Forwards Supplemental Response to NRC Bulletin 88-010, Suppl 1, Nonconforming Molded Case Circuit Breakers. Circuit Breakers Traceable to Original Plant Const Order Received Prior to Aug 1983 & Acceptable
ML13331A374
Person / Time
Site: San Onofre  
Issue date: 03/12/1990
From: Nandy F
SOUTHERN CALIFORNIA EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-88-010, IEB-88-10, NUDOCS 9003150366
Download: ML13331A374 (15)


Text

Southern California Edison Company 23 PARKER STREET IRVINE. CALIFORNIA 92718 F. R. NANDY March 1.2, 1990 TELEPHONE MANAGER OF NUCLEAR LICENSING (714) 587-5400 U. S. Nuclear Regulatory Commission Attention:

Document Control Desk Washington, D.C. 20555 Gentlemen:

Subject:

Docket Nos. 50-206, 50-361 and 50-362 Response to NRC Bulletin 88-10, Supplement 1 San Onofre Nuclear Generating Station Units 1, 2 and 3

References:

1) March 30, 1989 letter from M. 0. Medford (SCE) to Document Control Desk (NRC);

Subject:

Response to NRC Bulletin 88-10

2) September 6, 1989 letter from R. M. Rosenblum (SCE) to Document Control Desk (NRC);

Subject:

Supplement Report No. 1 for NRC Bulletin 88-10

3)

November 16, 1989 letter from F. R. Nandy (SCE) to Document Control Desk (NRC);

Subject:

Response to NRC Bulletin 88-10, Supplement 1 This letter provides, as Enclosure 1, a supplement to Southern California Edison's (SCE's) response to NRC Bulletin 88-10 Supplement 1, "Nonconforming Molded Case Circuit Breakers."

SCE's original NRC Bulletin 88-10 response was provided by Reference 1.

Reference 2 supplied additional information on Bulletin 88-10 regarding traceability verification for installed and spare molded case circuit breakers (MCCBs).

In Reference 3, SCE addressed seven clarifications to Bulletin 88-10, which the NRC issued as Positions 1 through 7 in Supplement 1 to the Bulletin. As documented in Reference 3, our evaluations of the seven Supplement 1 Positions concluded that the previous SCE submittals (References 1 and 2) were consistent with five of the seven positions, the two exceptions being NRC Positions 1 (Traceability of Circuit Breaker Procurement) and 5 (Use of Nonconforming Circuit Breakers as Spares).

In Reference 3, we discussed plant modifications which had been completed to address Position 5 and committed to supply the required additional information in response to Position 1.

F: I J

i T 11 11 Cii:

C.

0~~_~

0 Document Control Desk March 12, 1990 This submittal provides the SCE response to Position 1 of NRC Bulletin 88-10, Supplement 1. Position 1 states: "If CBs are traceable to an original plant construction order and the CBs were received prior to August 1983, there is reasonable assurance that the CBs are acceptable and no additional traceability is required."

Use of this NRC Position 1 has allowed us to reclassify 167 spare MCCBs as traceable which were previously classified as untraceable. These 167 MCCBs have been deleted from the previously submitted list of untraceable spare MCCBs. A revised list of nontraceable spare MCCBs is provided as Attachment 2 to Enclosure 1 of this submittal.

This Position 1 response does not change any conclusions presented in our previous Supplement 1 submittal for the other six NRC Positions (Reference 3), and it completes all SCE required responses to NRC Bulletin 88-10, Supplement 1.

In order to complete all other required NRC Bulletin 88-10 responses, SCE still needs to submit two additional reports as committed to in Reference 1.

These reports will summarize the testing results for MCCBs installed in Units 1 and 3. The submittal dates for these reports are 30 days following startup from the Unit 1 Cycle 11 and Unit 3 Cycle 5 refueling outages, respectively.

The currently estimated completion dates for these two refueling outages are November 28, 1990, for Unit 1 and July 1, 1990, for Unit 3.

Please let me know if you have any questions on SCE responses or commitments on NRC Bulletin 88-10 or Supplement 1.

Respectfully submitted, By:

F. R. Nandy Manager of Nuclear Licensing Subscribed and sworn to before me this

/-

d day o f Q-t.C o i

/9%0 OFFICIAL SEAL MICHELE R. KAHAL NOTARY PUBLIC - CALIFORNIA o

PRINCIPAL OFFICE IN ORANGE COUNTY n,,

My Commission Exp. Dec. 28, 1990 Ntary Public in the State of California cc:

J. B. Martin, Regional Administrator, NRC Region V C. Caldwell, NRC Senior Resident Inspector, San Onofre Units 1, 2 and 3

ENCLOSURE 1

SUBJECT:

NRC Bulletin 88-10 Supplement 1 Nonconforming Molded Case Circuit Breakers-(MCCBs)

Addition to Original SCE Response I.

REFERENCES

1)

March 30, 1989 letter from M.O. Medford (SCE) to Document Control Desk (NRC);

Subject:

Response to NRC Bulletin 88-10.

2)

September 6, 1989 letter from R.M. Rosenblum (SCE) to Document Control Desk (NRC);

Subject:

Supplement Report No.1 for NRC Bulletin 88-10.

3)

November 16, 1989 letter from F.R. Nandy (SCE) to Document Control Desk (NRC);

Subject:

Response to NRC Bulletin 88-10, Supplement 1.

II.

SCOPE In response to NRC Bulletin 88-10 Supplement 1, Southern California Edison (SCE) reviewed our previousBulletin 88-10 submittals (References 1 and 2) against the additional clarifications of the Bulletin supplement (NRC positions 1 through 7).

This review indicated that our previous submittals were consistent with the supplement clarifications except for NRC positions 1 and 5.

SCE completed and submitted the required corrections for NRC position 5 in Reference 3. Additional time was required to complete our review in response to NRC position 1.

The review for NRC Position 1 is now complete for San Onofre Nuclear Generating Station (SONGS) Units 1, 2 and 3. The results are summarized in this additional supplement to the Original SCE Response. It does not change any findings or corrections provided in the SCE Response to NRC Bulletin 88-10 Supplement 1 for the other six NRC Positions.

0 0

III. PREVIOUS SCE RESPONSE NRC Bulletin 88-10 states:

Item 4:

Identify and verify the traceability of all Molded Case Circuit Breakers that have been purchased between August 1, 1983 and August 1, 1988, and installed in safety related applications as replacements or installed during modifications.

Item 1:

Identify and verify the traceability of all Molded Case Circuit Breakers purchased prior to August 1, 1988 that are being maintained as stored spares for safety related applications.

NRC Bulletin 88-10, Supplement 1, NRC Position 1 states:

"If MCCBs are traceable to an original plant construction order and the MCCBs were received prior to August 1, 1983, there is reasonable assurance that the MCCBs are acceptable and no additional traceability is required."

The finding for NRC Position 1 in SCE's Response to Supplement 1 states:

"SCE traceability investigation was extended to all spare MCCBs regardless of the purchase date. As a result, SCE did not remove MCCBs received prior to August 1, 1983, or MCCBs purchased for original construction from this traceability effort. The determination of traceability was based on verifiable purchase order documentation only. This effort was documented in Appendix C of the Original SCE Response."

The finding further states:

"Based on the clarification provided in NRC Position 1, SCE will update our original response to designate MCCBs received prior to August 1, 1983, and which are traceable to an original plant construction order as traceable per NRC Bulletin 88-10 requirements."

2

IV.- REVISED SCE RESPONSE TO NRC POSITION 1 Based on the SCE finding stated for NRC Bulletin 88-10 Supplement 1 Position 1, SCE has reviewed the Spare and Installed Population of MCCBs to determine which were procured as original construction and thus might be designated as traceable to the circuit breaker manufacturer.

This was intended to establish the acceptance of MCCBs which had otherwise been designated as not traceable to the circuit breaker manufacturer. SCE considers MCCBs as traceable to an original plant construction order if they were: (1) installed in original equipment assemblies during either initial plant construction or major system modifications; or (2) procured as spares under the original equipment purchase order or as part of the initial order of spare parts supplied by the equipment manufacturer.

The MCCB traceable population was not included in this review as they had already been determined acceptable under rigorous Quality Assurance investigation. A major portion of the Purchace Orders (POs) for traceable MCCBs are also of original construction and would otherwise be under consideration for Position 1.

Of the nontraceable MCCB population, SCE identified 11 POs representing 220 MCCBs which were for original construction. contains a description of these 11 POs.

SCE identified this group of MCCBs in conjunction with other actions which are described in the SCE Response to Supplement 1 for NRC Position 4. The 11 POs applied to either original equipment assemblies or the initial supply of spare parts.

In each case, the equipment manufacturer accepted Title 10 CFR quality assurance and reporting requirements (i.e. Part 21 and Part 50 Appendix B).

The 220 MCCBs associated with the 11 POs are spares in quarantine and are not included in the Installed Population.

Seven of the 11 POs (involving 167 MCCBs) have MCCB receive dates prior to August 1, 1983.

Therefore, in accordance with NRC Position 1 these 167 MCCBs are now considered traceable.

Appendix A (non traceable MCCBs) from the Original SCE Response is hereby revised to reflect the change in status in MCCB traceability status for these 167 MCCBs. A revised Appendix A (with the 167 MCCBs deleted) is included as reflecting this change in MCCB status from nontraceable to traceable.

3

There are no further corrections needed to SCE's response to NRC Bulletin 88-10 Supplement 1 based on the review summary described above for NRC Position 1. This additional response completes the reporting actions which were committed to in SCE's Response to Supplement 1 of NRC Bulletin 88-10.

4

ATTACHMENT 1 MCCB PURCHASE ORDERS REVIEWED PURCHASE MANUFACTURER INTENDED USE RECEIVED ORDER DATE 65900977 Brown Boveri 4160 V Switchgear 12/15/82 65901912 Foxboro Transmitters 5/15/83 (Foxboro) 8D054017 Foxboro Aux Feedwater 12/10/84 8N074032 C&D Batteries Battery Charger 2/12/85 8N084016 Foxboro 2ARPS Power Supply 12/19/84 8N2N4001 Brown Boveri 480 V Load Centers 6/7/85 B8273001 Delaval Diesel Generators 3/4/77 G8203541 Square D Diesel Generators 8/8/78 480 V MCC's S5903351 GTE Sylvania 125 V DC Dist.

6/26/81 Switchgear S5903611 Brown Boveri 4160 V Switchgear 7/26/82 S5990021 Combust Engr NSSS 6/26/81 Page No.

1 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A Nontraceable MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL Purchase Order 441207-6-0002-01 253 1

NONE RSO-1544-86

/ /

NUTHERM GE TED1 254 1

NONE RSO-1544-86

/

/

NUTHERM GE TED1 260 1

RSO-1544-86

/ /

NUTHERM GE TED1 Purchase Order 64111135 18 1 026-34608 RS02-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 18 2 026-34608 RS02-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 176 1 025-89596 RS02-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 176 2 025-89596 RS02-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 176 3 025-89596 RS02-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 176 4 025-89596 RSO2-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 207 1 025-89596 RS02-P-734-82 04/10/82 AMFAC ELEC SUPPLY WEST HFB3 Purchase Order 65900044 174 1 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 174 2 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 174 3 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 174 4 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 174 5 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH C81 174 6 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 174 7 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 174 8 024-71209 RS02-P-1943-82 08/25/82 CE/MIDAN ELECT BUCH CBB1 Purchase Order 65900349 182 1 026-24955 RS02-P-1008-83 07/06/83 CONSOLIDATED ELECT ITE EF2A Purchase Order 65900439 111 1

024-75895 RS02-P-1385-83 08/21/83 THERMON GEO. YARDLEY SO D QOUl 111 2

024-75895 RS02-P-1385-83 08/21/83 THERMON GEO. YARDLEY SO D QOUl 135 1

025-27760 RS02-P-1385-83 08/12/83 THERMON GEO. YARDLEY SO D LK68 135 2 025-27760 RS02-P-1385-83 08/12/83 THERMON GEO. YARDLEY SQ D LK68 135 3

025-27760 RS02-P-1385-83 08/12/83 THERMON GEO. YARDLEY SO D LK68 135 4 025-27760 RSO2-P-1385-83 08/12/83 THERMON GEO. YARDLEY SQ D LK68 Purchase Order 65900921 110 1 024-75895 RS02-P-2602-82 10/21/82 THERMON GEO. YARDLEY SO D QOUl Purchase Order 65900957 60 1 023-02545 RS02-P-3206-82 12/08/82 PEERLESS PUMP WEST HLCF 60 2 023-02545 RS02-P-3206-82 12/08/82 PEERLESS PUMP WEST HLCF 130 1 023-04970 RS02-P-2233-82 09/22/82 PEERLESS PUMP HEIN JAlB 130 2 023-04970 RSO2-P-2233-82 09/22/82 PEERLESS PUMP HEIN JAiB

Page No.

2 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS MRC BULLETIN 88-10 APPENDIX A MontraceabLe MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL 130 3 023-04970 RS02-P-2233-82 09/22/82 PEERLESS PUMP HEIN JAlB 130 4 023-04970 RSO2-P-2233-82 09/22/82 PEERLESS PUMP HEIN JAiB Purchase Order 65900984 136 1 024-77792 RS02-P-2335-82 10/01/82 BROWN BOVERI ITE BoiB Purchase Order 65901909 57 1 024-87593 RSO-5107-85 11/15/82 SOLID STATE CONTROLS GE 7120' 173 1

024-80697 RSO2-P-2942-82 11/15/82 SOLID STATE CONTROLS GE THED Purchase Order 65901920 179 1 024-98970 RS02-P-836-83 05/02/83 CE/ELECTRO MECH.

HEIN AM2A 179 2 024-98970 RS02-P-836-83 05/02/83 CE/ELECTRO MECH.

HEIN AM2A 180 1 024-98988 RSO2-P-836-83 05/02/83 CE/ELECTRO MECH.

HEIN JAlA 180 2 024-98988 RSO2-P-836-83 05/02/83 CE/ELECTRO MECH.

HEIN JAlA Purchase Order 6A016020 223 1 024-06452 RSO-0870-86

/ /

ELECTRO COMP. DIST.

SQ,D FHL3 Purchase Order 6AO27062 123 1 027-29036 RSO-1329-87 05/09/87 GAMMA-METRICS HEIN JA2A 123 2 027-29036 RSO-1329-87 05/09/87 GAMMA-METRICS HEIN JA2A Purchase Order 6AO38056 153 1 027-26230 RSO-2016-88 07/16/88 ELGAR CORP GE 8523 258 1 027-26230 RSO-2016-88 07/16/89 ELGAR CORP GE 8522 Purchase Order 6A068028 8 1 024-04747 RSO-2442-88 09/06/88 SQUARE D SO D FHL3 8 2 024-04747 RSO-2442-88 09/06/88 SQUARE D So 0 FHL3 8 3 024-04747 RSO-2442-88 09/06/88 SQUARE D SQ D FHL3 Purchase Order 6A106064 139 1 023-04178 RSO-5304-86 12/15/86 NEWARK ELECT SUPPLY P&B W58X 139 2 023-04178 RSO-5304-86 12/15/86 NEWARK ELECT SUPPLY P&B W58X 139 3 023-04178 RSO-5304-86 12/15/86 NEWARK ELECT SUPPLY P&B W58X 139 4 023-04178 RSO-5304-86 12/15/86 NEWARK ELECT SUPPLY P&B W58X 139 5 023-04178 RSO-5304-86 12/15/86 NEWARK ELECT SUPPLY P&B W58X 139 6 023-04178 RSO-5304-86 12/15/86 NEWARK ELECT SUPPLY P&B W58X Purchase Order 6A126069 222 1 026-73408 RSO-1117-87(PIT

/ I ELECTRO COMP. DIST.

WEST FB31 222 2 026-73408 RSO-1117-87(PIT

/ /

ELECTRO COMP. DIST.

WEST FB31

Page No.

3 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A Nontraceabte MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL 222 3 026-73408 RSO-1117-87(PIT

/ /

ELECTRO COMP. DIST.

WEST FB31 222 4 026-73408 RSO-1117-87(PIT

/

/

ELECTRO COMP. DIST.

WEST FB31 222 5 026-73408 RSO-1117-87(PIT

/ /

ELECTRO COMP. DIST.

WEST FB31 Purchase Order 60035901 271 1

024-29439 RSO-0453-88 01/05/88 WEST WEST FB30 Purchase Order 6N016028 85 1

026-79876 RSO-0180-87 01/26/87 ELGAR CORP HEIN CDlA 86 1 026-79884 RSO-0180-87 01/26/87 ELGAR CORP AIRP AIRP Purchase Order 6NO28015 66 1 024-67587 RSO-1991-88 07/15/88 ELGAR CORP GE 8521 225 1 024-67587 RSO-2390-88 09/01/88 ELGAR CORP GE 8521 Purchase Order 6NO95008 167 1 026-85089 RSO-3761-86 07/08/86 ELGAR CORP GE TFJ2 167 2 026-85089 RSO-3761-86 07/08/86 ELGAR CORP GE TFJ2 Purchase Order 6N125004 156 1 026-83985 RSO-2416-87

/ /

TELEMECANIQUE ITE EF3A Purchase Order 6N126017 131 1

023-03220 RSO-0306-87 02/05/87 CUMMINGS WEST CORP TI 1081 Purchase Order 8AO25038 200 1 024-80697 RSO-6237-85

/ /

SOLID STATE CONTROLS GE TED1 Purchase Order 8A035901 265 1 NONE RSO-4269-86

/ /

WEST WEST FB30 Purchase Order 8A085404 230 1 025-44484 RSO-0499-87

/ /

POWER SYSTEMS DIV GE TEB1 230 2 025-44484 RSO-0499-87

/ /

POWER SYSTEMS DIV GE TEB1 230 3 025-44484 RSO-0499-87

/ /

POWER SYSTEMS DIV GE TEB1 230 4 025-44484 RSO-0499-87

/ /

POWER SYSTEMS DIV GE TEB1 Purchase Order 88112067 272 1 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 2 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 3 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 4 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 5 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP

Page No.

4 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A Nontraceable MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL 272 6 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 7 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 8 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 9 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP 272 10 024-93310 RIP-P-592-82 11/22/82 AIRPAX AIRP Purchase Order 80035423 224 1 024-87593 RSO-5107-85 11/15/82 SOLID STATE CONTROLS GE 7120' Purchase Order 80045027 275 1 026-10053 RSO-3510-85

/ /

AMFAC ELEC SUPPLY SQ D Q0B1 275 2 026-10053 RSO-3510-85

/ /

AMFAC ELEC SUPPLY SQ D 0081 Purchase Order 80054017 126 1 026-17371 RSO-8274-84 12/10/84 FOXBORO TI 51MO 126 2

026-17371 RSO-8274-84 12/10/84 FOXBORO TI 51MO 126 3

026-17371 RSO-8274-84 12/10/84 FOXBORO TI 51MO Purchase Order 80085017 9

1 026-76799 RSO-5819-85(PIT

/ /

CONSOLIDATED ELECT GE TEB1 99 1

026-76781 RSO-5819-85(PIT

/ /

CONSOLIDATED ELECT GE TEB1 259 1

026-76781 RSO-5819-85(PIT

/ /

CONSOLIDATED ELECT GE TEB1 Purchase Order 80085401 269 1

024-40584 RSO-4861-86 08/20/86 GE GE Purchase Order 8E094025 78 1

024-58255 RSO-5755-84

/

/

BROWN BOVERI ITE EE2B Purchase Order 8E113064 93 1

025-50531 RSO-3826-84 08/19/84 SQUARE 0 SQ D FHL3 Purchase Order 8N044055 134 1

025-27760 RSO-5239-85 08/23/85 THERMON GEO.

YARDLEY SQ D LL28 134 2

025-27760 RSO-5239-85 08/23/85 THERMON GEO.

YARDLEY SQ D LL28 134 3

025-27760 RSO-5239-85 08/23/85 THERMON GEO.

YARDLEY SQ D LL28 134 4

025-27760 RSO-5239-85 08/23/85 THERMON GEO.

YARDLEY SQ 0 LL28 Purchase Order 8NO65410 166 3

026-19716 RSO-0681-86 01/27/86 CE HEIN CD1B 166 4

026-19716 RSO-0681-86 01/27/86 CE HEIN CD1B

Page No.

5 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A Nontraceable MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL Purchase Order 8N074032 35 1 025-49327 RSO-1950-85 02/12/85 C&0 BATTERIES WEST JR34 35 2 025-49327 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR34 35 3 025-49327 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR34 35 4 025-49327 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR34 51 1

025-49319 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR49 51 2

025-49319 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR49 51 3

025-49319 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR49.

51 4

025-49319 RSO-1950-85 02/12/85 C&D BATTERIES WEST JR49 Purchase Order 8N084016 127 1

026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 2 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 3 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 4 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 5 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 -6 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 7 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 8 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO 127 9 026-17371 RSO-8456-84 12/19/84 FOXBORO TI 51MO Purchase Order 8N085423 250 1

024-29439 RSO-0179-87 12/24/85 ASSOCIATED OF L.A.

WEST FB30 250 2 024-29439 RSO-0179-87 12/24/85 ASSOCIATED OF L.A.

WEST FB30 250 3 024-29439 RSO-0179-87 12/24/85 ASSOCIATED OF L.A.

WEST FB30 Purchase Order 8N114025 81 1

025-88390 RSO-2609-85 03/13/85 GOLDN GATE SW BRO GE THQC 81 2

025-88390 RSO-2609-85 03/13/85 GOLDN GATE SW BRD GE THQC Purchase Order 8N124041 48 1 024-65938 RSO-4416-85 06/28/85 BROWN BOVERI ITE EE2B 75 1

024-58255 RSO-4416-85 06/28/85 BROWN BOVERI ITE EE28 75 2

024-58255 RSO-4416-85 06/28/85 BROWN BOVERI ITE EE28 75 3

024-58255 RSO-4416-85 06/28/85 BROWN BOVERI ITE EE2B 75 4

024-58255 RSO-4416-85 06/28/85 BROWN BOVERI ITE EE2B Purchase Order 8N124042 49 1 024-65938 RSO-4306-86 *

/ /

BROWN BOVERI ITE EE28 Purchase Order 8N2N4001 74 1 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE28 74 2

024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B

Page No.

6 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A montraceabte MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL 74 3 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE28 74 4 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE28 74 5 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE28 74 6 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B 74 7 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B 74 8 024-58255 RSO-4136-85

/

/

BROWN BOVERI ITE EE2B 74 9 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B 74 10 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE28 74 11 024-58255 RSO-4136-85

/

/

BROWN BOVERI ITE EE29 74 12 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B 74 13 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE28 74 14 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B 74 15 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE29 74 16 024-58255 RSO-4136-85

/ /

BROWN BOVERI ITE EE2B 137 1 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BC1B 137 2 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BaiB 137 3 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE 8018 137 4. 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BoiB 137 5 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE 8018 137 6 024-77792 RSO-4136-85 06/07/85 BROWN 8OVERI ITE BQ18 137 7 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE 818 137 8 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE Bo1 137 9 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BQ1B 137 10 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE 8018 137 11 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE Bo1B 137 12 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BQ1B 137 13 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BC1B 137 14 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BQ18 137 15 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE Bi 137 16 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE Bo1B 137 17 024-77792 RSO-4136-85 06/07/85 BROWN BOVERI ITE BC1B 137 18 024-7M2 RSO-4136-85 06/07/85 BROWN BOVERI ITE BC1B Purchase Order 8W065016 10 1

026-76799 RSO-4564-85(PIT 07/08/85 GE GE TEB1 98 1 026-76781 RSO-4564-85(PIT 07/08/85 GE SUPPLY CO GE TEB1 98 2 026-76781 RSO-4564-85(PIT 07/08/85 GE SUPPLY CO GE TEB1 226 1 025-44484 RSO-4797-85

/ /

GE SUPPLY CO GE TEB1 Purchase Order G8200041 227 1 027-29457 RSO-4267-86

/ /

IND CONTROL & SUPPLY WEST FA21 228 1 027-29481 RSO-4268-86

/ /

IND CONTROL & SUPPLY WEST FA20 228 2 027-29481 RSO-4268-86

/

IND CONTROL & SUPPLY WEST FA20

Page No.

7 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A Nontraceabte MCCBs MATERIAL REC'D MCCB ID ITM CODE RSO DATE VENDOR MFG MODEL 228 3 027-29481 RSO-4268-86

/ /

IND CONTROL & SUPPLY WEST FA20 228 4 027-29481 RSO-4268-86

/ /

IND CONTROL & SUPPLY WEST FA20 229 1 027-29432 RSO-4271-86

/ /

IND CONTROL & SUPPLY WEST FA20 229 2 027-29432 RSO-4271-86

/ /

IND CONTROL & SUPPLY WEST FA20 229 3 027-29432 RSO-4271-86

/ /

IND CONTROL & SUPPLY WEST FA20 229 4 027-29432 RSO-4271-86

/ /

IND CONTROL & SUPPLY WEST FA20 229 5 027-29432 RSO-4271-86

/ /

IND CONTROL & SUPPLY WEST FA20 Purchase Order G8207361 94 1

024-04218 MRR2604

/ /

WEST WEST EB20 94 2 024-04218 MRR2604

/ /

WEST WEST E820 94 3 024-04218 MRR2604

/ /

WEST WEST EB20 94 4 024-04218 MRR2604

/ /

WEST WEST EB20 94 5 024-04218 MRR2604

/ /

WEST WEST EB20 94 6 024-04218 MRR2604

/ /

WEST WEST EB20 94 7 024-04218 MRR2604

/ /

WEST WEST EB20 94 8

.024-04218 MRR2604.

/ /

WEST WEST EB20 94 9 024-04218 MRR2604

/ /

WEST WEST EB20 94 10 024-04218 MRR2604

/ /

WEST WEST EB20 94 11 024-04218 MRR2604

/ /

WEST WEST EB20 94 12 024-04218 MRR2604

/ /

WEST WEST EB20 Purchase Order R2405001 208 1 024-20677 PRE-NUMBER 09/15/75 WESCO WEST EA10 208 2 024-20677 PRE-NUMBER 09/15/75 WESCO WEST EA10 Purchase Order S1S00204 26 1 025-09438 RIP-F-1295-82 12/28/82 RAYCHEM ITE EF28 Purchase Order S2L00017 3 1 025-24726 RIP-F-38-80 07/18/80 WEST WEST FB30 4 1 025-24726 RIP-F-38-80 07/18/80 WEST WEST FB30 Purchase Order S5940053 113 1

026-18049 RS02-83

/ /

CARRIER CORP HEIN QoUl 113 2 026-18049 RS02-83

/ /

CARRIER CORP HEIN 00U1 Purchase Order S5990013 246 1

026-19716 RSO2-P-812-81 06/01/79 CE/MIDAN ELECT HEIN CD1B 246 2 026-19716 RSO2-P-812-81 06/01/79 CE/MIDAN ELECT HEIN CD1B Purchase Order S5990023 114 1

026-11093 RS02-233

/ /

CE HEIN AM2A

Page No.

8 01/31/90 SPARE MOLDED CASE CIRCUIT BREAKERS NRC BULLETIN 88-10 APPENDIX A Nontraceabte MCCBs MATERIAL REC'D MCCS ID ITM CODE RSO DATE VENDOR MFG MODEL 114 2 026-11093 RSo2-233

/ /

CE HEIN AM2A Purchase Order S5990044 103 1 024-41939 RSO2-117-80

/ /

CE/MIDAN ELECT HEIN AM3A 103 2 024-41939 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM3A 115 1 024-41855 RSO-117

/ /

CE/MIDAN ELECT HEIN AM2A 115 2 024-41855 RSO-117

/

/

CE/MIDAN ELECT HEIN AM2A 116 1 024-41921 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 116 2 024-41921 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 117 1 024-41848 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 117 2 024-41848 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 118 1 024-41905 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 118 2 024-41905 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 119 1 024-41897 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 119 2 024-41897 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 120 1. 024-41913 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 120 2 024-41913 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 121 1

024-41889 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 121 2 024-41889 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 163 1 024-41863 RS02-117-80

/

/

CE/MIDAN ELECT HEIN AM2A 163 2 024-41863 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 164 1 024-41871 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 164 2 024-41871 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 204 1

024-41822 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A 204 2 024-41822 RS02-117-80

/ /

CE/MIDAN ELECT HEIN AM2A Purchase Order V8200646 235 1

N/A RSO-3227-86

/

/

ASSOCIATED OF L.A.

WEST EHB3 240 1

025-36654 RSO-2732-86

/ /

ASSOCIATED OF L.A.

WEST EH82 Purchase Order V8200657 232 1

027-29432 RSO-4720-86

/ /

WESCO WEST FA20 233 1

027-29481 RSO-4740-86

/ /

WESCO WEST FA20 233 2

027-29481 RSO-4740-86

/ /

WESCO WEST FA20 233 3

027-29481 RSO-4740-86

/ /

WESCO WEST FA20 233 4

027-29481 RSO-4740-86

/ /

WESCO WEST FA20 233 5

027-29481 RSO-4740-86

/ /

WESCO WEST FA20 234 1

027-29457 RSO-4740-86

/ /

WESCO WEST FA21 234 2

027-29457 RSO-4740-86

/ /

WESCO WEST FA21 234 3

027-29457 RSO-4740-86

/ /

WESCO WEST FA21 234 4 027-29457 RSO-4740-86

/ /

WESCO WEST FA21 245 1

027-29457 RSO-3550-86

/ /

WESCO WEST FA21 268 1 027-29432 RSO-4740-86

/ /

WESCO WEST F830