Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000260/LER-1981-035-03, /03L-0:on 810708,while Performing Level Switch Testing,Scram Discharge Instrument Vol Tank Level Switch 2-LS-85-45F Failed to Operate.Caused by Inoperable Robertshaw Level Switch Model SL-305-EI-X.Switch Replaced + (12:44:33, 21 December 2024)
- L-81-321, Interim Deficiency Rept Re Omission of Locking Rings Slots on Modutronic Controller/Allen Bradley Selector Switches, Initially Reported 810624.Deficiency Being Evaluated.Addl Info Will Be Provided by 810803 + (12:44:34, 21 December 2024)
- IR 05000317/1981010 + (12:44:37, 21 December 2024)
- 05000271/LER-1981-017-03, /03L-1:on 810629,containment Isolation Valve LRN-95 Failed to Close During Quarterly Surveillance.Caused by three-way Air Solenoid Failure to Exhaust Air Due to Dirt Plugging Port.Solenoid Was Cleaned,Tested & Returned to Sv + (12:44:38, 21 December 2024)
- ML20009H560 + (12:44:41, 21 December 2024)
- 05000271/LER-1981-017, Forwards LER 81-017/03L-1 + (12:44:42, 21 December 2024)
- ML20009H556 + (12:44:45, 21 December 2024)
- ML20009H555 + (12:44:46, 21 December 2024)
- ML20009H554 + (12:44:47, 21 December 2024)
- ML20009H553 + (12:44:48, 21 December 2024)
- ML20009H551 + (12:44:49, 21 December 2024)
- 05000338/LER-1981-051-03, /03L-0:on 810703-08,containment Average Air Temp Exceeded Tech Specs.Caused by Temporary Loss of Cooling Medium.Temp Reduced by Placing Steam Chiller in Svc + (12:44:50, 21 December 2024)
- 05000213/LER-1981-010-03, /03L-0:on 810704,charging Pump B Found Leaking Oil.Caused by Vibration Which Cracked Hardened Pipe Thread Sealing Matl.Two Nipples & Union Replaced + (12:44:52, 21 December 2024)
- 05000213/LER-1981-010, Forwards LER 81-010/03L-0 + (12:44:55, 21 December 2024)
- 05000247/LER-1981-017-03, /03L-0:on 810630,feed Breaker for 480-volt Bus 5A Opened & Associated Lockout Relay Actuated.Caused by Defective Westinghouse DB-75 Breaker Tripping Device. Device Replaced + (12:44:57, 21 December 2024)
- 05000338/LER-1981-051, Forwards LER 81-051/03L-0 + (12:44:59, 21 December 2024)
- 05000247/LER-1981-017, Forwards LER 81-017/03L-0 + (12:45:01, 21 December 2024)
- IR 05000293/1981011 + (12:45:02, 21 December 2024)
- ML20009H538 + (12:45:03, 21 December 2024)
- 05000369/LER-1981-093-01, Three Instrument Lines Which Penetrate Containment Were Not Closed.Caused by Three Containment Isolation Valves Left Open Due to Omission from Containment Penetration List.Valves Closed + (12:45:05, 21 December 2024)
- 05000321/LER-1981-079-03, /03L-0:on 810713,pump P41-C001C Failed to Meet Acceptance Criteria for Total Dynamic Head.Caused by Wear & Erosion.Pump Removed & Rebuilt + (12:45:06, 21 December 2024)
- ML20009H535 + (12:45:07, 21 December 2024)
- 05000369/LER-1981-093, Forwards Updated LER 81-093/01X-1 + (12:45:09, 21 December 2024)
- ML20009H532 + (12:45:11, 21 December 2024)
- 05000321/LER-1981-079, Forwards LER 81-079/03L-0 + (12:45:12, 21 December 2024)
- 05000259/LER-1981-039-03, /03L-0:on 810703,inverter for Alarm Panel XA-55-8E Became Inoperable.Caused by Failure of Inverter Control Card.Card Replaced & Successfully Tested + (12:45:14, 21 December 2024)
- IR 05000277/1981002 + (12:45:15, 21 December 2024)
- 05000259/LER-1981-039, Forwards LER 81-039/03L-0 + (12:45:17, 21 December 2024)
- IR 05000409/1981011 + (12:45:19, 21 December 2024)
- 05000245/LER-1981-014-01, Primary Containment Isolation Valves Failed to Satisfy Tech Spec Limit for Local Leak Rate Testing.Caused by Cracked Discs,Worn Pilot Valve Seats & Worn Piston Rings + (12:45:21, 21 December 2024)
- ML20009H522 + (12:45:23, 21 December 2024)
- ML20009H518 + (12:45:26, 21 December 2024)
- 05000327/LER-1981-080-03, /03L-0:on 810701,refueling Water Storage Tank Dropped Approx 1,000 Gallons Below Required Vol.Caused by Failure of Check Valve 0-78-563 to Seat After Opening.Check Valve Isolated + (12:45:27, 21 December 2024)
- ML20009H515 + (12:45:29, 21 December 2024)
- ML20009H516 + (12:45:29, 21 December 2024)
- ML20009H514 + (12:45:30, 21 December 2024)
- ML20009H513 + (12:45:30, 21 December 2024)
- ML20009H512 + (12:45:31, 21 December 2024)
- 05000327/LER-1981-080, Forwards LER 81-080/03L-0 + (12:45:32, 21 December 2024)
- ML20009H509 + (12:45:33, 21 December 2024)
- 05000335/LER-1981-036-03, /03L-0:on 810701,measured Discard Containment Pressure Transmitter Failed Intermittently.Cause Not Stated.Spare Transmitter (Fischer-Porter Model 50EN1071BCXANS) Used to Replace Original Transmitter + (12:45:34, 21 December 2024)
- ML20009H506 + (12:45:36, 21 December 2024)
- 05000335/LER-1981-036, Forwards LER 81-036/03L-0 + (12:45:38, 21 December 2024)
- ML20009H501 + (12:45:40, 21 December 2024)
- 05000335/LER-1981-035-03, /03L-0:on 810701,RCS Inventory Balance Indicated Unidentified Leakage Greater than 1 Gpm.Caused by Scratches on V2318.Seat Lapped & Disc,Stem & All Gaskets Replaced + (12:45:42, 21 December 2024)
- IR 05000245/1981008 + (12:45:45, 21 December 2024)
- ML20009H498 + (12:45:46, 21 December 2024)
- 05000335/LER-1981-035, Forwards LER 81-035/03L-0 + (12:45:47, 21 December 2024)
- ML20009H495 + (12:45:48, 21 December 2024)
- ML20009H494 + (12:45:49, 21 December 2024)