N GTHZ0011 SOLENOID VALVE 252 RX BLDG/ 2000 M-237 NP8320A185V ASCO A D A GT ---

GTHY0011 ELEV 2047-6 N GTHZ0012 SOLENOID VALVE 153 AUX BLDG/ 1507 M-237 NP8320A185V ASCO A D D GT --- 34 GTHY0012 ELEV 2047-6 Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GT --- 34 GTD0009 - ELEC SPLY AIR HDLG and Ventilating GTHZ0026 UNIT RM A (Raymond Control Systems)

Y AUX BLDG ISO DAMPER ACTUATOR - 1506 CTMT PRG 1506 M-627A MAR-25 American Warming A D D GT --- 34 GTD0010 - ELEC SPLY AIR HDLG and Ventilating GTHZ0027 UNIT RM A (Raymond Control Systems)

N CTMT HIGH RANGE AREA RADN MON 261 RX BLDG/ 2000 J-361A RD-23 General Atomic Co. A D A GT --- 25 GTRE0059 ELEV 2068-8 N CTMT HIGH RANGE AREA RADN MON 252 RX BLDG/ 2000 J-361A RD-23 General Atomic Co. A D A GT --- 25 GTRE0060 ELEV 2047-6 Y GTHZ0004 LIMIT SWITCH 154 AUX BLDG/ 1506 NAMCO EA180-32302 NAMCO A D D GT --- 34 GTZS0004 ELEV 2047-6 EA180-31302 Y GTHZ0005 LIMIT SWITCH 252 RX BLDG/ 2000 NAMCO EA180-32302 NAMCO A D A GT ---

GTZS0005 ELEV 2047-6 EA180-31302 Y GTHZ0006 LIMIT SWITCH 154 AUX BLDG/ 1506 NAMCO EA180-32302 NAMCO A D D GT --- 34 GTZS0006 ELEV 2047-6 EA180-31302 Y GTHZ0007 LIMIT SWITCH 252 RX BLDG/ 2000 NAMCO EA180-32302 NAMCO A D A GT ---

GTZS0007 ELEV 2047-6 EA180-31302 Y GTHZ0008 LIMIT SWITCH 252 RX BLDG/ 2000 NAMCO EA180-32302 NAMCO A D A GT ---

GTZS0008 ELEV 2047-6 EA180-31302 Y GTHZ0009 LIMIT SWITCH 153 AUX BLDG/ 1507 NAMCO EA180-32302 NAMCO A D D GT --- 34 GTZS0009 ELEV 2047-6 EA180-31302 Y GTHZ0011 LIMIT SWITCH 252 RX BLDG/ 2000 NAMCO EA180-32302 NAMCO A D A GT ---

GTZS0011 ELEV 2047-6 EA180-31302

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 43 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Y GTHZ0012 LIMIT SWITCH 153 AUX BLDG/ 1507 NAMCO EA180-32302 NAMCO A D D GT --- 34 GTZS0012 ELEV 2047-6 EA180-31302 N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-028 1600 NUC Marathon Special A D A HB ---

HBHV7126-E01 ELEV 1998-6 Products N VALVE TERMINAL BOX 133 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D HB ---

HBHV7136-E01 ELEV 2000-0 N VALVE TERMINAL BOX 231 RX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D HB ---

HBHV7150-E01 ELEV 1998-6 N VALVE TERMINAL BOX 231 RX BLDG/ 2000 E-035B 601-JJ, 602-JJ, Kulka A D A HB ---

HBHV7176-E01 ELEV 1998-6 604-JJ N CONTAINMENT ISOLATION VALVE 231 RX BLDG/ 2000 M-237 NPK831654E ASCO A D A HB ---

HBHY7126 ELEV 1998-6 N CONTAINMENT ISOLATION VALVE ROOM 2000 2000 HE-8 N11007 Conax A D A HB ---

HBHY7126-E01 CONNECTOR N CONTAINMENT ISOLATION VALVE 133 AUX BLDG/ 1322 M-237 NPK831654E ASCO A D D HB ---

HBHY7136 ELEV 2000-0 N CONTAINMENT ISOLATION VALVE 133 AUX BLDG/ 1322 M-237 NPK831654E ASCO A D D HB ---

HBHY7150 ELEV 2000-0 HBHY7176 N CONTAINMENT ISOLATION VALVE ROOM 2000 2000 M-237 NPK831654E ASCO A D A HB ---

N CONTAINMENT ISOLATION VALVE ROOM 2000 2000 HE-8 N11007 Conax A D A HB ---

HBHY7176-E01 CONNECTOR Y CONTAINMENT ISOLATION VALVE 231 RX BLDG/ 2000 HE-3/6 EA180-14303 NAMCO A D A HB ---

HBZS7126 LIMIT SWITCH ELEV 1998-6 EA180-15303 N CONTAINMENT ISOLATION VALVE LS 231 RX BLDG/ 2000 HE-8 N11007 Conax A D A HB ---

HBZS7126-E01 CONNECTOR ELEV 1998-6 Y CONTAINMENT ISOLATION VALVE 133 AUX BLDG/ 1322 HE-3/6 EA180-14303 NAMCO A D D HB ---

HBZS7136 LIMIT SWITCH ELEV 2000-0 EA180-15303 Y CONTAINMENT ISOLATION VALVE 133 AUX BLDG/ 1322 NAMCO EA180-34302 NAMCO A D D HB ---

HBZS7150 LIMIT SWITCH ELEV 2000-0 EA180-35302 Y CONTAINMENT ISOLATION VALVE 231 RX BLDG 2000 HE-3/6 EA180-14303 NAMCO A D A HB ---

HBZS7176 LIMIT SWITCH EA180-15303 N CONTAINMENT ISOLATION VALVE LS 231 RX BLDG 2000 HE-8 N11007 Conax A D A HB ---

HBZS7176-E01 CONNECTOR N VALVE TERMINAL BOX 132 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D KA ---

KAFV0029-E01 ELEV 2000-0 Y KAFV0029 SOLENOID VALVE 133 AUX BLDG/ 1322 M-237 NP8320A187E ASCO A D D KA ---

KAFY0029 ELEV 2000-0 N HYDROGEN MAKEUP AIR SUPPLY 231 RX BLDG/ 2000 LIMITORQU SMB-000 LIMITORQUE A D C KA ---

KAHV0030 VALVE ELEV 1998-6 E Y KAFV0029 LIMIT SWITCH 133 AUX BLDG/ 1322 NAMCO EA180-11302 NAMCO A D D KA ---

KAZS0029 ELEV 2000-0 EA180-12302

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 44 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N CONTAINMENT ISOLATON VALVE 1322 PIPE 1322 LIMITORQU SMB-000 LIMITORQUE A D D KC ---

KCHV0253 PENETRATION E ROOM B N CONTAINMENT ISOLATON VALVE 231 RX BLDG/ 2000 LIMITORQU SMB-00 LIMITORQUE A D A LF ---

LFFV0095 ELEV 1998-6 E N LFFV0096 SOLENOID VALVE 133 AUX BLDG/ 1322 M-237 NP8321A6E ASCO A D D LF ---

LFFY0096A ELEV 2000-0 N VALVE TERMINAL BOX (LFZS0096B) 133 AUX BLDG/ 1322 E-093 NQB. 616822 Buchanan (Amerace) A D D LF ---

LFFY0096A-E01 ELEV 2000-0 N ISOLATION VALVE 111 AUX BLDG/ 1101 LIMITORQU SMB-000 LIMITORQUE A C D LF --- 27 LFHV0105 ELEV 1974-0 E N ISOLATION VALVE 111 AUX BLDG/ 1101 LIMITORQU SMB-000 LIMITORQUE A C D LF --- 27 LFHV0106 ELEV 1974-0 E N CTMT NORMAL SUMP 232 RX BLDG/ 2000 J-481 XM-54852 TransAmerica Delaval A D C LF --- 25 LFLE0009A ELEV 1998-6 Inc. GEMS Sensors Division N CTMT NORMAL SUMP 232 RX BLDG/ 2000 J-481 XM-54853 TransAmerica Delaval A D C LF --- 25 LFLE0009B ELEV 1998-6 Inc. GEMS Sensors Division N CTMT NORMAL SUMP 231 RX BLDG/ 2000 J-481 XM-54852 TransAmerica Delaval A D C LF --- 25 LFLE0010A ELEV 1998-6 Inc. GEMS Sensors Division N CTMT NORMAL SUMP 231 RX BLDG/ 2000 J-481 XM-54853 TransAmerica Delaval A D C LF --- 25 LFLE0010B ELEV 1998-6 Inc. GEMS Sensors Division N RHR PMP ROOM LEAKAGE LEVEL 111 AUX BLDG/ 1109 J-481 XM-54854 TransAmerica Delaval A D D LF COLD LFLE0101A ELEV 1974-0 Inc. GEMS Sensors Division N RHR PMP ROOM LEAKAGE LEVEL 111 AUX BLDG/ 1109 J-481 XM-54853 TransAmerica Delaval A D D LF COLD LFLE0101B ELEV 1974-0 Inc. GEMS Sensors Division N RHR PMP ROOM LEAKAGE LEVEL 112 AUX BLDG/ 1111 J-481 XM-54854 TransAmerica Delaval A D D LF COLD LFLE0102A ELEV 1974-0 Inc. GEMS Sensors Division N RHR PMP ROOM LEAKAGE LEVEL 112 AUX BLDG/ 1111 J-481 XM-54853 TransAmerica Delaval A D D LF COLD LFLE0102B ELEV 1974-0 Inc. GEMS Sensors Division N AUX BLDG SUMP LEVEL 114 AUX BLDG/ 1121 J-481 XM-54854 TransAmerica Delaval A A D LF --- 27 LFLE0103A ELEV 1974-0 Inc. GEMS Sensors Division

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 45 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N AUX BLDG SUMP LEVEL 114 AUX BLDG/ 1121 J-481 XM-54853 TransAmerica Delaval A A D LF --- 27 LFLE0103B ELEV 1974-0 Inc. GEMS Sensors Division N AUX BLDG SUMP LEVEL 114 AUX BLDG/ 1121 J-481 XM-54854 TransAmerica Delaval A A D LF --- 27 LFLE0104A ELEV 1974-0 Inc. GEMS Sensors Division N AUX BLDG SUMP LEVEL 114 AUX BLDG/ 1121 J-481 XM-54853 TransAmerica Delaval A A D LF --- 27 LFLE0104B ELEV 1974-0 Inc. GEMS Sensors Division Y LFFV0096 LIMIT SWITCH 133 AUX BLDG/ 1322 NAMCO EA180-11302 NAMCO A D D LF ---

LFZS0096A ELEV 2000-0 Y LFFV0096 LIMIT SWITCH 133 AUX BLDG/ 1322 NAMCO EA180-11302 NAMCO A D D LF ---

LFZS0096B ELEV 2000-0 EA180-12302 N AUX RELAY RACK 134 AUX BLDG/ 1320 E-093 219NE Cegelec Automation A B D RP BOTH 30 ELEV 2000-0 Inc. (Comsip RP209 Customline Corp)/

Struthers-Dunn N REVERSE ISOL RELAY RACK 134 AUX BLDG/ 1320 E-093 219NE Cegelec Automation A B D RP BOTH 30 ELEV 2000-0 Inc. (Comsip RP330 Customline Corp)/

Struthers-Dunn N AUX. RELAY RACK 134 AUX BLDG/ 1320 E-093 219NE Cegelec Automation A B D RP BOTH 30 ELEV 2000-0 Inc. (Comsip RP332 Customline Corp)/

Struthers-Dunn SENE0060 N EX-CORE NEUTRON FLUX DETECTOR ROOM 2000 2000 J-364 200262-101 Gamma Metric A D A SE ---

SENE0061 N EX-CORE NEUTRON FLUX DETECTOR ROOM 2000 2000 J-364 200262-101 Gamma Metric A D A SE ---

N H2 ANALYZER 154 AUX BLDG/ 1506 J-359 K-IV Comsip-Delphi Inc. A D D GS --- 34 SGS02A ELEV 2047-6 N H2 ANALYZER 153 AUX BLDG/ 1507 J-359 K-IV Comsip-Delphi Inc. A D D GS --- 34 SGS02B ELEV 2047-6 N CONTROL BOX FOR SJHV0006 NULL 1301 J-603A S1140-23-8 Valcor Engineering A D D SJ --- 30 SJ359 WEST N HOT LEG LOOP 1 SAMPLE VALVE 231 RX BLDG/ 2000 J-603A V52600-5688-9 Valcor Engineering A D A SJ --- 21 SJHV0003 ELEV 1998-6 N HOT LEG LOOP 3 SAMPLE VALVE 231 RX BLDG/ 2000 J-603A V526-5688-9 Valcor Engineering A D A SJ --- 21 SJHV0004 ELEV 1998-6 N PASS CONTAINMENT ISOLATION 231 RX BLDG/ 2000 J-603A V526-5688-9 Valcor Engineering A D A SJ --- 21 SJHV0005 VALVE ELEV 1998-6 N PASS CONTAINMENT ISOLATION 134 AUX BLDG/ 1323 J-603A V526-5688-6 Valcor Engineering A D D SJ --- 21 SJHV0006 VALVE ELEV 2000-0

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 46 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N PRESSURIZER VAPOR SPACE 231 RX BLDG/ 2000 J-603A V52600-6042-1A Valcor Engineering A D A SJ --- 21 SJHV0012 SAMPLE ISOLATION VALVE ELEV 1998-6 N PRESSURIZER VAPOR SPACE 134 AUX BLDG/ 1323 J-603A V52600-6042-1 Valcor Engineering A D D SJ --- 21 SJHV0013 SAMPLE ISOLATION VALVE ELEV 2000-0 N ACCUMULATOR SAMPLES CTMT 231 RX BLDG/ 2000 J-603A V52600-6040-7A Valcor Engineering A D A SJ --- 21 SJHV0018 ISOLATION VALVE ELEV 1998-6 N ACCUMULATOR SAMPLES CTMT 134 AUX BLDG/ 1323 J-603A V52600-6040-7 Valcor Engineering A D D SJ --- 21 SJHV0019 ISOLATION VALVE ELEV 2000-0 N PASS CONTAINMENT ISOLATION 134 AUX BLDG/ 1323 J-603A V526-5688-6 Valcor Engineering A D D SJ --- 21 SJHV0127 VALVE ELEV 2000-0 N PASS CONTAINMENT ISOLATION 231 RX BLDG/ 2000 J-603A V526-5688-9 Valcor Engineering A D A SJ --- 21 SJHV0128 VALVE ELEV 1998-6 N PASS CONTAINMENT ISOLATION 133 AUX BLDG/ 1322 J-603A V526-5688-6 Valcor Engineering A D D SJ --- 21 SJHV0129 VALVE ELEV 2000-0 N PASS CONTAINMENT ISOLATION 133 AUX BLDG/ 1322 J-603A V526-5688-6 Valcor Engineering A D D SJ --- 21 SJHV0130 VALVE ELEV 2000-0 N ELECTRICAL PENETRATION ROOM 1410 1410 E-035B Low Voltage Conax A D D XX BOTH 37, MODULES Power/Control/ 38 ZNE-1-EQ Instrumentation 7040-1000-(Kapton)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE263(Spare)

PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE264 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE265 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE267 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE268 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE269 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE271 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE272 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNE274 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE275 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 47 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE276 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE277 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE278 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE279 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE280 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE281 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNE282 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE283 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE284 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE285 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE287 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE288 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE289 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE290 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE291 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNE292 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNE293 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNE294 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 144 AUX BLDG/ 1410 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZNE295 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 124 AUX BLDG/ 1204 E-035 Low Voltage Amphenol (Bunker- A B D XX BOTH 38 ZNE296 (ENCAPSULATION) ELEV 1988-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 123 AUX BLDG/ 1203 E-035 Low Voltage Amphenol (Bunker- A B D XX BOTH 38 ZNE297 (ENCAPSULATION) ELEV 1988-0 50027200 Ramo)

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 48 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 124 AUX BLDG/ 1204 E-035 Low Voltage Amphenol (Bunker- A C D XX BOTH 38 ZNE298 (ENCAPSULATION) ELEV 1988-0 50027200 Ramo)

N ELECTRICAL PENETRATION ROOM 2000 2000 E-035B Low Voltage Conax A A D XX BOTH 37, ZNI-1-EQ MODULES Power/Control/ 38 Instrumentation 7040 1000 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI263(Spare) PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI264 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI265 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZNI267 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI268 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI269 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI271 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI272 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNI274 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI275 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZNI276 2026-0 / AREA 1

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 49 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI277 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI278 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI279 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI280 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI281 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNI282 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI283 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI284 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZNI285 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI287 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI288 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI289 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI290 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 50 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI291 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZNI292 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZNI293 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZNI294 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZNI295 ELEV 2026-0 50027200 Ramo)

N VALVE TERMINAL BOX 124 AUX BLDG/ 1204 E-035B 601-JJ, 602-JJ, Kulka A B D XX COLD ZNI296 ELEV 1988-0 604-JJ N VALVE TERMINAL BOX 123 AUX BLDG/ 1203 E-035B 601-JJ, 602-JJ, Kulka A B D XX COLD ZNI297 ELEV 1988-0 604-JJ N VALVE TERMINAL BOX 124 AUX BLDG/ 1204 E-035B 601-JJ, 602-JJ, Kulka A C D XX ---

ZNI298 ELEV 1988-0 604-JJ N ELECTRICAL PENETRATION ROOM 1409 1409 E-035B Low Voltage Conax A D D XX BOTH 37, ZSE-1-EQ MODULES Power/Control/ 38 Instrumentation N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE206(Spare)

PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE207 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE208 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE210 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 124 AUX BLDG/ 1204 E-035 Low Voltage Amphenol (Bunker- A B D XX BOTH 38 ZSE215 (ENCAPSULATION) ELEV 1988-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 123 AUX BLDG/ 1203 E-035 Low Voltage Amphenol (Bunker- A B D XX BOTH 38 ZSE216 (ENCAPSULATION) ELEV 1988-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 123 AUX BLDG/ 1203 E-035 Low Voltage Amphenol (Bunker- A C D XX BOTH 38 ZSE217 (ENCAPSULATION) ELEV 1988-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE218 ELEV 2026-0 50027200 Ramo)

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 51 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE219 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSE222 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE223 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSE224 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE225 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE226 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE233 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE234 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE240 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE243 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE249 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE250 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSE251(Spare)

PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSE252 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSE253 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSE254 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSE255 PRESSURE BOUNDARY ELEV 2026-0 Ramo)

N ELECTRICAL PENETRATION ASSY 143 AUX BLDG/ 1409 E-035 Low Voltage Amphenol (Bunker- A D D XX BOTH 38 ZSE258 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ROOM 2000 2000 E-035B Low Voltage Conax A A D XX BOTH 37, ZSI-1-EQ MODULES Power/Control/ 38 Instrumentation 7040 1000

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 52 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSI206(Spare) PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSI207 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSI208 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZSI210 2026-0 / AREA 1 N VALVE TERMINAL BOX 124 AUX BLDG/ 1204 E-035B 601-JJ, 602-JJ, Kulka A B D XX COLD ZSI215 ELEV 1988-0 604-JJ N VALVE TERMINAL BOX 123 AUX BLDG/ 1203 E-035B 601-JJ, 602-JJ, Kulka A B D XX COLD ZSI216 ELEV 1988-0 604-JJ N VALVE TERMINAL BOX 123 AUX BLDG/ 1203 E-035B 601-JJ, 602-JJ, Kulka A C D XX ---

ZSI217 ELEV 1988-0 604-JJ N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI218 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI219 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSI222 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSI223 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSI224 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSI225 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 53 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZSI226 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI233 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI234 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZSI240 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI243 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI249 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI250 ELEV 2026-0 50027200 Ramo)

N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH ZSI251(Spare) PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSI252 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSI253 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 ZSI254 PRESSURE BOUNDARY BLDG/ELEV Ramo) 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX 2000 E-035 50027200 Amphenol (Bunker- B D B XX BOTH 4 PRESSURE BOUNDARY BLDG/ELEV Ramo)

ZSI255 2026-0 / AREA 1 N ELECTRICAL PENETRATION ASSY 241 RX BLDG/ 2000 E-035 Low Voltage Amphenol (Bunker- A D A XX BOTH 38 ZSI258 ELEV 2026-0 50027200 Ramo)

N TERMINAL BOXES (commodity item) 8 E-028 1600 NUC Marathon Special A A A XX --- 8 ZTB-1-EQ Products

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 54 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N TERMINAL BOXES (commodity item) 2 E-093 NQB. 616822 Buchanan (Amerace) A A A XX --- 2 ZTB-2-EQ N TERMINAL BOXES (commodity item) 8 E-035B 601-JJ, 602-JJ, Kulka A A A XX --- 8 ZTB-3-EQ 604-JJ N TERMINAL BOXES (commodity item) 8 LIMITORQU EB-5, EB-25 General Electric A A A XX --- 8 ZTB-4-EQ E

N 5 KV POWER CABLES 5 - Used 5 E-029-P01 HTK/HTNs Type Kerite Company A D D XX BOTH throughout the ZZB-1-EQ plant - outside containment N 600 VOLT COPPER CONTROL CABLE 2 - Used 2 E-057 Firewall Rockbestos Company/ A A A XX BOTH throughout the III/Insulation Firewall III plant Formulation ZZC-1-EQ KXL760, KXL-760-5, KXL-7600, KXL-780 N 600 VOLT COPPER CONTROL CABLE 2 - Used 2 E-057A FR-EP Anaconda-Ericsson A A A XX BOTH ZZC-2-EQ throughout the Inc.

plant N 600 VOLT COPPER CONTROL CABLE 2 - Used 2 E-057B XLPE Brand-Rex A A A XX BOTH ZZC-3-EQ throughout the Company/XLPE plant N 600 VOLT FIRE-RESISTIVE CONTROL 1402 CORRIDOR 2 E-057C Appendix R Meggitt Safety D D A XX BOTH AND POWER CABLE NO. 1/141 AUX Systems, Inc.

ZZC-4-EQ BLDG AND 1501 CTRL RM A/C &

FILTRN UNITS RM B N 1/2, 3/4, 1-1/2 Inch Quick Disconnect 2 - Used 2 E-103 880701-1, 880702- EGS Corporation A A A XX BOTH Electrical Connector throughout the 1B, 9139601-1, plant 913601-1B, ZZE-1-EQ 913602-1, 913602-1B N 600 VOLT POWER CABLE 2 - Used 2 E-058 Durasheath 'EP' Anaconda-Ericsson A A A XX BOTH ZZG-1-EQ throughout the Inc./Durasheath 'EP' plant N 600 VOLT SHIELDED 2 - Used 2 E-062A Firewall Rockbestos Company/ A A A XX BOTH INSTRUMENTATION CABLE throughout the III/Insulation Firewall III ZZJ-1-EQ plant Formation KXL 760G

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 55 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N 600 VOLT SHIELDED 2 - Used 2 E-062 EPR-CSPE Boston Insulated Wire A A A XX BOTH ZZJ-2-EQ INSTRUMENTATION CABLE throughout the and Cable Company plant N PREFABRICATED CABLE 2 - Used 2 E-095 10-607590 thru 10- Bendix A A D XX BOTH ZZP-1-EQ ASSEMBLIES throughout the 607598 plant N NUCLEAR JACKET REPAIR TAPE 2 - Used 2 E-01013 NJRT (old part #, Raychem A A A XX BOTH ZZQ-1-EQ MATERIAL throughout the P02 original material) plant N CABLE BREAKOUT KIT MATERIAL 2 - Used 2 E-01013 NCBK, NCBX, Raychem A A A XX BOTH ZZR-1-EQ throughout the P05 NESK (old part #,

plant original material)

N 600 VOLT SHIELDED 2 - Used 2 E-062 EPR-CSPE Boston Insulated Wire A A A XX BOTH ZZS-1-EQ INSTRUMENTATION CABLE throughout the and Cable Company plant N THERMOCOUPLE EXTENSION CABLE 2 - Used 2 E-061 EPDM Eaton Corp. (Samuel A A A XX BOTH ZZT-1-EQ throughout the Moore Operations) plant N 5 KV CABLE SPLICE MATERIAL 5 - Used 5 E-029-P02 S-5NS-NUC-DISC Kerite Company A D D XX BOTH throughout the and IT/OT-5NS-ZZU-1-EQ plant - outside NUC containment N CABLE END SEAL, BREAKOUT, STUB 2 - Used 2 E-01013 NCBK,NESK, Raychem A A A XX BOTH CONNECTION, TRANSITION SPLICE throughout the P08 NJRT, NMCK, KITS MATERIAL AND JACKET REPAIR plant NPKC, NPKP, ZZV-1-EQ MATERIAL NPKS, NPKV, NPKX (new part #s

& materials)

N THREAD SEALANT 2 - Used 2 M-771 P-1 EGS Corporation A A A XX BOTH ZZV-2-EQ throughout the plant N NUCLEAR MOTOR CONNECTION KITS 2 - Used 2 E-01013 N-MCK (old part #, Raychem A A A XX BOTH ZZW-1-EQ MATERIAL throughout the P04 original material) plant N COAXIAL & TRIAXIAL CABLE 2 - Used 2 E-060 RG-11A/U, RG-58 Brand-Rex Company A A A XX BOTH ZZX-1-EQ throughout the C/U, RG-59 B/U plant (FR-XLPE)

N CABLE TERMINATION HEAT SHRINK 2 - Used 2 E-01013 WCSF-N (old part Raychem A A A XX BOTH ZZY-1-EQ FLD SPLICING MATERIAL SYSTEM throughout the P01 #, original material) plant

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 56 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN N HEAT SHRINK FLD. SPLICING 2 - Used 2 E-01013 WCSF-N (new part Raychem A A A XX BOTH ZZY-2-EQ SYSTEM MATERIAL throughout the P09 # & material) plant N SHIM STOCK MATERIAL 2 - Used 2 E-01013 WCSF-N-050 (old Raychem A A A XX BOTH ZZY-3-EQ throughout the P07 part #, original plant material)

N STUB CONNECTION KIT MATERIAL 2 - Used 2 E-01013 NPKV (old part #, Raychem A A A XX BOTH ZZZ-1-EQ throughout the P02 original material) plant N IN-LINE BOLTED CONNNECTION 2 - Used 2 E-01013 WCSF-N (old part Raychem A A A XX BOTH ZZZ-2-EQ MATERIAL throughout the P06 #, original material) plant N TRANSITION SPLICE KIT MATERIAL 2 - Used 2 E-01013 NPKS, NPKC, Raychem A A A XX BOTH throughout the P03 NPKP, NPKX (old ZZZ-3-EQ plant part #, original material)

GENERAL Electrical Equipment Categories for LOCA/MSLB/HELB fields Cat. A Item is required to function post accident Cat. B Item is not required to function post accident; however, item must not adversely fail post accident Cat. C Item's status post accident has no effect on plant safety Cat. D Item is in mild environment post accident Notes: Description 2 Used throughout the plant.

The spent fuel pool cooling system will be operated during these conditions to maintain fuel pool temperatures.

3 This note identifies that Non-IE Conax modules used in this penetration and addressed in PQE-E-035B-P01 have a safety related function of maintaining the pressure boundary of containment. PQE-E-035B-P01 documents that Conax modules used in ZSE/ZSI222E (I), ZSE/ZSI252E (I), ZNE/ZNI253C (I), ZSE/ZSI254E (I), ZSE/ZSI255E (I), ZSE/ZSI255D 4 (I), ZNE/ZNI292F (I) and ZNE/ZNI294C (I) ZSE/ZSI222F (LVP), ZNE/ZNI224C (LVP), ZNE/ZNI274A (LVP), ZNE/ZNI274G (LVP) and ZNE/ZNI282C (LVP) are acceptable for use in the environments identified.

5 Used throughout the plant - outside containment.

7 Used inside containment.

8 Used throughout the plant with exception of instrumentation circuits inside containment and auxilary building rooms 1411, 1412, 1508, and 1509 9 Alternate EGS connector approved for installation per CP 12467 as necessary.

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 57 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Determined by XX-81 analysis to be mild environment equipment post accident (also reference EQWP-J-605A R3) states that a location-specific dose calculation and analysis 11 was performed on the butterfly valves located in Room 1314, and concluded that the subject valves can be recategorized as mild environment equipment. The parameters constitute a mild environment.

Determined by XX-53 analysis to be mild environment equipment post accident. EQWP-E-018 R5 states that a specific-location dose calculation and analysis was performed on 12 the MCC's located in Room 1409 and 1410, and concluded that subject MCCs can be recategorized as a mild environment equipment.

16 Qualified as a sub-component of Panel RP209 17 Qualified as a sub-component of Panel RP330 18 Qualified as a sub-component of Panel RP332 19 Spared in Place 20 This equipment was added in response to NUREG-0737 Category II.B.1 21 This equipment was added in response to NUREG-0737 Category II.B.3 22 This equipment was added in response to NUREG-0737 Category II.D.3 24 This equipment was added in response to NUREG-0737 Category II.E.1.2 25 This equipment was added in response to NUREG-0737 Category II.F.1 26 This equipment was added in response to NUREG-0737 Category II.F.2 Rooms 1101, 1102, 1120, 1121, 1122 and 1130 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for 27 components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1107 and 1108 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for 28 the HELB barrier consideration in AP 10-104.

Rooms 1113 and 1114 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for 29 the HELB barrier consideration in AP 10-104.

Rooms 1301, 1314, 1315 and 1320 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of 30 these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1508 and 1509 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms 31 for the HELB barrier consideration in AP 10-104.

Rooms 1206 and 1207 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for 32 the HELB barrier consideration in AP 10-104.

Rooms 1401, 1402 and 1408 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these 33 rooms for the HELB barrier consideration in AP 10-104.

Rooms 1502, 1503, 1505 and 1507 plus Rooms 1504, 1506 and 1513 (due to transfer grill GLD0175 on M-1H1431) are all open to one another. A worst-case condition of any 34 associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 3401, 3406 and 3412 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these 35 rooms for the HELB barrier consideration in AP 10-104.

Rooms 6301 and 6302 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components in all of these rooms for 36 the HELB barrier consideration in AP 10-104.

EQSD-II Rev. 32 Table 1: EQ Harsh Environment Equipment List 58 of 58 Component MC Equipment Qualification Description Installed EQ EQ Spec Model # Manufacturer LO HE MS System HOT/ Notes Number Elevation Room CA LB LB COLD SHUT DOWN Reference E-035B-00050, Table 3.1, Page 11. The power and control modules are ZSE/ZSI233E, ZSE/ZSI233F, ZSE/ZSI234F, ZNE/ZNI278F and ZNE/ZNI278G. The instrumentation modules are ZSE/ZSI233D, ZSE/ZSI233G, ZSE/ZSI234E, ZSE/ZSI243C, ZSE/ZSI249C, ZSE/ZSI249D, ZSE/ZSI250A, ZSE/ZSI250B, ZSE/ZSI250D, 37 ZSE/ZSI250F, ZSE/ZSI250G, ZSE/ZSI258F, ZNE/ZNI277F, ZNE/ZNI278C, ZNE/ZNI278D, ZNE/ZNI278E, ZNE/ZNI279E, ZNE/ZNI287C, ZNE/ZNI287D, ZNE/ZNI287E, ZNE/ZNI288B, ZNE/ZNI288D, ZNE/ZNI288F, ZNE/ZNI295F and ZNE/ZNI295G.

GDI-30F (Long-glass, fiber filled, diallyl-phthalate) terminal blocks that are Series 601-JJ, 602-JJ, 604-JJ, 605-JJ, 812-JJ type are qualified under PQE-E-035B-P02 for each of 38 these applications. Instrumentation applications do not use the Kulka terminal blocks inside the containment, PQE-E-11013-P01/ P06/P07/ P08/ P09 splices are used in these applications.

These assets contain two limit switches. However one of the limit switches is an installed spare and doesnt have power running to it. Therefore, doesnt perform any safety 39 function and doesnt need qualified by the EQ program.

40 Not used 41 DRE 20217 approves changing the identified model 763 to 763A.

42 SWO 18-446734-002 changed model number to 763A.

43 PQE-ESE-43G-P01 44 CP 13788 45 CP 14701 50 Located in yard.

EQSD-II Rev. 32 EQSD-II Table 2: 1 of 31 EQ Mild Environment Equipment List Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B 27XQB01 AUX RELAY IN PANEL RP330 1320 E-093 C C C QB BOTH 17 30 27XQB02 AUX RELAY IN PANEL RP330 1320 E-093 C C C QB BOTH 17 30 3XAP02 AUX RELAY IN PANEL RP330 (APV0015) 1320 E-093 C C C AP BOTH 17 30 3XEG21 AUX RELAY IN PANEL RP332 FOR CONTROL OF EGHV0072 1320 E-093 C C C EG BOTH 18 30 3XEG23 AUX RELAY IN PANEL RP332 FOR CONTROL OF EGHV0075 1320 E-093 C C C EG BOTH 18 30 3XGS23 AUX RELAY IN PANEL RP209 1320 E-093 C C C GS BOTH 16 30 45XJE01 125 VDC AUX RELAY IN PANEL RP330 FOR FIRE SIGNAL ISO 1320 E-093 C C C JE BOTH 17 30 63XFC15 AUX RELAY IN PANEL RP330 1320 E-093 C C C FC BOTH 17 30 63XFC17 AUX RELAY IN PANEL RP330 1320 E-093 C C C FC BOTH 17 30 74XBG03 AUX RELAY PANEL RP209 1320 E-093 C C C BG BOTH 16 30 74XEJ05 AUX RELAY IN PANEL RP332 FOR EJHCV0606 COMPUTER POINT 1320 E-093 C C C EJ BOTH 18 30 95XGK07 AUX RELAY PANEL RP330 1320 E-093 C C C GK BOTH 17 30 AB007 AUX. RELAY RACK 3413 E-093 D D D AB BOTH ABFHC0002 ABPV0002 LOCAL CONTROLLER 1509 J-601B C D C AB BOTH 31 ABFHC0003 ABPV0003 LOCAL CONTROLLER 1509 J-601 C D C AB BOTH 31 ABHY0005 ABHV0005 SOLENOID VALVE 1412 J-601A C D C AB BOTH ABHY0006 ABHV0006 SOLENOID VALVE 1412 J-601A C D C AB BOTH ABHY0048A ABHV0048 SOLENOID VALVE 1412 J-601A C D C AB BOTH ABHY0049A ABHV0049 SOLENOID VALVE 1412 J-601 C D C AB BOTH ABLT0007 MAIN STM LINE DRN VLV LP 3 LV 1331 J-301 D C D AB BOTH ABLT0008 MAIN STM LINE DRN VLV LP 2 LV 1331 J-301 D C D AB BOTH ABLT0009 MAIN STM LINE DRN VLV LP 1 LV 1326 J-301 D D D AB BOTH ABLT0010 MAIN STM LINE DRN VLV LP 4 LV 1325 J-301 D D D AB BOTH ABPI0514A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0515A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0516A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0516X STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0524A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0524B STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0525A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0526A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0534A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0535A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0535X STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0536A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0544A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0544B STEAMLINE PRESSURE 1413 ESE-14 D D D AB BOTH ABPI0545A STEAMLINE PRESSURE 3501 ESE-14 D D D AB BOTH ABPI0546A STEAMLINE PRESSURE 3501 ESE-1 D D D AB BOTH ABPIC0001A STM GEN A ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0001B STM GEN A ATM STEAM DUMP 1413 J-110 D D D AB BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 2 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B ABPIC0002A STM GEN B ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0002B STM GEN B ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPIC0003A STM GEN C ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0003B STM GEN C ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPIC0004A STM GEN D ATM STEAM DUMP 3501 J-110 D D D AB BOTH ABPIC0004B STM GEN D ATM STEAM DUMP 1413 J-110 D D D AB BOTH ABPT0001 STM GEN A STEAMLINE PRESSURE 1304 J-301 D D D AB BOTH ABPT0002 STM GEN B STEAMLINE PRESSURE 1305 J-301 D D D AB BOTH ABPT0003 STM GEN C STEAMLINE PRESSURE 1305 J-301 D D D AB BOTH ABPT0004 STM GEN D STEAMLINE PRESSURE 1304 J-301 D D D AB BOTH ABPV0001 STM GEN A ATM RELIEF VLV 1508 J-601 C D C AB BOTH 31 ABPV0002 STM GEN B ATM RELIEF VLV 1509 J-601 C D C AB BOTH 31 ABPV0003 STM GEN C ATM RELIEF VLV 1509 J-601 C D C AB BOTH 31 ABPV0004 STM GEN D ATM RELIEF VLV 1508 J-601 C D C AB BOTH 31 ABPY0001 ABPV0001 I/P CONVERTER 1508 J-601B C D C AB BOTH 31 ABPY0002 ABPV0002 I/P CONVERTER 1509 J-601B C D C AB BOTH 31 ABPY0003 ABPV0003 I/P CONVERTER 1509 J-601B C D C AB BOTH 31 ABPY0004 ABPV0004 I/P CONVERTER 1508 J-601B C D C AB BOTH 31 ABZC0001 ABPV0001 POSITIONER - STM GEN A ATM VENT VALVE 1508 J-601B C D C AB BOTH ABZC0002 ABPV0002 POSITIONER - STM GEN B ATM VENT VALVE 1509 J-601B C D C AB BOTH ABZC0003 ABPV0003 POSITIONER - STM GEN C ATM VENT VALVE 1509 J-601B C D C AB BOTH ABZC0004 ABPV0004 POSITIONER - STM GEN D ATM VENT VALVE 1508 J-601B C D C AB BOTH ABZE0011AC LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 CLOSED 1508 M-630 C D C AB ---

POSITION DETECTION ELEMENT A ABZE0011AO LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 OPEN POSITION 1508 M-630 C D C AB ---

DETECTION ELEMENT A ABZE0011BC LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 CLOSED 1508 M-630 C D C AB ---

POSITION DETECTION ELEMENT B ABZE0011BO LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 OPEN POSITION 1508 M-630 C D C AB ---

DETECTION ELEMENT B ABZE0014AC LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 CLOSED 1508 M-630 C D C AB ---

POSITION DETECTION ELEMENT A ABZE0014AO LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 OPEN POSITION 1508 M-630 C D C AB ---

DETECTION ELEMENT A ABZE0014BC LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 CLOSED 1508 M-630 C D C AB ---

POSITION DETECTION ELEMENT B ABZE0014BO LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 OPEN POSITION 1508 M-630 C D C AB ---

DETECTION ELEMENT B ABZE0017AC LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 CLOSED 1509 M-630 C D C AB ---

POSITION DETECTION ELEMENT A

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 3 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B ABZE0017AO LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 OPEN POSITION 1509 M-630 C D C AB ---

DETECTION ELEMENT A ABZE0017BC LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 CLOSED 1509 M-630 C D C AB ---

POSITION DETECTION ELEMENT B ABZE0017BO LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 OPEN POSITION 1509 M-630 C D C AB ---

DETECTION ELEMENT B ABZE0020AC LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 CLOSED 1509 M-630 C D C AB ---

POSITION DETECTION ELEMENT A ABZE0020AO LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 OPEN POSITION 1509 M-630 C D C AB ---

DETECTION ELEMENT A ABZE0020BC LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 CLOSED 1509 M-630 C D C AB ---

POSITION DETECTION ELEMENT B ABZE0020BO LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 OPEN POSITION 1509 M-630 C D C AB ---

DETECTION ELEMENT B ABZS0005 ABHV0005 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZS0006 ABHV0006 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZS0048 ABHV0048 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZS0049 ABHV0049 LIMIT SWITCH 1412 NAMCO C D C AB BOTH ABZT0011A LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 POSITION 1508 M-630 C D C AB ---

TRANSMITTER A ABZT0011B LOOP 4 MAIN STEAM ISOLATION VALVE ABHV0011 POSITION 1508 M-630 C D C AB ---

TRANSMITTER B ABZT0014A LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 POSITION 1508 M-630 C D C AB ---

TRANSMITTER A ABZT0014B LOOP 1 MAIN STEAM ISOLATION VALVE ABHV0014 POSITION 1508 M-630 C D C AB ---

TRANSMITTER B ABZT0017A LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 POSITION 1509 M-630 C D C AB ---

TRANSMITTER A ABZT0017B LOOP 2 MAIN STEAM ISOLATION VALVE ABHV0017 POSITION 1509 M-630 C D C AB ---

TRANSMITTER B ABZT0020A LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 POSITION 1509 M-630 C D C AB ---

TRANSMITTER A ABZT0020B LOOP 3 MAIN STEAM ISOLATION VALVE ABHV0020 POSITION 1509 M-630 C D C AB ---

TRANSMITTER B ACPSL0231 MN STM CTRL VLV 2 PRESS SW 4401 J-110 D D D AC ---

ACPSL0232 MN STM CTRL VLV 3 PRESS SW 4401 J-110 D D D AC ---

ACPSL0233 MN STM CTRL VLV 1 PRESS SW 4401 J-110 D D D AC ---

ACPT0231 MN STM CTRL VLV 3 4401 J-301 D D D AC ---

ACPT0232 MN STM CTRL VLV 2 4401 J-301 D D D AC ---

ACPT0233 MN STM CTRL VLV 1 4401 J-301 D D D AC ---

ACPT0505 TURBINE IMPULSE PRESSURE 4401 M-771 D D D AC ---

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 4 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B ACPT0506 TURBINE IMPULSE PRESSURE 4401 M-771 D D D AC ---

ACZS0043C TURB TRP STOP VLV LMT SWITCH 4401 J-601A D D D AC ---

ACZS0044C TURB TRP STOP VLV LMT SWITCH 4401 J-601A D D D AC ---

ACZS0045C TURB TRP STOP VLV LMT SWITCH 4401 J-601A D D D AC ---

ACZS0046C TURB TRP STOP VLV LMT SWITCH 4401 J-601 D D D AC ---

AEFY0043 AEFV0043 SOLENOID VALVE 1411 J-601A C D C AE BOTH AEFY0044 AEFV0044 SOLENOID VALVE 1412 J-601A C D C AE BOTH AEFY0045 AEFV0045 SOLENOID VALVE 1412 J-601A C D C AE BOTH AEFY0046 AEFV0046 SOLENOID VALVE 1411 J-60 C D C AE BOTH AEFY0510AA FEEDWATER CONTROL VALVE LOOP 1 4401 HE-5 D D D AE ---

AEFY0510BB FEEDWATER CONTROL VALVE LOOP 1 4401 HE-5 D D D AE ---

AEFY0520AA FEEDWATER CONTROL VALVE LOOP 2 4401 HE-5 D D D AE ---

AEFY0520BB FEEDWATER CONTROL VALVE LOOP 2 4401 HE-5 D D D AE ---

AEFY0530AA FEEDWATER CONTROL VALVE LOOP 3 4401 HE-5 D D D AE ---

AEFY0530BB FEEDWATER CONTROL VALVE LOOP 3 4401 HE-5 D D D AE ---

AEFY0540AA FEEDWATER CONTROL VALVE LOOP 4 4401 HE-5 D D D AE ---

AEFY0540BB FEEDWATER CONTROL VALVE LOOP 4 4401 HE-5 D D D AE ---

AEFY0550A FEEDWATER CONTROL BYPASS VALVE LOOP 1 4401 HE-5 D D D AE ---

AEFY0550B FEEDWATER CONTROL BYPASS VALVE LOOP 1 4401 HE-5 D D D AE ---

AEFY0560A FEEDWATER CONTROL BYPASS VALVE LOOP 2 4401 HE-5 D D D AE ---

AEFY0560B FEEDWATER CONTROL BYPASS VALVE LOOP 2 4401 HE-5 D D D AE ---

AEFY0570A FEEDWATER CONTROL BYPASS VALVE LOOP 3 4401 HE-5 D D D AE ---

AEFY0570B FEEDWATER CONTROL BYPASS VALVE LOOP 3 4401 HE-5 D D D AE ---

AEFY0580A FEEDWATER CONTROL BYPASS VALVE LOOP 4 4401 HE-5 D D D AE ---

AEFY0580B FEEDWATER CONTROL BYPASS VALVE LOOP 4 4401 HE-5 > D D D AE ---

AELI0501 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0501A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0502 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0502A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0503 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0503A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0504 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0504A STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0517 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0517X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0518 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0519 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0527 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0527X STEAM GENERATOR WATER LEVEL (INSTALLED SPARE) 1413 ESE-14 D D D AE ---

AELI0528 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0528X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 5 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B AELI0529 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0537 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0537X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0538 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0539 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0547 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0548 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AELI0548X STEAM GENERATOR WATER LEVEL 1413 ESE-14 D D D AE BOTH AELI0549 STEAM GENERATOR WATER LEVEL 3501 ESE-14 D D D AE BOTH AEZE0039AC LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 CLOSED 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0039AO LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 OPEN 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0039BC LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 CLOSED 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0039BO LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 OPEN 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0040AC LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 CLOSED 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0040AO LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 OPEN 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0040BC LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 CLOSED 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0040BO LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 OPEN 1411 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0041AC LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 CLOSED 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0041AO LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV00341 OPEN 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0041BC LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 CLOSED 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0041BO LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 OPEN 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0042AC LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 CLOSED 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0042AO LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 OPEN 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT A AEZE0042BC LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 CLOSED 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT B AEZE0042BO LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 OPEN 1412 M-628 C D C AE ---

POSITION DETECTION ELEMENT B

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 6 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B AEZS0043 AEFV0043 LIMIT SWITCH 1411 NAMCO C D C AE BOTH AEZS0044 AEFV0044 LIMIT SWITCH 1412 NAMCO C D C AE BOTH AEZS0045 AEFV0045 LIMIT SWITCH 1412 NAMCO C D C AE BOTH AEZS0046 AEFV0046 LIMIT SWITCH 1411 NAMCO C D C AE BOTH AEZT0039A LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 POSITION 1411 M-628 C D C AE ---

TRANSMITTER A AEZT0039B LOOP 1 MAIN FEEDWATER ISOLATION VALVE AEFV0039 POSITION 1411 M-628 C D C AE ---

TRANSMITTER B AEZT0040A LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 POSITION 1411 M-628 C D C AE ---

TRANSMITTER A AEZT0040B LOOP 2 MAIN FEEDWATER ISOLATION VALVE AEFV0040 POSITION 1411 M-628 C D C AE ---

TRANSMITTER B AEZT0041A LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 POSITION 1412 M-628 C D C AE ---

TRANSMITTER A AEZT0041B LOOP 3 MAIN FEEDWATER ISOLATION VALVE AEFV0041 POSITION 1412 M-628 C D C AE ---

TRANSMITTER B AEZT0042A LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 POSITION 1412 M-628 C D C AE ---

TRANSMITTER A AEZT0042B LOOP 4 MAIN FEEDWATER ISOLATION VALVE AEFV0042 POSITION 1412 M-628 C D C AE ---

TRANSMITTER B ALFI0001A AUX FDWTR PMP TO STEAM GEN D 3501 J-110 D D D AL HOT 24 ALFI0001B AUX FDWTR PMP TO STEAM GEN D 1413 J-110 D D D AL HOT 24 ALFI0002A AUX FDWTR PMP TO STEAM GEN A 3501 J-110 D D D AL HOT 24 ALFI0002B AUX FDWTR PMP TO STEAM GEN A 1413 J-110 D D D AL HOT 24 ALFI0003A AUX FDWTR PMP TO STEAM GEN B 3501 J-110 D D D AL HOT 24 ALFI0003B AUX FDWTR PMP TO STEAM GEN B 1413 J-110 D D D AL HOT 24 ALFI0004A AUX FDWTR PMP TO STEAM GEN C 3501 J-110 D D D AL HOT 24 ALFI0004B AUX FDWTR PMP TO STEAM GEN C 1413 J-110 D D D AL HOT 24 ALFT0001 AUX FDWTR PMP TO STEAM GEN D 1304 J-301 C D D AL HOT 24 ALFT0002 AUX FDWTR PMP TO STEAM GEN A 1304 J-301 C D D AL HOT 24 ALFT0003 AUX FDWTR PMP TO STEAM GEN B 1305 J-301 D D D AL HOT 24 ALFT0004 AUX FDWTR PMP TO STEAM GEN C 1305 J-301 D D D AL HOT 24 ALFT0007 AUX FDW FLO TO SG A 1304 J-301 C D D AL HOT 24 ALFT0009 AUX FDW FLO TO SG B 1305 J-301 D D D AL HOT 24 ALFT0011 AUX FDW FLO TO SG C 1305 J-301 D D D AL HOT 24 ALHK0005A MOT AUX FW PMP B DISCH TO STM GEN D 3501 J-110 D D D AL HOT ALHK0005B MOT AUX FW PMP B DISCH TO STM GEN D 1413 J-110 D D D AL HOT ALHK0006A TURB AFP DISCH TO STEAM GEN D 3501 J-110 D D D AL HOT ALHK0006B TURB AFP DISCH TO STEAM GEN D 1413 J-110 D D D AL HOT ALHK0007A MOT AUX FW PMP B DISCH TO STM GEN A 3501 J-110 D D D AL HOT ALHK0007B MOT AUX FW PMP B DISCH TO STM GEN A 1413 J-110 D D D AL HOT

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 7 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B ALHK0008A TURB AFP DISCH TO STEAM GEN A 3501 J-110 D D D AL HOT ALHK0008B TURB AFP DISCH TO STEAM GEN A 1413 J-110 D D D AL HOT ALHK0009A MOT AUX FW PMP A DISCH TO STM GEN B 3501 J-110 D D D AL HOT ALHK0009B MOT AUX FW PMP A DISCH TO STM GEN B 1413 J-110 D D D AL HOT ALHK0010A TURB AFP DISCH TO STEAM GEN B 3501 J-110 D D D AL HOT ALHK0010B TURB AFP DISCH TO STEAM GEN B 1413 J-110 D D D AL HOT ALHK0011A MOT AUX FW PMP A DISCH TO STM GEN C 3501 J-110 D D D AL HOT ALHK0011B MOT AUX FW PMP A DISCH TO STM GEN C 1413 J-110 D D D AL HOT ALHK0012A TURB AFP DISCH TO STEAM GEN C 3501 J-110 D D D AL HOT ALHK0012B TURB AFP DISCH TO STEAM GEN C 1413 J-110 D D D AL HOT ALHV0005 MOT AUX FDWTR PMP B DISCH ISO 1324 J-601 D D D AL HOT ALHV0006-E01 VALVE TERMINAL BOX 1327 E-028 D D D AL HOT ALHV0007 MOT AUX FDWTR PMP B DISCH ISO 1324 J-601 D D D AL HOT ALHV0008-E01 VALVE TERMINAL BOX 1327 E-028 D D D AL HOT ALHV0009 MOT AUX FDWTR PMP A DISCH ISO 1328 J-601 D D D AL HOT ALHV0010-E01 VALVE TERMINAL BOX 1330 E-028 D D D AL HOT ALHV0011 MOT AUX FDWTR PMP A DISCH ISO 1328 J-601 D D D AL HOT ALHV0012-E01 VALVE TERMINAL BOX 1330 E-028 D D D AL HOT ALHV0030 ESW TO AUX. FEED PUMP B 1206 M-236A C D D AL HOT 32 ALHV0031 ESW TO AUX. FEED PUMP A 1206 M-236A C D D AL HOT 32 ALHV0032 TURBINE AF PUMP SUCTION FROM ESW A 1207 M-236A C D D AL HOT 32 ALHV0033 TURBINE AF PUMP SUCTION FROM ESW B 1207 M-236A C D D AL HOT 32 ALHV0034 CST TO AUXILIARY FEED PUMP B 1206 LIMITORQUE C D D AL HOT 32 ALHV0035 CST TO AUXILIARY FEED PUMP A 1206 LIMITORQUE C D D AL HOT 32 ALHV0036 TURBINE AF PUMP SUCTION FROM CST 1207 LIMITORQUE C D D AL HOT 32 ALHY0006 ALHV0006 I/P CONVERTER 1327 J-601A D D D AL HOT ALHY0008 ALHV0008 I/P CONVERTER 1327 J-601A D D D AL HOT ALHY0010 ALHV0010 I/P CONVERTER 1330 J-601A D D D AL HOT ALHY0012 ALHV0012 I/P CONVERTER 1330 J-601 D D D AL HOT ALPI0024A MOT AUX FDWTR PMP B SUCT PRESS 3501 J-110 D D D AL HOT ALPI0024B MOT AUX FDWTR PMP B SUCT PRESS 1413 J-110 D D D AL HOT ALPI0025A MOT AUX FDW PMP A SUCT PRESS 3501 J-110 D D D AL HOT ALPI0025B MOT AUX FDW PMP A SUCT PRESS 1413 J-110 D D D AL HOT ALPI0026A TURB AUX FDWTR PMP SUCT PRESS 3501 J-110 D D D AL HOT ALPI0026B TURB AUX FDWTR PMP SUCT PRESS 1413 J-110 D D D AL HOT ALPI0037 AFW SPLY PRESS FROM COND STR TK 3501 J-110 D D D AL HOT ALPI0038 AFW SPLY PRESS FROM COND STR TK 3501 J-110 D D D AL HOT ALPI0039 AFW SPLY PRESS FROM COND STR TK 3501 J-110 D D D AL HOT ALPT0024 MOT AUX FEEDWATER PMP B SUCT PRESS 1325 J-301 D D D AL HOT ALPT0025 CST TO MOT AUX FDW PMP A SUCT PRESS 1326 J-301 D D D AL HOT ALPT0026 TURB AUX FEEDWATER PMP SUCT PRESS 1331 J-301 D C D AL HOT

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 8 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B ALPT0037 ESFAS LOW SUCTION PRESS 1207 J-301 C D D AL HOT 32 ALPT0038 ESFAS LOW SUCTION PRESS 1207 J-301 C D D AL HOT 32 ALPT0039 ESFAS LOW SUCTION PRESS 1207 J-301 C D D AL HOT 32 ALZS0006 ALHV0006 LIMIT SWITCH 1327 J-601A D D D AL HOT ALZS0008 ALHV0008 LIMIT SWITCH 1327 J-601A D D D AL HOT ALZS0010 ALHV0010 LIMIT SWITCH 1330 J-601A D D D AL HOT ALZS0012 ALHV0012 LIMIT SWITCH 1330 J-601A D D D AL HOT BB007 D.C. CONTACTOR FOR PORV 1403 E-018A D D D BB BOTH BB008 D.C. CONTACTOR FOR PORV 1408 E-018 D D D BB BOTH 33 BBFT0414 RCS FLOW TRANSMITTER LOOP 1 2201 ESE-4 C D C BB BOTH BBFT0415 RCS FLOW TRANSMITTER LOOP 1 2201 ESE-4 C D C BB BOTH BBFT0416 RCS FLOW TRANSMITTER LOOP 1 2201 ESE-4 C D C BB BOTH BBFT0424 RCS FLOW TRANSMITTER LOOP 2 2201 ESE-4 C D C BB BOTH BBFT0425 RCS FLOW TRANSMITTER LOOP 2 2201 ESE-4 C D C BB BOTH BBFT0426 RCS FLOW TRANSMITTER LOOP 2 2201 ESE-4 C D C BB BOTH BBFT0434 RCS FLOW TRANSMITTER LOOP 3 2201 ESE-4 C D C BB BOTH BBFT0435 RCS FLOW TRANSMITTER LOOP 3 2201 ESE-4 C D C BB BOTH BBFT0436 RCS FLOW TRANSMITTER LOOP 3 2201 ESE-4 C D C BB BOTH BBFT0444 RCS FLOW TRANSMITTER LOOP 4 2201 ESE-4 C D C BB BOTH BBFT0445 RCS FLOW TRANSMITTER LOOP 4 2201 ESE-4 C D C BB BOTH BBFT0446 RCS FLOW TRANSMITTER LOOP 4 2201 ESE-4 C D C BB BOTH BBHV8037A PRT EMERGENCY DRAIN LINE 2000 LIMITORQUE C D C BB BOTH BBHV8037B PRT EMERGENCY DRAIN LINE 2000 LIMITORQUE C D C BB BOTH BBHV8157A EXCESS LETDOWN PATH TO PRT ISOLATION 2000 M-231E C D C BB BOTH BBHV8157B EXCESS LETDOWN PATH TO PRT ISOLATION 2000 M-231E C D C BB BOTH BBLI0459A PRESSURIZER LEVEL 3501 ESE-14 D D D BB BOTH BBLI0459B PRESSURIZER LEVEL 1413 ESE-14 D D D BB BOTH BBLI0460A PRESSURIZER LEVEL 3501 ESE-14 D D D BB BOTH BBLI0460B PRESSURIZER LEVEL 1413 ESE-14 D D D BB BOTH BBLI0461 PRESSURIZER LEVEL 3501 ESE-14 D D D BB BOTH BBLI1311 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB --- 26 BBLI1312 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB --- 26 BBLI1321 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB --- 26 BBLI1322 REACTOR VESSEL LEVEL INDICATORS 3501 ESE-14 D D D BB --- 26 BBPI0403 REACTOR COOLANT PRESSURE INDICATOR 3501 ESE-14 D D D BB BOTH BBPI0403X REACTOR COOLANT PRESSURE INDICATOR (ASP-SPARE) 1413 ESE-14 D D D BB ---

BBPI0405 REACTOR COOLANT PRESSURE INDICATOR 3501 ESE-14 D D D BB BOTH BBPI0405X REACTOR COOLANT PRESSURE INDICATOR 1413 ESE-14 D D D BB BOTH BBPI0406 REACTOR COOLANT PRESSURE INDICATOR 3501 ESE-14 D D D BB BOTH BBPI0406X REACTOR COOLANT PRESSURE INDICATOR 1413 ESE-14 D D D BB BOTH BBTI0413A TH WIDE RANGE LOOP 1 HOT LEG TEMP 3501 ESE-14 D D D BB BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 9 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B BBTI0413B TH WIDE RANGE LOOP 1 COLD LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0423A TH WIDE RANGE LOOP 2 HOT LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0423B TH WIDE RANGE LOOP 2 COLD LEG TEMP 3501 ESE-14 D D D BB BOTH BBTI0423X TH WIDE RANGE LOOP 2 COLD LEG TEMP 1413 ESE-14 D D D BB BOTH BBTI0443A TH WIDE RANGE LOOP 4 HOT LEG TEMP 1413 ESE-14 D D D BB BOTH BBTI1390A SUBCOOLING TEMP IND 3501 ESE-14 D D D BB --- 26 BBTI1390B SUBCOOLING TEMP IND 3501 ESE-14 D D D BB --- 26 BBTR1390A SUBCOOLING RECORDER 3605 ESE-46B D D D BB ---

BBTR1390B SUBCOOLING RECORDER 3605 ESE-46B D D D BB ---

BBUU1390A SUBCOOLING REMOTE DISPLAY 3605 ESE-46A D D D BB ---

BBUU1390B SUBCOOLING REMOTE DISPLAY 3605 ESE-46A D D D BB ---

BGFI0138A EXCESS LETDOWN FLOW TO PRT 3501 ESE-14 D D D BG BOTH BGFI0138B EXCESS LETDOWN FLOW TO PRT 3501 ESE-14 D D D BG BOTH BGFI0215A SEAL INJECTION FLOW 3501 ESE-14 D D D BG BOTH BGFI0215B SEAL INJECTION FLOW 3501 ESE-14 D D D BG BOTH BGFT0138A EXCESS LETDOWN PATH TO PRT FLOW TRANSMITTER 2000 ESE-3 C D C BG BOTH BGFT0138B EXCESS LETDOWN PATH TO PRT FLOW TRANSMITTER 2000 ESE-3 C D C BG BOTH BGHV8104 EMERGENCY BORATION PATH ISOLATION VALVE 1113 LIMITORQUE C D D BG BOTH 29 BGHV8357A CCP A ALTERNATE DISCHARGE TO RCP SEALS 1114 M-231E C D D BG BOTH 29 BGHV8357B CCP B ALTERNATE DISCHARGE TO RCP SEALS 1107 M-231E C D D BG BOTH 28 BGLI0102 BORIC ACID TANK #1 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0104 BORIC ACID TANK 1 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0105 BORIC ACID TANK #2 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0106 BORIC ACID TANK 2 LEVEL 3501 ESE-14 D D D BG BOTH BGLI0112 VOLUME CONTROL TANK LEVEL 3501 ESE-14 D D D BG BOTH BGLI0185 VOLUME CONTROL TANK LEVEL 3501 ESE-14 D D D BG BOTH BGLT0102 BORIC ACID TANK A LEVEL TRANSMITTER 1117 ESE-4 C D D BG BOTH BGLT0104 BORIC ACID TANK A LEVEL TRANSMITTER 1117 ESE-4 C D D BG BOTH BGLT0105 BORIC ACID TANK B LEVEL TRANSMITTER 1116 ESE-4 C D D BG BOTH BGLT0106 BORIC ACID TANK B LEVEL TRANSMITTER 1116 ESE-4 C D D BG BOTH BGLT0112 VCT LEVEL TRANSMITTER 1318 ESE-4 C C D BG BOTH BGLT0185 VCT LEVEL TRANSMITTER 1316 ESE-4A C C D BG BOTH BGTE0032 DPBG05A INBOARD BEARING TEMPERATURE 1114 M-721 C D D BG --- 29 BGTE0033 DPBG05A OUTBOARD BEARING TEMPERATURE 1114 M-721 C D D BG --- 29 BGTE0034 DPBG05B INBOARD BEARING TEMPERATURE 1107 M-721 C D D BG --- 28 BGTE0035 DPBG05B OUTBOARD BEARING TEMPERATURE 1107 M-721 C D D BG --- 28 BGTE0137A EXCESS LETDOWN PATH TO PRT TEMPERATURE ELEMENT 2000 ESE-42A C D C BG BOTH BGTE0137B EXCESS LETDOWN PATH TO PRT TEMPERATURE ELEMENT 2000 ESE-42A C D C BG BOTH BGTI0137A EXCESS LETDOWN TO PRT TEMP 3501 ESE-14 D D D BG BOTH BGTI0137B EXCESS LETDOWN FLOW TO PRT TEMP 3501 ESE-14 D D D BG BOTH BNHS8812B ISOLATION SWITCH FOR BNHV8812B 3302 E-028B D D D BN COLD

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 10 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B BNLI0930 RWST LEVEL 3501 ESE-14 D D D BN ---

BNLI0931 RWST LEVEL 3501 ESE-14 D D D BN ---

BNLI0932 RWST LEVEL 3501 ESE-14 D D D BN ---

BNLI0933 RWST LEVEL 3501 ESE-14 D D D BN ---

BNLT0930 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN ---

BNLT0931 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN ---

BNLT0932 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN ---

BNLT0933 RWST LEVEL TRANSMITTER 9102 ESE-4 D D D BN ---

BNTE0002 RWST TEMP 9102 J-558B D D D BN ---

BNTE0005 RWST TEMP 9102 J-558B D D D BN ---

BNTI0002 RWST TEMP 3501 J-110 D D D BN ---

BNTI0005 RWST TEMP 3501 J-110 D D D BN ---

BNTT0002 RWST TEMP 3605 J-110 D D D BN ---

BNTT0005 RWST TEMP 3605 J-110 D D D BN ---

BNZS0011 RWST OUTLET HEADER VALVE POSITION 9102 M-221 D D D BN ---

BNZS8717 POSITION SWITCH ON RHR RETURN VALVE 1310 HE-6 C D D BN ---

DCGD01A ESW PUMP ROOM SUPPLY FAN MOTOR K105 M-619.2 D D D GD BOTH DCGD01B ESW PUMP ROOM SUPPLY FAN MOTOR K104 M-619.2 D D D GD BOTH DCGG02A EMERGENCY EXH. FAN MOTOR 6304 M-619.2 D D D GG ---

DCGG02B EMERGENCY EXH. FAN MOTOR 6303 M-619.2 D D D GG ---

DCGK03A CONTROL ROOM FILTER FAN MOTOR 1512 M-619.2 D D D GK ---

DCGK03B CONTROL ROOM FILTER FAN MOTOR 1501 M-619.2 D D D GK ---

DCGK04A CONTROL ROOM PRESSURE FAN MOTOR 3416 M-619.2 D D D GK ---

DCGK04B CONTROL ROOM PRESSURE FAN MOTOR 3415 M-619.2 D D D GK ---

DCGM01A DIESEL GEN. VENT. SUPPLY FAN MOTOR 5203 M-619.2 D D D GM BOTH DCGM01B DIESEL GEN. VENT. SUPPLY FAN MOTOR 5201 M-619.2 D D D GM BOTH DCGN03A HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DCGN03B HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DCGN03C HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DCGN03D HYDROGEN MIXING FAN MOTOR 2000 M-619.3 C D C GN HOT DPAL01A AUX FEEDWATER PUMP A MOTOR 1326 E-012.2 D D D AL HOT DPAL01B AUX FEEDWATER PUMP B MOTOR 1325 E-012.2 D D D AL HOT DPBG02A BORIC ACID TRANSFER PUMP A MOTOR 1117 AE-3 C D D BG BOTH DPBG02B BORIC ACID TRANSFER PUMP B MOTOR 1116 AE-3 C D D BG BOTH DPEC01A SPENT FUEL POOL COOLING PUMP A MOTOR 6105 M-084 D D D EC --- 3 DPEC01B SPENT FUEL POOL COOLING PUMP B MOTOR 6104 M-084 D D D EC --- 3 DPEF01A ESW PUMP A MOTOR K105 E-012.2 D D D EF BOTH DPEF01B ESW PUMP B MOTOR K104 E-012.2 D D D EF BOTH DPEG01A CCW PUMP A MOTOR TRAIN A 1406 E-012.2 D D D EG BOTH DPEG01B CCW PUMP B MOTOR TRAIN B 1401 E-012.2 D D D EG BOTH 33 DPEG01C CCW PUMP C MOTOR TRAIN A 1406 E-012.2 D D D EG BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 11 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B DPEG01D CCW PUMP D MOTOR TRAIN B 1401 E-012.2 D D D EG BOTH 33 DPJE01A EMERGENCY FUEL OIL TRANSFER PUMP A MOTOR (50) M-087 D D D JE BOTH DPJE01B EMERGENCY FUEL OIL TRANSFER PUMP B MOTOR (50) M-087 D D D JE BOTH DPKJ01A JACKET WATER KEEP WARM PUMP A MOTOR 5203 M-018 D D D KJ BOTH DPKJ01B JACKET WATER KEEP WARM PUMP B MOTOR 5201 M-018 D D D KJ BOTH DPKJ02A ROCKER PRELUBE PUMP A MOTOR 5203 M-018 D D D KJ BOTH DPKJ02B ROCKER PRELUBE PUMP B MOTOR 5201 M-018 D D D KJ BOTH DPKJ03A AUXILIARY LUBE OIL KEEP WARM PUMP A MOTOR 5203 M-018 D D D KJ BOTH DPKJ03B AUXILIARY LUBE OIL KEEP WARM PUMP B MOTOR 5201 M-018 D D D KJ BOTH DSGF02A AUX FEED PUMP ROOM COOLER MOTOR 1326 M-612 D D D GF BOTH DSGF02B AUX FEED PUMP ROOM COOLER MOTOR 1325 M-612 D D D GF BOTH DSGG04A SFP PUMP ROOM COOLER MOTOR 6105 M-612 D D D GG --- 3 DSGG04B SFP PUMP ROOM COOLER MOTOR 6104 M-612 D D D GG --- 3 DSGL11A CCW PUMP ROOM COOLER MOTOR 1406 M-612 D D D GL BOTH DSGL11B CCW PUMP ROOM COOLER MOTOR 1401 M-612 D D D GL BOTH 33 ECHV0011 F.P.C.H. EX. CCW ISOLATION VALVE LOOP A 6105 M-236 D D D EC BOTH ECHV0012 F.P.C.H. EX. CCW ISOLATION VALVE LOOP B 6104 M-236 D D D EC BOTH ECLSL0057 FUEL POOL LEVEL SWITCH 6106 J-481 D D D EC BOTH ECLSL0058 FUEL POOL LEVEL SWITCH 6106 J-481 D D D EC BOTH EF155 ESW CONTROL PNL K104 J-201 D D D EF BOTH EF156 ESW CONTROL PNL K105 J-201 D D D EF BOTH EFFI0053 ESW A FLO TO POWER BLOCK 3501 J-110 D D D EF ---

EFFI0054 ESW B FLO TO POWER BLOCK 3501 J-110 D D D EF ---

EFFT0039 WARMING LINE FLOW TRANSMITTER K105 J-301 D D D EF ---

EFFT0042 WARMING LINE FLOW TRANSMITTER K104 J-301 D D D EF ---

EFFT0053 ESW A FLO TO POWER BLOCK 3101 J-301 D D D EF ---

EFFT0054 ESW B FLO TO POWER BLOCK 3101 J-301 D D D EF ---

EFHS0003 LOCAL CONTROL STATION K105 E-028 D D D EF ---

EFHS0004 LOCAL CONTROL STATION K104 E-028 D D D EF ---

EFHS0026A ISOLATION SWITCH FOR EFHV0026 3302 E-028B D D D EF BOTH EFHS0038A ISOLATION SWITCH FOR EFHV0038 3302 E-028B D D D EF BOTH EFHV0023 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0024 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0025 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0026 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0037 ULTIMATE HEAT SINK ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0038 ULTIMATE HEAT SINK ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0039 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0040 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0041 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH EFHV0042 SERVICE WATER ISOLATION VALVE 3101 M-235 D D D EF BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 12 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B EFHV0051 CCW ISOLATION VALVE 1406 M-236 D D D EF BOTH EFHV0052 CCW ISOLATION VALVE 1401 M-236 D D D EF BOTH 33 EFHV0059 CCW ISOLATION VALVE 1406 M-236 D D D EF BOTH EFHV0060 CCW ISOLATION VALVE 1401 M-236 D D D EF BOTH 33 EFHV0091 TRAVELING WATER SCREEN A SPRAY VALVE K105 LIMITORQUE D D D EF BOTH EFHV0092 TRAVELING WATER SCREEN B SPRAY VALVE K104 LIMITORQUE D D D EF BOTH EFHV0097 ESW PUMP A VENT VALVE K105 LIMITORQUE D D D EF BOTH EFHV0098 ESW PUMP B VENT VALVE K104 LIMITORQUE D D D EF BOTH EFPDI0019 ESW 2A SELF-CLN STR DIFF PRES K105 J-110 D D D EF BOTH EFPDI0020 ESW 2B SELF-CLN STR DIFF PRES K104 J-110 D D D EF BOTH EFPDS0019A ESW 2A SELF-CLN STR. DP SWITCH K105 J-301 D D D EF BOTH EFPDS0020A ESW 2B SELF-CLN STR. DP SWITCH K104 J-301 D D D EF BOTH EFPDT0019 ESW 2A SELF-CLN STR DIFF PRES K105 J-301 D D D EF BOTH EFPDT0020 ESW 2B SELF-CLN STR DIFF PRES K104 J-301 D D D EF BOTH EFPDV0019 STRAINER A TRASH VALVE K105 LIMITORQUE D D D EF BOTH EFPDV0020 STRAINER B TRASH VALVE K104 LIMITORQUE D D D EF BOTH EFPI0001 ESW PUMP 1A DISCH PRESS 3501 J-110 D D D EF BOTH EFPI0002 ESW PMP 1B DISCH PRESS 3501 J-110 D D D EF BOTH EFPT0001 ESW PMP 1A DISCH PRESS K105 J-301 D D D EF BOTH EFPT0002 ESW PMP 1B DISCH PRESS K104 J-301 D D D EF BOTH EFTE0061 ESW A TEMP TO POWER BLOCK 3101 J-558B D D D EF ---

EFTE0062 ESW B TEMP TO POWER BLOCK 3101 J-558B D D D EF ---

EFTI0061 ESW A TEMP TO POWER BLOCK 3501 J-110 D D D EF ---

EFTI0062 ESW B TEMP TO POWER BLOCK 3501 J-110 D D D EF ---

EGFI0128 CCW HX OUT TO RCP BY-PASS 3501 J-110 D D D EG BOTH EGFI0129 CCW HX OUT TO RCP BY-PASS 3501 J-110 D D D EG BOTH EGFT0107 CCW HX`S FLOW OUT TO RWB NONESSENTIAL COMP 1314 J-301 C D D EG BOTH 30 EGFT0108 CCW HX`S FLOW OUT TO RWB NONESSENTIAL COMP 1314 J-301 C D D EG BOTH 30 EGHS0070A LOCAL CONTROL STATION 1408 E-028B D D D EG COLD 33 EGHV0011 EMERGENCY MAKEUP WATER TRAIN A FROM ESW 1406 M-231B D D D EG BOTH EGHV0012 EMERGENCY MAKEUP WATER TRAIN B FROM ESW 1401 M-231B D D D EG BOTH 33 EGHV0013 EMERGENCY MAKEUP WATER TRAIN A FROM ESW 1406 M-231B D D D EG BOTH EGHV0014 EMERGENCY MAKEUP WATER TRAIN B FROM ESW 1401 M-231 D D D EG BOTH 33 EGHV0015 CCW COMMON HEADER RETURN ISO TRAIN A 1402 M-261 D D D EG COLD 33 EGHV0016 CCW COMMON HEADER RETURN ISO TRAIN B 1402 M-261 D D D EG COLD 33 EGHV0053 TRAIN A CCW TO COMMON HEADER 1402 M-261 D D D EG COLD 33 EGHV0054 TRAIN B CCW TO COMMON HEADER 1401 M-261 D D D EG COLD 33 EGHV0069A CCW SUPPLY WASTE HEADER ISO 1314 CORR. J-605A D D D EG COLD 11 EGHV0069A-E01 VALVE TERMINAL BOX 1314 CORR. E-028 D D D EG COLD EGHV0069B CCW RETURN WASTE HEADER ISO 1314 CORR. J-605A D D D EG COLD 11 EGHV0069B-E01 VALVE TERMINAL BOX 1314 CORR. E-028 D D D EG COLD

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 13 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B EGHV0070A CCW SUPPLY WASTE HEADER ISO 1314 CORR. J-605A D D D EG COLD 11 EGHV0070A-E01 VALVE TERMINAL BOX 1314 CORR. E-028 D D D EG COLD EGHV0070B CCW RETURN WASTE HEADER ISO 1314 CORR. J-605A D D D EG COLD 11 EGHV0070B-E01 VALVE TERMINAL BOX 1314 E-028 D D D EG COLD 30 EGHV0072 CCW TO PASS SAMPLE COOLER 1406 M-231B D D D EG ---

EGHV0073 CCW TO PASS SAMPLE COOLER 1406 M-231B D D D EG ---

EGHV0074 CCW FROM PASS SAMPLE COOLER 1406 M-231B D D D EG ---

EGHV0075 CCW FROM PASS SAMPLE COOLER 1406 M-231B D D D EG ---

EGHV0101 RHR A INLET CCW ISOLATION VALVE 1408 M-236 D D D EG COLD 33 EGHV0102 RHR B INLET CCW ISOLATION VALVE 1402 M-236 D D D EG COLD 33 EGHV0126 EGHV0071 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHV0127 EGHV0058 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHV0130 EGHV0060 BYPASS VALVE 2000 LIMITORQUE C D C EG BOTH EGHV0131 EGHV0059 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHV0132 EGHV0062 BYPASS VALVE 2000 LIMITORQUE C D C EG BOTH EGHV0133 EGHV0061 BYPASS VALVE 1323 LIMITORQUE C D D EG BOTH EGHY0069A EGHV0069A SOLENOID VALVE 1314 CORR. J-605A D D D EG COLD EGHY0069B EGHV0069B SOLENOID VALVE 1314 CORR. J-605A D D D EG COLD EGHY0070A EGHV0070A SOLENOID VALVE 1314 CORR. J-605A D D D EG COLD EGHY0070B EGHV0070B SOLENOID VALVE 1314 J-605A D D D EG COLD 30 EGLI0001 CCW SURGE TK A LEVEL 3501 J-110 D D D EG BOTH EGLI0002 CCW SURGE TK B LEVEL 3501 J-110 D D D EG BOTH EGLT0001 CCW SURGE TK A LEVEL 1503 J-301 D D D EG BOTH 34 EGLT0002 CCW SURGE TK B LEVEL 1502 J-301 D D D EG BOTH 34 EGPT0077 CCW PMPS A&C DISCH PRESS 1406 J-301 D D D EG BOTH EGPT0078 CCW PMPS B&D DISCH PRESS 1401 J-301 D D D EG BOTH 33 EGTE0031 CCW HX A OUTLET TEMP 1406 J-558B D D D EG BOTH EGTE0032 CCW HX B OUTLET TEMP 1401 J-558B D D D EG BOTH 33 EGTI0031 CCW HX A OUTLET TEMP 3605 J-110 D D D EG BOTH EGTI0032 CCW HX B OUTLET TEMP 3605 J-110 D D D EG BOTH EGTT0031 CCW HX A OUTLET TEMP 3605 J-110 D D D EG BOTH EGTT0032 CCW HX B OUTLET TEMP 3605 J-110 D D D EG BOTH EGTV0029 CCW HX A BYPASS ISO 1406 J-605A D D D EG BOTH EGTV0029-E01 VALVE TERMINAL BOX 1406 E-028 D D D EG BOTH EGTV0030 CCW HX B BYPASS ISO 1401 J-605A D D D EG BOTH 33 EGTV0030-E01 VALVE TERMINAL BOX 1401 E-028 D D D EG BOTH 33 EGTY0029A EGTV0029 SOLENOID VALVE 1406 J-605A D D D EG BOTH EGTY0030A EGTV0030 SOLENOID VALVE 1401 J-605A D D D EG BOTH 33 EGZS0029 EGTV0029 LIMIT SWITCH 1406 J-605A D D D EG BOTH EGZS0030 EGTV0030 LIMIT SWITCH 1401 J-605A D D D EG BOTH 33

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 14 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B EGZS0069A EGHV0069A LIMIT SWITCH 1314 CORR. J-605A D D D EG COLD EGZS0069B EGHV0069B LIMIT SWITCH 1314 CORR. J-605A D D D EG COLD EGZS0070A EGHV0070A LIMIT SWITCH 1314 CORR. J-605A D D D EG COLD EGZS0070B EGHV0070B LIMIT SWITCH 1314 J-605A D D D EG COLD 30 EJFIS0610 RHR PUMP A MIN. FLOW INDICATING SWITCH 1301 WEST ESE-40A D D D EJ COLD EJLI0007 CTMT RECIRC SUMP A LEV 3501 J-110 D D D EJ --- 25 EJLI0008 CTMT RECIRC SUMP B LEV 3501 J-110 D D D EJ --- 25 EJLR0006 CTMT RECIRC SUMP LEV 3501 J-110 D D D EJ --- 25 Electrical Equipment Categories for LOCA/MSLB/HELB Fields EMFI0917A CHARGING PUMP DISCHARGE FLOW 3501 ESE-14 D D D EM BOTH EMFI0917B CHARGING PUMP DISCHARGE FLOW 3501 ESE-14 D D D EM BOTH EMFS0917C CHARGING PUMP DISCHARGE MINI FLOW SWITCH 1126 ESE-40A C D D EM BOTH EMFS0917D CHARGING PUMP DISCHARGE MINI FLOW SWITCH 1126 ESE-40A C D D EM BOTH EMFT0917A CHARGING PUMP TO BIT FLOW TRANSMITTER 1126 ESE-4 C D D EM BOTH EMFT0917B CHARGING PUMP TO BIT FLOW TRANSMITTER 1126 ESE-4 C D D EM BOTH EMHS8843 LOCAL CONTROL STATION 1409 E-028 C D D EM BOTH EMTE0011 DPEM01A INBOARD BEARING TEMPERATURE 1113 M-721 C D D EM --- 29 EMTE0012 DPEM01A OUTBOARD BEARING TEMPERATURE 1113 M-721 C D D EM --- 29 EMTE0014 DPEM01B INBOARD BEARING TEMPERATURE 1108 M-721 C D D EM --- 28 EMTE0015 DPEM01B OUTBOARD BEARING TEMPERATURE 1108 M-721 C D D EM --- 28 ENLI0017 SPRAY ADD TANK LEVEL 3501 J-110 D D D EN ---

ENLI0019 SPRAY ADD TANK LEVEL 3501 J-110 D D D EN ---

ENZS0097 SPRAY ADDITIVE TANK DISC VALVE POSITION 1315 M-221 C D D EN --- 30 EPHV8808B ACCUMULATOR TANK B ISOLATION VALVE 2000 LIMITORQUE C D C EP COLD EPHV8808C ACCUMULATOR TANK C ISOLATION VALVE 2000 LIMITORQUE C D C EP COLD EPZS8808BB ACCUMULATOR TANK B ISOLATION VALVE LIMIT SWITCH 2000 HE-3 C D C EP COLD EPZS8808BB-E01 ACCUMULATOR TANK B ISOL VLV LS CONNECTOR 2000 HE-8 C D C EP COLD EPZS8808BB-E02 VALVE TERMINAL BOX 2000 E-028 C D C EP COLD EPZS8808CB ACCUMULATOR TANK C ISOLATION VALVE LIMIT SWITCH 2000 HE-3 C D C EP COLD EPZS8808CB-E01 ACCUMULATOR TANK C ISOL VLV LS CONNECTOR 2000 HE-8 C D C EP COLD EPZS8808CB-E02 VALVE TERMINAL BOX 2000 E-028 C D C EP COLD FC219 AFP TURBINE GAUGE AND CONTROL PANEL 1331 M-021 D C D FC BOTH FCFV0310-E01 VALVE TERMINAL BOX 1207 E-028 C D D FC --- 32 FCFV0313 TURBINE SPEED-GOVERNING VALVE 1331 M-021 D C D FC BOTH FCFY0310 FCFV0310 SOLENOID VALVE 1207 J-601 C D D FC --- 32 FCHIK0313A AUX FP TURB SPEED CTRL 3501 J-110 D D D FC BOTH FCHIK0313B AUX FDWTR PMP SPEED GOVERNOR 1413 J-110 D D D FC BOTH FCHV0312 TURBINE MANUAL TRIP AND THROTTLE VALVE 1331 M-021 D C D FC BOTH FCZS0310 FCFV0310 LIMIT SWITCH 1207 J-601 C D D FC --- 32 FEF01A TRAVELING WATER SCREEN A K105 M-020 D D D EF BOTH FEF01B TRAVELING WATER SCREEN B K104 M-020 D D D EF BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 15 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B FEF02A SELF-CLEANING STRAINER A K105 M-154 D D D EF BOTH FEF02B SELF-CLEANING STRAINER B K104 M-154 D D D EF BOTH FGG02A FILTER-ABSORBER UNIT 6304 M-621 D D D GG ---

FGG02B FILTER-ABSORBER UNIT 6303 M-621 D D D GG ---

FGK01A FILTER ADSORBER UNIT 1512 M-621 D D D GK ---

FGK01B FILTER ADSORBER UNIT 1501 M-621 D D D GK ---

FGK02A CR PRESS FILTER ADSORBER UNIT 3416 M-621 D D D GK ---

FGK02B CR PRESS FILTER ADSORBER UNIT 3415 M-621 D D D GK ---

GDHIS0001B LOCAL CONTROL STATION K105 E-028 D D D GD ---

GDHIS0011B LOCAL CONTROL STATION K104 E-028 D D D GD ---

GDHS0011 LOCAL CONTROL STATION 3302 E-028 D D D GD ---

GDHS0011A LOCAL CONTROL STATION 3302 E-028B D D D GD ---

GDTE0001 ESW PMP RM TEMP 1A DAMPER K105 J-558B D D D GD BOTH GDTE0011 ESW PMP RM TEMP 1B DAMPER K104 J-558B D D D GD BOTH GDTT0001 ESW PMP RM TEMP 1A DAMPER 3605 J-110 D D D GD BOTH GDTT0011 ESW PMP RM TEMP 1B DAMPER 3605 J-110 D D D GD BOTH GDTZ0001A FLOW CONTROL DAMPER ACTUATOR - GDD0002 - ELC/HYD K105 M-627A D D D GD BOTH GDTZ0001B FLOW CONTROL DAMPER ACTUATOR - GDD0004 - ELC/HYD K105 M-627A D D D GD BOTH GDTZ0001C FLOW CONTROL DAMPER ACTUATOR - GDD0012 - ELC/HYD K105 M-627A D D D GD BOTH GDTZ0011A FLOW CONTROL DAMPER ACTUATOR - GDD0009 - ELC/HYD K104 M-627A D D D GD BOTH GDTZ0011B FLOW CONTROL DAMPER ACTUATOR - GDD0011 - ELC/HYD K104 M-627A D D D GD BOTH GDTZ0011C FLOW CONTROL DAMPER ACTUATOR - GDD0013 - ELC/HYD K104 M-627A D D D GD BOTH GEHZ0103 AUX BLDG ISO DAMPER ACTUATOR - GED0045 - ELEC 1504 M-627A D D D GE --- 34 GEHZ0104 AUX BLDG ISO DAMPER ACTUATOR - GED0044 - ELEC 1504 M-627A D D D GE --- 34 GFHIS0015 LOCAL CONTROL STATION 1326 E-028 D D D GF ---

GFHIS0016 LOCAL CONTROL STATION 1325 E-028 D D D GF ---

GFHZ0022 AUX BLDG ISO DAMPER ACTUATOR - GFD0024 - ELEC 1504 M-627A D D D GF --- 34 GFHZ0023 AUX BLDG ISO DAMPER ACTUATOR - GFD0025 - ELEC 1504 M-627A D D D GF --- 34 GFHZ0032A AUX BLDG ISO DAMPER ACTUATOR - GFD0068 - ELEC 1305 M-627A D D D GF ---

GFHZ0032B AUX BLDG ISO DAMPER ACTUATOR - GFD0060 - ELEC 1328 M-627A D D D GF ---

GFHZ0033A AUX BLDG ISO DAMPER ACTUATOR - GFD0069 - ELEC 1305 M-627A D D D GF ---

GFHZ0033B AUX BLDG ISO DAMPER ACTUATOR - GFD0061 - ELEC 1328 M-627A D D D GF ---

GGHIS0015B LOCAL CONTROL STATION 6304 E-028 D D D GG ---

GGHIS0021B LOCAL CONTROL STATION 6303 E-028 D D D GG ---

GGHIS0036B LOCAL CONTROL STATION 6203 E-028 D D D GG ---

GGHIS0037B LOCAL CONTROL STATION 6203 E-028 D D D GG ---

GGHS0050 LOCAL CONTROL STATION 6301 E-028 D D D GG --- 36 GGHS0051 LOCAL CONTROL STATION 6301 E-028 D D D GG --- 36 GGHZ0040 FUEL BLDG ISO DAMPER ACTUATOR - GGD0025 - ELEC 6304 M-627A D D D GG ---

GGHZ0041 AUX BLDG ISO DAMPER ACTUATOR - GGD0026 - ELEC 6304 M-627A D D D GG ---

GGHZ0042 AUX BLDG ISO DAMPER ACTUATOR - GGD0032 - ELEC 6304 M-627A D D D GG ---

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 16 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B GGHZ0043 FUEL BLDG ISO DAMPER ACTUATOR - GGD0018 - ELEC 6303 M-627A D D D GG ---

GGHZ0044 AUX BLDG ISO DAMPER ACTUATOR - GGD0019 - ELEC 6303 M-627A D D D GG ---

GGHZ0056 FUEL BLDG ISO DAMPER ACTUATOR - GGD0042 - ELEC 6304 M-627A D D D GG ---

GGHZ0057 FUEL BLDG ISO DAMPER ACTUATOR - GGD0043 - ELEC 6303 M-627A D D D GG ---

GGPDT0019 EMERGENCY FILTER ADSORBER UNIT A HEPA 6304 M-621 D D D GG ---

GGRE0027 FUEL BLDG EXHAUST RAD MONIT 6301 J-361 D D D GG --- 36 GGRE0028 FUEL BLDG EXHAUST RAD MONIT 6301 J-361 D D D GG --- 36 GGRT0027 GGRE0027 TRANSMITTER 6304 J-361 D D D GG ---

GGRT0028 GGRE0028 TRANSMITTER 6304 J-361 D D D GG ---

GGRV0027A SFP RAD MONIT INTAKE 6301 J-603A D D D GG --- 36 GGRV0027B SFP RAD MONIT RETURN 6301 J-603A D D D GG --- 36 GGRV0027C SPENT FUEL POOL RAD CNTRL VLV 6301 J-603A D D D GG --- 36 GGRV0027D SPENT FUEL POOL RAD CNTRL VLV 6301 J-603A D D D GG --- 36 GGRV0028A SFP RAD MONIT INTAKE 6301 J-603A D D D GG --- 36 GGRV0028B SFP RAD MONIT RETURN 6301 J-603A D D D GG --- 36 GGRV0028C SPENT FUEL POOL RAD CONT VLV 6301 J-603A D D D GG --- 36 GGRV0028D SPENT FUEL POOL RAD CONT VLV 6304 J-603A D D D GG ---

GGRZ0036 FUEL BLDG ISO DAMPER ACTUATOR - GGD0003 - ELEC 6203 M-627A D D D GG ---

GGRZ0037 FUEL BLDG ISO DAMPER ACTUATOR - GGD0004 - ELEC 6203 M-627A D D D GG ---

GGTE0016 FGG02A TEMPERATURE 6304 M-621 D D D GG ---

GGTE0022 FGG02B TEMPERATURE 6303 M-621 D D D GG ---

GGTT0016 GGTE0016 TRANSMITTER 6304 M-621 D D D GG ---

GGTT0022 GGTE0022 TRANSMITTER 6303 M-621 D D D GG ---

GK195A SGK05A CONTROL PANEL 3416 M-622.1A D D D GK BOTH GK195B SGK05A POWER PANEL 3416 M-622.1A D D D GK BOTH GK195C SGK05A POWER AND CONTROL PANEL 3416 M-622.1A D D D GK BOTH GK196A SGK05B CONTROL PANEL 3415 M-622.1A D D D GK BOTH GK196B SGK05B POWER PANEL 3415 M-622.1A D D D GK BOTH GK196C SGK05B POWER AND CONTROL PANEL 3415 M-622.1A D D D GK BOTH GK198A SGK04A CONTROL PANEL 1512 M-622.1A D D D GK BOTH GK198B SGK04A POWER PANEL 1512 M-622.1A D D D GK BOTH GK198C SGK04A POWER AND CONTROL PANEL 1512 M-622.1A D D D GK BOTH GK199A SGK04B CONTROL PANEL 1501 M-622.1A D D D GK BOTH GK199B SGK04B POWER PANEL 1501 M-622.1A D D D GK BOTH GK199C SGK04B POWER AND CONTROL PANEL 1501 M-622.1A D D D GK BOTH GKAE0002 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK --- 34 GKAE0003 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK --- 34 GKAI0002 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 3501 J-110 D D D GK ---

GKAI0003 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 3501 J-110 D D D GK ---

GKAT0002 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK --- 34 GKAT0003 CTRL BLDG SUP AIR CHLORINE (SPARED IN PLACE) 1513 J-375A D D D GK --- 34

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 17 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B GKHS0040 LOCAL CONTROL STATION 1501 E-028 D D D GK ---

GKHS0103 LOCAL CONTROL STATION 1501 E-028 D D D GK ---

GKHY0013A GKHZ0013A SOLENOID VALVE 1501 M-627A D D D GK ---

GKHY0013B GKHZ0013B SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0013C GKHZ0013C SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0013D GKHZ0013D SOLENOID VALVE 1513 M-627A D D D GK --- 34 GKHY0013E GKHZ0013E SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0013F GKHZ0013F SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0013G GKHZ0013G SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0013H GKHZ0013H SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0055A GKHZ0055A SOLENOID VALVE 3801 M-627A D D D GK ---

GKHY0055B GKHZ0055B SOLENOID VALVE 3801 M-627A D D D GK ---

GKHY0057A GKHZ0057A SOLENOID VALVE 3609 M-627A D D D GK ---

GKHY0057B GKHZ0057B SOLENOID VALVE 3609 M-627A D D D GK ---

GKHY0059A GKHZ0059A SOLENOID VALVE 3501 M-627A D D D GK ---

GKHY0059B GKHZ0059B SOLENOID VALVE 3501 M-627A D D D GK ---

GKHY0098A GKHZ0098A SOLENOID VALVE 3411 M-627A D D D GK ---

GKHY0098B GKHZ0098B SOLENOID VALVE 3412 M-627A D D D GK --- 35 GKHY0122A GKHZ0122A SOLENOID VALVE 3302 M-627A D D D GK ---

GKHY0122B GKHZ0122B SOLENOID VALVE 3302 M-627A D D D GK ---

GKHY0123A GKHZ0123A SOLENOID VALVE 3211 M-627A D D D GK ---

GKHY0123B GKHZ0123B SOLENOID VALVE 3218 M-627A D D D GK ---

GKHY0123C GKHZ0123C SOLENOID VALVE 3218 M-627A D D D GK ---

GKHY0184A GKHZ0184A SOLENOID VALVE 1501 M-627A D D D GK ---

GKHY0184B GKHZ0184B SOLENOID VALVE 1512 M-627A D D D GK ---

GKHY0184C GKHZ0184C SOLENOID VALVE 1513 M-627A D D D GK --- 34 GKHY0184D GKHZ0184D SOLENOID VALVE 1513 M-627A D D D GK --- 34 GKHZ0013A CTRL BLDG ISO DAMPER ACTUATOR - GKD0002 - PNEU 1501 M-627A D D D GK ---

GKHZ0013B CTRL BLDG ISO DAMPER ACTUATOR - GKD0018 - PNEU 1512 M-627A D D D GK ---

GKHZ0013C CTRL BLDG ISO DAMPER ACTUATOR - GKD0025 - PNEU 1512 M-627A D D D GK ---

GKHZ0013D CTRL BLDG ISO DAMPER ACTUATOR - GKD0279 - PNEU 1513 M-627A D D D GK --- 34 GKHZ0013E CTRL BLDG ISO DAMPER ACTUATOR - GKD0283 - PNEU 1512 M-627A D D D GK ---

GKHZ0013F CTRL BLDG ISO DAMPER ACTUATOR - GKD0309 - PNEU 1512 M-627A D D D GK ---

GKHZ0013G CTRL BLDG ISO DAMPER ACTUATOR - GKD0311 - PNEU 1512 M-627A D D D GK ---

GKHZ0013H CTRL BLDG ISO DAMPER ACTUATOR - GKD0313 - PNEU 1512 M-627A D D D GK ---

GKHZ0019A CR FILT SYS ISO DAMPER ACTUATOR - GKD0082 - ELEC 1512 M-627A D D D GK ---

GKHZ0019B CR FILT SYS ISO DAMPER ACTUATOR - GKD0083 - ELEC 1512 M-627A D D D GK ---

GKHZ0019C A/C SYS ISO DAMPER ACTUATOR - GKD0286 - ELEC 1512 M-627A D D D GK ---

GKHZ0019D A/C SYS ISO DAMPER ACTUATOR - GKD0285 - ELEC 1512 M-627A D D D GK ---

GKHZ0029A A/C SYS ISO DAMPER ACTUATOR - GKD0080 - ELEC 1512 M-627A D D D GK BOTH GKHZ0029B A/C SYS ISO DAMPER ACTUATOR - GKD0081 - ELEC 1512 M-627A D D D GK BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 18 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B GKHZ0030A CR FILT SYS ISO DAMPER ACTUATOR - GKD0086 - ELEC 1501 M-627A D D D GK ---

GKHZ0030B CR FILT SYS ISO DAMPER ACTUATOR - GKD0087 - ELEC 1501 M-627A D D D GK ---

GKHZ0030C A/C SYS ISO DAMPER ACTUATOR - GKD0319 - ELEC 1501 M-627A D D D GK ---

GKHZ0030D A/C SYS ISO DAMPER ACTUATOR - GKD0318 - ELEC 1501 M-627A D D D GK ---

GKHZ0040A A/C UNIT ISO DAMPER ACTUATOR - GKD0084 - ELEC 1501 M-627A D D D GK BOTH GKHZ0040B CTRL ROOM ISO DAMPER ACTUATOR - GKD0085 - ELEC 1501 M-627A D D D GK BOTH GKHZ0055A CSR ISO DAMPER ACTUATOR - GKD0004 - PNEU 3801 M-627A D D D GK ---

GKHZ0055B CSR ISO DAMPER ACTUATOR - GKD0016 - PNEU 3801 M-627A D D D GK ---

GKHZ0057A CTRL BLDG ISO DAMPER ACTUATOR - GKD0005 - PNEU 3609 M-627A D D D GK ---

GKHZ0057B CTRL BLDG ISO DAMPER ACTUATOR - GKD0015 - PNEU 3609 M-627A D D D GK ---

GKHZ0059A CSR ISO DAMPER ACTUATOR - GKD0006 - PNEU 3501 M-627A D D D GK ---

GKHZ0059B CSR ISO DAMPER ACTUATOR - GKD0014 - PNEU 3501 M-627A D D D GK ---

GKHZ0075A PRESS SYS ISO DAMPER ACTUATOR - GKD0105 - ELEC 3416 M-627A D D D GK ---

GKHZ0075B PRESS SYS ISO DAMPER ACTUATOR - GKD0317 - ELEC 3416 M-627A D D D GK ---

GKHZ0075C CTRL BLDG ISO DAMPER ACTUATOR - GKD0323 - ELEC 3301 M-627A D D D GK ---

GKHZ0083A PRESS SYS ISO DAMPER ACTUATOR - GKD0088 - ELEC 3415 M-627A D D D GK ---

GKHZ0083B PRESS SYS ISO DAMPER ACTUATOR - GKD0292 - ELEC 3415 M-627A D D D GK ---

GKHZ0083C CTRL BLDG ISO DAMPER ACTUATOR - GKD0320 - ELEC 3302 M-627A D D D GK ---

GKHZ0098A SWGR ROOM ISO DAMPER ACTUATOR - GKD0007 - PNEU 3411 M-627A D D D GK ---

GKHZ0098B BATTERY RM ISO DAMPER ACTUATOR - GKD0013 - PNEU 3412 M-627A D D D GK --- 35 GKHZ0122A ESF SWGR RM ISO DAMPER ACTUATOR - GKD0008 - PNEU 3302 M-627A D D D GK ---

GKHZ0122B ESF SWGR RM ISO DAMPER ACTUATOR - GKD0012 - PNEU 3302 M-627A D D D GK ---

GKHZ0123A ACCESS CTRL ISO DAMPER ACTUATOR - GKD0009 - PNEU 3211 M-627A D D D GK ---

GKHZ0123B ACCESS CTRL ISO DAMPER ACTUATOR - GKD0219 - PNEU 3218 M-627A D D D GK ---

GKHZ0123C ACCESS CTRL ISO DAMPER ACTUATOR - GKD0220 - PNEU 3218 M-627A D D D GK ---

GKHZ0152 CTRL BLDG ISO DAMPER ACTUATOR - GKD0130 - ELEC 1513 M-627A D D D GK --- 34 GKHZ0153 CTRL BLDG ISO DAMPER ACTUATOR - GKD0131 - ELEC 1513 M-627A D D D GK --- 34 GKHZ0154 ACCESS CTRL ISO DAMPER ACTUATOR - GKD0132 - ELEC 1504 M-627A D D D GK --- 34 GKHZ0155 ACCESS CTRL ISO DAMPER ACTUATOR - GKD0133 - ELEC 1504 M-627A D D D GK --- 34 GKHZ0160 CR PRESS SYS ISO DAMPER ACTUATOR - GKD0179 - ELC 1512 M-627A D D D GK ---

GKHZ0161 CR PRESS SYS ISO DAMPER ACTUATOR - GKD0181 - ELC 1512 M-627A D D D GK ---

GKHZ0172A CTRL BLDG ISO DAMPER ACTUATOR - GKD0198 - ELEC 3101 M-627A D D D GK ---

GKHZ0172B CTRL BLDG ISO DAMPER ACTUATOR - GKD0203 - ELEC 3101 M-627A D D D GK ---

GKHZ0173A CTRL BLDG ISO DAMPER ACTUATOR - GKD0199 - ELEC 3101 M-627A D D D GK ---

GKHZ0173B CTRL BLDG ISO DAMPER ACTUATOR - GKD0202 - ELEC 3101 M-627A D D D GK ---

GKHZ0174A CTRL BLDG ISO DAMPER ACTUATOR - GKD0212 - ELEC 3224 M-627A D D D GK ---

GKHZ0174B CTRL BLDG ISO DAMPER ACTUATOR - GKD0209 - ELEC 3222 M-627A D D D GK ---

GKHZ0175A CTRL BLDG ISO DAMPER ACTUATOR - GKD0213 - ELEC 3224 M-627A D D D GK ---

GKHZ0175B CTRL BLDG ISO DAMPER ACTUATOR - GKD0208 - ELEC 3222 M-627A D D D GK ---

GKHZ0184A CTRL BLDG ISO DAMPER ACTUATOR - GKD0300 - PNEU 1501 M-627A D D D GK ---

GKHZ0184B CTRL BLDG ISO DAMPER ACTUATOR - GKD0301 - PNEU 1512 M-627A D D D GK ---

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 19 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B GKHZ0184C CTRL BLDG ISO DAMPER ACTUATOR - GKD0310 - PNEU 1513 M-627A D D D GK --- 34 GKHZ0184D CTRL BLDG ISO DAMPER ACTUATOR - GKD0312 - PNEU 1513 M-627A D D D GK --- 34 GKME0076 MOISTURE SENSOR ELEMENT (DISABLED) 3416 M-621 D D D GK ---

GKME0084 MOISTURE SENSOR ELEMENT (DISABLED) 3415 M-621 D D D GK ---

GKMT0076 FGK02A MOISTURE TRANS. (DISABLED) 3416 M-621 D D D GK ---

GKMT0076A FGK02A MOISTURE TRANS. (DISABLED) 3416 M-621 D D D GK ---

GKMT0084 FGK02B MOISTURE TRANS. (DISABLED) 3415 M-621 D D D GK ---

GKMT0084A FGK02B MOISTURE TRANS. (DISABLED) 3415 M-621 D D D GK ---

GKRE0004 CTRL BLDG SUP AIR RAD MONIT 1513 J-361 D D D GK --- 34 GKRE0005 CTRL BLDG SUP AIR RAD MONIT 1513 J-361 D D D GK --- 34 GKRT0004 GKRE0004 TRANSMITTER 1513 J-361 D D D GK --- 34 GKRT0005 GKRE0005 TRANSMITTER 1513 J-361 D D D GK --- 34 GLHIS0002 LOCAL CONTROL STATION 1406 E-028 D D D GL ---

GLHIS0023 LOCAL CONTROL STATION 1401 E-028 D D D GL --- 33 GLHZ0032-1 AUX BLDG ISO DAMPER ACTUATOR - GLD0052 - ELEC 1504 M-627A D D D GL --- 34 GLHZ0032-2 AUX BLDG ISO DAMPER ACTUATOR - GLD0052 - ELEC 1504 M-627A D D D GL --- 34 GLHZ0033-1 AUX BLDG ISO DAMPER ACTUATOR - GLD0053 - ELEC 1504 M-627A D D D GL --- 34 GLHZ0033-2 AUX BLDG ISO DAMPER ACTUATOR - GLD0053 - ELEC 1504 M-627A D D D GL --- 34 GLHZ0073 AUX BLDG ISO DAMPER ACTUATOR - GLD0036 - ELEC 1102 M-627A D C D GL --- 27 GLHZ0074 AUX BLDG ISO DAMPER ACTUATOR - GLD0037 - ELEC 1102 M-627A D C D GL --- 27 GLHZ0075 AUX BLDG ISO DAMPER ACTUATOR - GLD0038 - ELEC 1102 M-627A D C D GL --- 27 GLHZ0076 AUX BLDG ISO DAMPER ACTUATOR - GLD0039 - ELEC 1102 M-627A D C D GL --- 27 GLHZ0080 AUX BLDG ISO DAMPER ACTUATOR - GLD0157 - ELEC 1406 M-627A D D D GL BOTH GLHZ0081 AUX BLDG ISO DAMPER ACTUATOR - GLD0156 - ELEC 1406 M-627A D D D GL BOTH GMHS0011B LOCAL CONTROL STATION 5201 E-028 D D D GM ---

GMHS0019B LOCAL CONTROL STATION 5201 E-028 D D D GM ---

GMHY0009 GMHZ0009 SOLENOID VALVE 5203 M-627A D D D GM ---

GMHY0019 GMHZ0019 SOLENOID VALVE 5201 M-627A D D D GM ---

GMHZ0009 D.G. ROOM ISO DAMPER ACTUATOR - GMD0005 - PNEU 5203 M-627A D D D GM ---

GMHZ0019 D.G. ROOM ISO DAMPER ACTUATOR - GMD0010 - PNEU 5201 M-627A D D D GM ---

GMTE0001 DIESEL GEN VENT SUPPLY FAN 1A 5203 J-558B D D D GM ---

GMTE0011 DIESEL GEN VENT SUPPLY FAN 1B 5201 J-558B D D D GM ---

GMTT0001 DIESEL GEN VENT SUPPLY FAN 1A 3605 J-110 D D D GM ---

GMTT0011 DIESEL GEN VENT SUPPLY FAN 1B 3605 J-110 D D D GM ---

GMTZ0001A FLOW CTRL DAMPER ACTUATOR - GMD0002 - ELEC/HYD 5203 M-627A D D D GM ---

GMTZ0001B FLOW CTRL DAMPER ACTUATOR - GMD0003 - ELEC/HYD 5203 M-627A D D D GM ---

GMTZ0011A FLOW CTRL DAMPER ACTUATOR - GMD0007 - ELEC/HYD 5201 M-627A D D D GM ---

GMTZ0011B FLOW CTRL DAMPER ACTUATOR - GMD0008 - ELEC/HYD 5201 M-627A D D D GM ---

GNPI0934 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN ---

GNPI0935 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN ---

GNPI0936 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN ---

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 20 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B GNPI0937 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN ---

GNPI0938 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN HOT 25 GNPI0939 CONTAINMENT ATM PRESSURE 3501 ESE-14 D D D GN HOT 25 GNTI0060 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTI0061 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTI0062 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTI0063 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTR0063 CTMT ATMOS TEMP 3501 J-110 D D D GN BOTH GNTT0060 CTMT COOLER A TEMP 3605 J-110 D D D GN BOTH GNTT0061 CTMT COOLER B TEMP 3605 J-110 D D D GN BOTH GNTT0062 CTMT COOLER C TEMP 3605 J-110 D D D GN BOTH GNTT0063 CTMT COOLER D TEMP 3605 J-110 D D D GN BOTH GS001A RECOMBINER POWER PANEL 3301 M-637 D D D GS ---

GS001B RECOMBINER POWER PANEL 3302 M-637 D D D GS ---

GS065A H2 ANALYZER CONTROL PANEL 3605 J-359 D D D GS ---

GS065AA RECOMBINER CONTROL PANEL 3605 M-637 D D D GS ---

GS065B H2 ANALYZER CONTROL PANEL 3605 J-359 D D D GS ---

GS065BA RECOMBINER CONTROL PANEL 3605 M-637 D D D GS ---

GSAI0010 HYDROGEN ANALYZER 2B 3501 J-110 D D D GS ---

GSAI0019 HYDROGEN ANALYZER 2A 3501 J-110 D D D GS ---

GSAR0010 HYDROGEN ANALYZER 3501 J-110 D D D GS ---

GSAT0010 HYDROGEN ANALYZER 2B ANALYSIS TRANSMITTER 3605 J-359 D D D GS ---

GSAT0019 HYDROGEN ANALYZER 2A ANALYSIS TRANSMITTER 3605 J-359 D D D GS ---

GTHZ0028 AUX BLDG ISO DAMPER ACTUATOR - GTD0011 - ELEC 1504 M-627A D D D GT --- 34 GTHZ0029 AUX BLDG ISO DAMPER ACTUATOR - GTD0012 - ELEC 1504 M-627A D D D GT --- 34 GTRE0022 CTMT PURGE EXHAUST RAD MONIT 1507 J-361 C D D GT --- 34 GTRE0031 CTMT ATMOSPHERE RAD MONIT 1507 J-361 C D D GT --- 34 GTRE0032 CTMT ATMOSPHERE RAD MONIT 1506 J-361 C D D GT --- 34 GTRE0033 CTMT PURGE EXH RAD MONIT 1507 J-361 C D D GT --- 34 GTRIC0059 CTMT HRRM CONTROL/DISPLAY MODULE 3501 J-361A D D D GT ---

GTRIC0060 CTMT HRRM CONTROL/DISPLAY MODULE 3501 J-361A D D D GT ---

GTRR0060 CTMT HIGH RANGE AREA RADN RECORDER 3501 J-110 D D D GT --- 25 GTRT0022 GTRE0022 TRANSMITTER 1507 J-361 C D D GT --- 34 GTRT0031 GTRE0031 TRANSMITTER 1507 J-361 C D D GT --- 34 GTRT0032 GTRE0032 TRANSMITTER 1506 J-361 C D D GT --- 34 GTRT0033 GTRE0033 TRANSMITTER 1507 J-361 C D D GT --- 34 GTRT0059 CTMT HIGH RANGE AREA RADN MON 1512 J-361A D D D GT --- 25 GTRT0060 CTMT HIGH RANGE AREA RADN MON 1501 J-361A D D D GT --- 25 GTRV0022A CTMT PURGE EXHAUST 1507 J-603A C D D GT --- 34 GTRV0022B CTMT PURGE EXHAUST 1504 J-603A D D D GT --- 34 GTRV0033A CTMT PURGE EXHAUST 1507 J-603A C D D GT --- 34

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 21 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B GTRV0033B CTMT PURGE EXHAUST 1504 J-603A D D D GT --- 34 JELI0012A EMER FUEL OIL DAY TK A LEV 3501 J-110 D D D JE BOTH JELI0012B EMER FUEL OIL DAY TK A LEV 5203 J-110 D D D JE BOTH JELI0032A EMER FUEL OIL DAY TK B LEV 3501 J-110 D D D JE BOTH JELI0032B EMER FUEL OIL DAY TK B LEV 5201 J-110 D D D JE BOTH JELT0001 EMER FUEL OIL DAY TK A LEV 5203 J-301 D D D JE BOTH JELT0012 EMER FUEL OIL DAY TK A LEV 5203 J-301 D D D JE BOTH JELT0021 EMER FUEL OIL DAY TK B LEV 5201 J-301 D D D JE BOTH JELT0032 EMER FUEL OIL DAY TK B LEV 5201 J-301 D D D JE BOTH KFC02 AUX FEED PUMP TURBINE 1331 M-021 D D C FC BOTH KJ121 DIESEL GAUGE AND CONTROL PANEL 5203 M-018 D D D KJ BOTH KJ122 DIESEL GAUGE AND CONTROL PANEL 5201 M-018 D D D KJ BOTH KJHS0110 CONTROL ROOM FIRE ISO SWITCH 5201 M-018 D D D KJ ---

KJLI0031 L.O. LEVEL CONTROL TANK INDICATOR 5203 M-018 D D D KJ BOTH KJLI0038 L.O. AUX. TANK LEVEL INDICATOR 5203 M-018 D D D KJ BOTH KJLI0131 L.O. LEVEL CONTROL TANK INDICATOR 5201 M-018 D D D KJ BOTH KJLI0138 L.O. AUX. TANK LEVEL INDICATOR 5201 M-018 D D D KJ BOTH KJPS0062 JACKET WATER BACKUP TO ELECT SPEED SWITCH 5203 M-018 D D D KJ BOTH KJPS0162 JACKET WATER BACKUP TO ELECT SPEED SWITCH 5201 M-018 D D D KJ BOTH KJPSH0023A HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0023B HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0023C HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0023D HIGH CRANKCASE PRESSURE 5203 M-018 D D D KJ BOTH KJPSH0123A HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSH0123B HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSH0123C HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSH0123D HIGH CRANKCASE PRESS 5201 M-018 D D D KJ BOTH KJPSHL0002A AIR COMPR. A START/STOP PRESS. SWITCH 5203 M-018 D D D KJ BOTH KJPSHL0002B AIR COMPR. B START/STOP PRESS. SWITCH 5203 M-018 D D D KJ BOTH KJPSHL0102A AIR COMPR. A START/STOP PRESS. SWITCH 5201 M-018 D D D KJ BOTH KJPSHL0102B AIR COMPR. B START/STOP PRESS. SWITCH 5201 M-018 D D D KJ BOTH KJPSL0026A LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0026B LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0026C LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0026D LOW LUBE OIL PRESS 5203 M-018 D D D KJ BOTH KJPSL0126A LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPSL0126B LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPSL0126C LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPSL0126D LOW LUBE OIL PRESS 5201 M-018 D D D KJ BOTH KJPV0001A AIR START SOL VLV 1 5203 M-018 D D D KJ BOTH KJPV0001B AIR START SOL VLV 2 5203 M-018 D D D KJ BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 22 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B KJPV0008 SHUTDOWN AIR SOL VLV 5203 M-018 D D D KJ BOTH KJPV0101A AIR START SOL VLV 1 5201 M-018 D D D KJ BOTH KJPV0101B AIR START SOL VLV 2 5201 M-018 D D D KJ BOTH KJPV0108 SHUTDOWN AIR SOL VLV 5201 M-018 D D D KJ BOTH KJTCV0034 LUBE OIL COOLER TEMP CTRL VLV 5203 M-018 D D D KJ BOTH KJTCV0056 INTERCOOLER HEAT EXCHANGER TEMP CTRL VLV 5203 M-018 D D D KJ BOTH KJTCV0060 JACKET WATER HEAT EXCHANGER TEMP CTRL VLV 5203 M-018 D D D KJ BOTH KJTCV0134 LUBE OIL COOLER TEMP CTRL VLV 5201 M-018 D D D KJ BOTH KJTCV0156 INTERCOOLER HEAT EXCHANGER TEMP CTRL VLV 5201 M-018 D D D KJ BOTH KJTCV0160 JACKET WATER HEAT EXCHANGER TEMP CTRL VLV 5201 M-018 D D D KJ BOTH KJTSH0059A HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0059B HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0059C HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0059D HIGH JACKET WATER TEMP 5203 M-018 D D D KJ BOTH KJTSH0159A HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH KJTSH0159B HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH KJTSH0159C HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH KJTSH0159D HIGH JACKET WATER TEMP 5201 M-018 D D D KJ BOTH LELE0105 DIESEL GEN BLDG SUMP 5203 J-481 D D D LE BOTH LELE0106 DIESEL GEN BLDG SUMP 5201 J-481 D D D LE BOTH LELI0105 DIESEL GEN BLDG SUMP 3501 J-200 D D D LE BOTH LELI0106 DIESEL GEN BLDG SUMP 3501 J-200 D D D LE BOTH LELIT0105 DIESEL GEN BLDG SUMP 3605 J-481 D D D LE BOTH LELIT0106 DIESEL GEN BLDG SUMP 3605 J-481 D D D LE BOTH LFLE0124 CONTROL BLDG FL EQUIP DRAIN 3101 J-481 D D D LF ---

LFLE0125 CONTROL BLDG FL EQUIP DRAIN 3101 J-481 D D D LF ---

LFLI0009 CTMT NORMAL SUMP B LEVEL 3501 J-110 D D D LF --- 25 LFLI0010 CTMT NORMAL SUMP A LEVEL 3501 J-110 D D D LF --- 25 LFLI0101 RHR PMP ROOM SUMP LEVEL 3501 J-110 D D D LF COLD LFLI0102 RHR PMP ROOM SUMP LEVEL 3501 J-110 D D D LF COLD LFLI0103 AUX BLDG SUMP LEVEL 3501 J-110 D D D LF ---

LFLI0104 AUX BLDG SUMP LEVEL 3501 J-110 D D D LF ---

LFLI0124 CONTROL BLDG FL EQUIP DRAIN 3501 J-200 D D D LF ---

LFLI0125 CONTROL BLDG FL EQUIP DRAIN 3501 J-200 D D D LF ---

LFLIT0009 CTMT NORMAL SUMP 3605 J-481 D D D LF --- 25 LFLIT0010 CTMT NORMAL SUMP 3605 J-481 D D D LF --- 25 LFLIT0101 RHR PMP ROOM LEAKAGE LEVEL 3605 J-481 D D D LF COLD LFLIT0102 RHR PMP ROOM LEAKAGE LEVEL 3605 J-481 D D D LF COLD LFLIT0103 AUX BLDG LEAKAGE LEVEL 3605 J-481 D D D LF ---

LFLIT0104 AUX BLDG LEAKAGE LEVEL 3605 J-481 D D D LF ---

LFLIT0124 CONTROL BLDG FL EQUIP DRAIN 3605 J-481 D D D LF ---

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 23 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B LFLIT0125 CONTROL BLDG FL EQUIP DRAIN 3605 J-481 D D D LF ---

NB001 4.16 KV SWITCHGEAR 3301 E-009 D D D NB BOTH NB002 4.16 KV SWITCHGEAR 3302 E-009 D D D NB BOTH NBEI0001 4 KV BUS NB01 VOLTS 3501 J-200 D D D NB ---

NBEI0002 4 KV BUS NB02 VOLTS 3501 J-200 D D D NB ---

NBEI0003 4 KV BUS NB01 SYNCHROSCOPE 3501 J-200 D D D NB ---

NBEI0004 4 KV BUS NB02 SYNCHROSCOPE 3501 J-200 D D D NB ---

NE001 DIESEL GENERATOR 5203 M-018 D D D NE BOTH NE002 DIESEL GENERATOR 5201 M-018 D D D NE BOTH NE106 CONTROL & RELAY PANEL 5201 M-018 D D D NE BOTH NE107 CONTROL & RELAY PANEL 5203 M-018 D D D NE BOTH NF039A LOAD SHED/SEQ PANEL 3605 E-092 D D D NF BOTH NF039B LOAD SHED/SEQ PANEL 3605 E-092 D D D NF BOTH NF039C LOAD SHED/SEQ PANEL 3605 E-092 D D D NF BOTH NG001 LOAD CENTER 3301 E-017 D D D NG BOTH NG001A MCC 3301 E-018 D D D NG BOTH NG001B MCC 1410 E-018 D D D NG BOTH 12 NG001T MCC 1410 E-018 D D D NG BOTH 12 NG002 LOAD CENTER 3302 E-017 D D D NG BOTH NG002A MCC 3302 E-017 D D D NG BOTH NG002B MCC 1409 E-018 D D D NG BOTH 12 NG002T MCC 1409 E-018 D D D NG BOTH 12 NG003 LOAD CENTER 3301 E-017 D D D NG BOTH NG003C MCC 1512 E-018 D D D NG BOTH NG003D MCC 5203 E-018 D D D NG BOTH NG003T MCC 1410 E-018 D D D NG BOTH 12 NG004 LOAD CENTER 3302 E-017 D D D NG BOTH NG004C MCC 1501 E-018 D D D NG BOTH NG004D MCC 5201 E-018 D D D NG BOTH NG004T MCC 1409 E-018 D D D NG BOTH 12 NG005E MCC K105 E-018 D D D NG BOTH NG006E MCC K104 E-018 D D D NG BOTH NK001 125 VDC SWITCHBOARD 3408 E-020 D D D NK BOTH NK002 125 VDC SWITCHBOARD 3410 E-020 D D D NK BOTH NK003 125 VDC SWITCHBOARD 3414 E-020 D D D NK BOTH NK004 125 VDC SWITCHBOARD 3404 E-020 D D D NK BOTH NK011 BATTERY 3407 E-050A D D D NK BOTH NK012 BATTERY 3411 E-050A D D D NK BOTH NK013 BATTERY 3413 E-050A D D D NK BOTH NK014 BATTERY 3405 E-050A D D D NK BOTH NK021 CHARGER 3408 E-051 D D D NK BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 24 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B NK022 CHARGER 3410 E-051 D D D NK BOTH NK023 CHARGER 3414 E-051 D D D NK BOTH NK024 CHARGER 3404 E-051 D D D NK BOTH NK025 SPARE CHARGER 3301 E-051 D D D NK ---

NK026 SPARE CHARGER 3302 E-051A D D D NK ---

NK041 125 VDC SWITCHBOARD 3408 E-020 D D D NK BOTH NK042 125 VDC SWITCHBOARD 3410 E-020 D D D NK BOTH NK043 125 VDC SWITCHBOARD 3414 E-020 D D D NK BOTH NK044 125 VDC SWITCHBOARD 3404 E-020 D D D NK BOTH NK051 125 VDC SWITCHBOARD 3408 E-020 D D D NK BOTH NK051A LIGHTING PANEL 3408 E-020 D D D NK BOTH NK054 125 VDC SWITCHBOARD 3404 E-020 D D D NK BOTH NK071 TRANSFER SWITCH 3408 E-051B D D D NK BOTH NK072 TRANSFER SWITCH 3410 E-051B D D D NK BOTH NK073 TRANSFER SWITCH 3414 E-051B D D D NK BOTH NK074 TRANSFER SWITCH 3404 E-051B D D D NK BOTH NK075 SPARE CHARGER TRANSFER SWITCH 3301 E-051B D D D NK ---

NK076 SPARE CHARGER TRANSFER SWITCH 3302 E-051B D D D NK ---

NK077 SPARE CHARGER TRANSFER SWITCH 3301 E-051B D D D NK ---

NK078 SPARE CHARGER TRANSFER SWITCH 3302 E-051B D D D NK ---

NK079 MANUAL TRANSFER SWITCH 3301 M-766A D D D NK ---

NK080 MANUAL TRANSFER SWITCH 3302 M-766A D D D NK ---

NKEI0001 NK01 125 VDC BUS VOLTS 3501 J-200 D D D NK ---

NKEI0002 NK02 125 VDC BUS VOLTS 3501 J-200 D D D NK ---

NKEI0003 NK03 125 VDC BUS VOLTS 3501 J-200 D D D NK ---

NKEI0004 NK04 125 VDC BUS VOLTS 3501 J-200 D D D NK ---

NKII0001 NK21 BAT CHARGER AMPS 3501 J-200 D D D NK ---

NKII0002 NK11 BAT AMPS 3501 J-200 D D D NK ---

NKII0003 NK22 BAT CHARGER AMPS 3501 J-200 D D D NK ---

NKII0004 NK12 BAT AMPS 3501 J-200 D D D NK ---

NKII0005 NK23 BAT CHARGER AMPS 3501 J-200 D D D NK ---

NKII0006 NK13 BAT AMPS 3501 J-200 D D D NK ---

NKII0007 NK24 BAT CHARGER AMPS 3501 J-200 D D D NK ---

NKII0008 NK14 BAT AMPS 3501 J-200 D D D NK ---

NN001 VITAL AC INST DIST PANEL 3408 E-053 D D D NN BOTH NN002 VITAL AC INST DIST PANEL 3410 E-053 D D D NN BOTH NN003 VITAL AC INST DIST PANEL 3414 E-053 D D D NN BOTH NN004 VITAL AC INST DIST PANEL 3404 E-053 D D D NN BOTH NN011 INVERTER 3408 ESE-18 D D D NN BOTH NN012 INVERTER 3410 ESE-18 D D D NN BOTH NN013 INVERTER 3414 ESE-18 D D D NN BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 25 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B NN014 INVERTER 3404 ESE-1 D D D NN BOTH NN015 UPS/ INVERTER 3301 M-766A D D D NN ---

NN016 UPS/ INVERTER 3302 M-766A D D D NN ---

PA003 PT CUB. FOR RCP MOTOR DPBB01A 1410 E-009 C D D PA BOTH PA004 PT CUB. FOR RCP MOTOR DPBB01B 1410 E-009 C D D PA BOTH PA005 PT CUB. FOR RCP MOTOR DPBB01C 1409 E-009 C D D PA BOTH PA006 PT CUB. FOR RCP MOTOR DPBB01D 1409 E-009 C D D PA BOTH RL001 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL002 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL003 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL004 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL005 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL006 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL011 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL012 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL013 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL014 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL015 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL016 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL017 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL018 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL019 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL020 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL021 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL022 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL023 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL024 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL025 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL026 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL027 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RL028 MAIN CTRL BOARD 3501 J-200 D D D RL BOTH RP053AA BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053AB BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053AC BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053BA BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053BB BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053BC BOP INSTR RACK 3605 J-110 D D D RP BOTH RP053DA BOP INSTR RACK TERMN 3605 J-110 D D D RP BOTH RP053DB BOP INSTR RACK TERMN 3605 J-110 D D D RP BOTH RP068 MISC BOP CONT PNL 3605 J-201 D D D RP ---

RP080 RVLIS MICROPROCESSOR 3605 ESE-51 D D D RP --- 26

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 26 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B RP081A SUBCOOLING MONITORING PANEL 3605 ESE-46A D D D RP --- 26 RP081A-E01 SUBCOOLING MONITOR PANEL 3605 ESE-46B D D D RP --- 26 RP081B SUBCOOLING MONITORING PANEL 3605 ESE-46A D D D RP --- 26 RP081B-E01 SUBCOOLING MONITOR PANEL 3605 ESE-46B D D D RP --- 26 RP118A AUX SHUTDOWN PNL 1413 J-201 D D D RP BOTH RP118B AUX SHUTDOWN PNL 1413 J-201 D D D RP BOTH RP139 AUX RELAY RACK 3301 E-093 D D D RP BOTH RP140 AUX RELAY RACK 3302 E-093 D D D RP BOTH RP147A INSTR RACK 3302 J-110 D D D RP ---

RP147B INSTR RACK 3302 J-110 D D D RP ---

RP210 AUX RELAY RACK 1402 E-093 D D D RP BOTH 33 RP266 AUX RELAY RACK 1408 E-093 D D D RP BOTH 33 RP289 125 VDC PANEL 1513 E-028 D D D RP --- 34 RP290 125 VDC PANEL 1501 E-028 D D D RP ---

RP315 125 VDC PANEL K105 E-028 D D D RP ---

RP316 125 VDC PANEL K104 E-028 D D D RP ---

RP331 REVERSE ISOL RELAY RACK 1408 E-093 D D D RP BOTH 33 RP333 AUX. RELAY RACK 1408 E-093 D D D RP BOTH 33 RP334 LOCKOUT RELAY RACK 3302 E-093 D D D RP BOTH RP335 LOCKOUT RELAY RACK 3302 E-093 D D D RP BOTH SA036A ESFAS CABINET 3605 J-104 D D D SA BOTH SA036B ESFAS CABINET 3605 J-104 D D D SA BOTH SA036C ESFAS CABINET 3605 J-104 D D D SA BOTH SA036D ESFAS CABINET 3605 J-104 D D D SA BOTH SA036E ESFAS CABINET 3605 J-104 D D D SA BOTH SA066A CAB. STATUS LOGIC/TERM. 3605 E-094 D D D SA ---

SA066B CAB. STATUS LOGIC/TERM. 3605 E-094 D D D SA ---

SA066C CAB. STATUS LOGIC/TERM. 3605 E-094 D D D SA ---

SA066X STATUS LIGHT DISPLAY PANEL 3501 E-094 D D D SA ---

SA066Y STATUS LIGHT DISPLAY PANEL 3501 E-094 D D D SA ---

SA066Z STATUS LIGHT DISPLAY PANEL 3501 E-094 D D D SA ---

SA075A MN STM & FW ISO ACT PNL 3605 J-105 D D D SA BOTH SA075B MN STM & FW ISO ACT PNL 3605 J-105 D D D SA BOTH SB029A CAB W SS PROT SYS INPUT TRN A 3605 ESE-16 D D D SB BOTH SB029B CAB W SS PROT SYS LOGIC TRN A 3605 ESE-16 D D D SB BOTH SB029C CAB W SS PROT SYS OUT 1 TRN A 3605 ESE-16 D D D SB BOTH SB029D CAB W SS PROT SYS OUT 2 TRN A 3605 ESE-16 D D D SB BOTH SB030A CAB W SAFEGUARDS TEST 1 TRN A 3605 ESE-16 D D D SB BOTH SB030B CAB W SAFEGUARDS TEST 2 TRN A 3605 ESE-16 D D D SB BOTH SB032A CAB W SS PROT SYS INPUT TRN B 3605 ESE-16 D D D SB BOTH SB032B CAB W SS PROT SYS LOGIC TRN B 3605 ESE-16 D D D SB BOTH

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 27 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B SB032C CAB W SS PROT SYS OUT 1 TRN B 3605 ESE-16 D D D SB BOTH SB032D CAB W SS PROT SYS OUT 2 TRN B 3605 ESE-16 D D D SB BOTH SB033A CAB W SAFEGUARDS TEST 1 TRN B 3605 ESE-16 D D D SB BOTH SB033B CAB W SAFEGUARDS TEST 1 TRN B 3605 ESE-16 D D D SB BOTH SB037 CAB W PROCESS PROTECTION SET 3 3605 ESE-13 D D D SB BOTH SB038 CAB W PROCESS PROTECTION SET 1 3605 ESE-13 D D D SB BOTH SB041 CAB W PROCESS PROTECTION SET 4 3605 ESE-13 D D D SB BOTH SB042 CAB W PROCESS PROTECTION SET 2 3605 ESE-13 D D D SB BOTH SB078 RVLIS MICROPROCESSOR CABINET 3605 ESE-51 D D D SB --- 26 SB079 RVLIS MICROPROCESSOR CABINET 3605 ESE-51 D D D SB --- 26 SB102A CAB W REACTOR TRIP SWGR TRAIN A 1403 ESE-62 D D D SB BOTH SB102A-E01 CAB W REACTOR TRIP SWGR TRAIN A 1403 ESE-20 D D D SB BOTH SB102B CAB W REACTOR TRIP SWGR TRAIN B 1403 ESE-62 D D D SB BOTH SB102B-E01 CAB W REACTOR TRIP SWGR TRAIN B 1403 ESE-20 D D D SB BOTH SB148A CAB W CONTR RM ISOL 3302 ESE-13 D D D SB BOTH SB148B CAB W CONTR RM ISOL 3302 ESE-13 D D D SB BOTH SBUQ0761A SSPS POWER SUPPLY IN SB038 3605 ESE-13 D D D SB BOTH SBUQ0761B SSPS POWER SUPPLY IN SB038 3605 ESE-13 D D D SB BOTH SBUQ0761C SSPS POWER SUPPLY IN SB038 3605 ESE-13 D D D SB BOTH SBUQ0762A SSPS POWER SUPPLY IN SB042 3605 ESE-13 D D D SB BOTH SBUQ0762B SSPS POWER SUPPLY IN SB042 3605 ESE-13 D D D SB BOTH SBUQ0762C SSPS POWER SUPPLY IN SB042 3605 ESE-13 D D D SB BOTH SBUQ0763A SSPS POWER SUPPLY IN SB037 3605 ESE-13 D D D SB BOTH SBUQ0763B SSPS POWER SUPPLY IN SB037 3605 ESE-13 D D D SB BOTH SBUQ0763C SSPS POWER SUPPLY IN SB037 3605 ESE-13 D D D SB BOTH SBUQ0764A SSPS POWER SUPPLY IN SB041 3605 ESE-13 D D D SB BOTH SBUQ0764B SSPS POWER SUPPLY IN SB041 3605 ESE-13 D D D SB BOTH SBUQ0764C SSPS POWER SUPPLY IN SB041 3605 ESE-13 D D D SB BOTH SE001 WELL DET. (NE41) 2000 ESE-8 C D C SE BOTH SE002 WELL DET. (NE31 NE35) 2000 ESE-4 C D C SE ---

SE003 WELL DET. (NE43) 2000 ESE-8 C D C SE BOTH SE005 WELL DET. (NE42) 2000 ESE-8 C D C SE BOTH SE006 WELL DET. (NE32 NE36) 2000 ESE-4 C D C SE ---

SE007 WELL DET. (NE44) 2000 ESE-8 C D C SE BOTH SE031 PREAMP SR CHAN 1 1410 ESE-47B C D D SE ---

SE032 PREAMP SR CHAN 2 1409 ESE-47B C D D SE ---

SE054A W NUC INST. NIS 1 3605 ESE-10 D D D SE BOTH SE054B W NUC INST. NIS 2 3605 ESE-10 D D D SE BOTH SE054C W NUC INST. NIS 3 3605 ESE-10 D D D SE BOTH SE054D W NUC INST. NIS 4 3605 ESE-10 D D D SE BOTH SENI0060A EX-CORE NEUTRON FLUX INDICATOR 3501 J-110 D D D SE ---

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 28 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B SENI0060B EX-CORE NEUTRON FLUX INDICATOR 3501 J-110 D D D SE ---

SENI0061X EX-CORE NEUTRON FLUX INDICATOR 1413 J-110 D D D SE ---

SENI0061Y EX-CORE NEUTRON FLUX INDICATOR 1413 J-110 D D D SE ---

SENIR0061 EX-CORE NEUTRON FLUX RECORDER 3501 J-110 D D D SE ---

SENY0060A NFMS AMPLIFIER 1403 J-364 D D D SE ---

SENY0060B NFMS SIGNAL PROCESSOR 1403 J-364 D D D SE ---

SENY0061A NFMS AMPLIFIER 1501 J-364 D D D SE ---

SENY0061B NFMS SIGNAL PROCESSOR 1501 J-364 D D D SE ---

SGK04A CONTROL ROOM A/C UNIT 1512 M-622.1, M-622.1A D D D GK BOTH SGK04B CONTROL ROOM A/C UNIT 1501 M-622.1, M-622.1A D D D GK BOTH SGK05A CLASS IE ELEC. EQUIP. A/C UNIT 3416 M-622.1, M-622.1A D D D GK BOTH SGK05B CLASS IE ELEC. EQUIP. A/C UNIT 3415 M-622 D D D GK BOTH SGS03A H2 ANALYZER CALIB BOTTLE & CTRL PANEL SKID 1506 J-359 D D D GS --- 34 SGS03B H2 ANALYZER CALIB BOTTLE & CTRL PANEL SKID 1507 J-359 D D D GS --- 34 SP067 RAD MONITOR CONT PNL 3605 J-361 D D D SP ---

SP104A RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP --- 34 SP104B RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP --- 34 SP105A RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP --- 34 SP105B RAD MON SYS ISOLATION BOX 1513 J-361 D D D SP --- 34

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 29 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B SP122A RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP --- 34 SP122B RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP --- 34 SP127A RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP --- 36 SP127B RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP --- 36 SP128A RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP --- 36 SP128B RAD MON SYS ISOLATION BOX 6301 J-361 D D D SP --- 36 SP131A RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP --- 34 SP131B RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP --- 34 SP132A RAD MON SYS ISOLATION BOX 1506 J-361 C D D SP --- 34 SP132B RAD MON SYS ISOLATION BOX 1506 J-361 C D D SP --- 34 SP133A RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP --- 34 SP133B RAD MON SYS ISOLATION BOX 1507 J-361 C D D SP --- 34 SP159A RAD MON SYS ISOLATION BOX 1512 J-361 D D D SP ---

SP159B RAD MON SYS ISOLATION BOX 1512 J-361 D D D SP ---

SP160A RAD MON SYS ISOLATION BOX 1501 J-361 D D D SP ---

SP160B RAD MON SYS ISOLATION BOX 1501 J-361 D D D SP ---

SS001 AMSAC PANEL 3605 J-203 D D D SS ---

XNG01 LC TRANSFORMER 3301 E-017 D D D NG BOTH XNG02 LC TRANSFORMER 3302 E-017 D D D NG BOTH XNG03 LC TRANSFORMER 3301 E-017 D D D NG BOTH XNG04 LC TRANSFORMER 3302 E-017 D D D NG BOTH XNG05 ESW MCC TRANSFORMER K105 E-075 D D D NG BOTH XNG06 ESW MCC TRANSFORMER K104 E-075 D D D NG BOTH XNN05 XFMR 3408 E-075 D D D NN BOTH XNN06 XFMR 3408 E-075 D D D NN BOTH ZHS-1-EQ SWITCHES 1410 E-028A D D D XX BOTH ZHS-2-EQ SWITCHES 1409 E-028A D D D XX BOTH Cat. A Item is required to function post accident Cat. B Item is not required to function post accident; however, item must not adversely fail post accident Cat. C Item's status post accident has no effect on plant safety Cat. D Item is in mild environment post accident Notes:

2 Used throughout the plant.

3 The spent fuel pool cooling system will be operated during these conditions to maintain fuel pool temperatures.

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 30 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B This note identifies that Non-IE Conax modules used in this penetration and addressed in PQE-E-035B-P01 have a safety related function of maintaining the pressure boundary of containment. PQE-E-035B-P01 documents that Conax modules used in ZSE/ZSI222E (I), ZSE/ZSI252E (I), ZNE/ZNI253C (I),

4 ZSE/ZSI254E (I), ZSE/ZSI255E (I), ZSE/ZSI255D (I), ZNE/ZNI292F (I) and ZNE/ZNI294C (I) ZSE/ZSI222F (LVP), ZNE/ZNI224C (LVP), ZNE/ZNI274A (LVP), ZNE/ZNI274G (LVP) and ZNE/ZNI282C (LVP) are acceptable for use in the environments identified.

5 Used throughout the plant - outside containment.

7 Used inside containment.

8 Splices used inside boxes instead of terminal blocks.

9 Alternate EGS connector approved for installation per CP 12467 as necessary.

Determined by XX-81 analysis to be mild environment equipment post accident (also reference EQWP-J-605A R3) states that a location-specific dose 11 calculation and analysis was performed on the butterfly valves located in Room 1314, and concluded that the subject valves can be recategorized as mild environment equipment. The parameters constitute a mild environment.

Determined by XX-53 analysis to be mild environment equipment post accident. EQWP-E-018 R5 states that a specific-location dose calculation and 12 analysis was performed on the MCC's located in Room 1409 and 1410, and concluded that subject MCCs can be recategorized as a mild environment equipment.

16 Qualified as a sub-component of Panel RP209 17 Qualified as a sub-component of Panel RP330 18 Qualified as a sub-component of Panel RP332 19 Spared in Place 20 This equipment was added in response to NUREG-0737 Category II.B.1 21 This equipment was added in response to NUREG-0737 Category II.B.3 22 This equipment was added in response to NUREG-0737 Category II.D.3 24 This equipment was added in response to NUREG-0737 Category II.E.1.2 25 This equipment was added in response to NUREG-0737 Category II.F.1 26 This equipment was added in response to NUREG-0737 Category II.F.2 Rooms 1101, 1102, 1120, 1121, 1122 and 1130 are all open to one another. A worst-case condition of any associated room boundary breach should be 27 addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1107 and 1108 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components 28 in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1113 and 1114 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components 29 in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1301, 1314, 1315 and 1320 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed 30 for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1508 and 1509 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for 31 components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1206 and 1207 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components 32 in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 1401, 1402 and 1408 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for 33 components in all of these rooms for the HELB barrier consideration in AP 10-104.

EQSD-II Rev. 32 Table 2: EQ Mild Environment Equipment List 31 of 31 Component Number Environmental Qualification Description EQ Room EQ Spec L H M System Hot/Cold Notes O E S Shutdown C L L A B B Rooms 1502, 1503, 1505 and 1507 plus Rooms 1504, 1506 and 1513 (due to transfer grill GLD0175 on M-1H1431) are all open to one another. A worst-34 case condition of any associated room boundary breach should be addressed for components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 3401, 3406 and 3412 are all open to one another. A worst-case condition of any associated room boundary breach should be addressed for 35 components in all of these rooms for the HELB barrier consideration in AP 10-104.

Rooms 6301 and 6302 are open to one another. A worst-case condition of any associated room boundary breach should be addressed for components 36 in all of these rooms for the HELB barrier consideration in AP 10-104.

Reference E-035B-00050, Table 3.1, Page 11. The power and control modules are ZSE/ZSI233E, ZSE/ZSI233F, ZSE/ZSI234F, ZNE/ZNI278F and ZNE/ZNI278G. The instrumentation modules are ZSE/ZSI233D, ZSE/ZSI233G, ZSE/ZSI234E, ZSE/ZSI243C, ZSE/ZSI249C, ZSE/ZSI249D, 37 ZSE/ZSI250A, ZSE/ZSI250B, ZSE/ZSI250D, ZSE/ZSI250F, ZSE/ZSI250G, ZSE/ZSI258F, ZNE/ZNI277F, ZNE/ZNI278C, ZNE/ZNI278D, ZNE/ZNI278E, ZNE/ZNI279E, ZNE/ZNI287C, ZNE/ZNI287D, ZNE/ZNI287E, ZNE/ZNI288B, ZNE/ZNI288D, ZNE/ZNI288F, ZNE/ZNI295F and ZNE/ZNI295G.

GDI-30F (Long-glass, fiber filled, diallyl-phthalate) terminal blocks that are Series 601-JJ, 602-JJ, 604-JJ, 605-JJ, 812-JJ type are qualified under PQE-E-38 035B-P02 for each of these applications. Instrumentation applications do not use the Kulka terminal blocks inside the containment, PQE-E-11013-P01/

P06/P07/ P08/ P09 splices are used in these applications.

These assets contain two limit switches. However one of the limit switches is an installed spare and doesnt have power running to it. Therefore, doesnt 39 perform any safety function and doesnt need qualified by the EQ program.

50 Located in yard.