Corrected Redacted Version of Rev. 33 to Updated Safety Analysis Report, M-6630-00017A W08 G3D to H, Structural Steel Fireproofing Data
ML20290A606
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 07/23/2020
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20290A562 List:
References
WO 20-0041
Download: ML20290A606 (179)


Text

M-663-00017A, Revision W03 Page G3D-1 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1126-1974 Building: Auxiliary Fire Area: A-07

==

Description:==

Boron Injection Tank & Pump Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S1341 N/A Member Type: Beam N/A Member Size: 18 X 45 N/A Comments: Additional attachments in close Column is embedded, columns proximity, beam temp acceptable. considered bounded no review required.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 125, Open Grille Compartment Width (ft): 17 Vent

Description:

Exht: 125 Open Grille Compartment Length (ft): 16 Compartment Height (ft): 25 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature @ 180 minutes (F): 1067.67 Room Sketch:

M-663-00017A, Revision W03 Page G3D-2 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1126-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-3 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1311-2000 Building: Auxiliary Fire Area: A-08

==

Description:==

Sampling Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S1421 N/A Member Type: Beam N/A Member Size: 24 X 76 N/A Comments: Orientation reduces 1 ea 4" I area. No columns.

Beam temp. acceptable.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 100 Exht: 100 Compartment Width (ft): 18 Vent

Description:

Temp not in USAR Table 3.11, used adjacent Compartment Length (ft): 16 rooms that are similar Compartment Height (ft): 25 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature @ 180 minutes (F): 1036.29 Room Sketch:

M-663-00017A, Revision W03 Page G3D-4 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1311-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-5 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1325-2000 Building: Auxiliary Fire Area: A-13

==

Description:==

Aux Feedwater Pump Rm B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 N/A Member Type: Beam N/A Member Size: 30 X 99 N/A Comments: Beam temp. acceptable. Columns (2) encapsulated in concrete, no issues w/columns, considered bound by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 100 Exht: 100 Compartment Width (ft): 22 Vent

Description:

Compartment Length (ft): 14 Compartment Height (ft): 24 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature @ 180 minutes (F): 1012.05 Room Sketch:

M-663-00017A, Revision W03 Page G3D-6 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1325-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-7 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1326-2000 Building: Auxiliary Fire Area: A-14

==

Description:==

Aux Feedwater Pump Rm A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 N/A Member Type: Beam N/A Member Size: 24 X 76 N/A Comments: Column encapsulated in concrete, no issues w/column, considered bounded by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 100 Exht: 100 Compartment Width (ft): 22 Vent

Description:

Compartment Length (ft): 12.25 Compartment Height (ft): 24 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature @ 180 minutes (F): 1072.29 Room Sketch:

M-663-00017A, Revision W03 Page G3D-8 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1326-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-9 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1331-2000 Building: Auxiliary Fire Area: A-15

==

Description:==

Aux Feedwater Pump Rm C Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 C-1S1001 Member Type: Column Beam Member Size: 14 X 184 18 X 60 Comments: Additional attachments in close proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 1400 Exht: 1400 Compartment Width (ft): 22.5 Vent

Description:

Compartment Length (ft): 27.75 Compartment Height (ft): 24 Initial Room Temp. (F): 115 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 245.29 Hot Gas Layer Temperature @ 180 minutes (F): 764.51 Room Sketch:

M-663-00017A, Revision W03 Page G3D-10 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1331-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-11 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1331-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G3D-12 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1501-2047 Building: Auxiliary Fire Area: A-21

==

Description:==

Control Rm A/C & Filtration Units B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S1621 C-0S1002 Member Type: Beam Column Member Size: 18 X 45 14 X 193 Comments: Orientation of one tube causes 40 Orientation of one tube causes 40 square inches of unprotected steel. square inches of unprotected steel.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 400 Exht: 0 Compartment Width (ft): 53.5 Vent

Description:

Compartment Length (ft): 37.5 Compartment Height (ft): 25.25 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 267.09 Hot Gas Layer Temperature @ 180 minutes (F): 487.20 Room Sketch:

M-663-00017A, Revision W03 Page G3D-13 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1501-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-14 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1501-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G3D-15 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1512-2047 Building: Auxiliary Fire Area: A-22

==

Description:==

Control Rm A/C & Filtration Units A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S1621 C-0S1002 Member Type: Beam Column Member Size: 27 X 84 14 X 184 Comments: Additional attachments in close proximity orientation of 1 ea. 4" tube causes 40 SQ IN.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 400 Exht: 0 Compartment Width (ft): 53.5 Vent

Description:

Compartment Length (ft): 40 Compartment Height (ft): 25.25 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 264.44 Hot Gas Layer Temperature @ 180 minutes (F): 474.87 Room Sketch:

M-663-00017A, Revision W03 Page G3D-16 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1512-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-17 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1512-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G3D-18 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1323-2000 Building: Auxiliary Fire Area: A-24

==

Description:==

Pipe Penetration Rm A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S1441 C-1S1001 Member Type: Beam Column Member Size: 33 X 118 14 X 314 Comments: Additional attachments in close proximity (2 Items 43 sq. in.).

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 200 Plus Transfer Compartment Width (ft): 49 Vent

Description:

Grille = 250 Compartment Length (ft): 33.5 Compartment Height (ft): 25 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 307.82 Hot Gas Layer Temperature @ 180 minutes (F): 563.90 Room Sketch:

M-663-00017A, Revision W03 Page G3D-19 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1323-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-20 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1323-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G3D-21 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1322-2000 Building: Auxiliary Fire Area: A-25

==

Description:==

Pipe Penetration Rm B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S1431 C-1S1001 Member Type: Beam Column Member Size: 33 X 118 14 X 264 Comments: Additional attachments in close proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 200 Plus Transfer Compartment Width (ft): 49 Vent

Description:

Grille = 250 Compartment Length (ft): 33.5 Compartment Height (ft): 25 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 307.82 Hot Gas Layer Temperature @ 180 minutes (F): 563.90 Room Sketch:

M-663-00017A, Revision W03 Page G3D-22 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1322-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-23 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1322-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G3D-24 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 1405-2026 Building: Auxiliary Fire Area: A-26

==

Description:==

Chemical Storage Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1511 N/A Member Type: Beam N/A Member Size: 21 X 62 N/A Comments: Columns embedded in concrete, no exposed surfaces.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 900, Open Grille Compartment Width (ft): 16.5 Vent

Description:

Exht: 900 Temp. not in USAR Table 3.11, used adjacent Compartment Length (ft): 36.75 room temperatures Compartment Height (ft): 20 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 275.16 Hot Gas Layer Temperature @ 180 minutes (F): 844.46 Room Sketch:

M-663-00017A, Revision W03 Page G3D-25 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 1405-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-26 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 3101-1974 Building: Control Fire Area: C-01

==

Description:==

Pipe Space & Tank Area and Duct Chase on all levels of the Co Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3211 N/A Member Type: Beam Column Member Size: 12 X 27 N/R Comments: Additional attachments in close Columns have no thermal shorts except proximity. Unistrut.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 550 Exht: 700 Compartment Width (ft): 65.5 Vent

Description:

Compartment Length (ft): 99 Compartment Height (ft): 9 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 36 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 210.80 Hot Gas Layer Temperature @ 180 minutes (F): 330.99 Room Sketch:

M-663-00017A, Revision W03 Page G3D-27 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 3101-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-28 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 0NAC-1984 Building: Control Fire Area: C-05

==

Description:==

Area Above Suspended Ceiling Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3311 N/A Member Type: Beam Column Member Size: 27 X 94 N/R Comments: Additional 3" angle and 2-4" I in close Columns below drop ceiling are incased proximity. within CMU wall, and above drop ceiling there are no attachments.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 4925 Exht: 4350 Compartment Width (ft): 65.5 Vent

Description:

Temp not in USAR Table 3.11, temp used is Compartment Length (ft): 54.25 based on other similar rooms within the Control Compartment Height (ft): 15 Building Initial Room Temp. (F): 90 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 30 Compartment Starting Temp. for Closed Room No Vent. FDT: 200.83 Hot Gas Layer Temperature @ 180 minutes (F): 362.91 Room Sketch:

M-663-00017A, Revision W03 Page G3D-29 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 0NAC-1984 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-30 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 0SAC-1984 Building: Control Fire Area: C-06

==

Description:==

Area Above Suspended Ceiling Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3311 N/A Member Type: Beam Column Member Size: 27 X 94 N/R Comments: None. Columns below drop ceiling are incased within CMU wall, and above drop ceiling there are no attachments.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 3275 Exht: 2950 Compartment Width (ft): 65.5 Vent

Description:

Temp not in USAR Table 3.11, temp used is Compartment Length (ft): 31.25 based on other similar rooms within the Control Compartment Height (ft): 15 Building.

Initial Room Temp. (F): 90 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 10 Compartment Starting Temp. for Closed Room No Vent. FDT: 212.74 Hot Gas Layer Temperature @ 180 minutes (F): 477.18 Room Sketch:

M-663-00017A, Revision W03 Page G3D-31 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 0SAC-1984 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-32 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 3415-2016 Building: Control Fire Area: C-13

==

Description:==

Access Ctrl & Elec Equip A/C Units No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 750 Exht: 750 Compartment Width (ft): 13 Vent

Description:

Compartment Length (ft): 53.5 Compartment Height (ft): 15.25 Initial Room Temp. (F): 90 Barrier Type: Block Barrier Thickness (in): 8 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature @ 180 minutes (F): 1062.38 Room Sketch:

M-663-00017A, Revision W03 Page G3D-33 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 3415-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-34 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 3416-2016 Building: Control Fire Area: C-14

==

Description:==

Access Ctrl & Elec Equip A/C Units No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: Additional attachments in close No columns.

proximity (3" x 1/4" angles).

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 750 Exht: 750 Compartment Width (ft): 13 Vent

Description:

Compartment Length (ft): 63.5 Compartment Height (ft): 15.25 Initial Room Temp. (F): 90 Barrier Type: Block Barrier Thickness (in): 8 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature @ 180 minutes (F): 939.95 Room Sketch:

M-663-00017A, Revision W03 Page G3D-35 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 3416-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-36 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 3501-2032 Building: Control Fire Area: C-21

==

Description:==

Lower Cable Spreading Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3611 C-0S3001 Member Type: Beam Column Member Size: 30 X 108 14 X 342 Comments: Additional attachment in close proximity (6" X 5/16 I).

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 500 Exht: 500 Compartment Width (ft): 65.5 Vent

Description:

Compartment Length (ft): 99 Compartment Height (ft): 14.75 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 219.78 Hot Gas Layer Temperature @ 180 minutes (F): 326.12 Room Sketch:

M-663-00017A, Revision W03 Page G3D-37 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 3501-2032 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-38 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 3501-2032 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G3D-39 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 3801-2073 Building: Control Fire Area: C-22

==

Description:==

Upper Cable Spreading Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S3811 N/R Member Type: Beam Column Member Size: 33 X 118 N/R Comments: Orientation cause large area of Unistrut only attached to columns.

unprotected steel. Columns only have Unistrut, acceptable.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 3450 Exht: 3020 Compartment Width (ft): 65.5 Vent

Description:

Compartment Length (ft): 99 Compartment Height (ft): 11.75 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 15 Compartment Starting Temp. for Closed Room No Vent. FDT: 200.00 Hot Gas Layer Temperature @ 180 minutes (F): 308.20 Room Sketch:

M-663-00017A, Revision W03 Page G3D-40 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 3801-2073 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-41 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 6104-2000 Building: Fuel Fire Area: F-02

==

Description:==

Fuel Pool Cooling Heat Exch Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C0S6211 N/A Member Type: Beam N/A Member Size: 24 X 55 N/A Comments: Additional thermal shorts in close No columns.

proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 1300 Exht: 1300 Compartment Width (ft): 15.25 Vent

Description:

Open Grille Compartment Length (ft): 80 Compartment Height (ft): 25 Initial Room Temp. (F): 122 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 238.05 Hot Gas Layer Temperature @ 180 minutes (F): 501.86 Room Sketch:

M-663-00017A, Revision W03 Page G3D-42 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 6104-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-43 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 6105-2000 Building: Fuel Fire Area: F-03

==

Description:==

Fuel Pool Cooling Heat Exch Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C0S6211 N/A Member Type: Beam N/A Member Size: 24 X 55 N/A Comments: 6" pipe. No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 1300 Exht: 1300 Compartment Width (ft): 15.25 Vent

Description:

Open Grille Compartment Length (ft): 80 Compartment Height (ft): 25 Initial Room Temp. (F): 122 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 238.05 Hot Gas Layer Temperature @ 180 minutes (F): 501.86 Room Sketch:

M-663-00017A, Revision W03 Page G3D-44 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 6105-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-45 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 6202-2026 Building: Fuel Fire Area: F-05

==

Description:==

Electrical Equipment Room Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C1S6311 N/A Member Type: Beam N/A Member Size: 36 X 135 N/A Comments: Additional attachments in close No columns.

proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 10800 Exht: 10800 Compartment Width (ft): 30.5 Vent

Description:

Open Grille Compartment Length (ft): 39 Compartment Height (ft): 20.5 Initial Room Temp. (F): 110 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 10 Compartment Starting Temp. for Closed Room No Vent. FDT: 200.76 Hot Gas Layer Temperature @ 180 minutes (F): 556.31 Room Sketch:

M-663-00017A, Revision W03 Page G3D-46 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 6202-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-47 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 6304-2047 Building: Fuel Fire Area: F-06

==

Description:==

Exhaust Filter Absorber Room A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C1S6411 N/A Member Type: Beam N/A Member Size: 16 X 36 N/A Comments: No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 300 Exht: 300 Compartment Width (ft): 13.5 Vent

Description:

Open Grille Compartment Length (ft): 49.5 Compartment Height (ft): 16.5 Initial Room Temp. (F): 110 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 363.95 Hot Gas Layer Temperature @ 180 minutes (F): 921.91 Room Sketch:

M-663-00017A, Revision W03 Page G3D-48 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 6304-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G3D-49 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation: 6303-2047 Building: Fuel Fire Area: F-07

==

Description:==

Exhaust Filter Absorber Room B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C1S6411 N/A Member Type: Beam N/A Member Size: 16 X 36 N/A Comments: No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 300 Exht: 300 Compartment Width (ft): 13.5 Vent

Description:

Open Grille Compartment Length (ft): 49.5 Compartment Height (ft): 16.5 Initial Room Temp. (F): 110 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 363.95 Hot Gas Layer Temperature @ 180 minutes (F): 921.91 Room Sketch:

M-663-00017A, Revision W03 Page G3D-50 of G3D-50 Structural Steel Fireproofing Data Appendix G3D 6303-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

Page 1 M-663-00017A Attachment G4 Fire Protection Evaluation For Structural Steel Fireproofing With Unprotected Thermal Shorts in Closed Rooms with a Credible Fire and No Ventilation or Forced Ventilation Rev. No. Prepared By Date Reviewed By Date W03 6/20/07 06/20/07

M-663-00017A Page 2 of 12 Attachment G4 Revision W03 Table of Contents Revision Log .................................................................................................................................3 1.0 Purpose.............................................................................................................................4 2.0 Scope ................................................................................................................................4 3.0 References........................................................................................................................4 4.0 Assumptions......................................................................................................................5 5.0 Assessment of Condition to Design Requirements ...........................................................5 6.0 Methodology......................................................................................................................7 7.0 Evaluation .........................................................................................................................8 8.0 Conclusions.....................................................................................................................12 Appendix G4A, NUREG-1805 FDT Example -

Closed Room No Ventilation .. (2 Total Pages)

Appendix G4B, NUREG-1805 FDT Example -

Closed Room Forced Ventilation . (4 Total Pages)

Appendix G4C, Thermal Short and Room Data Sheets Closed Room No Ventilation (13 Total Pages)

Appendix G4D, Thermal Short and Room Data Sheets Closed Room Forced Ventilation (19 Total Pages)

M-663-00017A Page 3 of 12 Attachment G4 Revision W03 Revision Log Revision Reason for Revision W03 Original Issue

M-663-00017A Page 4 of 12 Attachment G4 Revision W03 1.0 Purpose 1.1 The purpose of this document is to evaluate the acceptability of protected structural steel with unprotected steel attachments (thermal shorts) that are welded to the building steel. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10 and Regulatory Guide 1.189.

2.0 Scope 2.1 This evaluation is applicable to the Rooms identified in Table II.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.3 NRC Inspection Manual 0609, Appendix F, Fire Protection Significant Determination Process, dated 02/28/05.

3.4 NUREG/CR-6850, Fire PRA Methodology for Nuclear Power Facilities, published 09/2005 3.5 NUREG-1805, Fire Dynamics Tools (FDTs) Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program, published 12/2004 3.6 NUREG-1824, Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications 3.7 Regulatory Guide 1.189, Fire Protection For Operating Nuclear Power Plants, April 2001 3.8 ASTM E-119, Standard Test Methods for Fire Tests of Building Construction and Materials 3.9 UL N-711, (A-126-00001), Fire Test Report Of Loaded Restrained Beams Protected By Cementitious Mixture, Dated August 11, 1976 3.10 UL N-712, (A-126-00002), Fire Test Report Of Loaded Restrained Beams Protected By Cementitious Mixture, Dated May 13, 1977 3.11 A-126, Technical Specification For Cementitious Fireproofing Of Structural Steel For The Standardized Nuclear Unit Power Plant Unit (SNUPPS) 3.12 PIR 2002-2287, Structural Steel Fireproofing With Unprotected Attachments 3.13 FP-M-012, Rev 0, Structural Steel Fireproofing Thermal Shorts and Omissions Evaluation

M-663-00017A Page 5 of 12 Attachment G4 Revision W03 3.14 CNT-MC-600, Rev. 2, Fireproofing of Structural Steel 3.15 Drawing A-1801, Rev. 10, Architectural Fire Delineation Floor Plan EL 1974-0 3.16 Updated Safety Analysis Report (USAR) Section 9.5.1.2.2.3.c, Rev. 15 and Table 9.5A-1 Sheet 27, Rev. 4 3.17 AN-94-041, WCGS IPEEE Project IPEEE Fire Ignition Frequencies 4.0 Assumptions 4.1 It is assumed that fireproofing material used to protect building steel is applied to a thickness as required by CNT-MC-600. This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial fireproofing installation activities and subsequent inspections during ongoing plant repairs witnessed by Fire Protection personnel.

5.0 Assessment of Condition to Design Requirements 5.1 Requirements USAR Section 9.5.1.2.2.3.c , identifies that the notes contained on Figure 9.5.1-2

[Drawing A-1801] define the structural steel fireproofing requirements. The structural steel of all of the ceilings of the fire areas is fireproofed with 3-hour protection with the exception that no fireproofing is provided on the underside of the fuel building roof.

USAR Table 9.5A-1 Sheet 27 (Rev. 4), that structural steel supporting the Control and Auxiliary Building roofs is protected with [3-hour] rated fireproofing.

Table I identifies the ASTM E-119 temperature limitations for structural steel protected with fireproofing.

TABLE I ASTM E-119 Temperature Limitations for 3-Hour Fire Exposure Structural Member Maximum Single Point Maximum Average Type Temperature (qF) Temperature (qF)

Beam 1300q(F) 1100q(F)

Column 1200q(F) 1000q(F) 5.2 Assessment At Wolf Creek, fireproofing material is generally applied over exposed surfaces of structural members with the exception of thermal shorts and intervening items.

Underwriters Laboratories (UL) has tested several different size members utilizing both Albi Duraspray and Monokote Z-146 coatings to 3-hour ASTM E-119 fire exposures. The testing for beams and columns, utilized W8 x 28 steel shapes incorporating two protection methods; contour and boxed. However, testing of both techniques did not incorporate thermal short attachments.

Therefore, the affect of heat flux into plant structural steel with unprotected

M-663-00017A Page 6 of 12 Attachment G4 Revision W03 thermal shorts is not directly bounded by fire testing. FP-M-012 revealed that unprotected thermal shorts, larger than Unistrut, contribute to single point temperatures that in some cases exceed the ASTM E-119 acceptance criteria, assuming a 3-hour fire exposure. Typically, average temperatures satisfied the ASTM E-119 acceptance criteria.

Refer to Table II for the specific rooms that are addressed by this evaluation.

TABLE II Thermal Shorts in Closed Rooms with Credible Fire and No Ventilation or Forced Ventilation Fire Room Building Elev.

Description:

Table III Table III Area Group ASTM E-119 Rating A-3 1407 Auxiliary 2026-0 Boric Acid Batching Tank 1 Beam: About 2-Hours Area See Note 3 A-29 1304 Auxiliary 2013-6 Aux Feedwater Pipe 1&4 Beam: 1.8 Hours, Attachment size is Chase smaller than analyzed, See Note 2 1327 Auxiliary 2000-0 Feedwater Pump Valve 1&4 Beam: 1.8 Hours, Attachment size is Compartment No. 2 smaller than analyzed, See Note 2 A-30 1305 Auxiliary 2013-6 Aux Feedwater Pipe 1 Beam: About 2-Hours Chase 3 Column: About 1-Hour, Attachment size is smaller than analyzed 1328 Auxiliary 2000-0 Feedwater Pump Valve 1 Beam: About 2-Hours Compartment No. 3 A-33 1329 Auxiliary 2000-0 Vestibule 1 Beam: About 2-Hours C-15 3403 Control 2016-0 Non-Vital Swgr & Xfmr Rm 1 Beam: About 2-Hours No. 1 See Note 3 Below 3404 Control 2016-0 Switchboard Rm No. 4 1 Beam: About 2-Hours, See Note 3 3405 Control 2016-0 Battery Rm No. 4 1 Beam: About 2-Hours, See Note 3 2 Column: Nearly 3-Hours, See Note 2 3410 Control 2016-0 Switchboard Rm No. 2 1 Beam: About 2-Hours See Note 3 3411 Control 2016-0 Battery Rm No. 2 1 Beam: About 2-Hours C-16 3407 Control 2016-0 Battery Rm No. 1 1 Beam: About 2-Hours 3408 Control 2016-0 Switchboard Rm No. 1 1 Beam: About 2-Hours 2 Column: Nearly 3-Hours, See Note 2 3409 Control 2016-0 Non-Vital Swgr & Xfmr Rm 1&4 Beam: 1.8 Hours, Attachment size is No. 2 smaller than analyzed, See Notes 2 & 3 3413 Control 2016-0 Battery Rm No. 3 1 Beam: About 2-Hours 3414 Control 2016-0 Switchboard Rm No. 3 1 Beam: About 2-Hours

M-663-00017A Page 7 of 12 Attachment G4 Revision W03 Table II Notes:

1. Category 1 (H member) as been conservatively assigned to this beam attachment configuration due to the lack of analysis of a W shape configuration welded to the bottom beam flange. It should be noted that W shapes thermally perform significantly better than H shapes due to the larger exposed area of the H shape.
2. Hot spot forms in Web area around thermal short. Structural considerations could show this element performs its intended design function for three-hours. This Note is a direct excerpt from Calculation FP-M-012.
3. Refer to Attachment G5 for the Heat Affected Zone (HAZ) review where steel is an integral element of the fire barrier assembly.

6.0 Methodology As discussed in Section 12.2.2 of M-663-00017A, Section 4.2.2 of Regulatory Guide 1.189 identifies that structural steel is not required to be protected to the fire resistance rating of the barrier [typically 3-hours], provided analysis demonstrates that the steel temperature reached during fire exposure does not result in structural failure of the steel.

Considering the results of FP-M-012, where an ASTM E-119 3-hour fire was modeled to assess thermal insult presented by unprotected attachments connected to protected steel, the Reg. Guide 1.189 approach allowance is utilized to address impact of unprotected thermal short attachments larger than Unistrut.

Walkdowns were conducted on a room-by-room basis utilizing structural steel drawings and a best effort visual inspection to determine the worse case thermal short configuration for columns, beams and where structural steel serves as an Appendix R fire boundary. For the purpose of this evaluation, all unprotected thermal shorts greater than Unistrut were reviewed and considered relevant to determine worse case scenario.

FP-M-012 demonstrated that thermal short attachments equivalent to Unistrut did not present a thermal conductive path that would challenge structural steel integrity, assuming an ASTM E-119 fire exposure.

See section 12.2.3 of M-663-00017A for further discussion regarding the overall fireproofing assessment methodology utilized in the identification process for selecting the worse case thermal short configuration.

Each worse case thermal short configuration was then compared to the configurations identified in Table III, from FP-M-012, which were modeled assuming an ASTM E-119 3-hour fire exposure. The fire resistance rating of the Table III configuration that provided the closest match to the worse case configuration was utilized to infer an approximate fire resistance rating, again assuming an ASTM E-119 3-hour fire exposure.

This comparison information is captured in Table II. In all cases the structural steel for the rooms satisfied at least a 1-hour rating, and in several cases nearly a 3-hour rating.

Additionally, many unprotected attachment members were smaller than that analyzed in FP-M-012, and therefore the beam or column being evaluated is expected to perform better than that indicated.

In effort to assess structural steel performance considering representative plant configurations and hazards, the NUREG-1805 Fire Dynamics Tools (FDT) were utilized to determine the maximum hot gas layer temperature anticipated within the rooms

M-663-00017A Page 8 of 12 Attachment G4 Revision W03 considering simple fire heat release rates provided in Appendix F of NRC Inspection Manual 0609.

TABLE III Thermal Short Configurations Analyzed in FP-M-012 Thermal Short Summary Of Thermal ASTM E119 Fire Findings Configuration Short Configuration Resistance Rating 1 Typical H-Shape thermal About two-hours Large segment of flange short on a moderate size exceeds peak temperature beam criterion.

2 Multiple W-Shape thermal Nearly three- Hot spot formation on the web.

shorts on a large size hours Structural considerations could column show this element performs function for three-hours.

3 Large H Shape thermal short About one-hour Large segment of entire cross-on a large size column section exceeds peak temperature criterion.

4 Typical W-Shape thermal 1.8-hours Hot spot forms in web area short on a moderate size around thermal short, Structural beam considerations could show this element performs function for three-hours.

5 Small thermal short Over three-hours Provides indications of Unistrut (Unistrut) on a moderate impact on temperature field in size beam structural steel. These thermal shorts have little impact on primary structural element steel temperature.

6 Small thermal short Over three-hours Provides indications of Unistrut (Unistrut) on a moderate impact on temperature field in size beam. Thermal structural steel. This is the Insulation on beam within most severe type of Unistrut the Unistrut is missing. thermal short.

7.0 Evaluation Each Room identified in Table II was reviewed and evaluated to determine if building structural members with unprotected steel attachments larger than Unistrut would affect the steel integrity in the event of fire. It was determined by utilizing NUREG-1805 Fire Dynamics Tools that these rooms would not develop a hot gas layer that would influence the existing building steel, and existing building steel protection configurations are acceptable to maintain building integrity.

Each Table II room is either a closed room with no ventilation or a closed room with forced ventilation. A closed room with no ventilation is consistent with the application of NUREG-1805 FDT 02.3_temperature_cc_rev1.xls (Version 1805.1), as it addresses modeling closed compartments with natural ventilation associated only with compartment leakage. This is an acceptable approach, as rooms of concern will have limited natural ventilation leakage occurring predominantly around allowed door gaps.

Therefore, this FDT was utilized to assess room hot gas layer temperature development

M-663-00017A Page 9 of 12 Attachment G4 Revision W03 for closed rooms containing no ventilation. An example of the FDT is provided in Appendix G4A.

Where rooms were closed, with the exception of forced air ventilation openings, it was recognized that these rooms would effectively become a closed room once HVAC fire damper closure was achieved. HVAC fire dampers are closed by one of the following means:

x Automatically close by the fire alarm system, following smoke detection activation, for dampers provided with an electro-thermal link (ETL).

x Close by the melting of a fusible link with a temperature rating of 165 qF.

Rooms with ETL controlled fire dampers were considered closed rooms with no forced ventilation, since room forced ventilation flow would be eliminated by fire alarm system activation, which would occur early in the fire development stage. Therefore, closed rooms with forced ventilation controlled by ETL fire dampers also utilize NUREG-1805 FDT 02.3_temperature_cc_rev1.xls (Version 1805.1).

Where fusible link fire dampers provide room ventilation isolation, it was recognized that forced ventilation would continue for the room until the compartment temperature reached the activation point of the fire damper fusible link. Therefore, each of these rooms was first treated as compartment with forced ventilation until room hot gas layer temperature exceeded 200qF. NUREG-1805 FDT 02.2_Temperature_FV.xls (Version 1805.0), was utilized for this application. An example of the FDT is provided in Appendix G4B. At the point that the hot gas layer temperature exceeded 200 qF, effectively creating a closed room with no ventilation following fire damper closure, relevant data from the Closed Room - Forced Ventilation FDT was extracted and utilized as input within the previously discussed FDT, for a closed room with no forced ventilation. When the duration for reaching 200°F was less than 1 minute, 200°F was utilized as the input temperature for the Closed Room - Forced Ventilation FDT.

Data collection necessary for FDT input is provided in the individual room data sheets documented in Appendices G4C and G4D. Appendix G4C contains data for closed rooms with no ventilation, while G4D is for closed rooms with forced ventilation. Input information necessary for each FDT utilized is as follows:

M-663-00017A Page 10 of 12 Attachment G4 Revision W03 Closed Room - No Ventilation NUREG -1805 FDT 02.3_temperature_cc_rev1.xls (Version 1805.1) x Compartment width (ft) x Compartment length (ft) x Compartment height (ft) x Barrier type (concrete or concrete block) x Barrier thickness (in) x Ambient air temperature (qF) x Fire Heat Release Rate (kW) x Time when Closed Room - Forced Ventilation FDT exceeds 200qF (min)

  • x Compartment starting temperature for Closed Room - No Ventilation FDT (qF) *
  • Data input from Closed Room - Forced Ventilation FDT Closed Room - Forced Ventilation NUREG-1805 FDT 02.2_Temperature_FV.xls (Version 1805.0) x Compartment width (ft) x Compartment length (ft) x Compartment height (ft) x Barrier type (concrete or concrete block) x Barrier thickness (in) x Forced Ventilation Rate (cfm) x Ambient air temperature (qF) x Fire Heat Release Rate (kW)

Initially, a fire with a constant 650 kW heat release rate (HRR) was utilized for the Table II rooms. This HRR was chosen considering the guidance of Appendix F to NRC Inspection Manual 0609. Table IV, extracted from the Inspection Manual, reveals that a 650 kW HRR is based on a large electrical fire that reflects a high confidence limit (98th percentile) fire severity. This fire severity envelops large electrical fires, transient combustible fires, and 90% of very large fire sources. This HRR exceeds the credible fire severity for each room of concern. It was initially chosen in effort to eliminate the need for a detailed quantitative review of room contents. When utilizing a 650 kW HRR for each of the Table II rooms, the gas layer modeled did develop temperatures that exceeded the Table I maximum average exposure temperatures limitations for beams and/or columns.

To further evaluate and assess the Table II rooms, a room by room walk down along with a comparison to the IEEE ignition source frequency calculation AN-94-041 was conducted in effort to reasonably develop a credible scenario heat release rate, considering room combustible loading, equipment, and the associated fire hazard.

NRC Inspection Manual 0609, Appendix F was utilized to aid in the process of mapping the general fire scenario characterization to a for each room evaluated. Table IV was

M-663-00017A Page 11 of 12 Attachment G4 Revision W03 used to bin predefined fire characteristics for each room considering AN-94-041 and walkdown data. Each room was binned to either a 200 kW or 70 kW HRR fire based on an assessment of room contents in relation to Table IV information. Specifically, a 200 kW fire envelops small electrical, engine/heater, and transient combustible fires, while a 70 kW fire envelopes 90% of both engine/heater and transient combustible fires. The credible heat release rates determined for each room are identified in the Appendix G4C and G4D room data sheets.

In all cases, specific room area input into the FDT using a credible HRR yielded hot gas layer results at a 180-minute duration that were less than the ASTM E-119 average temperature limitations identified in Table I. Refer, to the Appendix G4C and G4D room data sheets for specific results. During ASTM E-119 fire testing, temperatures are recorded on the steel surface underneath the fireproofing protective coating in effort to assess fireproofing effectiveness when subjected to approximate 1925 qF fire exposure for a 3-hour duration. Considering that the FDT calculated room hot gas layer temperature was less than the Table I ASTM E-119 average temperature limitations, it is reasonable to conclude that unprotected thermal short attachments will not present a thermal failure mode to the structural steel, since the room will not attain temperatures during the postulated fire event that would challenge steel structural integrity.

TABLE IV Generic Fire Bins1 Mapping of General Fire Scenario Characterization Type Bins to Fire Intensity Characteristics Generic Fire Type Bins with Simple Predefined Characteristics Fire Size Bins Small Large Indoor Oil- Very Large Engines and Solid and Electrical Electrical Filled Fire Heaters Transient Fire Fire Transformers Sources Combustibles 70 kW 75th Percentile 75th 75th Percentile Fire Percentile Fire Fire 200 kW 98th Percentile 75th 98th 98th Percentile Fire Percentile Percentile Fire Fire Fire 650 kW 98th 75th Percentile 75th Percentile Fire Percentile Fire Fire 2 MW 98th Percentile Fire th 10 MW 98 Percentile Fire Table IV Note:

1. Information extracted from NRC Inspection Manual 0609, Appendix F, Table 2.3.1.

M-663-00017A Page 12 of 12 Attachment G4 Revision W03 8.0 Post Fire Safe Shutdown Impact There is no impact to post-fire safe shutdown (PFSSD) capability, as the evaluation demonstrates that postulated fire event room temperate will not result in detrimental impact to structural steel integrity.

Refer to Attachment G5 for the Heat Affected Zone (HAZ) review where steel is an integral element of the fire barrier assembly.

9.0 Conclusions This evaluation demonstrates that unprotected thermal shorts, attached to structural steel within the Table II rooms, does not result in a detrimental impact to structural steel integrity. Utilization of NUREG-1805 FDTs revealed that hot gas layer temperatures for each of the Table II rooms did not exceed the ASTM E-119 maximum average exposure temperature for beam or column limitation in the associated room. Therefore, the protected structural steel configurations within these rooms are acceptable for the intended service, and will not degrade the affected fire barrier or structural integrity of the building steel, or affect redundant PFSSD capability.

Based on the above discussion, it is reasonable to conclude that the existing fireproofing on the structural steel with unprotected attachments will satisfy regulatory expectations and commitments as well as WCNOC Fire Protection Program requirements, to prevent building steel failure as a result of fire exposure.

M-663-00017A, Revision W03 Page G4A-1 of G4A-2 Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Appendix G4A Plant Systems Branch Fire Protection Engineering and Special Projects Section CHAPTER 2. PREDICTING HOT GAS LAYER TEMPERATURE IN A ROOM FIRE WITH DOOR CLOSED Version 1805.1 The following calculations estimate the hot gas layer temperature in enclosure fire with door closed.

This method assume that compartment has sufficient leaks to prevent pressure buildup, but the leakages are ignored.

Parameters in YELLOW CELLS are Entered by the User.

Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Material Selected.

All subsequent output values are calculated by the spreadsheet and based on values specified in the input parameters. This spreadsheet is protected and secure to avoid errors due to a wrong entry in a cell(s).

The chapter in the NUREG should be read before an analysis is made.

INPUT PARAMETERS COMPARTMENT INFORMATION Compartment Width (wc) 15.00 ft 4.57 m Compartment Length (lc) 15.00 ft 4.57 m Compartment Height (hc) 15.00 ft 4.57 m Interior Lining Thickness (G) 12.00 in 0.3048 m Ambient Air Temperature (Ta) 77.00 °F 25.00 °C 298.00 K AMBIENT CONDITIONS Specific Heat of Air (cp) 1.00 kJ/kg-K Ambient Air Density (Ua) 1.18 kg/m3 3

Volume of the Compartment (V) 3375.00 ft3 95.57 m Mass of the Gas in the Compartment (m = V x Ua) 113.21 kg Note: Air density will automatically correct with Ambient Air Temperature (Ta) Input THERMAL PROPERTIES OF COMPARTMENT ENCLOSING SURFACES Interior Lining Thermal Inertia (kUc) 2.9 (kW/m 2-K)2-sec Interior Lining Thermal Conductivity (k) 0.0016 kW/m-K Interior Lining Specific Heat (c) 0.75 kJ/kg-K Interior Lining Density (U) 2400 kg/m3 THERMAL PROPERTIES FOR COMMON INTERIOR LINING MATERIALS kUc k c U Select Material Material (kW/m2-K)2-sec (kW/m-K) (kJ/kg-K) (kg/m3) Concrete Aluminum (pure) 500 0.206 0.895 2710 Scroll to desired material then Steel (0.5% Carbon) 197 0.054 0.465 7850 Click on selection Concrete 2.9 0.0016 0.75 2400 Brick 1.7 0.0008 0.8 2600 Glass, Plate 1.6 0.00076 0.8 2710 Brick/Concrete Block 1.2 0.00073 0.84 1900 Gypsum Board 0.18 0.00017 1.1 960 Plywood 0.16 0.00012 2.5 540 Fiber Insulation Board 0.16 0.00053 1.25 240 Chipboard 0.15 0.00015 1.25 800 Aerated Concrete 0.12 0.00026 0.96 500 Plasterboard 0.12 0.00016 0.84 950 Calcium Silicate Board 0.098 0.00013 1.12 700 Alumina Silicate Block 0.036 0.00014 1.0 260 Glass Fiber Insulation 0.0018 0.000037 0.8 60 Expanded Polystyrene 0.001 0.000034 1.5 20 User Specified Value Enter Value Enter Value Enter Value Enter Value

Reference:

Klote, J., J. Milke, Principles of Smoke Management , 2002, Page 270.

FIRE SPECIFICATIONS Fire Heat Release Rate (Q) 500.00 kW Time after Ignition 120 sec Calculate METHOD OF BEYLER nd

Reference:

SFPE Handbook of Fire Protection Engineering, 3 Edition, 2002, Page 3-180.

'Tg = (2 K2 / K12) (K1 ¥t-1+e(- K1 ¥t))

Where 'Tg = Tg - Ta = upper layer gas temperature rise above ambient (K)

Ta = ambient air temperature (K)

Parameter K1 = 2 (0.4¥kUc) AT / mcp Parameter K2 = Q / m cp kUc = interior construction thermal inertia (kW/m2-K)2-sec m = mass of gas in the compartment (kg) cp = specific heat of air (kJ/kg-K)

AT = total area of the compartment enclosing surface boundaries (m2)

Q = heat release rate of the fire (kW) t = exposure time (sec)

Calculation for Parameter K1 K1 = 2 (0.4¥kUc) AT / mc Where kUc = interior construction thermal inertia (kW/m2-K)2-sec AT = total area of the compartment enclosing surface boundaries (m2) m = mass of gas in the compartment (kg)

Area of Compartment Enclosing Surface Boundaries AT = [2(wc x lc) + 2(hc x wc) + 2(hc x lc)]

Where AT = total area of the compartment enclosing surface boundaries (m2) wc = compartment width (m) 1

M-663-00017A, Revision W03 Page G4A-2 of G4A-2 Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Appendix G4A Plant Systems Branch Fire Protection Engineering and Special Projects Section lc = compartment length (m) hc = compartment height (m) 2 AT = 125.42 m 2

K1 = 1.51 kW/m -K Calculation for Parameter K2 K2 = Q / m cp Where Q = heat release rate of the fire (kW) m = mass of gas in the compartment (kg) cp = specific heat of air (kJ/kg-K)

K2 = 4.42 Compartment Hot Gas Layer Temperature, Compartment Door Closed

'Tg = (2 K2 / K12) (K1 ¥t-1+e(- K1 ¥t))

'Tg = Tg - Ta = 60.23 Tg = 358.23 K Tg = 85.23 °C 185.42 °F Answer NOTE The above calculations are based on principles developed in the SFPE Handbook of Fire Protection Engineering, 3nd Edition, 2002.

Calculations are based on certain assumptions and have inherent limitations. The results of such calculation may or may not have reasonable predictive capabilities for a given situation, and should only be interpreted by an informed user.

Although each calculation in the spreadsheet has been verified with the results of hand calculation, there is no absolute guarantee of the accuracy of these calculations.

Any questions, comments, concerns, and suggestions, or to report an error(s) in the spreadsheet, please send an email to nxi@nrc.gov or mxs3@nrc.gov.

Prepared by: Date Organization Checked by: Date Organization Additional Information Revision Log Description of Revision Date 1805.0 Original issue with final text. January 2005 1805.1 Corrected calculation for Parameter K1. Added area of compartment enclosing surface September 2005 boundaries (AT) in Parameter K1.

2

M-663-00017A, Revision W03 Page G4B-1 of G4B-4 Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Appendix G4B Plant Systems Branch Fire Protection Engineering and Special Projects Section CHAPTER 2. PREDICTING HOT GAS LAYER TEMPERATURE IN A ROOM FIRE WITH FORCED VENTILATION COMPARTMENT WITH THERMALLY THICK/THIN BOUNDARIES Version 1805.0 The following calculations estimate the hot gas layer temperature and smoke layer height in enclosure fire.

Parameters in YELLOW CELLS are Entered by the User.

Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Material Selected.

All subsequent output values are calculated by the spreadsheet and based on values specified in the input parameters. This spreadsheet is protected and secure to avoid errors due to a wrong entry in a cell(s).

The chapter in the NUREG should be read before an analysis is made.

INPUT PARAMETERS COMPARTMENT INFORMATION Compartment Width (wc) 16.50 ft 5.03 m Compartment Length (lc) 36.50 ft 11.13 m Compartment Height (hc) 20.00 ft 6.10 m Interior Lining Thickness (G) 12.00 in 0.3048 m AMBIENT CONDITIONS Ambient Air Temperature (Ta) 104.00 °F 40.00 °C 313.00 K Specific Heat of Air (cp) 1.00 kJ/kg-K 3

Ambient Air Density (Ua) 1.13 kg/m THERMAL PROPERTIES OF COMPARTMENT ENCLOSING SURFACES Interior Lining Thermal Inertia (kUc) 2.9 (kW/m 2-K)2-sec Interior Lining Thermal Conductivity (k) 0.0016 kW/m-K Interior Lining Specific Heat (c) 0.75 kJ/kg-K Interior Lining Density (U) 2400 kg/m 3 Note: Air density will automatically correct with Ambient Air Temperature (Ta) Input THERMAL PROPERTIES FOR COMMON INTERIOR LINING MATERIALS kUc k c U Select Material Material (kW/m 2-K)2-sec (kW/m-K) (kJ/kg-K) (kg/m3) Concrete Aluminum (pure) 500 0.206 0.895 2710 Scroll to desired material then Steel (0.5% Carbon) 197 0.054 0.465 7850 Click on selection Concrete 2.9 0.0016 0.75 2400 Brick 1.7 0.0008 0.8 2600 Glass, Plate 1.6 0.00076 0.8 2710 Brick/Concrete Block 1.2 0.00073 0.84 1900 Gypsum Board 0.18 0.00017 1.1 960 Plywood 0.16 0.00012 2.5 540 Fiber Insulation Board 0.16 0.00053 1.25 240 Chipboard 0.15 0.00015 1.25 800 Aerated Concrete 0.12 0.00026 0.96 500 Plasterboard 0.12 0.00016 0.84 950 Calcium Silicate Board 0.098 0.00013 1.12 700 Alumina Silicate Block 0.036 0.00014 1 260 Glass Fiber Insulation 0.0018 0.000037 0.8 60 Expanded Polystyrene 0.001 0.000034 1.5 20 User Specified Value Enter Value Enter Value Enter Value Enter Value

Reference:

Klote, J., J. Milke, Principles of Smoke Management, 2002 Page 270.

COMPARTMENT MASS VENTILATION FLOW RATE 3

Forced Ventilation Flow Rate (m) 100.00 cfm 0.047 m /sec 0.053 kg/sec FIRE SPECIFICATIONS Fire Heat Release Rate (Q) 70.00 kW Calculate METHOD OF FOOTE, PAGNI, AND ALVARES (FPA)

Reference:

SFPE Handbook of Fire Protection Engineering , 3rd Edition, 2002, Page 3-177.

'Tg/Ta = 0.63(Q/mcpTa)0.72(hkAT/mcp)-0.36 Where 'Tg = Tg - Ta = upper layer gas temperature rise above ambient (K)

Ta = ambient air temperature (K)

Q = heat release rate of the fire (kW) m = compartment mass ventilation flow rate (kg/sec) cp = specific heat of air (kJ/kg-K) hk = convective heat transfer coefficient (kW/m2-K)

AT = total area of the compartment enclosing surface boundaries (m2)

Thermal Penetration Time Calculation tp = (Ucp/k) (G/2)2 Where tp = thermal penetration time (sec)

U = interior construction density (kg/m3) cp = interior construction heat capacity (kJ/kg-K) k = interior construction thermal conductivity (kW/m-K)

G = interior construction thickness (m) tp = 26128.98 sec Heat Transfer Coefficient Calculation 1

M-663-00017A, Revision W03 Page G4B-2 of G4B-4 Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Appendix G4B Plant Systems Branch Fire Protection Engineering and Special Projects Section hk = ¥(kUc/t) for t < tp or (k/G) for t > tp Where hk = heat transfer coefficient (kW/m2-K) kUc = interior construction thermal inertia (kW/m2-K)2-sec (a thermal property of material responsible for the rate of temperature rise) t = time after ignition (sec)

See table below for results Area of Compartment Enclosing Surface Boundaries AT = 2 (wc x lc) + 2 (hc x wc) + 2 (hc x lc)

Where AT = total area of the compartment enclosing surface boundaries (m2) wc = compartment width (m) lc = compartment length (m) hc = compartment height (m)

Av = area of ventilation opening (m2) 2 AT = 308.86 m Compartment Hot Gas Layer Temperature With Forced Ventilation

'Tg/Ta = 0.63(Q/mcpT0)0.72(hkAT/mcp)-0.36

'Tg = Tg - Ta Tg = 'Tg + Ta Results Time After Ignition (t) hk 'Tg/T0 'Tg Tg Tg Tg (min) (sec) (kW/m 2-K) (K) (K) (°C) (°F) 0 0 - - - 313.00 40.00 104.00 1 60 0.22 0.13 42.24 355.24 82.24 180.02 2 120 0.16 0.15 47.85 360.85 87.85 190.13 3 180 0.13 0.16 51.47 364.47 91.47 196.65 4 240 0.11 0.17 54.21 367.21 94.21 201.57 5 300 0.10 0.18 56.43 369.43 96.43 205.57 10 600 0.07 0.20 63.93 376.93 103.93 219.07 15 900 0.06 0.22 68.77 381.77 108.77 227.78 20 1200 0.05 0.23 72.42 385.42 112.42 234.36 25 1500 0.04 0.24 75.39 388.39 115.39 239.70 30 1800 0.04 0.25 77.90 390.90 117.90 244.23 35 2100 0.04 0.26 80.10 393.10 120.10 248.17 40 2400 0.03 0.26 82.05 395.05 122.05 251.68 45 2700 0.03 0.27 83.80 396.80 123.80 254.85 50 3000 0.03 0.27 85.41 398.41 125.41 257.73 55 3300 0.03 0.28 86.89 399.89 126.89 260.39 60 3600 0.03 0.28 88.26 401.26 128.26 262.86 Hot Gas Layer Temperature Forced Ventilation - FPA Method 300 Temperature (°F) 200 100 0

0 10 20 30 40 50 60 Time (min)

METHOD OF DEAL AND BEYLER

Reference:

SFPE Handbook of Fire Protection Engineering , 3rd Edition, 2002, Page 3-178.

Heat Transfer Coefficient Calculation hk = 0.4 ¥(kUc / t) for t < tp Where hk = heat transfer coefficient (kW/m2-K) kUc = interior construction thermal inertia (kW/m2-K)2-sec (a thermal property of material responsible for the rate of temperature rise)

G = thickness of interior lining (m) 2 hk = 0.088 kW/m -K Area of Compartment Enclosing Surface Boundaries AT = 2(w c x lc) + 2(h c x wc) + 2(hc x lc) 2 AT = 308.86 m Compartment Hot Gas Layer Temperature With Forced Ventilation

'Tg = Q / (m cp + hk AT)

Where 'Tg = Tg - Ta = upper layer gas temperature rise above ambient (K) 2

M-663-00017A, Revision W03 Page G4B-3 of G4B-4 Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Appendix G4B Plant Systems Branch Fire Protection Engineering and Special Projects Section Ta = ambient air temperature (K)

Q = heat release rate of the fire (kW) m = compartment mass ventilation flow rate (kg/sec) cp = specific heat of air (kJ/Kg-K) hk = convective heat transfer coefficient (kW/m2-K)

AT = total area of the compartment enclosing surface boundaries (m2)

Results Time After Ignition (t) hk 'Tg Tg Tg Tg (min) (sec) (kW/m 2-K) (K) (K) (°C) (°F) 0 0 - - 313.00 40.00 104.00 1 60 0.09 2.57 315.57 42.57 108.63 2 120 0.06 3.63 316.63 43.63 110.54 3 180 0.05 4.45 317.45 44.45 112.01 4 240 0.04 5.13 318.13 45.13 113.24 5 300 0.04 5.74 318.74 45.74 114.33 10 600 0.03 8.10 321.10 48.10 118.58 15 900 0.02 9.91 322.91 49.91 121.83 20 1200 0.02 11.43 324.43 51.43 124.57 25 1500 0.02 12.76 325.76 52.76 126.97 30 1800 0.02 13.97 326.97 53.97 129.14 35 2100 0.01 15.07 328.07 55.07 131.13 40 2400 0.01 16.10 329.10 56.10 132.98 45 2700 0.01 17.06 330.06 57.06 134.72 50 3000 0.01 17.97 330.97 57.97 136.35 55 3300 0.01 18.84 331.84 58.84 137.91 60 3600 0.01 19.66 332.66 59.66 139.40 Hot Gas Layer Temperature Forced Ventilation - Deal and Beyler Method 160 140 120 Temperature (°F) 100 80 60 40 20 0

0 10 20 30 40 50 60 Time (min)

Summary of Hot Gas Layer Temperature Forced Ventilation 300 FPA Method Deal and Beyler Method Temperature (°F) 200 100 0

0 10 20 30 40 50 60 Time (min)

NOTE The above calculations are based on principles developed in the SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002.

Calculations are based on certain assumptions and have inherent limitations. The results of such calculations may or may not have reasonable predictive capabilities for a given situation, and should only be interpreted by an informed user.

Although each calculation in the spreadsheet has been verified with the results of hand calculation, there is no absolute guarantee of the accuracy of these calculations.

Any questions, comments, concerns, and suggestions, or to report an error(s) in the spreadsheet, please send an email to nxi@nrc.gov or mxs3@nrc.gov. 3

M-663-00017A, Revision W03 Page G4B-4 of G4B-4 Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Appendix G4B Plant Systems Branch Fire Protection Engineering and Special Projects Section Prepared by: Date Organization Checked by: Date Organization Additional Information Revision Log Description of Revision Date 1805.0 Original issue with final text. January 2005 4

M-663-00017A, Revision W03 Page G4C-1 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation: 3403-2016 Building: Control Fire Area: C-15

==

Description:==

Non-Vital Swgr & Xfmr Rm No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 C-0S3001 Member Type: Beam Column Member Size: 14 X 30 14 X 370 Comments: No thermal shorts, column is bounded by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature_cc_rev1.xls (Version 1805.1)

Barrier Type: Block Credible Fire HRR (kW: 200 KW Barrier Thickness (in): 8 Credible Fire Basis:

Compartment Width (ft): 12.5 SWGR: Moderate Fire MCC: Moderate Fire Compartment Length (ft): 30 Cabinet: Small Fire Transformer 480V Moderate Fire Compartment Height (ft): 15.25 Exposed cable: Minimal, Small Fire Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 90 IPEEE Ignition Source Evaluation: 1.82E-03 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 534.27 Room Sketch:

M-663-00017A, Revision W03 Page G4C-2 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3403-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4C-3 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation: 3404-2016 Building: Control Fire Area: C-15

==

Description:==

Switchboard Rm No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 C-0S3001 Member Type: Beam Column Member Size: 24 X 76 14 X 370 Comments: Column has no thermal shorts, considered bounded by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature_cc_rev1.xls (Version 1805.1)

Barrier Type: Block Credible Fire HRR (kW: 200 KW Barrier Thickness (in): 8 Credible Fire Basis:

Compartment Width (ft): 22.5 SWGR: Moderate Fire MCC: Moderate Fire Compartment Length (ft): 17 Cabinet: Small Fire Transformer 480V Moderate Fire Compartment Height (ft): 15.25 Exposed cable: Minimum, Small Fire Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 90 IPEEE Ignition Source Evaluation: 2.00E-03 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 551.23 Room Sketch:

M-663-00017A, Revision W03 Page G4C-4 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3404-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4C-5 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation: 3410-2016 Building: Control Fire Area: C-15

==

Description:==

Switchboard Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 24 X 76 N/A Comments: No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature_cc_rev1.xls (Version 1805.1)

Barrier Type: Block Credible Fire HRR (kW: 200 KW Barrier Thickness (in): 8 Credible Fire Basis:

Compartment Width (ft): 19 SWGR: Moderate Fire MCC: Moderate Fire Compartment Length (ft): 18 Cabinet: Small Fire Transformer 480V Moderate Fire Compartment Height (ft): 15.25 Exposed cable: Minimum, Small Fire Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 90 IPEEE Ignition Source Evaluation: 1.93E-03 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 591.41 Room Sketch:

M-663-00017A, Revision W03 Page G4C-6 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3410-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4C-7 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation: 3408-2016 Building: Control Fire Area: C-16

==

Description:==

Switchboard Rm No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 C-0S3001 Member Type: Beam Column Member Size: 24 X 68 14 X 398 Comments:

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature_cc_rev1.xls (Version 1805.1)

Barrier Type: Block Credible Fire HRR (kW: 200 KW Barrier Thickness (in): 8 Credible Fire Basis:

Compartment Width (ft): 22 SWGR: Moderate Fire MCC: Moderate Fire Compartment Length (ft): 18 Cabinet: Small Fire Transformer 480V Moderate Fire Compartment Height (ft): 15.25 Exposed cable: Minimal, Small Fire Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 90 IPEEE Ignition Source Evaluation: 2.00E-03 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 541.47 Room Sketch:

M-663-00017A, Revision W03 Page G4C-8 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3408-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4C-9 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3408-2016 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G4C-10 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation: 3409-2016 Building: Control Fire Area: C-16

==

Description:==

Non-Vital Swgr & Xfmr Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 27 X 94 N/A Comments: Additional Items in close proximity (4" No columns.

I's and 21/2" angles).

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature_cc_rev1.xls (Version 1805.1)

Barrier Type: Block Credible Fire HRR (kW: 200 KW Barrier Thickness (in): 8 Credible Fire Basis:

Compartment Width (ft): 28 SWGR: Moderate Fire MCC: Moderate Fire Compartment Length (ft): 12.25 Cabinet: Small Fire Transformer 480V Moderate Fire Compartment Height (ft): 15.25 Exposed cable: Minimal, Small Fire Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 90 IPEEE Ignition Source Evaluation: 2.22E-03 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 565.18 Room Sketch:

M-663-00017A, Revision W03 Page G4C-11 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3409-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4C-12 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation: 3414-2016 Building: Control Fire Area: C-16

==

Description:==

Switchboard Rm No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature_cc_rev1.xls (Version 1805.1)

Barrier Type: Block Credible Fire HRR (kW: 200 KW Barrier Thickness (in): 8 Credible Fire Basis:

Compartment Width (ft): 19 SWGR: Moderate Fire MCC: Moderate Fire Compartment Length (ft): 18 Cabinet: Small Fire Transformer 480V Moderate Fire Compartment Height (ft): 15.25 Exposed cable: Minimal, Small Fire Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 90 IPEEE Ignition Source Evaluation: 1.93E-03 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 591.41 Room Sketch:

M-663-00017A, Revision W03 Page G4C-13 of G4C-13 Structural Steel Fireproofing Data Appendix G4C 3414-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-1 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 1407-2026 Building: Auxiliary Fire Area: A-03

==

Description:==

Boric Acid Batching Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1521 N/A Member Type: Beam Column Member Size: 30 X 108 N/R Comments: Only 1 of 4 points are required to be No thermal short attachments on evaluated. column, bounded by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 19 Forced Ventilation Rate (cfm): Supply: 300, Open Grille Compartment Length (ft): 29.75 Vent

Description:

Exht: 300 Compartment Height (ft): 20 No Attachments to columns, Open Grille Credible Fire HRR (kW): 70 KW Barrier Type: Block Credible Fire Basis:

Small Motors: Small Fire Barrier Thickness (in): 12 Small Pumps: Small Fire Cabinet: Small Fire Initial Room Temp. (F): 104 Exposed cable: Minimum, Small Fire Transient Package: Majority of NUREG-1805 FDT Results BTU: Small Fire IPEEE Ignition Source Time When Forced Ventilation Exceeds 200 F (min): 15 Evaluation: 1.69E-03 Compartment Starting Temp. for Closed Room No Vent FDT (F): 204.41 Hot Gas Layer Temperature @ 180 minutes (F): 303.16 Room Sketch:

M-663-00017A, Revision W03 Page G4D-2 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1407-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-3 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 1304-2013 Building: Auxiliary Fire Area: A-29

==

Description:==

Aux Feedwater Pipe Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 C-1S1001 Member Type: Beam Column Member Size: 18 X 50 14 X 111 Comments: Additional attachments in close Column in room only has Unistrut &

proximity. JBs, column considered acceptable based on calculation FP-M-012.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 22 Forced Ventilation Rate (cfm): Supply: 150 Exht: 150 Compartment Length (ft): 10 Vent

Description:

Compartment Height (ft): 12 Opening in floor where ladder is (3.5' X 3.5')

Credible Fire HRR (kW): 70 KW Barrier Type: Concrete Credible Fire Basis:

Exposed cable: Negligible Barrier Thickness (in): 12 Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 104 IPEEE Ignition Source Evaluation: 3.76E-04 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 2 Compartment Starting Temp. for Closed Room No Vent FDT (F): 211.16 Hot Gas Layer Temperature @ 180 minutes (F): 380.73 Room Sketch:

M-663-00017A, Revision W03 Page G4D-4 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1304-2013 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-5 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 1327-2000 Building: Auxiliary Fire Area: A-29

==

Description:==

Feedwater Pump Valve Compartment No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 N/A Member Type: Beam N/A Member Size: 14 X 34 N/A Comments: Additional attachments in close No columns.

proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 10 Forced Ventilation Rate (cfm): Supply: 100 Exht: 100 Compartment Length (ft): 10 Vent

Description:

Compartment Height (ft): 12 Credible Fire HRR (kW): 70 KW Barrier Type: Concrete Credible Fire Basis:

Exposed cable: Negligible Barrier Thickness (in): 24 Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 104 IPEEE Ignition Source Evaluation: 3.76E-04 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature @ 180 minutes (F): 502.33 Room Sketch:

M-663-00017A, Revision W03 Page G4D-6 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1327-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-7 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 1305-2013 Building: Auxiliary Fire Area: A-30

==

Description:==

Aux Feedwater Pipe Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 C-1S1001 Member Type: Beam Column Member Size: 18 X 50 14 X 111 Comments: Additional attachments in close proximity orientation of 1 ea. 4" tube causes 40 SQ IN.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 22 Forced Ventilation Rate (cfm): Supply: 150 Exht: 150 Compartment Length (ft): 10 Vent

Description:

Compartment Height (ft): 12 Opening in floor where ladder is (3.5' X 3.5')

Credible Fire HRR (kW): 70 KW Barrier Type: Concrete Credible Fire Basis:

Exposed cable: Negligible Barrier Thickness (in): 12 Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 104 IPEEE Ignition Source Evaluation: 3.76E-04 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 2 Compartment Starting Temp. for Closed Room No Vent FDT (F): 211.16 Hot Gas Layer Temperature @ 180 minutes (F): 380.73 Room Sketch:

M-663-00017A, Revision W03 Page G4D-8 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1305-2013 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-9 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1305-2013 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G4D-10 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 1328-2000 Building: Auxiliary Fire Area: A-30

==

Description:==

Feedwater Pump Valve Compartment No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 N/A Member Type: Beam N/A Member Size: 14 X 34 N/A Comments: Column encapsulated in concrete, columns considered bounded by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 10 Forced Ventilation Rate (cfm): Supply: 100 Exht: 100 Compartment Length (ft): 10 Vent

Description:

Compartment Height (ft): 12 Credible Fire HRR (kW): 70 KW Barrier Type: Concrete Credible Fire Basis:

Exposed cable: Negligible Barrier Thickness (in): 24 Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 104 IPEEE Ignition Source Evaluation: 3.76E-04 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature @ 180 minutes (F): 502.33 Room Sketch:

M-663-00017A, Revision W03 Page G4D-11 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1328-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-12 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 1329-2000 Building: Auxiliary Fire Area: A-33

==

Description:==

Vestibule Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1352 N/A Member Type: Beam N/A Member Size: 10 X 21 N/A Comments: Only 1 of 6 points are required to be Column encapsulated in concrete, evaluated. columns considered bounded by testing.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 7 Forced Ventilation Rate (cfm): Supply: 100 Exht: 100 Compartment Length (ft): 27.75 Vent

Description:

Compartment Height (ft): 12 Vent at floor (Hatchway to 1207, 3.5' X 3.5'). Temp not in USAR Table 3.11, used room 1207 below Credible Fire HRR (kW): 70 KW Barrier Type: Concrete Credible Fire Basis:

Exposed cable: Negligible Barrier Thickness (in): 12 Transient Package: Majority of BTU: Small Fire Initial Room Temp. (F): 106 IPEEE Ignition Source Evaluation: 3.76E-04 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature @ 180 minutes (F): 368.12 Room Sketch:

M-663-00017A, Revision W03 Page G4D-13 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 1329-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-14 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 3405-2016 Building: Control Fire Area: C-15

==

Description:==

Battery Rm No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 C-0S3001 Member Type: Beam Column Member Size: 24 X 76 14 X 426 Comments: Column embedded on both sides. ALBI is 2-1/2" thick minimum due to finish requirements.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 20.5 Forced Ventilation Rate (cfm): Supply: 300 Exht: 390 Compartment Length (ft): 12 Vent

Description:

Compartment Height (ft): 15.25 Credible Fire HRR (kW): 200 KW Barrier Type: Block Credible Fire Basis:

Batteries Barrier Thickness (in): 8 IPEEE Ignition Source Evaluation: 7.76E-04 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature @ 180 minutes (F): 812.83 Room Sketch:

M-663-00017A, Revision W03 Page G4D-15 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 3405-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-16 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 3407-2016 Building: Control Fire Area: C-16

==

Description:==

Battery Rm No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: Additional items in close proximity. No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 12 Forced Ventilation Rate (cfm): Supply: 300 Exht: 390 Compartment Length (ft): 20.5 Vent

Description:

Compartment Height (ft): 15.25 Credible Fire HRR (kW): 200 KW Barrier Type: Block Credible Fire Basis:

Batteries Barrier Thickness (in): 8 IPEEE Ignition Source Evaluation: 7.76E-04 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature @ 180 minutes (F): 812.83 Room Sketch:

M-663-00017A, Revision W03 Page G4D-17 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 3407-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G4D-18 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation: 3413-2016 Building: Control Fire Area: C-16

==

Description:==

Battery Rm No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0S3511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_Temperature_FV.xls (Version 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1)

Compartment Width (ft): 21 Forced Ventilation Rate (cfm): Supply: 200 Exht: 340 Compartment Length (ft): 12 Vent

Description:

Compartment Height (ft): 15.25 Credible Fire HRR (kW): 200 KW Barrier Type: Block Credible Fire Basis:

Batteries Barrier Thickness (in): 8 IPEEE Ignition Source Evaluation: 7.76E-04 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature @ 180 minutes (F): 801.75 Room Sketch:

M-663-00017A, Revision W03 Page G4D-19 of G4D-19 Structural Steel Fireproofing Data Appendix G4D 3413-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

Page 1 M-663-00017A Attachment G5 Fire Protection Evaluation For HAZ Assessment of Structural Steel Integral to Fire Boundary Rev. No. Prepared By Date Reviewed By Date W03 7/6/2007 7/6/2007

M-663-00017A Page 2 of 15 Attachment G5 Revision W03 Table of Contents Revision Log .................................................................................................................................3 1.0 Purpose.............................................................................................................................4 2.0 Scope ................................................................................................................................4 3.0 References........................................................................................................................4 4.0 Assumptions......................................................................................................................5 5.0 Assessment of Condition to Design Requirements ...........................................................5 6.0 Methodology......................................................................................................................6 7.0 Evaluation .........................................................................................................................8 8.0 Conclusions.....................................................................................................................15 Appendix G5A, Room Data Sheets... (63 Total Pages)

M-663-00017A Page 3 of 15 Attachment G5 Revision W03 Revision Log Revision Reason for Revision W03 Original Issue

M-663-00017A Page 4 of 15 Attachment G5 Revision W03 1.0 Purpose 1.1 The purpose of this document is to evaluate the Heat Affected Zone (HAZ) impact of 10 CFR 50 Appendix R fire barriers containing integral structural steel where either of the following is present:

x Steel is provided with fireproofing on only one barrier side.

x Fireproofing is provided on both steel sides and an unprotected thermal short attachment larger than Unistrut is present.

This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 This evaluation is applicable to the Rooms identified in Table II.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.3 ASTM E-119, Standard Test Methods for Fire Tests of Building Construction and Materials 3.4 UL N-711, (A-126-00001), Fire Test Report Of Loaded Restrained Beams Protected By Cementitious Mixture, Dated August 11, 1976 3.5 UL N-712, (A-126-00002), Fire Test Report Of Loaded Restrained Beams Protected By Cementitious Mixture, Dated May 13, 1977 3.6 A-126, Technical Specification For Cementitious Fireproofing Of Structural Steel For The Standardized Nuclear Unit Power Plant Unit (SNUPPS) 3.7 PIR 2002-2287, Structural Steel Fireproofing With Unprotected Attachments 3.8 FP-M-012, Rev 0, Structural Steel Fireproofing Thermal Shorts and Omissions Evaluation 3.9 CNT-MC-600, Rev. 2, Fireproofing of Structural Steel 3.10 E-15000, Electrical Cable And Raceway List, Rev. 65 3.11 A-126, Cementitious Fireproofing of Structural Steel, Rev. 7 3.12 Updated Safety Analysis Report (USAR) Section 9.5.1.2.2.3.a, Rev. 19

M-663-00017A Page 5 of 15 Attachment G5 Revision W03 3.13 Change Package 012323, M-663-00017A Revision to incorporate Structural Steel Fireproofing Evaluation and Analysis, Rev. 0 3.14 IEEE 383, Standard for Qualifying Class 1E Electric Cables and Field Splices for Nuclear Power Generating Stations 4.0 Assumptions 4.1 It is assumed that fireproofing material used to protect building steel is applied to a thickness as required by CNT-MC-600. This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial fireproofing installation activities and subsequent inspections during ongoing plant repairs witnessed by Fire Protection personnel and inspections performed during the this evaluation process.

5.0 Assessment of Condition to Design Requirements 5.1 Requirements USAR Section 9.5.1.2.2.3.a identifies that the design, construction, test method, and acceptance criteria for fire rated barriers is per applicable sections (determined by construction type) of ASTM E-119, UL standards, and state building codes.

5.2 Assessment Fire testing does not directly bound the use of protected steel as part of a fire barrier assembly. Such a configuration presents the potential to transmit detrimental temperatures from the fire side through the steel element of the fire barrier to insitu combustibles and/or post-fire safe shutdown (PFSSD) circuits located in close proximity to the unexposed side of the steel fire barrier segment.

Attachment G1, Section 7.1, evaluated that steel with fireproofing on both barrier sides containing unprotected thermal short attachments no larger than Unistrut in size and mass provides an equivalent 3-hour F and T rated configuration.

Therefore, HAZ review, similar to that discussed in Section 7.2.3 of M-663-00017A for non-T rated penetration seals, is only necessary for structural steel integral to a fire barrier assembly where either of the following is present:

x Steel is provided with fireproofing on only one barrier side.

x Fireproofing is provided on both steel sides and an unprotected thermal short attachment larger than Unistrut is present.

M-663-00017A Page 6 of 15 Attachment G5 Revision W03 6.0 Methodology Where a HAZ review was necessary for steel that is integral to a fire barrier assembly, a review similar to M-663-00017A Section 7.2.3 was conducted with the exception that a review distance of two feet from the unexposed steel surface was utilized. This is an acceptable distance considering the air gap temperature drop discussion provided in M-663-00017A Section 7.2.3. This two-foot distance from the structural steel member on the unexposed side is the area that encompasses the HAZ. Assuming an ASTM E-119 three-hour fire duration, a temperature of either 1925qF or 1100qF was assigned to the unexposed barrier side based on the fireproofing configuration provided, including consideration for unprotected thermal short attachments larger than Unistrut.

A 1925qF temperature was utilized for the following configurations:

x Fireproofing is single sided with an unprotected attachment on either barrier side.

x Fireproofing is provided on both barrier sides and an unprotected attachment larger than Unistrut is located on the fire side such that it is in proximity (within two feet) to an unexposed side attachment that supports a raceway within the HAZ.

An unexposed side temperature assignment of 1925qF for the above configurations is a conservative approach, as it utilizes the maximum temperature attained during ASTM E-119 fire testing, with no credit given for concrete barrier heat sink or recognition that the hot spot created by the unprotected thermal short on the exposed barrier side will be localized.

An 1100qF temperature was utilized for the following configurations:

x Fireproofing is single sided and no unprotected attachments larger than Unistrut are present on either barrier side.

x Fireproofing is provided on both barrier sides and an unprotected attachment larger than Unistrut is not in close proximity (within two feet) of an unprotected attachment on the opposing barrier side.

An unexposed side temperature assignment of 1100qF for the above configurations is a an acceptable approach based on subtraction of ASTM E-119 furnace temperature (1925qF) from Reference 3.4 and 3.5 thermocouple data (1,100qF). This yields an approximate 825qF temperature drop across the exposed fireproofing during ASTM E-119 fire endurance testing.

For PFSSD circuits and IEEE-383 cable, an insult temperature limitation of 700qF was utilized. A temperature limitation of 400qF was utilized for other Class A combustibles.

These temperature limitations are consistent with M-663-00017A, Section 7.2.3.

Figure 6-1 reflects the review process utilized to assess HAZ impact.

M-663-00017A Page 7 of 15 Attachment G5 Revision W03 Walkdown thermal short & building steel incorporated into Appendix R barriers to determine if circuits and/or exposed combustibles are present in the HAZ (within 2 of barrier of concern).

Assign unexposed side temperature (1925qF or 1100qF).

No Yes Circuits in HAZ?

No Yes

1) Document in M-663-00017A PFSSD?

Attachment G data sheet for unprotected thermal short.

2) Implement design control for scheduled circuit(s) to ensure HAZ issue is addressed if circuit(s) is to be credited for PFSSD in the future. No IS Yes PFSSD AFFECTED Further Action Required to Address Issue:

x Evaluation or x Field Work Required No Exposed Yes Combustibles within HAZ?

Document in M-663-00017A Further Action Required to Attachment G data sheet for Address Issue:

unbounded thermal shorts x Evaluation or x Field Work Required Figure 6-1, Heat Affected Zone Review Process

M-663-00017A Page 8 of 15 Attachment G5 Revision W03 7.0 Evaluation 7.1 Where structural steel is incorporated into a 10 CFR 50 Appendix R barrier, one-sided protection does not satisfy cold side temperatures, when considering an ASTM E-119 3-hour design basis fire. The one-sided protection configuration will not allow flame passage through the barrier. However, it could result in temperatures up to 1100qF or 1925ºF on the unexposed steel surface of the barrier. Each room was reviewed for HAZ impact in effort to document each raceway and insitu combustibles within two (2) feet of the barrier segment containing steel protected with cementitious fireproofing to ensure PFFSD is not impacted. In addition, two-side protection with unprotected attachments can also produce localized high temperatures. Therefore, protected steel with unprotected attachments was also reviewed for HAZ impact at barriers separating fire areas. No credit was given to area suppression systems, in effort to achieve a level of conservatism in the analysis process.

One sided structural steel fireproofing is determined to be F rated only and does not satisfy T rating requirements when exposed to a design basis fire.

Specification A-126, Section 7.1 states in part, stair towers and elevator construction shall be protected from external hazards, thus in these cases structural steel fireproofing was not required on both sides of the barrier. Where these barriers provide 10 CFR 50 Appendix R separation, this configuration does not satisfy maximum cold side temperature limitations required by the WCNOC Fire Protection Program (250qF plus ambient for fire barrier construction and 325qF plus ambient for fire barrier penetration seals). Therefore, each location where one-sided fireproofing or significant attachments are present was evaluated for HAZ impact to ensure PFSSD is not affected. As such, any raceway/circuit or component within 2 feet of the one-sided protected barrier steel and/or two-sided protected steel with large thermal shorts will be considered within the HAZ and will be evaluated for PFSSD impact utilizing the Figure 6-1 methodology. Thermal shorts attached to stairwell steel will not impact the structural integrity of the steel or induce steel failure due to the corbel support afforded by the under supporting walls.

Table II defines the review scope and identifies the communicating rooms and fire areas along with the raceways that are potentially subject to thermal insult, based on proximity to the barriers evaluated. Each room and raceway (where applicable) is dispositioned in the Comments/Disposition Section of Table II, with reference provided to the appropriate evaluation paragraph section below.

Area walkdown reviews revealed that no insitu combustibles (other than IEEE-383 cable) were located within the HAZ for each of the Table II areas.

Appendix G5A documents the result of the Fire Protection reviews and assessments for each room and area listed in Table II, below. The data sheets contain relevant information for each location reviewed for HAZ impact.

M-663-00017A Page 9 of 15 Attachment G5 Revision W03 TABLE II HAZ Barrier Review Fire Room Bldg Elev. Room Communicating Air Gap1 Comments/Disposition:

Area

Description:

Rooms/ Fire (TempºF)

Areas (Inches)

A-1 1201 Aux 1988-0 Vestibule 1201 1119 1925ºF 1). No HAZ review required, no items in close proximity.

A-1 A-5 N/A A-3 1116 Aux 1974-0 Boric Acid 1116 1301 Bounded 1.) No HAZ review required, Tank Room B embedded steel (Concrete) on A-3 A-8 N/A backside.

1117 Boric Acid 1117 1320 Bounded 1.) No HAZ review required, Tank Room A embedded steel (Concrete) on A-3 A-8 N/A backside.

1407 Aux 2026-0 Boric Acid 1407 1408 Bounded 1.) No HAZ review required, Batching embedded steel (Concrete) on A-3 A-16 N/A backside.

Tank Area A-5 1119 Aux 1988-0 Aux. Stair A-1 1119 1201 1100ºF 1). No HAZ review required, no items in close proximity.

A-5 A-1 N/A Aux 2000-0 1321 1925ºF 1). No HAZ review required, no items in close proximity.

A-8 N/A Aux 2047-6 1502 1100ºF-R Items 1, 2 & 3 are NOT PFSSD:

A-20 4 (R)1 1). Conduit 5U4B8R, See Section 7.1.3, NO Set Route Control Required 4 (R)1 2). Conduit 6U1214, See Section 7.1.3, NO Set Route Control Required 4 (R)1 3). Conduit 5C1014, See Section 7.1.3, NO Set Route Control Required A-6 1127 Aux 1974-0 Aux. Stair A-2 1127 1120 1925ºF 1). No HAZ review required, no items in close proximity.

A-6 A-1 N/A Aux 2000-0 1320 1925ºF-C Items 1 and 2 are NOT PFSSD.

A-8 1100ºF-R Item 3 IS PFSSD:

1 3/4 (C) 1). Conduits 1J1E1D, Set Route Control Required See Section 7.1.2 11/2 (C)1 2). Conduit 1U1F2G, Set Route Control Required See Section 7.1.2 4 (C)1 3). Conduit 4U3D5H, Set Route Control Required See Section 7.1.6 A-8 1320 Aux 2000-0 Aux. Corridor 1320 1127 1100ºF-R Item 1 is NOT PFSSD:

No. 4 A-8 A-6 1 1). Conduit 4J3C1E, See Section 141/2 (R) 7.1.3, NO Set Route Control Required 1321 Aux 2000-0 Exit Vestibule 1321 1119 1100ºF-R 1). No HAZ review required, no items in close proximity.

A-8 A-5 N/A A-26 1405 Aux 2026-0 Chemical 1405 1401 Bounded 1.) No HAZ review required, Storage Area embedded steel (Concrete) on A-26 A-16 N/A backside.

M-663-00017A Page 10 of 15 Attachment G5 Revision W03 Fire Room Bldg Elev. Room Communicating Air Gap1 Comments/Disposition:

Area

Description:

Rooms/ Fire (TempºF)

Areas (Inches)

C-2 3106 Cntrl 1974-0 Electrical 3106 3101 1100ºF-R Items 1, 2 & 3 are NOT PFSSD:

Chase C-2 C-1 1 1). Cable Tray 5J1A90, See Section 6 (C) 7.1.3, NO Set Route Control Required 3 (R)1 6 (C)1 2). Cable Tray 5U4A90, See Section 1 7.1.3, NO Set Route Control Required 3 (R) 6 (C)1 3). Cable Tray 5U1B90, See Section 1 7.1.3, NO Set Route Control Required 3 (R)

C-3 3105 Cntrl 1974-0 Electrical 3105 3101 1100ºF-R Items 1 & 2 are NOT PFSSD:

Chase C-3 C-1 9 (C)1 1). Cable Tray 6U1B90, See Section 1 7.1.3, NO Set Route Control Required 7 (R) 6 (C)1 2). Cable Tray 6U3G90, See Section 1 7.1.3, NO Set Route Control Required 2 (R)

C-6 3201 Cntrl 1984-0 Control 3201 0SAC 1100ºF-R 1). N/A lighting conduit, Same Fire Building, Stair Area, No HAZ review required, See C-6 C-6 N/A Section 7.1.1, no items in close C-1 proximity.

Cntrl 2000-0 3201 3302 1925ºF-R 1). N/A lighting and communications conduit No HAZ review required, See C-6 C-10 N/A Section 7.1.1, no items in close proximity.

Cntrl 2016-0 3201 3403 1925ºF-R Items 1 is NOT PFSSD and Item C-6 C-15 2 IS PFSSD:

23 (C)1 1). Cable Tray 6J8D22, See Section 1 7.1.3, NO Set Route Control Required 15 (R) 23 (C)1 2). Cable Tray 6U3E21, Set Route 1 Control Required See Section 7.1.5 3 (R)

Cntrl 2032-0 3201 3501 1100ºF-C 1). Lighting conduit, Same Fire Area, No HAZ review required, See Section C-6 C-21 N/A 7.1.1, no items in close proximity.

Cntrl 2047-6 3201 3605 1100ºF-R Item 1 is NOT PFSSD:

C-6 C-17 14 (R)1 1). Conduit 6J1T1A, See Section 7.1.3, NO Set Route Control Required 1925ºF-C Items 2 & 3 are NOT PFSSD:

1 21 (C) 2). Conduit 4J3006, Set Route Control Required See Section 7.1.2 7 (C)1 3). Conduit 4J3007, Set Route Control Required See Section 7.1.2 Cntrl 2073-0 3201 3801 1100ºF-R 1). No HAZ review required, items noted were Lighting and Detection C-6 C-22 conduits no other items in close N/A proximity, See Section 7.1.1.

C-8 3229 Cntrl 1984-0 Electrical 3229 3204 1100ºF-R Item 1 is NOT PFSSD:

Chase C-8 C-6 7 (R)1 1). Cable Tray 6U3G90, See Section 7.1.3, NO Set Route Control Required

M-663-00017A Page 11 of 15 Attachment G5 Revision W03 Fire Room Bldg Elev. Room Communicating Air Gap1 Comments/Disposition:

Area

Description:

Rooms/ Fire (TempºF)

Areas (Inches)

C-9 3301 Cntrl 2000-0 ESF 3301 3306 1100ºF-R Item 1 IS PFSSD & Item 2 is Switchgear C-9 C-12 NOT PFSSD:

Room No. 1 6 (C)1 1). Cable Tray 5C8Q81, See Section 1 7.1.4, NO Set Route Control Required 4 (R) 6 (C)1 2). Cable Tray 5C8A81, See Section 1 7.1.3, NO Set Route Control Required 2 (R)

C-11 3305 Cntrl 2000-0 Electrical 3305 3302 1100ºF-R Items 1 & 2 are NOT PFSSD:

Chase C-11 C-10 1 1). Cable Trays 6J1S70, See Section 5 (R) 7.1.3, NO Set Route Control Required 23 (R)1 2). Cable Trays 6U3H70, See Section 7.1.3, NO Set Route Control Required C-13 3415 Cntrl 2016-0 Access Ctrl & 3415 3416 1100ºF-C Items 1& 2 are NOT PFSSD:

Elec Equip C-13 C-14 1 1). Conduit 4U3061, Set Route 11/2 (C)

A/C Units No. Control Required See Section 7.1.2 1

1925ºF-C Item 2 is NOT PFSSD:

1 12 (C) 2). Conduit 6U3089, Set Route Control Required See Section 7.1.2 2 (R)1 C-15 3403 Cntrl 2016-0 Non-Vital 3403 3404 Bounded 1). No HAZ Issue, Lighting Conduit Swgr & Xfmr Only, See Room 3201-2016, No HAZ C-15 C-15 review required Rm No. 1 N/A 3404 Cntrl 2016-0 Switchboard 3404 3403 Bounded 1). Same Fire Area, No HAZ review Rm No. 4 required C-15 C-15 N/A 3405 Cntrl 2016-0 Battery Rm 3405 3406 Bounded 1). Same Fire Area, No HAZ review No. 4 required C-15 C-35 N/A 3410 Cntrl 2016-0 Switchboard 3410 3418 1100ºF-R Item 1 is NOT PFSS:

Rm No. 2 C-15 C-17 12 (C)1 1). Conduit 5J3027, See Section 1 7.1.3, NO Set Route Control Required 10 (R)

C-16 3409 Cntrl 2016-0 Non-Vital 3409 3401 1100ºF-R 1). No HAZ review required, no items Swgr & Xfmr in close proximity.

C-16 C-35 N/A Rm No. 2 C-17 3418 Cntrl 2016-0 Electrical 3418 3410 1100ºF-R Items 1 and 2 ARE PFSSD and Chase C17 C-15 Item 3 is NOT PFSSD:

8 (R)1 1). Cable Tray 6C8A60, See Section 7.1.4, NO Set Route Control Required 8 (R)1 2). Cable Tray 6U3H60 See Section 7.1.4, NO Set Route Control Required 8 (R)1 3). Cable Tray 6J1A60, See Section 7.1.3, NO Set Route Control Required C-18 3419 Cntrl 2016-0 Electrical 3419 3414 1100ºF-R Item 1 is NOT PFSSD and Item Chase C-18 C-16 2 IS PFSSD:

8 (C)1 1). Cable Tray 5C8A70, See Section 1 7.1.3, NO Set Route Control Required 3 (R) 1 8 (C) 2). Cable Tray 5C8Q70, See Section 1 7.1.4, NO Set Route Control Required 3 (R)

C-21 3501 Cntrl 2032-0 Lower Cable 3501 3505 1100ºF-R 1). See Room 3505, Item 1. No HAZ Spreading review required, no items in close C-21 C-23 N/A proximity.

Room

M-663-00017A Page 12 of 15 Attachment G5 Revision W03 Fire Room Bldg Elev. Room Communicating Air Gap1 Comments/Disposition:

Area

Description:

Rooms/ Fire (TempºF)

Areas (Inches)

C-22 3801 Cntrl 2073-0 Upper Cable 3801 3201 1100ºF-R 1). No HAZ Issue, Gatronics Conduit Spreading Only, See Section 7.1.1 C-22 C-6 N/A Room C-23 3505 Cntrl 2032-0 Electrical 3505 3501 1100ºF-R Item 1 is NOT PFSSD:

Chase C-23 C-21 1 1). Cable Tray 6J1A56, See Section 7 (R) 7.1.3, NO Set Route Control Required C-27 3605 Cntrl 2047-6 Equipment 3605 3617 N/A 1). See Room 3617, Duplicate HAZ Cabinet Area C-27 C-30 C-30 3617 Cntrl 2047-6 Electrical 3617 3605 1100ºF-R Items 1, 2 & 3 are NOT PFSSD:

Chase C-30 C-27 18 (C)1 1). Conduit 4J1032, Set Route 1 Control Required See Section 7.1.2 1/2 (R) 8 (R)1 2). Cable Tray 6J1A40, See Section 7.1.3, NO Set Route Control Required 8 (R)1 3). Cable Tray 6C8A40, See Section 7.1.3, NO Set Route Control Required C-35 3406 Cntrl 2016-0 Corridor No. 2 3406 3405 1100ºF-R 1). Grid Plug Mounting, No HAZ review required. No HAZ Issues C-35 C-15 N/A 3412 Cntrl 2016-0 Emergency 3412 3101 1100ºF-R Items 1, 2 and 3 are NOT Shower & C-35 C-1 PFSSD:

Eyewash Duct 2 (C)1 1). Conduit 4U1E2N, Set Route Area Control Required See Section 7.1.2 Chase 2 (C)1 2). Conduit to JB 4U3045, Set Route Control Required See Section 7.1.2 2 (C)1 3). Conduit to JB 4U3046, Set Route Control Required See Section 7.1.2 3412 3411 1100ºF-R Item 1 is NOT PFSSD:

1 C-35 C-15 8 (C) 1). Conduit 4U1E2N, See Section 7.1.3, NO Set Route Control Required 2 (R)1 C-36 C36 Cntrl 2000-0 Cable Chase C36 3302 1100ºF-R 1). Conduits in close proximity enter

@ CA-C6, adjacent FA, No HAZ Issue C-36 C-10 N/A 2000-0 to 2016-0, C-37 C37 Cntrl 2000-0 Cable Chase Elec. 3301 Bounded Item 1 is NOT PFSSD:

@ CA-C3, Chase C-9 2000-0 to 11/2 1). Conduit 2U1034, See Section 2016-0 C-37 1 7.1.3, NO Set Route Control Required (R)

Unistrut only, no thermal impact F-4 6203 Fuel 2026-0 Air Handling 6203 6202 1925ºF-C Item 1 is NOT PFSSD:

Equipment F-4 F-5 N/A 1). Conduit 6J6014, Assumed failed, Room see Room 6202 F-5 6202 Fuel 2026-0 Electrical 6202 6203 1925ºF-C Item 1 is NOT PFSSD:

Equipment F-5 F-4 1 14 (C) 1). Conduit 6J6014, Set Route Room Control Required See Section 7.1.2 Table Notes:

1. To determine acceptable air gap distance, conductive pathways, estimated exposure temperature is based on existing steel protection configuration and whether the exposure is C-Conduction or R-Radiant. In each case, the worse case Conductive and Radiant distance is used, either cumulative or a single thermal pathway exposure were reviewed as applicable.

M-663-00017A Page 13 of 15 Attachment G5 Revision W03 7.1.1 Unscheduled conduit such as communication, fire detection and general plant lighting are not considered relevant to PFSSD and are not evaluated for PFSSD impact. Cabling contained within conduit cannot support combustion, propagate flame or hot gases. Therefore, fire propagation is not credible.

7.1.2 Scheduled Non-PFSSD conduits referring to this section are located within the HAZ and cable within the conduits have the potential to sustain damage from heat transmission through the barrier segment fabricated from building steel protected with cementitious fireproofing, as postulated temperature exposure exceeds 700ºF for the respective raceway.

However, fire propagation will not occur, as cabling contained within conduit cannot support combustion, propagate flame or hot gases; therefore, fire propagation is not credible. Future use of these raceways shall be restricted or may require field modification if they are credited for PFSSD in the future. E-15000 set-route control is required for these raceways to ensure future raceway use continue to satisfy the conclusions of this evaluation. Referenced E-15000 set-route changes were completed by change package 012323.

7.1.3 Scheduled Non-PFSSD conduit and cable tray raceways referring to this section have been determined to have sufficient distance from the point of thermal insult and will not be thermally affected by conductive or radiant heat on the unexposed barrier side. This determination is supported by use of the air gap methodology described in M-663-00017A, Section 7.2.3, which credits air space to reduce exposure temperatures to cabling and combustibles within or adjacent to the HAZ. Each HAZ issue was reviewed to ensure combustibles on the unexposed side of the barrier would not be affected by radiant energy and/or auto-ignition. Air gaps and thermal short distances were measured to permit use of the 222ºF temperature drop rule for every 1 of air gap. After considering the air gap distance, each of the HAZ issues would have to meet acceptable cable exposures of <700ºF. Maintaining exposure temperatures below this limitation will ensure that fire propagation cannot occur, and the raceway will not be affected through conduction or radiant heat.

7.1.4 PFSSD credited conduit or cable tray raceways referring to this section have been determined to have sufficient distance from the point of thermal insult and will not be thermally affected by conductive or radiant heat on the unexposed barrier side. This determination is supported by use of the air gap methodology described in M-663-00017A, Section 7.2.3, which credits air space to reduce exposure temperatures to cabling and combustibles within or adjacent to the HAZ. Each HAZ issue was reviewed to ensure combustibles on the unexposed side of the barrier would not be affected by radiant energy and/or auto-ignition. Air gaps and thermal short distances were measured to permit use of the 222ºF temperature drop rule for every 1 of air gap. After considering the air gap distance, each of the HAZ issues would have to meet acceptable cable exposures of <700ºF. Maintaining exposure temperatures below this limitation will ensure that fire propagation cannot occur, and the raceway will not be affected through conduction or radiant heat.

M-663-00017A Page 14 of 15 Attachment G5 Revision W03 7.1.5 PFSSD credited cable tray 6U3E21, located in Room 3403, is a 12 X 4 open cable tray in close proximity to a 6 x .375 thick I beam that is attached to the building steel. The building steel separates 10 CFR 50 Appendix R fire areas and is protected on the cable tray side with cementitious fireproofing (one-sided protection). The exposed side of the barrier is Room 3201, North Control Building Stairwell.

The cable tray is 23 away from the postulated exposure temperature of 1925ºF as determined by the steel configuration and one-side fireproofing. Conservatively applying the M-663-00017A, Table 7.2.3-2B review distance for a 12 diameter pipe, in relation to the 6 beam, reveals that at 24 the thermal exposure would be approximately 1209qF.

Application of the air gap methodology of 222qF drop per 1 air gap reveals an approximate temperature of 543qF for the cables within the tray of concern. This is less than the 700qF insult temperature limitation for the IEEE-383 cable. However, this raceway requires E-15000 set route control to ensure future cable additions consider impact to this evaluation. This E-15000 set-route change was completed by change package 012323.

7.1.6 PFSSD credited conduit 4U3D5H, located in Room 1320 is a 3 rigid steel conduit supported by a 4 tube steel and Unistrut design mounted to the vertical column separating fire areas. The conduit contains PFSSD cabling associated with BIT injection. The building steel separates 10 CFR 50 Appendix R fire areas and is protected on the conduit side with cementitious fireproofing (one-sided protection). The exposed side of the barrier is Room 1127, North Auxiliary Building Stairwell.

The conduit is 4 away and mounted directly on to the conductive path to the postulated exposure temperature of 1925ºF, as determined by the steel configuration and one-side fireproofing. The thermal path is conductive and thermal failure is expected due to the close proximity of the conduit to the exposure temperature of 1925ºF. A fire in A-6 does not require BIT injection. Seal injection is available with no inventory loss through letdown. Therefore, PFSSD capability is not affected if a fire would occur in Fire Area A-6. However, this raceway requires E-15000 set route control to ensure future cable additions consider impact to this evaluation. This E-15000 set-route change was completed by change package 012323.

7.2 Post Fire Safe Shutdown Impact There is no impact to PFSSD capability, as the evaluation demonstrates that steel integral to 10 CFR 50 Appendix R fire barriers will prevent fire propagation.

The comprehensive walkdown review for each of the areas revealed that no exposed insitu combustibles or PFSSD capability is negatively affected by the steel fire barrier segments.

M-663-00017A Page 15 of 15 Attachment G5 Revision W03 8.0 Conclusions Based on physical plant walk downs, reviews and assessments performed by Fire Protection the room and areas identified in Table II above, contain protected structural steel that separate 10 CFR 50 Appendix R fire areas. Each of these barriers vary in configuration, some with one-sided protection and others with two-sided protection with unprotected attachments that could induce heat through the barrier beyond WCNOC cold side temperature limitations, if an ASTM E-119 three hour fire were to occur in the adjacent fire area. Therefore, each raceway that was located within the HAZ was reviewed for potential impact to PFSSD. All raceways listed in Table II above have been determined to be acceptable and do not affect PFSSD considering the protective coating or thermal short configurations that are present.

It is reasonable to conclude that the building steel integral to a fire barrier will satisfy regulatory expectations and commitments as well as WCNOC Fire Protection Program requirements, to prevent fire propagation and unacceptable thermal insult to raceways on the unexposed side of the fire barrier.

M-663-00017A, Revision W03 Page G5A-1 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1201-1988 Building: Auxiliary Fire Area: A-01

==

Description:==

Vestibule Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-2 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1116-1974 Building: Auxiliary Fire Area: A-03

==

Description:==

Boric Acid Tank Room B Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-3 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1117-1974 Building: Auxiliary Fire Area: A-03

==

Description:==

Boric Acid Tank Room A Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-4 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1407-2026 Building: Auxiliary Fire Area: A-03

==

Description:==

Boric Acid Batching Tank Area Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-5 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1119-1988 Building: Auxiliary Fire Area: A-05

==

Description:==

Aux. Stair A-1 & A-1A Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-6 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1119-2000 Building: Auxiliary Fire Area: A-05

==

Description:==

Aux. Stair A-1 & A-1A Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-7 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 1119-2000 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-8 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1119-2047 Building: Auxiliary Fire Area: A-05

==

Description:==

Aux. Stair A-1 & A-1A Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-9 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1127-1974 Building: Auxiliary Fire Area: A-06

==

Description:==

Aux. Stair A-2 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-10 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 1127-1974 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-11 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1127-2000 Building: Auxiliary Fire Area: A-06

==

Description:==

Aux. Stair A-2 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-12 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 1127-2000 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-13 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 1127-2000 HAZ #3 Sketch HAZ #3 Photo

M-663-00017A, Revision W03 Page G5A-14 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1127-2026 Building: Auxiliary Fire Area: A-06

==

Description:==

Aux. Stair A-2 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-15 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1320-2000 Building: Auxiliary Fire Area: A-08

==

Description:==

Corridor No. 4 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-16 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1321-2000 Building: Auxiliary Fire Area: A-08

==

Description:==

Exit Vestibule Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-17 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 1405-2026 Building: Auxiliary Fire Area: A-26

==

Description:==

Chemical Storage Area Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-18 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3106-1974 Building: Control Fire Area: C-02

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-19 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3105-1974 Building: Control Fire Area: C-03

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-20 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3105-1974 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-21 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3201-1984 Building: Control Fire Area: C-06

==

Description:==

Control, Stair C-1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-22 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3201-2000 Building: Control Fire Area: C-06

==

Description:==

Control, Stair C-1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-23 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3201-2000 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-24 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3201-2016 Building: Control Fire Area: C-06

==

Description:==

Control, Stair C-1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-25 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3201-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-26 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3201-2032 Building: Control Fire Area: C-06

==

Description:==

Control, Stair C-1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-27 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3201-2032 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-28 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3201-2047 Building: Control Fire Area: C-06

==

Description:==

Control, Stair C-1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-29 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3201-2047 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-30 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3201-2047 HAZ #3 Sketch HAZ #3 Photo

M-663-00017A, Revision W03 Page G5A-31 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3201-2073 Building: Control Fire Area: C-06

==

Description:==

Control, Stair C-1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-32 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3229-1984 Building: Control Fire Area: C-08

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-33 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3301-2000 Building: Control Fire Area: C-09

==

Description:==

ESF Switchgear Room No. 1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-34 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3305-2000 Building: Control Fire Area: C-11

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-35 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3305-2000 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-36 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3415-2016 Building: Control Fire Area: C-13

==

Description:==

Access Ctrl & Elec Equip A/C Units No. 1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-37 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3415-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-38 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3415-2016 HAZ #3 Sketch HAZ #3 Photo

M-663-00017A, Revision W03 Page G5A-39 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3403-2016 Building: Control Fire Area: C-15

==

Description:==

Non-Vital Swgr & Xfmr Rm No. 1 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-40 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3403-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-41 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3404-2016 Building: Control Fire Area: C-15

==

Description:==

Switchboard Rm No. 4 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-42 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3405-2016 Building: Control Fire Area: C-15

==

Description:==

Battery Rm No. 4 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-43 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3410-2016 Building: Control Fire Area: C-15

==

Description:==

Switchboard Rm No. 2 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-44 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3410-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-45 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3410-2016 HAZ #3 Sketch HAZ #3 Photo

M-663-00017A, Revision W03 Page G5A-46 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3409-2016 Building: Control Fire Area: C-16

==

Description:==

Non-Vital Swgr & Xfmr Rm No. 2 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-47 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3418-2016 Building: Control Fire Area: C-17

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-48 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3418-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-49 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3418-2016 HAZ #3 Sketch HAZ #3 Photo

M-663-00017A, Revision W03 Page G5A-50 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3419-2016 Building: Control Fire Area: C-18

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-51 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3801-2073 Building: Control Fire Area: C-22

==

Description:==

Upper Cable Spreading Room Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-52 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3505-2032 Building: Control Fire Area: C-23

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-53 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3605-2047 Building: Control Fire Area: C-27

==

Description:==

Equipment Cabinet Area Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-54 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3617-2047 Building: Control Fire Area: C-30

==

Description:==

Electrical Chase Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-55 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3406-2016 Building: Control Fire Area: C-35

==

Description:==

Corridor No. 2 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-56 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3406-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-57 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 3412-2016 Building: Control Fire Area: C-35

==

Description:==

Emergency Shower & Eyewash Area Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-58 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3412-2016 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-59 of G5A-63 Structural Steel Fireproofing Data Appendix G5A 3412-2016 HAZ #3 Sketch HAZ #3 Photo

M-663-00017A, Revision W03 Page G5A-60 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: C036-2000 Building: Control Fire Area: C-36

==

Description:==

Cable Chase @ CA-C6, 2000-0 to 2016-0, Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-61 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: C037-2000 Building: Control Fire Area: C-37

==

Description:==

Cable Chase @ CA-C3, 2000-0 to 2016-0 Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

M-663-00017A, Revision W03 Page G5A-62 of G5A-63 Structural Steel Fireproofing Data Appendix G5A C037-2000 HAZ #2 Sketch HAZ #2 Photo

M-663-00017A, Revision W03 Page G5A-63 of G5A-63 Structural Steel Fireproofing Data Appendix G5A Room-Elevation: 6202-2026 Building: Fuel Fire Area: F-05

==

Description:==

Electrical Equipment Room Room Sketch:

HAZ #1 Sketch HAZ #1 Photo

Wolf Creek Nuclear Operating Corporation Page 1 of 1 M-663-00017A, Revision W01 Attachment H Fire Protection Evaluations for Unique or Unbounded Firestop and Cable Tray Cover Configurations (There are currently no evaluations in this attachment)