- ML20076F596 + (07:43:13, 15 December 2024)
- 05000443/LER-1994-015, :on 940909,missed TS 4.0.5 Surveillance on Ms Drain (Msd) Valves Due to Inadequate Procedure.Msd Valve Stroke Tests Performed & Procedures Governing Repetitive Task Sheets Will Be Revised + (07:43:15, 15 December 2024)
- ML20076F588 + (07:43:16, 15 December 2024)
- 05000373/LER-1983-078-03, /03L-0:on 830719,LPCS Injection Valve Permissive Alarm Sounded on Panel 1H13-P601 W/Reactor Pressure at 600 Psig.Caused by Microswitch in Pressure Switch Stuck Closed. Switch Freed,Exercised & Recalibr + (07:43:17, 15 December 2024)
- JAFP-83-0554, Responds to NRC Re Violations Noted in IE Insp Rept 50-333/83-06.Corrective Actions:Out of Date Annunciator Response Procedures Revised.Pathway & Area Transversed by Employees Outside Restricted Area Surveyed + (07:43:18, 15 December 2024)
- AECM-83-0468, RO83-066/0:on 830709 & 13,triaxial Peak Recording Accelerographs Used for Seismic Monitoring of Auxiliary Bldg Foundation & Reactor Vessel Support Failed Surveillance. Caused by Damage Apparently Incurred from Const Activity + (07:43:19, 15 December 2024)
- ML20076F574 + (07:43:19, 15 December 2024)
- ML20076F573 + (07:43:20, 15 December 2024)
- 2CAN109402, Requests Relief from Performing Quarterly Reverse Flow Test for Each Individual Valve in Three Pairs of Charging Pump Discharge Check Valves to Be Installed in Series Configuration.Ist Relief Request CVCS-1 Encl + (07:43:22, 15 December 2024)
- ML20076F565 + (07:43:22, 15 December 2024)
- ML20076F564 + (07:43:23, 15 December 2024)
- 05000328/LER-1983-101-01, /01T-0:on 830806,during Pumpdown of Refueling Cavity to Perform Maint on Loop 4 RCS Cold Leg Nozzle Insp Plate,Train B RHR Pump Began to Cavitate.Caused by Loss of Suction Head + (07:43:24, 15 December 2024)
- 05000324/LER-1983-067-03, /03L-0:on 830724,while Performing Rpts,Reactor Low Water Recirculation Pump 2A Tripped When Temporary Electrical Jumper Removed.Caused by Removal of Wrong Jumper + (07:43:27, 15 December 2024)
- 0CAN068308, Notifies That 1 H Fire Barriers Installed by 830422,per 830329 Request for Schedular Exemption from App R Requirements for Installation of Barriers to 830501 + (07:43:28, 15 December 2024)
- JAFP-83-0436, Responds to NRC Re Violations Noted in IE Insp Rept 50-333/83-04.Corrective Actions:Two Surveillance Audits Re Limiting Conditions of Operations Performed.Program Addressing Audit Functions,Per Procedure 18.1,developed + (07:43:32, 15 December 2024)
- ML20076F535 + (07:43:32, 15 December 2024)
- 05000389/LER-1983-038-03, /03L-0:on 830712,during Startup Operations,Control Element Assemblies 54 & 17 Slipped Greater than 15 Inches from Groups During Withdrawal.Cause Unknown.Investigation Underway + (07:43:34, 15 December 2024)
- ML20076F531 + (07:43:35, 15 December 2024)
- ML20076F526 + (07:43:36, 15 December 2024)
- 05000254/LER-1983-030-03, /03L-0:on 830722,while Performing Core Spray Sys Motion Operated Valve Operability Check Qos 1400-2,discharge Valve Mo 1-1402-25A Failed to Open.Caused by Defective Circuit Breaker Feeding Valve.Breaker Replaced + (07:43:37, 15 December 2024)
- ML20076F521 + (07:43:38, 15 December 2024)
- 05000324/LER-1983-068-03, /03L-0:on 830725,drywell Equipment Drain Sump Flow Square Root Signal Converter 2-G16-FY-K600 Found Functioning Out of Tolerances.Caused by Instrument Drift. Instrument Will Be Replaced + (07:43:40, 15 December 2024)
- ML20076F508 + (07:43:41, 15 December 2024)
- 05000278/LER-1994-004-02, :on 940924,HPIS Inoperable When Steam Supply Valve Was Closed to Isolate Leak.Caused by Packing Leak on MO-3-23-15.Corrective Actions Being Developed.W/Undated Ltr + (07:43:42, 15 December 2024)
- 05000261/LER-1983-020-01, /01T-0:on 830803,w/unit at 79% Power,Current Tech Spec Cooldown Curves Determined to Be in Error,Per Review of New Draft Curves Based on Analysis of Reactor Vessel Surveillance Capsule.Curves Revised on 830804 + (07:43:48, 15 December 2024)
- ML20076F503 + (07:43:49, 15 December 2024)
- 05000338/LER-1983-052-03, /03L-0:on 830729,individual Rod Position Indication for Rod J-13 Indicated 110 Steps Instead of Required 228.Caused by Bad Connection of Signal Conditioning Module.Connection Reseated + (07:43:50, 15 December 2024)
- ML20076F500 + (07:43:51, 15 December 2024)
- ML20076F499 + (07:43:52, 15 December 2024)
- 05000315/LER-1983-068-03, /03L-0:on 830715,ice Condenser Intermediate Deck Door Found Frozen Shut.Caused by Failed Defrost Heater for Handling Unit 3-7A.Ice Removed & Defrost Heater Replaced + (07:43:53, 15 December 2024)
- ML20076F492 + (07:43:54, 15 December 2024)
- ML20076F491 + (07:43:55, 15 December 2024)
- 05000302/LER-1983-028-03, /03L-0:on 830722,HPI Pump Motor (MUP-1C) Failed. Caused by Personnel Inadvertently Securing Cooling Water Supplied by DCP-1B.Precautionary Tags Placed on Control Board.Operators Cautioned + (07:43:56, 15 December 2024)
- 05000339/LER-1983-058-03, /03L-0:on 830717,18 & 25,individual Rod Position Indicators Deviated from Group Demand Position.Caused by Instrument Drift,Generic to Westinghouse Analog Position Sys.Channels Recalibr + (07:43:58, 15 December 2024)
- ML20076F473 + (07:43:59, 15 December 2024)
- ML20076F468 + (07:44:00, 15 December 2024)
- ML20076F470 + (07:44:00, 15 December 2024)
- 05000331/LER-1983-027-03, /03L-0:on 830803,RCIC Discharge Pressure Indicator Found Indicating Improperly.Caused by out-of-calibr Pressure Transmitter.Transmitter Calibr + (07:44:02, 15 December 2024)
- IR 05000346/2020301 + (07:44:03, 15 December 2024)
- W3P83-2783, Forwards Vital Equipment Block Diagram,Per 830725 Request. Diagram Withheld + (07:44:04, 15 December 2024)
- ML20076F463 + (07:44:04, 15 December 2024)
- ML20076F462 + (07:44:05, 15 December 2024)
- ML20076F461 + (07:44:06, 15 December 2024)
- ML20076F459 + (07:44:06, 15 December 2024)
- ML20076F458 + (07:44:07, 15 December 2024)
- AECM-83-0477, RO 83-070/0:on 830716,listed Fire Rated Doors Blocked Open to Support Planned Maint Activities in Auxiliary & Control Bldgs.Fire Watches Established.Doors Expected to Be Restored by 830930 + (07:44:10, 15 December 2024)
- ML20076F454 + (07:44:11, 15 December 2024)
- 05000260/LER-1983-041-03, /03L-0:on 830721,following Preconditioning Operations,Tech Spec Limit for Linear Heat Generation Rate Exceeded in Four Nodes.Caused by Insufficient Communication Between Operators During Flow Increases + (07:44:13, 15 December 2024)
- 1CAN088309, Provides Current Status of Dresser Safety Valve Settings. Valve Settings Are -48,-93,+5 & W/No Lift Restriction. Adjustments Assure Safety Valves Will Achieve 100% of ASME Rated Capacity + (07:44:14, 15 December 2024)
- JPN-94-051, Forwards Application for Amend to License DPR-59,changing TS Re Safety/Relief Valve Testing Requirements + (07:44:14, 15 December 2024)
- ML20076F443 + (07:44:15, 15 December 2024)