- 05000206/LER-1989-005, :on 890220 & 0317,emergency Diesel Generator 2 Automatically Started by Sequencer 2 on Loss of Bus Signal. Probably Caused by Partial Cycling of Relay Designed to Actuate During Undervoltage.Components Tested + (ML13331A344)
- 05000206/LER-1989-009, :on 890308,determined That Several Effluent Monthly Repts Had Exceeded 31-day Surveillance Interval. Caused by Negligence on Part of Effluent Engineers.Chemistry Procedure Revised Requiring That Surveillances Be Performed + (ML13331A347)
- 05000206/LER-1989-024, :on 890929,determined That Plant Could Be Placed in Configuration Which Could Result in Degraded Containment Spray Sys Flow.Caused by Weak Engineering & Technical Support.Controls Established + (ML13331A348)
- ML13331A349 + (ML13331A349)
- ML13331A350 + (ML13331A350)
- 05000206/LER-1989-031, :on 891228,determined That Auxiliary Feedwater Could Produce Flow Rate Exceeding Water Hammer Design Basis Max.Apparently Caused by Error in Modeling Turbine Driven Pump.Worker Placed at Control Room Panel + (ML13331A351)
- ML13331A352 + (ML13331A352)
- ML13331A353 + (ML13331A353)
- 05000206/LER-1989-030, :on 891228,determined That Previous Evaluations of post-loss of Cooling Accident ECCS Recirculation Flow Incorrectly Credited.Caused by Programmatic Weaknesses Noted in Util 881003 Submittal.Valve Closed + (ML13331A354)
- 05000206/LER-1989-032, :on 890103,discovered That Tech Spec 18-month Insp of Former Security Uninterruptible Power Supply Battery D-20 Not Performed Following Installation of Temporary Mod. Mod Procedure Enhanced + (ML13331A355)
- ML13331A356 + (ML13331A356)
- 05000206/LER-1990-001, :on 900120,dc Bus Feeder Breakers Opened During Dc Ground Troubleshooting,Resulting in Violation of Tech Spec 3.3.1.Ground Attributed to Degraded Cable Installation & Corrosion Conduit Joint.Ground Cleared + (ML13331A358)
- ML13331A359 + (ML13331A359)
- 05000206/LER-1990-002, :on 900124,required Sample/Analysis Not Performed When Power Change Exceeded 15% within 1 H.Caused by Personnel Error.Individual Reprimanded & Event Discussed w/on-shift Operations Personnel + (ML13331A360)
- PNO-V-90-009, on 900302,earthquake Occurred in Southern California.Quake Felt at Plant But Did Not Trigger Recording Instruments.No Further Licensee Actions Planned.Preliminary Notification Issued for Info Only + (ML13331A361)
- ML13331A363 + (ML13331A363)
- 05000206/LER-1990-003, :on 900126,discovered That Tech Spec 4.15.8 Not Fully Implemented as Required by Newly Issued Amend Which Required Implementation by 891215.Caused by Personnel Error. Station Procedure SO123-III-6.6 Revised + (ML13331A364)
- ML13331A366 + (ML13331A366)
- ML13331A369 + (ML13331A369)
- ML13331A371 + (ML13331A371)
- 05000206/LER-1989-033, :on 900131,discovered That RCS Sample for Gross Activity Determination Not Taken Prior to Entry Into Mode 4 on 890624.Caused by Failure to Incorporate New Chemistry Procedure.Procedures Revised & Incorporated + (ML13331A373)
- ML13331A374 + (ML13331A374)
- ML13331A375 + (ML13331A375)
- 05000206/LER-1989-021, :on 890803,reactor Tripped on Low Flow Due to Instrument Cable Degradation.Caused by Polyethylene Insulation Becoming Brittle Due to Oxidation.Cable W/Loss of Insulation to Ground Replaced + (ML13331A376)
- ML13331A377 + (ML13331A377)
- ML13331A378 + (ML13331A378)
- ML13331A379 + (ML13331A379)
- 05000206/LER-1990-005, :on 900215,containment Spray Sys Flow Restricting Valve CV-518 Actuator Failure Alarm Annunicated.Caused by Accumulator Pressure Decreasing Due to Cold Weather.Pressure Indication Will Be Added + (ML13331A380)
- ML13331A381 + (ML13331A381)
- ML13331A382 + (ML13331A382)
- ML13331A384 + (ML13331A384)
- 05000206/LER-1990-006, :on 900219,during Testing of Valve fail-safe Position Associated W/Pneumatic Control Valves for Chemical & Vol Control Sys,Discovered That Control Valve Failed to Open Upon Loss of Instrument Air.Cause Unknown + (ML13331A385)
- ML13331A386 + (ML13331A386)
- 05000206/LER-1989-023-02, :on 890918,manual Reactor Trip Occurred Following Dropped Shutdown Bank Rods.Caused by Failed Contactor Coil & Blown Fuse.Contactor Coil & Fuse Replaced w/in-kind Parts + (ML13331A388)
- ML13331A389 + (ML13331A389)
- ML13331A391 + (ML13331A391)
- ML13331A393 + (ML13331A393)
- ML13331A394 + (ML13331A394)
- ML13331A395 + (ML13331A395)
- ML13331A396 + (ML13331A396)
- ML13331A397 + (ML13331A397)
- 05000206/LER-1990-004, :on 900223,determined That Such Leakage Could Be Inconsistent W/Basis of Tech Spec 3.1.4, Leakage & Leakage Detection Sys Relative to Extended Loss of All Ac Power.Caused by Inadequate Procedures + (ML13331A398)
- ML13331A399 + (ML13331A399)
- ML13331A401 + (ML13331A401)
- 05000206/LER-1990-008, :on 900411,safety Injection Pump Breaker Declared Inoperable Which Resulted in Tech Spec 3.0.3 Entry. Caused by Holding Pawl Failure.Circuit Breaker Replaced & New Driving & Holding Pawls Will Be Installed + (ML13331A402)
- 05000206/LER-1990-009, :on 900413,testing of Six safety-related 1/2 Inch Valves in Secondary Chemical Feed Sys Not Performed. Caused by Inadequate Adminstrative Controls.Procedure for Inservice Testing Program Will Be Revised + (ML13331A403)
- ML13331A404 + (ML13331A404)
- ML13331A406 + (ML13331A406)
- PNO-V-90-025, on 900515,operator Manually Tripped Reactor When Steam Generator Level Indicated Less than 5%.Caused by Lead Inadvertently Grounded While Connecting Electrical Leads for Valve Position Indicator.Design Change Planned + (ML13331A409)
- ML13331A410 + (ML13331A410)
- ML13331A412 + (ML13331A412)