- 05000324/LER-1979-081-03, /03L-0:on 790926,both Doors to Reactor Bldg Breezeway Airlock Could Be Opened Simultaneously.Caused by Loose Door Position Solenoids Preventing Interlock Feature from Working.Lock Washers Installed to Ensure Tightness + (ML19209C421)
- ML19209C422 + (ML19209C422)
- ML19209C424 + (ML19209C424)
- ML19209C425 + (ML19209C425)
- 05000324/LER-1979-084, Forwards LER 79-084/03L-0 + (ML19209C426)
- ML19209C427 + (ML19209C427)
- ML19209C428 + (ML19209C428)
- 05000265/LER-1979-018-03, /03L-0:on 790905,spray Valve Mo 2-1001-23B Found to Trip Breaker When Operated.Caused by Broken Bolt in Valve Motor Operator.All Four Bolts on Motor Operator Replaced + (ML19209C429)
- ML19209C430 + (ML19209C430)
- ML19209C431 + (ML19209C431)
- 05000324/LER-1979-084-03, /03L-0:on 790912,1/8-inch Diameter Hole Developed in Nuclear Svc Water Header on Elbow Between 2SW-103-30-157 & 2SW-20-157.Caused by Cement Lining Becoming Detached from Pipe,Allowing Corrosion to Create Hole.Pipe to Be Repl + (ML19209C432)
- ML19209C433 + (ML19209C433)
- 05000338/LER-1979-102, Forwards LER 79-102/03L-0 + (ML19209C434)
- ML19209C435 + (ML19209C435)
- ML19209C436 + (ML19209C436)
- ML19209C437 + (ML19209C437)
- ML19209C438 + (ML19209C438)
- 05000295/LER-1979-068, Forwards LER 79-068/01T-0 + (ML19209C439)
- ML19209C441 + (ML19209C441)
- 05000338/LER-1979-102-03, /03L-0:on 790911,bistable for Containment high- Risk Pressure Channel I Actuated High Pressure Signal & Failed in Low Pressure State During Test.Caused by Bad Signal Comparator Card.Defective Card Replaced & Calibr + (ML19209C442)
- 05000295/LER-1979-068-01, /01T-0:on 790917,seismic Anchor Point SIA-4 for RHR Hot Leg Injection Lines & Cold Leg Crosstie Lines Found Underdesigned.Caused by A/E Design Deficiency.Temporary Supports Installed.Redesigning New Permanent Support + (ML19209C443)
- ML19209C444 + (ML19209C444)
- ML19209C445 + (ML19209C445)
- ML19209C446 + (ML19209C446)
- 05000295/LER-1979-065, Forwards LER 79-065/03L-0 + (ML19209C447)
- ML19209C448 + (ML19209C448)
- ML19209C449 + (ML19209C449)
- ML19209C450 + (ML19209C450)
- ML19209C451 + (ML19209C451)
- ML19209C452 + (ML19209C452)
- 05000338/LER-1979-114-03, /03L-0:on 790912,temp at Top Corner of Steam Generator Support Exceeded Tech Spec Limit.Caused by Heaters Being Left on Too Long When Control Resistance Temp Detector Failed to Cycle Heaters Automatically + (ML19209C453)
- 05000338/LER-1979-113-03, /03L-0:on 790912,pressurizer Level Channel II Gave Erratic Indication on Control Board.Cause Unknown.Testing Revealed No Problems + (ML19209C454)
- ML19209C455 + (ML19209C455)
- ML19209C457 + (ML19209C457)
- ML19209C458 + (ML19209C458)
- ML19209C459 + (ML19209C459)
- ML19209C460 + (ML19209C460)
- ML19209C461 + (ML19209C461)
- ML19209C462 + (ML19209C462)
- ML19209C463 + (ML19209C463)
- ML19209C464 + (ML19209C464)