- ML20024B753 + (05:20:57, 21 December 2024)
- ML20024B752 + (05:20:58, 21 December 2024)
- ML20024B750 + (05:20:59, 21 December 2024)
- ML20024B751 + (05:20:59, 21 December 2024)
- ML20024B748 + (05:21:00, 21 December 2024)
- ML20024B749 + (05:21:00, 21 December 2024)
- PNO-II-83-052, during Insps Per IE Bulletin 83-02,cracks Identified in 33 of 91 Pipe Welds in Recirculation Sys & 14 of 32 Pipe Welds in RHR Sys.Caused by Igscc.Evaluation Ongoing + (05:21:02, 21 December 2024)
- ML20024B745 + (05:21:03, 21 December 2024)
- ML20024B746 + (05:21:03, 21 December 2024)
- ML20024B742 + (05:21:05, 21 December 2024)
- ML20024B743 + (05:21:05, 21 December 2024)
- ML20024B741 + (05:21:06, 21 December 2024)
- 05000309/LER-1983-020, Updated LER 83-020/01T-1:on 830607,HPCI Line Boron Concentration Not Verified.Caused by Inadequate Startup Procedures.Procedures Will Be Revised by 830715 + (05:21:08, 21 December 2024)
- ML20024B739 + (05:21:09, 21 December 2024)
- ML20024B738 + (05:21:10, 21 December 2024)
- 05000261/LER-1983-011-03, /03L-0:on 830605,circuit Breaker for Boron Injection Tank Heater Channel B Tripped.Caused by Component Failure Due to Normal End of Life.Failed Heater Replaced + (05:21:11, 21 December 2024)
- ML20024B735 + (05:21:13, 21 December 2024)
- ML20024B736 + (05:21:13, 21 December 2024)
- ML20024B734 + (05:21:14, 21 December 2024)
- ML20024B733 + (05:21:15, 21 December 2024)
- IR 05000322/1983019 + (05:21:17, 21 December 2024)
- IR 05000412/1983004 + (05:21:19, 21 December 2024)
- 05000305/LER-1983-014-03, /03L-0:on 830603,while Performing Monthly RHR Pump & Valve Surveillance Test,Containment Sump B Isolation Valve SI-350B Would Not Cycle Closed.Caused by Mechanical Interlock Sticking in Open Position + (05:21:21, 21 December 2024)
- TXX-3666, Submits Responses to 811112-14 Requests at ACRS 259th Meeting Re Containment Hydrogen Purge Sys Filters & Control Room Occupancy Vs Containment Leakage Rate + (05:21:22, 21 December 2024)
- 05000245/LER-1983-022-03, /03L-0:on 830603,time Delay Relay 590-125D Tripped During Turbine Control Valve Fast Closure Function & Calibr Test.Caused by Low Tolerance.Tolerance Bank Increased & Setpoints Decreased + (05:21:25, 21 December 2024)
- ML20024B724 + (05:21:27, 21 December 2024)
- ML20024B723 + (05:21:28, 21 December 2024)
- 05000305/LER-1983-015-03, /03L-0:on 830606,during Valve Timing Test for Td Auxiliary Feedwater Pump,Valve Failed to Electrically Open. Caused by Faulty Torque Switch & Maladjusted Tripper Cam. Valve Operator Rebuilt & Cam Reset + (05:21:29, 21 December 2024)
- IR 05000461/1983008 + (05:21:31, 21 December 2024)
- PNO-I-83-075, on 830705,reactor Tripped from 95% Power When MSIV Closed.Caused by Steam Line Isolation Spike Due to Increase in Condensate Demineralizer Resin.Water Sample Sent to Peach Bottom for Analysis.Rcic Being Reevaluated + (05:21:34, 21 December 2024)
- ML20024B719 + (05:21:35, 21 December 2024)
- ML20024B718 + (05:21:35, 21 December 2024)
- ML20024B717 + (05:21:37, 21 December 2024)
- 05000309/LER-1983-021, Updated LER 83-021/01T-0,re Control Rod Drop Analysis. Procedure Deficiency Specified in Determined Not Reportable.Procedure Changes Will Remain in Effect + (05:21:39, 21 December 2024)
- ML20024B714 + (05:21:40, 21 December 2024)
- IR 05000220/1983013 + (05:21:43, 21 December 2024)
- IR 05000309/1983011 + (05:21:45, 21 December 2024)
- ML20024B711 + (05:21:46, 21 December 2024)
- 05000220/LER-1983-011-03, /03L-0:on 830604,electromatic Relief Valve 121 Failed to Open.Caused by Dirty Pilot Due to Oxide Buildup During Extended Outage.Pilot Cleaned & Retested & Normal Shutdown Initiated + (05:21:48, 21 December 2024)
- ML20024B708 + (05:21:50, 21 December 2024)
- ML20024B705 + (05:21:52, 21 December 2024)
- ML20024B706 + (05:21:52, 21 December 2024)
- ML20024B703 + (05:21:53, 21 December 2024)
- ML20024B702 + (05:21:54, 21 December 2024)
- PNO-II-83-053, on 830705,workers Removed Concrete Block Shielding to Perform Maint on Valve,Leaving Unguarded Access Path to Reactor Containment.Guard Observed Sleeping at Torus Post.Security Evaluated Incidents During 830706 & 07 Insps + (05:21:56, 21 December 2024)
- ML20024B699 + (05:21:57, 21 December 2024)
- ML20024B698 + (05:21:58, 21 December 2024)
- 05000389/LER-1983-021-03, /03L-0:on 830602,waste Gas Decay Tank Oxygen Level Found Out of Tech Specs.Possibly Caused by in-leakage.Leaks Corrected + (05:22:00, 21 December 2024)
- ML20024B695 + (05:22:01, 21 December 2024)
- ML20024B694 + (05:22:04, 21 December 2024)
- ML20024B693 + (05:22:06, 21 December 2024)