Ro:Followup Rept for Tech Spec Fire Rated Assemblies Found Inoperable During Routine Surveillances in Jan 1990.One Fire Door Found Blocked Open W/O Proper Authorization.Individual Identified & Disciplinary Action Taken
ML13331A363
Person / Time
Site: San Onofre  
Issue date: 02/16/1990
From: Nandy F
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
NUDOCS 9003120218
Download: ML13331A363 (5)


Text

0 0

Southern California Edison Company 23 PARKER STREET IRVINE, CALIFORNIA 927 18 F. R. NANDY February 16, 1990 TELEPHONE MANAGER OF NUCLEAR LICENSING (714) 587-5400 U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 Attention:

Mr. J. B. Martin, Regional Administrator

Subject:

Docket Nos. 50-206, 50-361 and 50-362 Followup Report, Inoperable Fire Doors - January 1990 San Onofre Nuclear Generating Station, Units 1, 2 and 3 The purpose of this letter is to provide a follow-up report for Technical Specification (TS) fire-rated assemblies (specifically fire doors) found inoperable during routine surveillances in January 1990. This monthly report and previous monthly reports provide updated information associated with the initial 1983 report for Units 2 and 3.

The enclosed report identifies: a) 3 latching mechanism failures and no closure mechanism failures for Unit 1 and; b) 31 latching mechanism failures and 8 closure mechanism failures for Units 2 and 3.

As each of these deficiencies was identified, compensatory fire watches were established pursuant to TS 3.14.7, Action "A" for Unit 1 and TS 3.7.9, Action "a" for Units 2 and 3.

For this report month, one fire door (AC-326) which is common to Units 2 and 3 was found to be blocked open without proper authorization.

The responsible party was identified and appropriate disciplinary action was taken.

F DR -

DOCk 0002

0 0

Mr. J.

February 16, 1990 If you require any additional information, please let me know.

Very truly yours,.

Enclosure cc:

C. W. Caldwell (NRC Senior Resident Inspector, Units 1, 2 and 3)

U. S. Nuclear Regulatory Commission Document Control Desk Institute of Nuclear Power Operations (INPO)

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF JANUARY 1990 SAN ONOFRE NUCLEAR GENERATING STATION UNIT 1, DOCKET NO. 50-206 I.

Latching Mechanism Failures:

Number of doors inoperable - 3, as follows:

Door Number Inoperable Operable S1-FBD-130 12/13/89 01/25/90 S1-FBD-141 01/19/90 01/23/90 S1-FBD-185 01/19/90 01/23/90 II. Closure Mechanism Failures:

Number of doors inoperable - None Door Number Inoperable Operable NA NA NA III.

Doors Blocked Open:

Number of doors blocked open -

None fdr.jan/1

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF JANUARY 1990 SAN ONOFRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 AND 50-362 I.

Latching Mechanism Failures:

Number of doors inoperable - 31, as follows:

Door Number Inoperable Operable AC-428 09/21/89 FH2-101 10/10/89 FH2-404 11/28/89 01/03/90 AC-107 12/07/89 01/23/90 S2-016 12/07/89 S3-016 12/07/89 02/02/90 AC-223 12/13/89 01/05/90 AR-504 12/14/89 01/17/90 AC-349 12/29/89 01/02/90 FH3-303 12/29/89 01/03/90 FH3-403 12/29/89 01/31/90 S2-018 12/29/89 AC-101 12/31/89 01/17/90 AC-108 01/02/90 01/05/90 AC-239 01/12/90 01/25/90 DG2-103 01/15/90 01/23/90 DG2-201 01/15/90 01/23/90 FH3-101 01/15/90 01/26/90 FH3-304 01/17/90 01/24/90 AC-119 01/19/90 01/23/90 AC-101 01/24/90 01/26/90 AC-131 01/24/90 01/25/90 AC-325 01/24/90 01/25/90 AC-350 01/24/90 01/26/90 FH2-303 01/24/90 01/31/90 FH2-404 01/24/90 01/31/90 FH3-103 01/24/90 01/31/90 FH3-404 01/24/90 01/31/90 C3-406 01/25/90 FH3-101 01/28/90 S3-016 01/28/90 02/02/90 fdr.dec/2

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF JANUARY 1990 SAN ONOFRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 AND 50-362 II.

Closure Mechanism Failures:

Number of doors inoperable - 8, as follows:

Door Number Inoperable Operable AC-428 10/10/89 AC-242 11/02/89 01/25/90 FH2-404 11/28/89 01/31/90 S2-016 12/07/89 S3-016 12/07/89 02/02/90 AC-218 12/14/89 01/18/90 AC-119 12/27/89 AC-236 01/19/90 01/26/90 III.

Doors Blocked Open:

Number of doors blocked open - 1, as follow:

Door Number Date Found Blocked Open AC-326 01/24/90 fdr.dec/3