- ML20041B363 + (ML20041B363)
- 05000331/LER-1982-005, Forwards LER 82-005/03L-0 + (ML20041B366)
- 05000305/LER-1982-003, Forwards LER 82-003/03L-0 + (ML20041B368)
- ML20041B372 + (ML20041B372)
- 05000331/LER-1982-005-03, /03L-0:on 820114,torus Water Level Recorder Lr 4385 Found in Failed Downscale Condition.Caused by Excessive Heat Buildup in Recorder Cabinet Due to Poor Ventilation. Cabinet Being Kept Open Temporarily to Increase Cooling + (ML20041B375)
- ML20041B376 + (ML20041B376)
- 05000305/LER-1982-003-03, /03L-0:on 820116,1A Zone SV Fan Started Automatically.Caused by Solenoid Valve Failure Due to Burned Out Coil in Closed Position Which Automatically Opened Damper.Coil Replaced & Sys Tested Satisfactorily + (ML20041B379)
- ML20041B380 + (ML20041B380)
- 05000331/LER-1982-004, Forwards LER 82-004/03L-0 + (ML20041B381)
- IR 05000387/1981018 + (ML20041B383)
- ML20041B386 + (ML20041B386)
- ML20041B387 + (ML20041B387)
- 05000155/LER-1982-003, Forwards LER 82-003/01T-0 + (ML20041B389)
- 05000331/LER-1982-004-03, /03L-0:on 820115,drywell High Pressure Switch Ps 4315B Tripped out-of-spec.Caused by Instrument Drift. Switch Recalibr + (ML20041B391)
- ML20041B392 + (ML20041B392)
- ML20041B394 + (ML20041B394)
- ML20041B395 + (ML20041B395)
- 05000155/LER-1982-003-01, /01T-0:on 820128,investigation of Increased Water Collection in Reactor Containment Sump Revealed through-wall Leakage of 0.15 Gpm in Pipeway Air Cooler Unit B.Caused by Corrosion.Tubing Repaired & Unit Returned to Svc + (ML20041B396)
- 05000331/LER-1982-002, Forwards LER 82-002/03L-0 + (ML20041B397)
- 05000282/LER-1981-029-03, During Surveillance Test of Bus 16 Undervoltage Relays,Error in Disconnecting Test Equipment Resulted in Blown Fuse for A-phase Relays.Fuses Replaced & Normal Power Restored to Bus + (ML20041B399)
- ML20041B400 + (ML20041B400)
- PNO-III-82-020, a:on 820211 Meeting Held Re 820208 Finding of Tritium in Offsite Groundwater Samples at Sheffield Low Level Waste Burial Site.Hearing Will Be Held on 820216 to Resolve Permanent Site Closure Issues + (ML20041B401)
- ML20041B402 + (ML20041B402)
- 05000306/LER-1981-030-03, During Testing,Degraded Voltage Relay 27A1/B25 Found W/Voltage Setpoint Outside Allowable Band.Exact Cause Unknown.Relays Recalibr & Found to Operate Correctly + (ML20041B404)
- 05000331/LER-1982-002-03, /03L-0:on 820112,reactor Core Isolation Cooling Steam Line High Flow Pressure Differential Indicating Switches PDIS2441 & 2442 Tripped at 118 & 125 Inches of Water.Caused by Instrument Drift.Switches Recalibr + (ML20041B405)
- ML20041B406 + (ML20041B406)
- 05000368/LER-1982-003, Forwards LER 82-003/03L-0 + (ML20041B407)
- ML20041B409 + (ML20041B409)
- ML20041B411 + (ML20041B411)
- IR 05000483/1981025 + (ML20041B415)
- 05000315/LER-1982-005-03, /03L-0:on 820115,during Surveillance Testing, Leakage Rate on Inner Door of Personnel Air Lock at 650 Ft Elevation Exceeded Tech Specs Limit.Caused by Broken Threaded Nipple Where Air Supply Line Enters Door Seal Area + (ML20041B417)
- ML20041B418 + (ML20041B418)
- ML20041B420 + (ML20041B420)
- ML20041B422 + (ML20041B422)
- IR 05000220/1981020 + (ML20041B424)
- ML20041B425 + (ML20041B425)
- 05000315/LER-1982-006-03, /03L-0:on 820123,during Surveillance Testing, Valve 1-WMO-737,emergency Svc Water Discharge from W Component Cooling Water Heat Exchanger Would Not Close. Cause Could Not Be Determined.Valve Cycled Manually + (ML20041B428)
- ML20041B429 + (ML20041B429)
- ML20041B431 + (ML20041B431)
- ML20041B432 + (ML20041B432)
- ML20041B434 + (ML20041B434)
- IR 05000344/1981035 + (ML20041B436)
- ML20041B437 + (ML20041B437)
- IR 05000322/1982003 + (ML20041B440)
- ML20041B441 + (ML20041B441)
- ML20041B442 + (ML20041B442)
- ML20041B444 + (ML20041B444)
- ML20041B445 + (ML20041B445)
- ML20041B447 + (ML20041B447)
- ML20041B449 + (ML20041B449)