Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20082F168 + (ML20082F168)
- 05000327/LER-1983-143-03, /03L-0:on 831021,review of Surveillance Tests Revealed That on 831006,waste Gas Decay Tank H Had High Oxygen Concentration of 2.2%.Caused by Vol Control Tank Returned to Svc After Being Open to Atmosphere + (ML20082F174)
- ML20082F178 + (ML20082F178)
- ML20082F182 + (ML20082F182)
- 05000278/LER-1991-011-03, :on 910710,RPS Half Scram Occurred When RPS B Motor Generator Set Outpoint Breaker Tripped During Troubleshooting.Caused by RPS M/G Set Outpoint Breaker Trip. Scram & Isolations Reset + (ML20082F184)
- ML20082F186 + (ML20082F186)
- ML20082F189 + (ML20082F189)
- BSEP-83-3724, Ro:On 831115,while Performing Addl Insps on Recirculation Piping,Per IE Bulletin 83-02 & 831026 Order,Determined Two Addl Welds in Suction Piping to Recirculation Pump 2B Had Indication of Intergranular Stress Corrosion Cracking + (ML20082F190)
- ML20082F192 + (ML20082F192)
- ML20082F193 + (ML20082F193)
- 05000361/LER-1983-133-03, /03L-0:on 831007,reactor Trip Occurred.During post-review Noted That ex-core Linear Power Level Channel C Failed.Caused by Failed Linear Amplifier Card.Card Replaced + (ML20082F199)
- 05000282/LER-1991-010-01, :on 910719,auto-start of Control Room Ventilation Sys Occurred Due to Spurious Radiation Monitor Actuation During Monitor Calibration.Caused by Procedure Inadequacy.Affected Procedure Revised + (ML20082F200)
- ML20082F202 + (ML20082F202)
- ML20082F204 + (ML20082F204)
- ML20082F211 + (ML20082F211)
- ML20082F214 + (ML20082F214)
- 05000318/LER-1983-060-03, /03L-0:on 831019,while at 70% Power,Water from Clogged Control Room Toilet Entered Control Room & Dripped Down Ceiling Into Cable Spreading Room,Shorting Components in Coil Power Programmers.Update Rept Expected + (ML20082F219)
- ML20082F228 + (ML20082F228)
- 05000362/LER-1983-094-03, /03L-0:on 831012,plant Protection Sys Channel C Observed in Tripped Condition.Caused by Test/Calibr Card Failure.Card Removed & New Card Installed & Tested + (ML20082F230)
- RBG-16-396, Final Deficiency Rept DR-72 Re Concrete drilled-in expansion-type Anchor Installation (Torquing),Testing & Insp.Item Determined Not Reportable Per 10CFR50.55(e) + (ML20082F238)
- 05000482/LER-1995-001, :on 950308,reactor Tripped Resulting in Loss of Two CW Sys Pumps,Condenser Vacuum & Two Rcps.Caused by Failure of RT Manual Actuation Switch Contacts to Maintain Continuity.Surveillance Procedures Revised + (ML20082F248)
- 05000362/LER-1983-087-01, /01T-0:on 831026,plant Monitoring Sys Computer Failed While Entering Limiting Condition of Operation 3.10.2.Caused by Moving Head Disk Error in Computer.Cause of Disk Error Unknown + (ML20082F255)
- ML20082F258 + (ML20082F258)
- 05000247/LER-1983-038-03, /03L-0:on 831011,during Refueling Water Storage Tank Level Surveillance Test,One of Two Level Alarm Set Points Found Above Max Level.Cause by Drift of Foxboro Model 635-BROCHA Level Alarm Bistable.Bistable Reset + (ML20082F268)
- 05000362/LER-1983-095-03, /03L-0:on 831015,channel a Accident Monitoring Instrumentation for Pressurizer Water Level Indication Declared Inoperable.Caused by Minor Leakage from Ref Leg Tubing Fitting & Pipe Plug.Leak Repaired + (ML20082F271)
- ML20082F273 + (ML20082F273)
- ML20082F280 + (ML20082F280)
- ML20082F287 + (ML20082F287)
- ML20082F293 + (ML20082F293)
- 05000370/LER-1991-006-05, :on 910708,emergency Personnel Hatch Between Upper & Lower Containment Discovered Unlatched W/Tamper Seals Intact.Cause Not Determined.New Tamper Seals Installed & Plan Will Be Developed to Adjust Hatches + (ML20082F294)
- 05000414/LER-1991-009-01, :on 910710,discovered That Annulus Ventilation Sys Flow Rates Exceeded 8,700 CFM Limit.Caused by Failure to Complete Procedure Change & Mgt Deficiency. Flow Rates Adjusted + (ML20082F296)
- 05000413/LER-1991-015, :on 910710,reactor Trip Occurred as Result of Turbine Trip Above P-9 (69% Reactor Power).Caused by Loss of Both Main Feedwater Pumps on Low Suction Pressure.Tubing Replaced W/New Copper Tubing + (ML20082F299)
- AECM-83-0744, RO 83-102/0:on 831014,radwaste Bldg 93-ft Elevation Fire Door OR122 Blocked Open to Support Planned Maint Activities. Fire Watches Established.Door Will Be Restored by 831230 + (ML20082F302)
- 05000327/LER-1991-015, :on 910708,fire Watch Patrol Not Performed for Approx 4 H.Caused by Inadequate Shift Turnover,Resulting from Ineffective Communication of Revised Turnover Process. Fire Watch Reestablished + (ML20082F305)
- 05000285/LER-1991-015, :on 910710,personnel Declared Radiation Monitor RM-060 Inoperable Due to Flow Totalizer,Located Inside Monitor Cabinet,Not Seismically Mounted.Caused by Inadequacies in Design Process + (ML20082F307)
- ML20082F311 + (ML20082F311)
- 3F1183-05, Assures Adequacy of Station Electric Distribution Sys Voltage.Upon Completion of Mods to Second Level Undervoltage Relay Sys,Tech Spec Change Requests Will Be Submitted to Cover Surveillance Requirements + (ML20082F312)
- W3P83-3827, Forwards Water Chemistry Rept for Groundwater Sample Associated W/Basemat.Rept Info Provided Orally at 841103 Meeting + (ML20082F316)
- ML20082F332 + (ML20082F332)
- ML20082F335 + (ML20082F335)
- ML20082F344 + (ML20082F344)
- ML20082F362 + (ML20082F362)
- ML20082F367 + (ML20082F367)
- ML20082F368 + (ML20082F368)
- 05000362/LER-1983-080-03, /03L-0:on 831012,during RCS Water Inventory Balance,Min Temp Dropped Below Tech Spec Min.Caused by Operator Delay in Diluting RCS to Compensate for Xenon Buildup.Min Temp Specs Being Reviewed + (ML20082F369)
- 05000445/LER-1991-020, :on 910713,reactor Trip Resulting from Erratic Operation of Main Turbine Electrohydraulic Controller Occurred Due Turbine Trip Initiated by Hi-Hi Levels of SGs 1 & 2.Testing & Design Mods Performed + (ML20082F375)
- ML20082F383 + (ML20082F383)
- 05000382/LER-1991-011, :on 910528,reactor Trip Occurred.Caused by Faulty Relay That Prevented Electrical Bus Transfer.Faulty Relay Replaced & Procedures Revised + (ML20082F384)
- ML20082F390 + (ML20082F390)
- ML20082F407 + (ML20082F407)
- 05000318/LER-1991-007, :on 910711,B Train Failure Occurred for Number 22 Bast Heater Circuit While Number 12 EDG Was Out of Svc. Caused by Component Failure.Replaced Fuses & Verified Integrity & Function of Control Power Circuit + (ML20082F413)